Title: Optimization of Central Air-conditioning Chillers System Team: Leader: Joselito Mendez Assistant: Oscar Roman Members: Manny Mabalot George Villamor Gabriel Custodio - BCC Jojo Placer – Trane Philippines Champion: Chatiya Nantham Project No. OAS-06-003 (2W)
68
Embed
Title: Optimization of Central Air-conditioning Chillers System
Title: Optimization of Central Air-conditioning Chillers System. Project No. OAS-06-003 (2W). Team: Leader: Joselito Mendez Assistant:Oscar Roman Members:Manny Mabalot George Villamor Gabriel Custodio - BCC Jojo Placer – Trane Philippines - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Title: Optimization of Central Air-conditioning Chillers System
Team:Leader: Joselito MendezAssistant: Oscar RomanMembers: Manny Mabalot
George Villamor Gabriel Custodio - BCC Jojo Placer – Trane Philippines
Champion: Chatiya Nantham
Project No. OAS-06-003 (2W)
The operation of air-conditioning is the largest energy user in ADB HQ utilizing about 44% of the total energy consumption. Operation of Chiller plant is a major component of the high energy consumption of the whole air-conditioning system.
Improving the operating efficiency range of the chillers operation is a key energy saving opportunity.
As part of EHSMS, energy conservation from this project certainly contribute to reduction of air pollution in the local environment particularly fuel exhaust emission from thermal power plant.
Project Charter
Business Case:
DEFINE
DEFINE
Problem Statement:
Project Goal:
Improve and maintain Chiller plant operating efficiency not more than 0.75 kW/ton to realize energy saving without sacrificing the quality of air-conditioning services.
The central chiller plant serves the 24/7 cooling requirement of the building ranging from 200 to over 1,800 tons. Data shows that the plant has the capability to operate from 0.74 – 0.80 kW/ton efficiency range to deliver this cooling demand. However, it also operates inefficiently to an undesirably low value of 1.10 kW/ton. This clearly indicates that there are factors that affect the overall performance efficiency of the plant.
Automation System
Space heat load
Chiller Plant
ChwPCP
Chiller
CT
Illustration of Basic Chiller Plant Operation
Amount of heat in the space = Air-conditioning load which expressed in Tons
Efficiency = KW / TON
Chillers (5-units)ChwP – Chilled Water Pump (4-units) CP – Condenser Water Pump (5-units) CT – Cooling Tower (4-units)
StartChiller-5(350T)
6:30 amAdd 1-Chiller
(700T)
Add 1-Chiller(700T)
Add 1-Chiller(700T)
Load?
>/ = 1750
> 1750
= 1400
Subtract1-Chiller(350T)
MaintainOperatingChillers
Subtract1-Chiller(350T)
Subtract1-Chiller(700T)
Subtract1-Chiller(700T)
Subtract1-Chiller(350T)
Load?
= 1400
= 1400
= 700
Load?
Subtract1-Chiller(700T)
Subtract1-Chiller(700T)
Subtract1-Chiller(700T)
Subtract1-Chiller(700T)
= 700
= 700
= 350
MonitoredLoad= 350T
MonitoredLoad
>1050T
A
B
C
A
B
C
A
B
C
High Level Process Map
24/7
Operation
Automation System
3 x 700T
2 x 700 T1 x 350 T
2 x 700
Air-conditioning Load (Tons)
> 1750> 1400< or = 350 > 1050> 700> 350
1- 350T Chiller1- ChwP1- CP1-CT
1- 700T Chiller1- ChwP1- CP1- CT
1- 350T Chiller1- 700T Chiller1- ChwP2- CP2- CT
3- 700T Chiller3- ChwP3- CP3- CT
2- 700T Chiller2- ChwP2- CP2- CT
1- 350T Chiller2- 700T Chiller2- ChwP3- CP3- CT
Legend: ChwP – Chilled Water Pump (4-units) CP – Condenser Water Pump (5-units) CT – Cooling Tower (4-units)
High Level Process Map
C h i l l e r s O p e r a t i o n
Supplier Inputs Process Output Customer
ADB Air-conditioning load Load based Efficient chillers ADB
Chillers Chillers operation
Instrumentation Operation
Controls (automation)
Operators
Operation best practices
Power
Auxiliaries (Pumps/ Cooling Tower)
Weather
SIPOC DiagramS I P O C D i a g r a mS I P O C D i a g r a m
Ave. Eff. = 0.75 kw/ ton
0.70 kw/ Ton
Present:
Translation to Savings ( Illustration )
Improved by 7.5%:
Savings for every 100 Tons
100 tons x (0.75 – 0.70) Kw/ton x Php 7.00/Kw-hr = Php 35.00 per 100 ton/hr
Load, tons x (1.0 - .75) kW/ton x 8 hrs x Php 7 =
Measure
Data Collection and Consolidation:
Retrieve/ download 2005 data from Chillers Automation System (Trane Tracer Summit).
Average 24-hrs operation efficiency of central chiller plant.
Initially use 5-months (March – July 2005) as sample data to measure the process capability.
Measurement
Date Average Date Average Date Average Date Average Date Average
Mar 14, Monday Mar 15, Tuesday Mar 16, Wednesday Mar 17, Thursday Mar 18, Friday
Date/ TotalkW/ ton Date/ Total
kW/ton Date/ Total
kW/ ton Date/ Total
kW/ ton Date/ Total
kW/ton
Time Tons Time Tons Time Tons Time Tons Time Tons
3/18/05 7:00 PM 853.25 0.85
3/18/05 6:45 PM
1046.61 0.79
03/14/05 6:30 PM
826.59 0.81 3/18/05 6:30 PM
912.92 0.83
3/14/05 6:15 PM
876.22 0.8 3/18/05 6:15 PM
943.03 0.83
03/14/05 6:00 PM
956.06 0.77 3/15/05 6:00 PM
913.04 0.78
3/16/05 6:00 PM
903.39 0.76 3/17/05 6:00 PM
941.75 0.8 3/18/05 6:00 PM
1040.84 0.78
3/14/05 5:45 PM
943.11 0.78 3/15/05 5:45 PM
931.97 0.79
3/16/05 5:45 PM
914.07 0.79 3/17/05 5:45 PM
936.55 0.81 3/18/05 5:45 PM
1004.8 0.8
3/14/05 5:30 PM
971.48 0.77 3/15/05 5:30 PM
977 0.78
3/16/05 5:30 PM
942.56 0.78 3/17/05 5:30 PM
924.59 0.82 3/18/05 5:30 PM
999.77 0.81
03/14/05 5:15 PM
982.08 0.78 3/15/05 5:15 PM
950.66 0.81
3/16/05 5:15 PM
923.15 0.79 3/17/05 5:15 PM
925.29 0.82 3/18/05 5:15 PM
996.56 0.8
03'14/05 5:00 PM
864.11 0.86 3/15/05 5:00 PM
865.88 0.86
3/16/05 5:00 PM
801.28 0.88 3/17/05 5:00 PM
819.13 0.91 3/18/05 5:00 PM
915.62 0.84
3/15/05 4:45 PM
3/15/05 4:45 PM
1328 0.78
3/16/05 4:45 PM
1314.46 0.77 3/17/05 4:45 PM
1230.31 0.81 3/18/05 4:45 PM
1314.73 0.77
TOTAL6,419.
65 5.57 5,966.554.8
0 5,798.91 4.77 5,777.62 4.97 10,028.13 8.10
AVERAGE 917.09 0.80 994.430.8
0 966.49 0.80 962.94 0.83 1,002.81 0.81
After Office Hour Operation
.
( kW, TONS)
Chiller System
CHILLER PLANT LAY-OUT
TonskW
Chilled WaterPump (kW)
Condenser WaterPump (kW)
Cooling Tower ( kW )
PLANT OUTPUT
Efficiency
CONDENSER
EVAPORATOR
COMPRESSOR
Building Cooling Demand
LOADTons
Power
Chilled Water(Flow, Temp.)
Chiller AutomationSystem
qualification
common knowledge
training
load
approach temperature
chilled water flow
condenser water temp.
chilled water temp.
regular maintenance
condenser water flow
malfunctioning control devices
data monitoring and indepth analysis
guides on decision making
chillers vs. pumps, cooling tower requirements
operating chillers vs. demand load
reporting of abnormalities
PEOPLE
C
chillers combination
C
C
C
CC
C
C
N
C
C
C
C
PARAMETERS BEST PRACTICES
OPERATION
c.t. out
chiller out
difference
difference
N
N
C
C
attitudeN
field
bms
C
Chiller
Plant Eff. Variation
weatherN
timely correction/ adjustment of
timely start-up/ shut-downof chillersC
Analyze Cause and Effect Diagram for Chiller Plant Operation
Cause and Effect Diagram for Chiller Plant Operation
Technology
– can’t be controlled
C
ChillerAutomation
C
– can be controlled
N
C
C
ChillerObsolencyN
I. Covered in the previous reviews - Analyze Phase:
a. Chillers load vs. efficiency profile at different operating time frames:office hours operationafter office hours operationnight operationSaturday and Sunday operation
b. Chiller plant’s load and efficiency trends for (5) five months (March – July 2005) operation;
c. Verification of individual chiller performance.
d. Cause and effect diagram for chiller plant operation.
II. Last review - Analysis Phase:
a. Trending of chillers operating parameters to verify whether these arewithin or outside normal range.
1. With the operation of chiller no.1, the chiller plant efficiency goes to undesirably low value of more than 1kW/Ton.
2. Chiller no.4 is not efficient to operate below 650-Tons load and this contributes in not achieving the target of 0.75kW/ton. However, it was found that although this chiller is rated 700-tons but it can efficiently handle the load up to 800-tons.
3. Chillers nos. 2 and 3 are identical machine but the latter is more energy efficient than the former.
4. Chiller no.2 is exhibiting relatively higher condenser approach than chiller no.3. This could be one factor that affects the performance of chiller no.2.
5. Higher percentage of over 0.75kW/Ton chiller plant efficiency is in the load range of 701 - 900 tons which normally occurs outside regular office hours. This air-conditioning load is shared by 2 x 700-tons chillers which are operating at their lower efficiency zone.
6. Interview with Chiller and BMS operators revealed that their awareness on the chillers and Tracer operations is not consistent.
Improve
Short-term: Improve Best Practices:
1. Maintain the following chillers combination during office hours: a. chillers no. 2 + no. 3 at cooling demand range of 700+ – 1400 Tons;
b. chillers no. 2 + no.3 + no. 5 at cooling demand range 1400+ – 1750 Tons c. either chiller no. 2 or 3 + no. 5 + no. 4 when cooling demand is in the
range 1,750+ - 1,900 Tons.
2. Run either chiller no.2 or no. 3 on Saturday instead of chiller 4 which is programmed to run every Saturday.
3. Run chiller no.4 when it can be loaded by 650 – 850 Tons.
4. Coincide the operational test run of chiller no. 1 during weekly Genset operation on Sunday. This is more practical because the standby Generator units can be used more efficiently and stored diesel can also be gradually replaced rather its quality degrade overtime. This can bring savings from wastage of diesel, and payment to Meralco on energy used. This is possible because the Gensets are already undergoing regular preventive maintenance.
5. Maintain chillers operating parameters within the design tolerable range.
Long Term:
1. Installation of additional new 2 x 400-tons chillers will further improve the chiller plant operation in terms of available capacity and efficiency: a. there will be back up units in the event of efficient chillers breakdown; b. it will provide flexibility in the chillers operation particularly when cooling
demand only requires 1-big chiller and 1-small chiller; c. this will prolong the life of the chillers because there are more units to operate alternately.
2. Replace the 18-year old Chillers no.1 and 4 with new units having an efficiency of not lower than 0.6kW/Ton.
Improve
6. Weekly generation of chiller plant performance data from automation system and conduct an in-depth data analysis to identify areas which can be further
improved.
7. Enhance awareness of chillers operators and BAS on the chillers operation best practices and design operating parameters.
Date
Average Chiller Plant Efficiency,
kW/Ton
Remarks
02-Sep Saturday 0.72 Chiller no.4 operates from 8:00am - 1:00pm at a load range of 650 - 850 Tons. Chiller no.2 operates from 1:00pm - 6:30pm
03-Sep Sunday 0.69 Chiller no.5 operates the whole day because cooling demand was within 350-Tons
04-Sep Monday 0.71
05-Sep Tuesday 0.70 Chiller nos. 2, 3 and 5 operates during office hours
06-Sep Wednesday 0.70
07-Sep Thursday 0.69 Chiller no.5 on nighttime
08-Sep Friday 0.71
09-Sep Saturday 0.92 Chiller #1 operates from 11:00am - 4:40pm
10-Sep Sunday 1.11 Chiller #1 operates (9:00am - 6:00pm) during Gensets operational test run.
11-Sep Monday 0.70 Chiller nos. 2, 3 and 5 operates during office hours
12-Sep Tuesday 0.69 Chiller no.5 on nighttime
Chiller Plant Performance: September 02 – 12, 2006
Chart of Chiller Plant Efficiency - Setpember 2006a
Improve
Full Operation of Chiller PlantSeptember 2006
Data from Chiller no.1 operation not included
Data from Chiller no. 1 operation on 09, 10 & 17 included.
Date
EFFI
CIE
NCY, k
W/T
on
*
Fri-
30
Thu-
29
Wed
-28
Tue-
27
Mon
-26
Sun-
25
Sat-
24
Fri-
23
Thu-
22
Wed
-21
Tue-
20
Mon
-19
Sun-
18
Sat-
17
Fri-
16
Thu-
15
Wed
-14
Tue-
13
Mon
-12
Sun-
11
Sat-
10
Fri-
9
Thu-
8
Wed
-7
Tue-
6
Mon
-5
Sun-
4
Sat-
3
Fri-
2
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
CHILLER PLANT EFFICIENCY: September 2005
Date
EFFI
CIE
NCY, k
W/T
on
Sat
-30
Fri-
29
Thu
r-28
Wed
-27
Tue
-26
Mon
-25
Sun
-24
Sat
-23
Fri-
22
Thu
r-21
Wed
-20
Tue
-19
Mon
-18
Sun
-17
Sat
-16
Fri-
15
Thu
r-14
Wed
-13
Tue
-12
Mon
-11
Sun
-10
Sat
-09
Fri-
08
Thu
r-07
Wed
-06
Tue
-05
Mon
-04
Sun
-03
Sat
-02
Fri-
01
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
CHILLER PLANT EFFICIENCY: September 2006 (a) The Chiller plant operation data sampled in 2006 is compared directly against the 2005 recorded data for statistical comparison
(b) 2006 efficiency graph does not include operation of chiller no. 1 on 09, 16 & 17 September.
NOTE:
Improve
Comparison of Chiller Plant Performance:September 2005 vs. September 2006
Day
Coolin
g L
oad, T
ons
Sat-
30-*
*
Fri-
29-3
0
Thu-
28-2
9
Wed
-27-
28
Tue-
26-2
7
Mon
-25-
26
Sun-
24-2
5
Sat-
23-2
4
Fri-
22-2
3
Thu-
21-2
2
Wed
-20-
21
Tue-
19-2
0
Mon
-18-
19
Sun-
17-1
8
Sat-
16-1
7
Fri-
15-1
6
Thu-
14-1
5
Wed
-13-
14
Tue-
12-1
3
Mon
-11-
12
Sun-
10-1
1
Sat-
09-1
0
Fri-
08-0
9
Thu-
07-0
8
Wed
-06-
07
Tue-
05-0
5
Mon
-04-
05
Su-0
3-04
Sat-
02-0
3
Fri-
01-0
2
1200
1050
900
750
600
450
300
150
VariableLOAD-05_1
LOAD-06_1
Chiller Plant Performance: September 2005 vs. September 2006
Discussed in BCC’s Training - conducted by J. Mendez last June 2006
3. Updating of Tracer Summit program when necessary.
Proposal for improvement Trane Philippines George Villamor/ Joey Mendez
Updated based on improve phase - 04 October 2006
4. Conduct a weekly in-depth analysis of data from Tracer Summit for the following: i. to detect any deviation from target efficiency of 0.75kW/Ton; ii. to identify areas for continual improvement.
Tracer Summit data logging Service provider supervisors – (BCC)
Joey Mendez Implemented – 10 September 2006
5. Immediate reporting of abnormalities on chillers and auxiliary equipment, and Tracer operation to FM shift engineers so that appropriate action can be decided.
Chillers Operation Log-sheets and Tracer Summit Monitoring
Service provider supervisorBMS and Chillers Operator - BCC
Discussed in BCC’s Training - conducted by J. Mendez last June 2006
6. Calibration of ADB Engineers and service providers on the chiller plant operation.
i. Trainings on Chillers and Tracer Summit Operation;ii. This 6-sigma control measure to be circulated in O&M group.
Service Provider Management – (BCC)
Joey MendezFM Shift Engineers
Provided BCC with Training on Chiller and Tracer Operation – June 2006
7. Monthly review of maintenance of the following: i. Chillers and Tracer Summit ii. Cooling towers and pumps, and associated electrical system and instrumentation devices. Improve as necessary.
i.Maintenance technical field report (Trane Philippines)ii. Computerized Maintenance Management System (CMMS) report - (BCC)
George Villamor (for Tracer and instrumentation)Assistant Engineers (for mechanical and electrical system)
On-going
8. Ensure availability of spare parts and supplies for the continuous operation of chiller plant.
Critical items inventory in Oracle system
ADB Assistant Mechanical Engineers
covered in 1st wave 6-sigma project
Control Control Measure And Guidelines
Control Measure And Guidelines
Table 1: SUNDAY OPERATION
CHILLERS CONDITION OF OPERATION REMARKS
RM no. 1
Run during half-day Gensets operational test. This unit is in normally unavailable status at Tracer Summit;
Manually start-up/ shut-down the chiller through Tracer Summit. Proceed to local start up/ shut-down if Tracer is not working.
RM no. 5 Maintain in operation if No GENSETS operational test and if the load is within 350-Tons.
Or after Genset operation if the load is within 350-tons
Closely monitor the chiller load.
RM no. 3 No Genset Operation and if load is over 350-Tons
Or after the Genset operation if load is over 350-tons
Closely monitor chiller load.
Manually start the chiller through Tracer Summit. Proceed to local start up/ shut-down if Tracer is not working.
Environment Sustainability – Pollution prevention through reduction in carbon and other pollutants emission.
Quality air-conditioning services to ADB HQ (customer) at a lower cost.
- END -
Lesson Learned:
1. Using Minitab in analyzing the data, we found the following:> chiller no. 4 operates efficiently at loads higher than its rated capacity;> chillers no.2 and 3 though they are identical in design duty but perform at
different efficiencies.
2. Consistent compliance to the chiller plant operation best practices can significantly contribute to optimum performance of the plant.
3. Strength and weaknesses of the chiller plant operation are clearly identify to put in effective operating measures.
4. Process is simplified for the service providers to carry out the operation.
5. Raw data becomes highly valuable when it is properly organized, analyzed and used correctly for effective continual improvement.