ABB STOTZ-KONTAKT a Zone Terminal MT/S 4.12.1 Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 1 The Security and Monitoring Program from ABB STOTZ-KONTAKT
18

The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

Jul 06, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

1

TheSecurity and

Monitoring Programfrom

ABB STOTZ-KONTAKT

Page 2: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

2

What is the Zone Terminal?

The Zone Terminal MT/S 4.12.1 is used for connecting passive sensors(e.g. reed contacts or glass breakage detectors) via monitored cablesto the ABB i-bus® EIB and /or for the connection of other potential free contacts in applications where greater security is required.

a

ABB i-bus EIB

1 2 3 4 5 6 7 8

9 10 11 12

AT/S 6.6.1

A B C D

6A 250 V ~

µ µ

µ µ µ µ

E F

a

ABB i-bus EIB

1 2 3 4 5 6 7 8

9 10 11 12

MT/S 4.12.1

A B C D

S/U Test

A B C D

+ - + - + -+ -

+-

Us12 V DC

+12 VS/U

+12 VTest

Un = 12 V DC EIBMonitored Cables

Sensors Zone Terminal EIB Components

Page 3: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

3

Application Areas :

The Zone Terminal MT/S 4.12.1 is designed to fulfill the function of a EIB security terminal for emergency, burglary und security monitoring functions in privat andsmall commercial buildings.

Burglary- Window- / Door Contacts- Motion Detectors- Glass Breakage Detectors

Water- Water Leakage Detectors

Emergency or Panic Alarm- Emergency Push Buttons

Fire- Smoke Detectors

Page 4: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

4

Product Charateristics :

4 Zone Loops

‘Walk test’ und ‘Set/Unset’ outputs for the control of common passive infrared motion detectors

LED status display - condition of the Zone Terminal and the outputs

Application software for ‘System’ or‘Stand Alone’ operation

VdS Device registration in progress

a

ABB i-bus EIB

1 2 3 4 5 6 7 8

9 10 11 12

MT/S 4.12.1

A B C D

S/U Test

A B C D

+ - + - + -+ -

+-

Us12 V DC

+12 VS/U

+12 VTest

Un = 12 V DC

Page 5: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

5

Technical Data Ι :

Inputs :4 Zones - Zone Loops A, B, C and DOpen circuit voltage - approx. 12 V DCShort circuit current - max. approx. 5 mAMaximum cable length - limited only by the maximum total cable

impedance per loop of 200ΩEnd of line resistor - 2,7 kΩ

Outputs :2 Control outputs - 'Set/Unset' und 'Walk test'Open circuit voltage - approx. 12 V DCOutput impedance - 1 kΩShort circuit current - max. approx. 12 mA

Page 6: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

6

Technical Data ΙΙ :

Power Supply :Voltage - 12 V DC ± 15%, SELVRipple - 1,0 VssCurrent consumption - < 50 mA, typically 20 mA

(without supply to external sensors)

Control und Display Elements :

LED and push-button for entering the physical address

6 LEDs - Status of the 4 Zones,status of the 'Set/Unset' and 'Walk test' outputs

Connection - Screw terminalsCable cross section 0,2 - 2,5 mm2

Installation depth / width - 68 mm / 4 modules @ 18 mm

Page 7: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

7

Communication Objects and Parameters : ‘Stand Alone’-Version

No. Function Type Objet Note

0 Telegr. Status Zone A 1 bit Send Zone Status

1 Telegr. Status Zone B 1 bit Send “

2 Telegr. Status Zone C 1 bit Send “

3 Telegr. Status Zone D 1 bit Send “

4 Set/Unset Request 1 bit Receive Request : set device

5 Reset Zones A ...D 1 bit Receive Reset the zones A, B, C, D

6 Supply Voltage Fault 1 bit Send Report loss of power supply

7 Set Confirmation 1 bit Send Device is set

Configurable Characteristics (via the ETS)Cyclic sending : Yes/No (Supply Disturbance) Debounce time : 10 ms ........ 130 ms

Condition of device on return of the EIB-Bus : Set/Unset; ‘Walk test’ On/Off

Page 8: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

8

Communication Objects und Parameters : ‘System’-Version

No. Function Type Object Note

0 Configuration 1 byte Receive/Read

1 Status 1 byte Send/Read

Configuration Object Status Object

Bit 0* Set/Unset Bit 0 .. 3 Zone A ... D - Trip/OKBit 1 Walk test On/Off Bit 4,5 no functionBit 2 Reset Bit 6 TamperBit 3..7 no function Bit 7 Power Supply Disturbance

Configurable Characteristics (via the ETS)Debounce time : 25 ms ........ 140 ms

* Bit 0 = LSB

Page 9: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

9

Parameter :

Page 10: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

10

Schematic of a Zone Loop (Primary Cable) :

NO Contact NC Contact

Zone Input Zone Loop (Primary Cable)

End of Line Resistor2,7 kΩ

GNDmax. number of sensors per loop is limited according to type

12 V DC

2,7 kΩSensors

VREF1

VREF2

+-

Page 11: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

11

Connection of Glass Breakage Detectors and Reed Contacts :Cross sectional representation of the connecting cable

1st

Sensorlast

SensorEnd of Line Resistor

2,7 kΩ

a

1 2 3 4 5 6 7 8

MT/S 4.12.1

A B C D

A B C D

+ - + - + -+ -

In each case any 2 cores running next to one another are connected to the zone loop or terminal and the two remaining wires to the next sensor.

The end of line resistor must be connected across the circuit after the last sensor.

Page 12: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

12

Sensors Ι :

Peripheral Protection Lock Monitoring

Magnetic Reedkontakt

Glass Breakage Detector

Closure Monitoringfor Windows

Lock Contact

Page 13: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

13

Sensors ΙΙ :

Indoor Protection Technical Sensors

Passive Infrared Sensor

Energency Push-Switch

Optical Smoke Detector

Water Leakage Detector

Page 14: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

14

EIB-Security Installation : (EG 3.20)

GMA-Controller(Bosch Telecom)

Control Element(Insta)

Display Unit(Insta)

Arming Device(Winkhaus)

PIRU U ~

CentralCentral 10

10

10

10

GMADisplay

EIB

Zone Terminal(ABB)

Sensor Interface(Merten)

Motion Detector Power Supplyand Alarm Siren(Bosch Telecom)

Page 15: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

15

Overview : EIB Security Program

LED’sBulbsAlarmsLocking ElementLocks

Binary OutputAT/S 6.6.1

LCD-DisplayLD/W

Panel UnitTL/E 12.1

Display and Alarm Signalisation

Switch InterfaceTS/U 4.1

Binary InputET/S 6.24.1

Set/Unset ControlSwitch

Reset Switch Control Inputs

Control

Zone TerminalMT/S 4.12.1

Monitoring

Window/ Door ContactsGlass Breakage SensorsMotion DetectorsSmoke DetectorsWater Leakage DetectorEmergency Push-Switch

Evaluation and Control Functions

Logic BlockLB/S 1.1

EIB Alarm functions (Evaluation) Group AlarmGroup Disturbance / TamperSet prevention/ acknowledge

EIB Central functionenLight On/OffBlind Up/DownPresence simulation

TeleswitchTS/AP

Remote Call

EIB

Page 16: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

16

Netzteile : NT/S 12.800 und NT/S 24.400

a

ABB i-bus EIB

1 2 3 4

NT/S 12.800

~ ~ +-

Us230 V AC

230 V AC = OK

Un12 V DC

12 V DC = OK12 V DC800 mA230 V AC

NT/S 12.800 12 V DC 800 mA SELV

NT/S 24.400 24 V DC 400 mA SELV

Overload protection :

Thermal and electrical

Output short circuit protected (continuous)

Status LEDs for main’s supply and output voltage

Application :Zone Terminal MT/S 4.12.1Binary Input ET/S 6.24.1Panel Unit TT/E 12.1, TL/E 12.1.......Universal I/O UK/S 32.1

Page 17: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

17

Power Suppply :

Zone TerminalMT/S 4.12.1

ABB i-bus EIB

SV/S 30.640

L N PE 230 VAC

29 VDC- +

I>Imax

ON

RESET

S1

230V AC

RESET

29V DC29V DC640mA

S1

a

a

ABB i-bus EIB

3 41 2

SV/S 12.300

P N+-12 V DC

Un = 12 V DC

Us 230 VAC

ON/U = OK

Motion DetectorIR/N

EIB

230 V AC

Voltage SupplySV/S 30.640

230 V AC

Netz

USV

12 V DC

Voltage SupplyNT/S 12.800

Page 18: The Security and Monitoring Program from ABB STOTZ-KONTAKT · Zone Terminal MT/S 4.12.1 STO/MG1/Beniston 20.01.98 MGTEng.ppt 2 What is the Zone Terminal? The Zone Terminal MT/S 4.12.1

ABB STOTZ-KONTAKT a

Zone Terminal MT/S 4.12.1Zone Terminal MT/S 4.12.1

STO/MG1/Beniston 20.01.98 MGTEng.ppt

18

DocumentationZone Terminal

• New Product Prospect• Application Handbook• User Handbook• Specification Text• Overhead Set