2009 Red Valve Co. / Tideflex Technologies. All rights reserved. The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc.
35

The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Mar 13, 2018

Download

Documents

phungque
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

2009 Red Valve Co. / Tideflex Technologies. All rights reserved.

The Science of Mixing Water Storage Tanks

Presented by:

Jason Barrett, Flomec Inc.

Page 2: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Ground Level Tanks (Rectangular) Ground Level Tanks (Circular) Elevated Tanks Standpipes

Common Types of Water Storage Tanks

All Have Unique Challenges with Short-Circuiting and Mixing Solely based on Volume, Geometry, and Inlet/Outlet Pipe Configuration

Page 3: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

1) Minimize Short-Circuiting and Stagnant Areas (SEPARATE INLET AND OUTLET PIPE) 2) Achieve Complete Mixing During Fill Cycle (MIXING TIME LESS THAN FILL TIME) 3) Achieve Adequate Turnover to Minimize Water Age (FLUCTUATE LEVELS)

** MAINTAIN ADEQUATE DISINFECTANT RESIDUAL **

How to Maintain Water Quality in Reservoirs

COMBINATION OF MIXING SYSTEM DESIGN AND TURNOVER/FLUCTUATION OF THE TANK

DESIGN

OPERATIONS

Page 4: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Short Circuiting First In, Last Out (Last in, First Out) Water in Close Proximity to Inlet/Outlet is Continually Turned Over. Water away from Inlet/Outlet stagnates. Some States Now Mandate Separate Inlet/Outlet Pipes

Common Inlet / Outlet Separate Inlet / Outlet

Page 5: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Computational Fluid Dynamics (CFD) Modeling

Georgia Institute of Technology and Red Valve Company

2006 AwwaRF Project

Page 6: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

CAUTION When Separating Inlet and Outlet

• Must Understand the Circulation Patterns in Order to Know Where Mixing Happens Last. Outlet(s) Would Go in Those Locations

• Getting Inlet and Outlet “As Far Apart As Possible” is Often the Wrong Assumption

• Circulation Patterns Change with Temperature Differences Between Inlet and Tank Water

Page 7: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Multiple Inlet Ports Result in Up to 50% Faster Mixing Compared to Single Inlets

Single Shell Penetration 5-Port TMS

Animations courtesy of :

Los Angeles Department of Water & Power Northwest Hydraulic Consultants

Page 8: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Mixing time (hours) = K (V2/3 / M1/2) K = Coefficient (based on Mixing Efficiency of Pipe/Manifold) V = Volume of water in tank at start of fill, feet3 M = Momentum = flow rate x velocity (Q * U)

Q = Inflow rate, cfs U = Inflow velocity, feet per second

Empirical Mixing Time Equation

How Long doYou Need to Fill Tank to Mix it?

Caution: No Variables in Equations or Limitations of Equation for Considering Temperature Differences

Between Inlet Water and Tank Water

Page 9: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Mixing Time Equation is Limited to Same Inlet and Tank Water Temperature

■ Mixing Time Equation May Grossly Underestimate Fill Time Required to Mix

■ Jet Must Reach Water Surface to Mix Tank

■ Mixing Will Only Occur to Terminal Rise Height (TRH) of Jet

■ Below TRH - Adequate Mixing, Temperature, and Residual

■ Above TRH – No Mixing, Water Age Continually Increases With Each Fill & Draw Cycle, Lose Residual

■ Have No Idea of Potential Problem Even if Sampling Outside of Tank

2oF Colder Inlet Water

Page 10: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Effect Of Colder Inlet Water on Mixing in Reservoir

INLET 4° F COLDER Will Short-Circuit Even with Separate Outlet Pipe

Will Not Mix Tank Regardless How Long it is Filled

ISOTHERMAL

Will Not Short-Circuit with Separate Outlet Pipe

Will Mix Tank IF Fill Long Enough

CFD Model – 2.5MG Reservoir (120’ Dia. X 30’ SWD)

Page 11: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Temperature and Cl2 Residual Data 4MG Steel Reservoir – Northern California

Temperature Variation Thru Depth (Thermocline) Indicates Incomplete Mixing and Warns of Potential Water Quality Problems

Warning: Samples Taken Just Outside of Tank Would Never Show the W.Q. Problem

Thermocline

Water Quality Problem

Page 12: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground
Page 13: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Mixing Time Comparison ( 48” and 12” Inlet )

Increasing Velocity Easier To Do Than Increasing Flow Rates, but Requires Careful Considerations With Headloss

Page 14: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Greener than Green. Passive. Uses energy source inherent to distribution systems – differential pressure

All TMS Configurations are CFD and/or Scale Modeled and Field Validated for Every Tank Style

Achieves Separate Inlet and Outlet on a Single Manifold Pipe Achieves Complete Mixing with Variable Orifice Tideflex Inlet Nozzles No Maintenance - No Mechanical Parts NSF61 Certified Valves Connected to Inlet/Outlet Pipe – No Additional Tank Penetrations

Required Easy Retrofit (dry or wet installation) Complete System Design At Least 30 year life

Tideflex Mixing System (TMS) Features

Page 15: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

TMS for Circular Reservoirs

Page 16: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

OUTLETS

Use of Tideflex for Inlet/Outlet Separation on Single Manifold Pipe

INLETS

DUCKBILL INLET NOZZLES

OUTLET CHECK VALVES

OLD 2-PIPE SYSTEM

DUCKBILL MANIFOLD PIPE

Page 17: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

PROBLEM

TIDEFLEX “Duckbill” Check Valves

SOLUTION

Overflow Pipe Protection Overflow Security

Valve (OSV)

Page 18: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

PROBLEM

TIDEFLEX Research & Development

FINITE ELEMENT ANALYSIS (FEA)

INDEPENDENT HYDRAULIC TESTING

OVER 50 VARIATIONS IN GEOMETRY AND STIFFNESS PER SIZE FOR HYDRAULIC

OPTIMIZATION OF TMS

Page 19: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Optimized Hydraulics of Tideflex

Tideflex Inlet Nozzles Maximize Jet Velocity at ALL Flow Rates Compared to Fixed-Diameter Pipe

Page 20: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

TMS Manifold Hydraulics Modeling

• Hydraulics account for all pipe, fittings, valves

• Use hydraulic data in Mixing Analysis model

• Iterate quantity, size, and stiffness of Tideflex Nozzles until complete mixing is achieved based on tank turnover

Page 21: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Typical TMS for Rectangular Reservoirs

Page 22: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Wet Riser

Inlet

Dry Riser Inlet

Elevated Storage Tanks

Page 23: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

TMS for Elevated Tank with Wet Riser

INLET NOZZLES

OUTLETS

Wet Riser Typically 36”-96” Diameter KNOCKS MOMENTUM OUT OF INFLOW!!

CFD- Wet Riser Inlet, Cold Water

CFD- Multiport Inlet, Isothermal

Page 24: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

TMS for Pedesphere, Hydropillar and Composite Elevated Tanks

Tideflex Inlet Nozzles

Waterflex Outlet Valves

Page 25: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

CFD Model – Elevated Hydropillar

Two Inlet Valves at Two Elevations (Four Total)

Page 26: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Sampling 1.5MG and 2MG Elevated Tanks with and without TMS - McKinney, TX

2MG Composite Elevated with TMS

2MG Composite Elevated with TMS

1.5MG Composite Elevated without TMS

Page 27: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

TMS for Standpipes TIDEFLEX INLET NOZZLES

WATERFLEX OUTLET VALVES

2008 Red Valve Company/Tideflex Technologies. All rights reserved

Page 28: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Clark Public Utilities, WA Temperature Profiling Adjacent Standpipes, 0.5 MG and 1.5MG (125’ Deep)

Tideflex Mixing System installed in

larger tank

Smaller Tank Left with Common

Inlet/Outlet at Bottom of Tank

Temp. Data Loggers Installed Every 20’ Thru Depth. Logged Temp’s Every 30 minutes for

Over 1 Year

Page 29: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Temperature vs. Depth Data

7/12/03

60

62

64

66

68

70

72

74

76

10 30 50 70 90

0.5 MG 1.5 MG

8/1/03

60

62

64

66

68

70

72

74

76

10 30 50 70 90

0.5 MG 1.5 MG

Without TMS

Without TMS

With TMS With TMS

Stratification Gets Worse in Smaller Tank from July to August

Stratification Eliminated in Larger Tank with Mixing System

Page 30: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Region of Peel (Canada) Mono Mills 0.55MG Standpipe (30’ Dia. x 110.5’)

Discovered 30’ Dia. x 10’ Deep Slug of Ice in May of 2005

Page 31: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Region of Peel Mono Mills 0.55MG Standpipe (30’ Dia. X 110.5’)

Ice removal took 2 weeks and $27,000

Page 32: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Region of Peel Mono Mills 0.55MG Standpipe Installed TMS

Page 33: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Region of Peel Mono Mills 0.55MG Standpipe Installed TMS

Page 34: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Consider: External Energy Source Capital Cost Operational Cost No Impact on Water Age No Separation of Inlet/Outlet Safety? Electric & Water Maintenance Roof Reinforcement Req’d Another Penetration for Wires Interfere with Cathodic Protection Contamination? Vandalism NSF Certified? Limited Installations Limited Testing and Field Validation

Mechanical Mixers (Electric and Solar Powered)

Simply put, mechanical mixers add another source of energy to the tank to mix. However, there is already a built-in source of energy –

differential pressure. Tanks need to fill and draw to minimize water age. The differential pressure

present during the fill can mix the tank with properly designed mixing system.

Page 35: The Science of Mixing Water Storage Tanks Operations/TMS...The Science of Mixing Water Storage Tanks Presented by: Jason Barrett, Flomec Inc. Ground Level Tanks (Rectangular) Ground

Complete System Design and Hydraulic Analysis