Top Banner
57

The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

Mar 07, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,
Page 2: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 1

(Translation of the original instructions)

INDEX

1 DISCLAIMER ............................................................................................................................................................................................................. 2

2 EU- DECLARATION OF CONFORMITY ......................................................................................................................................................................... 3

3 SAFETY INSTRUCTIONS AND WARNINGS ................................................................................................................................................................... 4

3.1.1 Water draining, packing, transport and storage instructions of DTE installations. .......................................................................................... 5 3.1.2 Draining water from the machine .................................................................................................................................................................... 5 3.1.3 Packing, transport and storage instructions ..................................................................................................................................................... 7 3.2 Correct applications............................................................................................................................................................................................... 7 3.3 Application area .................................................................................................................................................................................................... 8

4 GENERAL DESCRIPTION ............................................................................................................................................................................................ 9

4.1 General description CoolMaster (K)(N)(NF)(NO)(NOF) .......................................................................................................................................... 9 4.2 General description CoolMaster (L)(O)(OF) ......................................................................................................................................................... 11 4.3 Identification ....................................................................................................................................................................................................... 13

5 COMMISSIONING ................................................................................................................................................................................................... 14

5.1 Commissioning CoolMaster (K)(N)(NF)(NO)(NOF) ............................................................................................................................................... 14 5.2 Commissioning CoolMaster (L)(O)(OF) ................................................................................................................................................................ 15 5.3 Refrigerant circuit with ball valves CoolMaster (L)(O)(OF) .................................................................................................................................. 17 5.4 General CoolMaster (L)(O)(OF) ............................................................................................................................................................................ 18 5.5 Connecting cooling water pipes........................................................................................................................................................................... 19 5.6 Connecting overflow pipe .................................................................................................................................................................................... 20 5.7 Connecting power supply .................................................................................................................................................................................... 20 5.7.1 Plug-in terminals ............................................................................................................................................................................................ 21 5.7.2 Screw terminals .............................................................................................................................................................................................. 22 5.8 Connecting external contacts .............................................................................................................................................................................. 23 5.9 Water quality ...................................................................................................................................................................................................... 23 5.10 Filling of (external) pipes and systems CoolMaster (K)(L) .................................................................................................................................... 24 5.11 Filling of (external) pipes and systems CoolMaster (N)(NF)(NO)(NOF)(O)(OF)..................................................................................................... 25 5.12 Filling of the systems CoolMaster (K)(L)............................................................................................................................................................... 28 5.13 Filling of the systems CoolMaster (N)(NF)(NO)(NOF)(O)(OF) ............................................................................................................................... 29 5.14 Deaerating .......................................................................................................................................................................................................... 30 5.15 Setting thermostat .............................................................................................................................................................................................. 31 5.16 Commissioning after long standstill .................................................................................................................................................................... 32

6 MEANING OF ALARMS (IF APPLICABLE) .................................................................................................................................................................. 33

7 FAULT ANALYSIS..................................................................................................................................................................................................... 34

8 MINIMUM INSPECTION-INTERVAL SCHEME ............................................................................................................................................................ 35

9 CLEANING OF THE MACHINE................................................................................................................................................................................... 36

10 CHECKS .............................................................................................................................................................................................................. 36

11 SERVICE ............................................................................................................................................................................................................. 36

12 GUARANTEE ...................................................................................................................................................................................................... 37

13 REMOVAL .......................................................................................................................................................................................................... 37

14 APPENDIX .......................................................................................................................................................................................................... 38

14.1 Connection diagram filling the system ................................................................................................................................................................ 39 14.2 Watertreatment .................................................................................................................................................................................................. 40 14.3 Guidline for water quality in DTE installations .................................................................................................................................................... 41 14.4 User manual thermostat ..................................................................................................................................................................................... 42 14.5 Safety information sheets .................................................................................................................................................................................... 47 14.6 Comments ........................................................................................................................................................................................................... 55 14.7 Technical information .......................................................................................................................................................................................... 56

** SSppeecciiffiiccaattiioonn lliisstt .............................................................................................................................................................................................................. 56

** MMaacchhiinnee ddrraawwiinngg ............................................................................................................................................................................................................ 56

** PPaarrttss lliisstt .......................................................................................................................................................................................................................... 56

** FFllooww sscchheemmee .................................................................................................................................................................................................................... 56

** EElleeccttrriiccaall sscchheemmee ............................................................................................................................................................................................................. 56

** UUsseerr mmaannuuaall tthheerrmmoossttaatt ................................................................................................................................................................................................. 56

** SSaaffeettyy ddaattaa sshheeeett rreeffrriiggeerraanntt .......................................................................................................................................................................................... 56

** OOtthheerr ............................................................................................................................................................................................................................... 56

ENGLISH

Page 3: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 2

11 DDiissccllaaiimmeerr

The manufacturer reserves the right to change parts at any time to change, without prior or immediate notice to the customer. The contents of this manual may also be changed without prior warning. This is an original manual, and is valid for the machine in its standard version. The manufacturer can therefore not be held liable for any damages resulting from specifications that deviate from the standard version delivered to you. For information on adjustments, maintenance and repair insofar as this guide does not provide it, please contact the technical department of your supplier. This manual was drawn up with the greatest possible care, however the manufacturer cannot accept any liability for any errors in this book or any consequences thereof. Finally, this manual is a personal and confidential communication to the user. No part of this publication may be reproduced, copied, altered or transmitted in any form or in any manner whatsoever without written permission from Dutch Thermal Engineering n.v.

Page 4: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 3

22 EEUU-- DDeeccllaarraattiioonn ooff ccoonnffoorrmmiittyy

Manufacturer: D.T.E. n.v. Address: Westerbroekstraat 18 7011 EX GAANDEREN / HOLLAND Hereby certifies that:

The CoolMaster meets the requirements of the Machinery Directive (Directive 2006/42/EC, as amended), and the national legislation implementing this Directive;

Meets the provisions of the following other EC directives.

- 2014/35/EU Low voltage directive - 2014/30/EU EMC-directive - 2014/68/EU Pressure Equipment Directive (PED)

- Classification: Category III, Module B + C1 (DTE type approval, date dec. 2016)

- Installation Type: Direct expansion - Refrigerant: HFK (group 2) - Design pressure: HP 31,0 bar(o) : LP 18,8 bar(o) - Design temperature: -20 / +100 °C

EC-Type examination Certificate: INTRON-DA-10-0008 Notified Body: SGS INTRON CERTIFICATIE N.V., Culemborg, the Netherlands NoBo identification number: 0958

And certify that: The following (parts of) harmonized standards are applied:

- NEN-EN-IEC 60204-1:2006/C11:2010 - NEN-EN-ISO 12100:2010 - NEN-EN 378-2:2016 - NEN-EN-ISO 13857:2008

The following (parts of) national technical standards and specifications are used:

- Cooling system leaktightness (RLK). Person authorised to draw up technical documentation: Mr T.J.H.M Ratering (Manager Engineering) Made in Gaanderen on 09-12-2016 F.G.R. Geerdink

General Manager

Page 5: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 4

33 SSaaffeettyy iinnssttrruuccttiioonnss aanndd wwaarrnniinnggss

Always observe the following safety instructions and warnings! WARNING! Warning of possible damage to the device, environment or user WARNING! Warning of electricity and / or current threat WARNING! Warning of possible entrapment hazard Compliance with the technical manual is a prerequisite for fault-free operation and the honouring of any warranty claims. Therefore please read the technical manual carefully before you start working with your device! The manual must therefore be kept near the machine. The CoolMaster is under pressure with a refrigerant, more information about this can be found in 14.5. This user’s manual was written for types similar to DTE CoolMaster (K), (N), (NF), (NO), (NOF), (OF), (L), (O) type machines. Therefore certain topics may not apply to your machine. For the same reason, the images may differ slightly from how your machine actually looks. The machine drawing is included as an attachment with the correct dimensions and connections.

Page 6: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 5

33..11..11 WWaatteerr ddrraaiinniinngg,, ppaacckkiinngg,, ttrraannssppoorrtt aanndd ssttoorraaggee iinnssttrruuccttiioonnss ooff DDTTEE iinnssttaallllaattiioonnss..

These actions are general and have to been carried out, of course, if applicable for the application by qualified personal!

33..11..22 DDrraaiinniinngg wwaatteerr ffrroomm tthhee mmaacchhiinnee

Step 1: Close the filling connection (D1) Step 2: Drain the Water tank of the cooling system by opening the ball valve. (See Figure 3.1) Further draining of the Water tank with a wet vacuum cleaner. (See Figure 3.2) Step 3: Drain the Tempering/Hot water tank by opening the drainage/overflow valve. (See Figure 3.3) Step 4: If present, switch on all solenoid valve by external power. Step 5: If present, switch al 3 way-mix- regulation valve into the middle position. (See Figure 3.4)

Figure 3.1

Figure 3.2

Figure 3.3

Figure 3.4

Page 7: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 6

Step 6: Drain all connection on the machine with a wet vacuum cleaner. (See Figure 3.5) Step 7: Open all BVS valves if present (See flow diagram) and remove the interior (See Figure 3.6). Drain the connection on the outside of the machine with a wet vacuum cleaner. The interior will be transported separately and has to be assembled before commissioning. Step 8: Remove all plugs of the water pumps. After this drain al pumps with a wet vacuum cleaner. (See Figure 3.7 and Figure 3.8)

Figure 3.5

Figure 3.6

Figure 3.7

Figure 3.8

Page 8: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 7

33..11..33 PPaacckkiinngg,, ttrraannssppoorrtt aanndd ssttoorraaggee iinnssttrruuccttiioonnss

Before packing, transport and storage, first follow the instructions of chapter 3.1.1 Draining water from the machine.

Attention! Before transport the machine has to be protected with the also delivered cardboard box or has to be wrapped with bubble wrap. The machine has to be transported and stored perpendicular at all time on its fundament on the provided pallet! The machine has to be placed perpendicular on its fundament at all time. Attention! In no way the machine can be stacked or overturned. This during transport and storing as well during repairs and commissioning. Even when the machine is not used it should be perpendicular at all times. Attention! Not following these instruction can cause big damage to the machine. Use at all time the right equipment such as a pallet truck and a forklift truck.

33..22 CCoorrrreecctt aapppplliiccaattiioonnss

The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated, frost-free building! The CoolMaster (NO) is applicable for outdoor installation with ambient temperature until - 15°C by preference under shelter. The CoolMaster (NOF) is applicable for outdoor installation with ambient temperature until - 30°C by preference under shelter. The CoolMaster (K) is only suitable for tap water of drinking quality. The CoolMaster (N)(NF)(OF)(NO)(NOF) is only suitable for tap water of drinking quality, mixing with appropriate antifreeze (glycol) in suitable mixing ratio. The CoolMaster (L) with external condenser is only suitable for tap water of drinking quality. The CoolMaster (O)(OF) with external condenser is only suitable for water/glycol. Information on the correct water-glycol ratio and the recommended type of glycol can be found on the specification list corresponding to the machine. ATTENTION! The CoolMaster must always have at least 3 metres free airflow above it. With an external condenser, this also applies to the condenser. Attention! In no way the machine can be stacked or overturned. This during transport and storing as well during repairs and commissioning. Even when the machine is not used it should be perpendicular at all times. Attention! Not following these instruction can cause big damage to the machine.

Page 9: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 8

33..33 AApppplliiccaattiioonn aarreeaa

CAUTION! Application is prohibited: - In explosive atmospheres. - In environments with hazardous oils, acids, gases, fumes, substances, radiation, etc. - Corrosive environment.

Page 10: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 9

44 GGeenneerraall ddeessccrriippttiioonn

44..11 GGeenneerraall ddeessccrriippttiioonn CCoooollMMaasstteerr ((KK))((NN))((NNFF))((NNOO))((NNOOFF))

The CoolMaster is a complete plug and play water cooler with integrated water cooler tank, pump, condenser and controls. Is built for perfect cooling in closed industrial process water systems. CoolMaster sample drawing range L1*:

* This is a sample drawing, the relevant machine drawing is included as an attachment!

Page 11: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 10

A

=

Cooling water inlet, see specification list

B

=

Cooling water outlet, see specification list

C+E =

Drainage/Overflow cooling section, see specification list

D1

=

Filling water connection, see specification list (not present in machines, specified as (N)(NO)(NOF)(O)(OF))

D2

=

Manual filling device

F = Bushing coupling electrical supply cable G = Control panel H = Incoming condenser air I = Service panel

CAUTION: POSITION THE SERVICE PANEL (I) BEFORE SWITCHING ON THE MACHINE!

K = Outgoing condenser air L = Legs, U-Profile P = Sight glass

Maximum glycol/water level

Minimum glycol/water level

V = Refrigerant relief (if applicable)

Page 12: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 11

44..22 GGeenneerraall ddeessccrriippttiioonn CCoooollMMaasstteerr ((LL))((OO))((OOFF))

The CoolMaster is a complete plug and play water cooler with integrated water cooler tank, pump, external condenser and controls. Is built for perfect cooling in closed industrial process water systems. CoolMaster sample drawing range L1*:

External condenser sample drawing range L1*:

* This is a sample drawing, the relevant machine drawing is included as an attachment!

Page 13: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 12

A

=

Cooling water inlet, see specification list

B

=

Cooling water outlet, see specification list

C+E =

Drainage/Overflow cooling section, see specification list

D1

=

Filling water connection, see specification list (not present in machines, specified as (N)(NO)(NOF)(O)(OF))

D2/D3

=

Manual filling device

E2

=

De-aeration water tank (if applicable)

F = Bushing coupling electrical supply cable G = Control panel H = Incoming condenser air I = Service panel

CAUTION: POSITION THE SERVICE PANEL (I) BEFORE SWITCHING ON THE MACHINE!

K = Outgoing condenser air L = Legs, U-Profile

P =

Hotgas pipe, see specification list

Q =

Liquid pipe, see specification list

S = Sight glass

Maximum glycol/water level

Minimum glycol/water level

V = Refrigerant relief (if applicable)

Page 14: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 13

44..33 IIddeennttiiffiiccaattiioonn

Standard Type plate: The identification plate is located on the left side from the machine. (Figure 4.1)

A = Machine number/ serial number

Figure 4.1

B = Machine type

C = Voltage

D = Maximum Current

E = Number of phases

F = Frequency in Hz.

G = Refrigerant type

H = Refrigerant mass

I = Maximum ambient temperature

J = CO2 equivalent

K = GWP-values

L = Thermostat Temperature range

M = Maximum pressure

N = Compressor lubrication

O = Compressor oil volume

P = Built

Q = Weight

R = Cooling capacity

Type plate according 2014/68/EU PED-Directive: The identification plate is located on the left side from the machine. (Figure 4.2)

A = Machine number/ serial number

Figure 4.2

B = Machine type

C = Voltage

D = Maximum Current

E = Number of phases

F = Frequency in Hz.

G = Thermostat Temperature range

H = Maximum ambient temperature

I = Built

J = Weight

K = Cooling capacity

L = Category

M = Module

N = Product low pressure

O = Product high pressure

P = Product temperature

Q = GWP-values

R = Refrigerant type

S = Refrigerant mass

T = CO2 equivalent

Page 15: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 14

55 CCoommmmiissssiioonniinngg

55..11 CCoommmmiissssiioonniinngg CCoooollMMaasstteerr ((KK))((NN))((NNFF))((NNOO))((NNOOFF))

CAUTION! The installation work must be carried out by a certified professional! Place the CoolMaster at a level position and at least 1 meter from a wall. For a good functioning of the CoolMaster we recommend keeping the distance between the CoolMaster and the user to a minimum. CAUTION! The diameter of the pipes/tubes must correspond with the connections on the CoolMaster. See for the connections chapter 4.1 on the CoolMaster. For diameters see the corresponding specification list. The tubes must be suitable for use in the same conditions as those for which the CoolMaster is suitable (pressure and temperature). Consult the specification list for this information. The hoses MUST be reinforced with braided fibre to prevent kinking the hose. CAUTION! When using metal pipes, the galvanic series of the materials used should be taken into account to prevent corrosion.

Page 16: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 15

55..22 CCoommmmiissssiioonniinngg CCoooollMMaasstteerr ((LL))((OO))((OOFF))

CAUTION! The installation work must be carried out by a certified professional! For the correct operation of the CoolMaster we recommend that you keep distance between the CoolMaster and the user as small as possible. The cooling water pipe between the CoolMaster and the user must be max. 4 metres. We recommend a max. distance between the CoolMaster and External Condenser of 15 metres. CAUTION! The diameter of the pipes/tubes must correspond with the connections on the CoolMaster and external condenser. See for the connections chapter 4.2 on the CoolMaster. For diameters see the corresponding specification list. For connect the pipes like ball valves, see 5.3

Page 17: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 16

Place the external condenser at a platform or a roof at a level position. The airflow direction of the condenser depends on which type external condenser installation. The space around the condenser can be calculated Figure 5.1 and Figure 5.2. Vertical installation external condenser:

Vertical installation external condenser:

Place the external condenser at a level position and at least 1 meter from a wall.

Figure 5.1

Figure 5.2

Page 18: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 17

55..33 RReeffrriiggeerraanntt cciirrccuuiitt wwiitthh bbaallll vvaallvveess CCoooollMMaasstteerr ((LL))((OO))((OOFF))

Connect the hot gas (P) and the liquid (Q) pipes. NOTE! The CoolMaster and the condenser are already factory filled with the right amount of refrigerant. The connection should only be made by specialized cool technical engineers. Do not open the ball valves when the connections are not correctly made! Open the ball valves after vacuuming! NOTE! The system is under pressure. We recommend checking the connection for leaks after this installation.

Page 19: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 18

55..44 GGeenneerraall CCoooollMMaasstteerr ((LL))((OO))((OOFF))

In case the vertical distance between the external condenser and the CoolMaster is more than 3 meters there should be provide an so called “Oil trap” in the hot gas pipes. At every next difference in level of 9 meters there should be provide an extra Oil trap. (See drawing) The external condenser must be set up at the same height or higher than the CoolMaster. NOTE! The connection between CoolMaster and the external condenser should not exceed 15 meters! (for piping diameters, see flow scheme)

NOTE! THE PIPES BETWEEN THE CoolMaster AND THE EXTERNAL CONDENSER CAN BE HOT! If these pipes accidentally can be touched it is recommendable to isolate these pipes. Connect the electrical cable(s) from the CoolMaster to the control switch (S) and fan(s) at the condenser. These cable(s) may not touch the hot gas (P) and the liquid pipes (Q) of the condenser, as these pipes could be very hot! The cable(s) are already connected at the CoolMaster. For the connection of these cable(s), see electrical diagram. Switch on main switch on control panel (G) to enable the crankcase heating of the compressors. At the first start up is not allowed to switch the CoolMaster immediately on by means of the control switch. There must be a delay time of at least 24 hours before the CoolMaster is switched on for the first time by means of the control switch or external start/stop. During this period the sump heater will evaporate the coolant out of the sump oil of the compressor. NOTE! The CoolMaster may not be switched off by means of the main switch, due to the crankcase heating which will be switched off. To prevent serious damage to the CoolMaster, the crankcase heating may never be switched off. When the CoolMaster is to be switched off, it must be done by means of the control switch which is located at the control panel (G). EVEN ON LONG TERMS OF STANDSTILL! WARNING! In case of shutdown with control switch all parts in the control box will still be under tension. If this will result into hazardous situations, in example maintenance to the CoolMaster, the CoolMaster needs to be switched off with the main switch.

Page 20: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 19

55..55 CCoonnnneeccttiinngg ccoooolliinngg wwaatteerr ppiippeess11

Attention! Before making any connections to the CoolMaster, clean the external pipes. Dirt must be prevented from entering the CoolMaster. It may cause serious damage to the system and the CoolMaster. Connect the following pipes: - A and B: cooling water pipes between CoolMaster and the user. - D1: If you wish to fill automatically (does not apply to machinery specified as (N)(NO)(NOF)(O)(OF)). Step 1: 1. Install the ball valve (BVS-1) on the cooling water inlet (A). 2. Install cooling water pipe between CoolMaster (BVS-1) and User. (See Figure 5.3) The ball valve (BVS-1) must be kept closed, unless otherwise indicated! Step 2: 1. Install the ball valve (BVS-2) on the cooling water outlet (B). 2. Install the ball valve (BVS-3) on the T-piece (central section). 3. Install the cooling water pipe between CoolMaster (on the T-piece) and the user. (See Figure 5.4) The ball valves (BVS-2 and BVS-3) must be kept closed, unless otherwise indicated! Step 3: 1. Connect the cooling water pipes between CoolMaster and user (BVS-1 and BVS-3). (See for supplied connecting diagram) 2. Connect D1 to a water tap if you wish to fill automatically. (does not apply to machinery specified as (N)(NO)(NOF)(O)(OF))

Figure 5.3

Figure 5.4

1 Ball valves are not supplied as standard. Available by DTE with art. no. 87000090

Page 21: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 20

55..66 CCoonnnneeccttiinngg oovveerrffllooww ppiippee

Connect the overflow pipe (C+E). To enable good outflow of superfluous water, the overflow pipe must be able to flow out into the open sewer without any foreseeable obstructions. The length of the overflow pipe should be kept to a minimum. The pipe should also flow downwards, from the perspective of the CoolMaster (C+E). CAUTION! For machines filled with a mixture of water and glycol (machines specified as (N)(NO)(NOF)(O) the excess mix from connection E may not be discharged into public sewers for environmental reasons. Connect refrigerant relief (V). This connection is an safety valve which blows off refrigerant in unusual extreme conditions. Because refrigerant results to asphyxiation, the refrigerant relief (V) must be connected to the open air at a position where it is not dangerous! The refrigerant relief between the CoolMaster and the open air should be fixed tightly and must not be longer than 20 meters. The minimum internal diameter must correspond with the diameter of connection on the CoolMaster. (if applicable)

55..77 CCoonnnneeccttiinngg ppoowweerr ssuuppppllyy

Attention! Work may only be carried out on the electrical installation of the CoolMaster by an authorised, professionally competent person.

Attention! The CoolMaster must only be connected to a clockwise rotary field.

Turn off the main switch on the control panel (G). Connect your electrical power supply cable to the appropriate terminals in the control box via the cable entry (F). Refer to the electro-technical diagram for the connection of the cable cores. Consult the diagram number as stated on the technical specifications sheet corresponding to the serial number of the CoolMaster. Consult the type plate for the correct voltage. Attention! Ensure the voltage as stated on the type plate is also the voltage on each phase wire. Of no less importance is the mains frequency (50 or 60 Hz) corresponding to the frequency on the type plate. The maximum voltage deviation is +6% and –10% from the voltage indicated on the type plate

Page 22: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 21

55..77..11 PPlluugg--iinn tteerrmmiinnaallss

Use a screwdriver with a 3mm wide point. Push the screwdriver in the square recess to open the spring. (See Figure 5.5)

Figure 5.5

Place the 10mm stripped wire with cable end into the round

recess and press the wire into the terminal as deeply as possible. (See Figure 5.6)

Figure 5.6

Remove the screwdriver. Check whether the wire is firmly connected. (See Figure 5.7)

Figure 5.7

Page 23: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 22

55..77..22 SSccrreeww tteerrmmiinnaallss

Unscrew both M4 screws. (See Figure 5.8)

Figure 5.8

Insert the 10mm stripped wire, which should be fitted with a wire

ferrule, into the designated recess and press it as deeply as possible into the terminal. (See Figure 5.9)

Figure 5.9

Screw both M4 screws with a tightening torque of 1.5<1.8Nm.

(See Figure 5.10)

Figure 5.10

Page 24: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 23

55..88 CCoonnnneeccttiinngg eexxtteerrnnaall ccoonnttaaccttss

Also connect the electrical cables for the external contact(s). See for supplied wiring diagram.

55..99 WWaatteerr qquuaalliittyy

CAUTION! The CoolMaster is not suitable for use with demineralized water or water containing high levels of minerals or iron.

The filling water which is used must be of good quality. It must at least be of drinking water quality and the water must not contain high levels of lime and/or iron, as it may cause serious damage. You must check the water regularly. The minimum filling pressure must be 2,5 bar. See appendix 14.2 for extra information. See appendix 14.3 for directive water quality.

CAUTION! The CoolMaster (N)(NF)(NO)(NOF)(O)(OF) are only suitable for tap water of drinking water quality mixed with the correct ratio of a suitable anti-freeze (glycol).

Page 25: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 24

55..1100 FFiilllliinngg ooff ((eexxtteerrnnaall)) ppiippeess aanndd ssyysstteemmss CCoooollMMaasstteerr ((KK))((LL))

Step 1: 1. All the connections must be made in accordance with §5.5 2. Turn the air vent(s) in your system to “open”. (The venting must take place at the highest point(s) in pipe(s)) CAUTION! Do not use automatic air vents! CAUTION! CoolMaster (N)(NF)(NO)(NOF)(O)(OF) filling procedure in §5.13 3. Connecting the filling water (min. 2.5 Bar) to BVS-3. 4. Turn the valve (BVS-3) to “open” position. (See Figure 5.11)

Step 2: Excess air will be released from the pipe(s) though the air release valve(s). If the water spills from the air release valve(s), the external pipes/systems are filled with water. 1. Turn the ball valve (BVS-3) to “closed” position. (See Figure 5.12) 2. Turn the water fill line to “closed” position. 3. Remove the fill water line which is mounted on BVS-3. Step 3: 1. Turn the ball valve (BVS-1) to “open” position. (See Figure 5.13) 2. Turn the ball valve (BVS-2) to “open” position. (See Figure 5.14) When these steps have been completed correctly, the entire system will be filled with water.

Figure 5.11

Figure 5.12

Figure 5.13

Figure 5.14

Page 26: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 25

55..1111 FFiilllliinngg ooff ((eexxtteerrnnaall)) ppiippeess aanndd ssyysstteemmss CCoooollMMaasstteerr ((NN))((NNFF))((NNOO))((NNOOFF))((OO))((OOFF))

Step 1: 1. The connections must be made in accordance with §5.1 The ball valve (BVS-1 and BVS-2) must be kept closed, unless otherwise indicated!

CoolMaster (N)(NF)(NO)(NOF)(O)(OF)

Filling set for mixture of water and glycol 2 Step 2: 1. Install the link (BVS-5) onto the ball valve (BVS-3) (Minimum pressure 2.5 bar) (See Figure 5.16) See Figure 5.17 and Figure 5.18. For a complete image from the filling set. The mixture of water and glycol will be provided in the supplied tank. The ratio of the mixture is indicated in the relevant specification list.

Figure 5.15

Figure 5.16

Figure 5.17

Figure 5.18

2 The fillingset is not supplied as standard.

Available by DTE with art. no. 87000089

Page 27: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 26

Step 3: 1. Turn the air release valve(s) to “open” (It is essential that the air release(s) takes place at the highest point(s) in the pipe(s))

CAUTION! Do not use automatic air release valves! 2. Turn the ball valve (BVS-5) to “open” position. (See Figure 5.19) 3. Turn the ball valve (BVS-3) to “open” position. (See Figure 5.20 and Figure 5.21)

Figure 5.19

Figure 5.20

Figure 5.21

Page 28: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 27

Step 4: Excess air will be released from the pipe(s) though the air release valve(s). If the water and glycol mixture spills from the air release valve(s), the external pipes/systems are filled with the water and glycol mix. 1. Turn the ball valve (BVS-3) to “closed” position. (See Figure 5.22) 2. Turn the air release valve(s) in your system to the "closed" position. 3. Turn the ball valve (BVS-5) to “closed” position. 4. Remove the ball valve (BVS-5). (See Figure 5.23) Step 5: 1. Turn the ball valve (BVS-1) to “open” position. (See Figure 5.24) 2. Turn the ball valve (BVS-2) to “open” position. (See Figure 5.25) When these steps have been completed correctly, the entire system will be filled with the water and glycol mixture.

Figure 5.22

Figure 5.23

Figure 5.24

Figure 5.25

Page 29: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 28

55..1122 FFiilllliinngg ooff tthhee ssyysstteemmss CCoooollMMaasstteerr ((KK))((LL))

Fill the CoolMaster with water (fill automatically or manually): 1. Auto fill (D1) (a power supply is required; a minimum filling pressure of 2.5 bar is required). (See Figure 5.26) 2. Manual fill (D2). (See Figure 5.27)

External systems must be filled via an external filling point. See chapter 5.10 for instructions. CAUTION! To add any chemicals or other substances, please consult the supplier.

Figure 5.26

Figure 5.27

Page 30: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 29

55..1133 FFiilllliinngg ooff tthhee ssyysstteemmss CCoooollMMaasstteerr ((NN))((NNFF))((NNOO))((NNOOFF))((OO))((OOFF))

CoolMaster (N)(NF)(NO)(NOF)(O)(OF): Fill the CoolMaster with the mix of water and glycol (using manual fill D2). (See Figure 5.28) CAUTION! This mixture must be prepared beforehand. Filling with water first and adding the glycol afterwards or vice versa is prohibited. For the mixing ratio for this machine see the appropriate specifications list. External systems must be filled via an external filling point. See chapter 5.11 for instructions. To add any chemicals or other substances, please consult the supplier. CAUTION! To prevent the heat exchanger and/or other parts from freezing, the ratio of water to glycol must be weekly checked. An incorrect ratio or type of glycol may invalidate the warranty.

Figure 5.28

Page 31: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 30

55..1144 DDeeaaeerraattiinngg

CAUTION! Do not start the pump before it has been vented! (The pump can be turned off using installation machine F30.)

CAUTION! Ensure the compressor is disabled when starting up for the first time! (The compressor can be switched off using installation machine F1.)

CAUTION! If necessary, allow the crankcase heater to heat for at least 24 hours before use.

Step 1: Open the control box door and control box.

Step 2: Switch off the compressor by turning off installation machine F1 (See Figure 5.30).

Step 3: Turn on the installation and let the pump run for 10 minutes to get the system deaerated. Step 4: Now the entire system is air free, the cover can on the installation. The compressor is activated by the service panel (I) and the system can be used.

Figure 5.29

Figure 5.30

Page 32: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 31

55..1155 SSeettttiinngg tthheerrmmoossttaatt

CAUTION! SERVICE PANEL (I) MUST BE PLACED, BEFORE STARTING UP THE MACHINE! (n.a. with external condenser).

Switch on the main switch on the control panel (G). Switch on the external start/stop. Set the thermostat to the correct value, which is on the front of the control panel (G). See Appendix 14.4 for the settings.

CAUTION! It is important that the values in the specifications list are adhered to otherwise damage to the compressor may occur! When temperatures set incorrectly the guarantee claim may expire!

CAUTION! This machine is equipped with a bypass KV1-1, which is erected between water supply and water return pipe inside the CoolMaster. The minimum flow is already factory defined and sealed and may not be hanged!

The CoolMaster is now ready for use.

Page 33: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 32

55..1166 CCoommmmiissssiioonniinngg aafftteerr lloonngg ssttaannddssttiillll

CAUTION! BEFORE OPENING MACHINE, ALWAYS ENSURE POWER SUPPLY IS COMPLETELY DISCONNECTED!

DTE uses reputable components in its products, whereby DTE will reduce the risk of faults in its machines. This also applies to the water pumps. These pumps are made with a stainless steel fan, a high quality pump house and a “Mechanical seal” to seal the axis. The mechanical seal is a high quality axis seal made from polished hard metal, and all contact surfaces are polished. This will guarantee a good sealing even under the toughest operating circumstances. The mechanical seal will lubricate itself by means of a thin liquid layer of the pumped fluid. When the machine has not been used for a long period there is a chance that the water pump will not run. The cause of this fault may be cohesion between the polished contact surfaces of the mechanical seals. The seals "stick together". This problem is easily solved by rotating the pump axis by hand. In the Grundfos pump, it can be done by first removing the roster by unscrewing the two or four screws. You can now rotate the engine fan by hand. The sticking together has now been broken and the machine can be started. See Figure 5.31 and Figure 5.32) CAUTION! MAKE SURE TO REPLACE THE ROSTER, OTHERWISE THE PUMP ENGINE WILL NOT BE COOLED PROPERLY!

Figure 5.31

Figure 5.32

Page 34: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 33

66 MMeeaanniinngg ooff aallaarrmmss ((iiff aapppplliiccaabbllee))

Fault → Possible cause → Check and solution

1. LP Alarm 1.1. Pressure is too low in the system 1.1. Contact your supplier

2. HP Alarm

2.1. Pressure is too high in the system 2.2. Place service panels

2.1. Check the condenser for dirt and clean with compressed air if necessary 2.2. Contact your supplier if necessary 2.3. Resetting

3. Level Alarm

3.1. Water level is too low

3.1. Check the water level on the gauge glass, refill if necessary 3.2. Check whether the machine refills automatically (if connected) 3.3. Check water inlet 3.4. Check valves 3.5. Check for leaks

4. Compressor alarm

4.1. Thermal alarm or short-circuit compressor(s)

4.1. Check for short-circuit 4.2. Check for overload of compressor(s) 4.3. All phases present

5. Compressor oil Alarm

5.1. No oil, or shortage of oil

5.1. Check sight glass 5.2. Check for leaks 5.3. Contact your supplier if necessary

6. Condenser Alarm

6.1. Thermal alarm or short-circuit fan(s)

6.1. Check for short-circuit 6.2. Check for overload of fan(s) 6.3. All phases present

7. Water pump alarm

7.1. Thermal alarm or short-circuit water pump(s)

7.1. Check for short-circuit 7.2. Check for overload of pump(s) 7.3. All phases present

8. Filling

8.1. Filling system

8.1. Check liquid level 8.2. Refill manually if necessary. 8.3. In the event of malfunctions please contact the supplier

Page 35: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 34

77 FFaauulltt aannaallyyssiiss

Have all checks and repairs performed by a certified technician!

Fault → Possible cause → Check and solution

1. Unit does not start 1.1. Faulty wiring 1.2. Components down to earth 1.3. Faulty main switch 1.4. Phase protection tripped (If present)

1.1. Check wiring and connections 1.2. Check and replace 1.3. Check and replace 1.4. Swap over the two power supply phases

2. Fan(s) run but compressor will not start

2.1. Faulty wiring 2.2. Faulty relay, or security 2.3. Faulty compressor

2.1. Check wiring and connections 2.2. Check components 2.3. Check and replace

3. Compressor starts but no air is delivered over the condenser

3.1. Fan loose on shaft 3.2. Faulty fan motor 3.3. Faulty wiring 3.4. Blocked air flow

3.1. Tighten fixing screw 3.2. Check and replace 3.3. Check wiring and connections 3.4. Clean the condenser

4. Compressor switches off

4.1. Electricity supply 4.2. Faulty thermostat 4.3. Faulty relay, or security 4.4. Internal security activated

4.1. Check electricity supply 4.2. Check and replace 4.3. Check and replace 4.4. Water and/or ambient temperature too high. Check cleanliness of condenser and clean it

5. Unit does not cool 5.1. Shortage of freon 5.2. Faulty compressor 5.3. Faulty thermostat 5.4. Faulty pump

5.1. Refill 5.2. Check and replace 5.3. Check and replace 5.3. Check and replace

6. Water pump gives no water

6.1. Water pump not de-aerated 6.2. Impeller of water pump is stuck 6.3. Faulty relay, or security

6.1. De-aerate water pump 6.2. See: chapter 5.16 6.3. Check components

7. Shortage of freon 7.1. Leak in the system 7.1. Check the system for leakage and repair

Page 36: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 35

88 MMiinniimmuumm IInnssppeeccttiioonn--iinntteerrvvaall sscchheemmee

Inspection interval

Inspection points

Weekly

monthly

Every 6 months

Every 12 months

Every 24 months

Mechanical

Visual check on damage outside of the unit

X

Visual check fans on damage X

Visual check fan on prevalence X

Visual (and auditive) check on defects

X

Visual check of wiring/cabling X

Cleaning condenser by using with compressed air or vacuum cleaner

X

Cleaning fan blade(s) to prevent imbalance

X

Check the hermetical system leaks X

Pressure temperatures and refrigeration installation check

X

Cleaning the compressor with damp cloth.

X

Retracing hose clamps X

Check mixing ratio water/glycol (only for CoolMaster (N)(NO)(NOF)(O)

X

Check water quality X

Electrical

Check all potential indicators and earthings

X

Power consumption check X

Check wiring main switch for damage X

Visual check electrical components and contactors

X

Torque for hose clamps

Hose ø 13mm. 10 N/m

Hose ø 19mm. 12 N/m

Hose ø 25mm. 14 N/m

Hose ø 32mm. 14 N/m

Page 37: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 36

99 CClleeaanniinngg ooff tthhee mmaacchhiinnee

CAUTION! ONLY APPLIES TO THE EXTERIOR CASING!

Before cleaning the machine, make sure you completely disconnect the power supply. To clean the machine use a soft brush, with lukewarm water with a non-aggressive cleaner. Then rub the machine dry with a soft, dry cloth. Unless explicitly stated otherwise the machine must not be cleaned with a high-pressure cleaner and/or other powerful water jets!

1100 CChheecckkss

We recommend carrying out the following checks every week:

- Check the fan motor(s) and fan blade(s) for pollution and operation. - Ensure the water pump(s) has no leaks. - Check the water and glycol mixture. (if applicable)

We recommend carrying out the following checks every month:

- Clean condenser plates with compressed air and/or vacuum cleaner. - (Caution: The condenser plates can be sharp!) - Check all wiring and connections. - Ensure the hermetical system has no leaks. - Check water level of the water tank at the gauge glass (P) or (S). - Check the flow of the by-pass.

1111 SSeerrvviiccee

If a problem and/or advise is needed from our technical staff, please always mention: - Serial number - Ambient temperature - What is shown at the display of the thermostat - What is the setpoint of the thermostat - Which alarm signals are given By mention these points, a quick solution of the problem can be given.

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Tel.: +31(0)315-328311 E-mail: [email protected]

Page 38: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 37

1122 GGuuaarraanntteeee

One or more components in this CoolMaster are sealed. Breaking these seals or adjusting components which are not sealed, may void your guarantee. Always contact your supplier. When claiming one or more components under the guarantee, these components must be returned to the supplier uncleaned and in their original state. Otherwise, the guarantee conditions on this machine apply as described in the general conditions of delivery and payment. These were deposited at the Chamber of Commerce in Arnhem on 05-06-1989, a copy of which is available upon request.

1133 RReemmoovvaall

The CoolMaster consists primarily of stainless steel, copper, brass and aluminium. The CoolMaster is also compressed with a refrigerant which is specified in the “specification list” and the relevant safety data sheet. Removal of the CoolMaster must be carried out in accordance with local or national legislation. Contact your government for instructions.

Page 39: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 38

1144 AAppppeennddiixx

Page 40: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 39

1144..11 CCoonnnneeccttiioonn ddiiaaggrraamm ffiilllliinngg tthhee ssyysstteemm

Figure 14.1

Page 41: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 40

1144..22 WWaatteerrttrreeaattmmeenntt

INTRODUCTION Semi-closed and closed cooling systems are used in many processes. An efficient and effective cooling system is needed for a process to function without problems. Generally such cooling systems contain between 0.5 and 5.0 m³ water, which is normally topped up with tap water. The tap water available is often, technically speaking, of poor quality:

• contains limescale and/or

• is corrosive The system may contain many different materials with which the cooling water comes into contact. Such as:

• steel/cast iron

• copper/brass

• aluminium

• synthetics/sealants PROBLEM DEFINITION Corrosion problems can occur in cooling systems, which have different causes. The presence of different materials can result in galvanic corrosion, which is where the least precious metal is dissolved. The action of oxygen on iron and steel causes oxygen corrosion and the formation of iron oxide or silt. Natural silt accumulation can lead to “under deposit corrosion”. High flow-speeds can lead to erosion corrosion. The quality of the cooling water plays a significant role in this. GENERAL MEASURES

Contamination Measure

Mechanical contamination caused by iron oxides or silt Install filters, depending on contamination

High hardness Soften water via ion exchange

Minor contamination caused by presence of oxides and hardness

Use water treatment in the form of hardness stabilisation and corrosion inhibitors

Biological contamination caused by presence of algae and slime bacteria

Use water treatment in the form of biocides

WATER TREATMENT Specific water treatment should be used if one or more values cannot be maintained or achieved. Water treatment products can be used for a wide variety of applications in this case. DTE has a water treatment in the form of PollutionMaster. This product can optionally be supplied. If the temperature of the water exceeds approx. 40°C, (partial) water softening must in general be applied. A complete water treatment proposal can be drawn up after the water quality has been assessed on site. CLEANING If the cooling system is already very contaminated, we recommend cleaning the system with a suitable cleaning product. The cleaning solution can be pumped around using the system pump or an cleaning pump. For the best cleaning result, at least some flow should be established across all components. The cleaning progress can be monitored through visual inspection and using pH test strips. Systems with considerable biological contamination should be rinsed thoroughly first. A bio-dispergator can also be used for this purpose. The cleaning method and costs will be assessed and determined per situation. Note: You can contact DTE anytime.

Page 42: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 41

1144..33 GGuuiiddlliinnee ffoorr wwaatteerr qquuaalliittyy iinn DDTTEE iinnssttaallllaattiioonnss

Water quality for use in all DTE installations is prescribed in this general guideline. Water quality used in DTE

installations should meet this standard at all times.

Standard values for water quality: - Acidity: PH 7 < PH 9,5

- Chloride: < 50mg / L

- Conductivity: 150 µS < 350µS

- Bicarbonate (HCO3): 80mg/L < 100mg/L

- Hardness: 2dH° < 8dH°

This directive is a general directive which also applies to systems in which water with a percentage of glycol is used. In cases where a water-glycol mixture is to be applied, the quality of water must first be analysed to be ensured the water quality is within the norm values. Subsequently, a water-glycol mixture may be prepared that must be tested on mixing ratio before use. In the system the absorption of oxygen must prevented to keep the hydrogen carbonate (HCO3) level within the acceptable range. In case of doubt, this should be tested with a sufficient frequency.

Page 43: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 42

1144..44 UUsseerr mmaannuuaall tthheerrmmoossttaatt

KLT12ID: SETPOINT CHANGE

• Push “SET” once (set point will be displayed flashing).

• Change the set point by pressing “UP” and “DOWN”.

• Confirm the changed set point with “SET”. Parameter programming (These parameters are factory set. Do not change them!) 1. To enter the parameters push the ‘’SET’’-button for at least 8 seconds. Value ‘’00’’ will appear, flashing. 2. Enter the correct code by pressing “UP” and “DOWN”. (this is factory-set to ‘’00’’) 3. Press ‘’SET’’ to confirm the code. If this is correct, the label of the first parameter will appear. 4. Using the “UP” and “DOWN” button, select the desired parameter. 5. Press ‘’SET’’ to see the value. 6. Change the parameter by pushing “UP” and “DOWN”. 7. Confirm with "SET". 8. To change more parameters, repeat step 4, 5 and 6. 9. The controller will return to its normal condition after 60 sec, or just press the ‘’SET’’ + ‘’DOWN’’ button. Parameter list

Parameter

Description

Factory-value

Comment

‘’SET’’ Set point 15 Change possible between US and LS

r0 Set point differential 2 Differential on/off controller, this parameter may not be changed!!

r1 Minimum set point 5 Sets the minimum acceptable value for the set point

r2 Maximum set point 20 Sets the maximum acceptable value for the set point

r3 Normal or differential adjustment

Nor

r4 Diff. For diff. mode 0.1

r5 Diff. setpoint 0.0

r6 Fan operation con

d0 Cold or Hot control re Re=Cold, in=Hot

d1 End of defrost. temp 80

d2 Max. defrost time 0

d3 Defrost when connecting No

d4 Delay first defrost 0.0 h-m

d5 Display on defrosting Off

d6 Display return limit 15

d7 Compressor drip time 0

d8 Interval between defrost 0

d9 Fan works with defrost No

d10 Fan drip time 0

d11 Manual defrost sync. No

d12 Defrost probe SD1

d14 Units to count defrost cycle Rt

Page 44: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 43

Parameter list

Parameter

Description

Factory-value

Comment

A0 Fan and alarm diff. 2.0 Degrees

A1 Max. alarm temperature 85 Alarm high value (Sp+A1= ALH)

A2 Min. alarm temperature 5.0 Alarm low value (Sp-A2= ALL)

A3 Alarm exclusion time during continuous cycle

0.0 Minutes

A4 Alarm exclusion time After defrost

0.0 Minutes

A5 Alarm exclusion time after opening door

0.0 Minutes

A6 Alarm exclusion after connection

0.0 Minutes

A7 Alarm verification time 0.0 Minutes

A8 Ext. alarm verification time 0.0 Minutes

F0 Fan stoppage temperature 0.0

F1 Fan works with door open Yes

c0 Min. stoppage time compressor

1 Minimum interval between the compressor start and stop (value in minutes)

c1 Continuous cycle time 0.0 Minutes

c2 ON-time of fault cycle 0 Minutes

c3 OFF-time of fault cycle 999 Minutes

c4 Min. ON-time 0 Minutes

c5 Min. time between 2 ignitions of compressor

0 Minutes

P0 Temperature scale °C °C or °F

P1 Ambient probe calibration -1.0 Allows to adjust possible offset of the thermostat probe

P2 Defrosting probe calibration 0 Allows to adjust possible offset of the thermostat probe

P4 Decimal point Yes Display point on/off

P5 Probe to be displayed SD1

P6 Number of probes used 1

E0 Digital input off Digital input not used

H0 Selection to record a configuration

0

H1 Keypad protection No

H2 Service cut due to digital input

No

H3 Delay time on connecting 0 Minutes

H4 Address for serial comms 0

H5 Keyboard code 0

H6 Type of probe PTC

Page 45: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 44

DISPLAY MESSAGES: In normal operation the probe temperature selected by P5 will be displayed. But the following messages may also appear:

- ‘’Err’’ - Memory reading error - ‘’Erp’’ - Probe error, not viewed in display - ‘’Eri’’ - Internal parameter error. In this case, enter the above DTE-configuration - ‘’ALH’’ - High temperature alarm - ‘’ALL’’ - Low temperature alarm (temperature is 5 degrees lower then ‘’SET”) - ‘’ALE’’ - External alarm - ‘’AEL’’ - High and external alarm - ‘’000’’ - Probe open - ‘’---‘’ - Probe short-circuited - ‘’DON’’ - Defrosting activated - ‘’DOF’’ - Defrosting de-activated, or cannot be done - ‘’CON’’ - Continuous cold cycle - ‘’COF’’ - Continuous cold cycle de-activated, or cannot be done - ‘’-d-‘’ - Thermostat on defrosting - ‘’OFF’’ - Thermostat switched OFF, can be switched on by pressing the ‘’UP’’ and ‘’DOWN’’-button

simultaneously for at least 8 seconds

ONDERHOUD

- Cleaning:

Clean the surface of the controller with a soft, damp cloth. NEVER use abrasive detergents, alcohol or solvents

- Repairs/Programming All repairs and the programming of the thermostat must be carried out by authorised professional.

Page 46: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 45

KLT22 (COOLING 2 STAGE): SETPOINT CHANGE

• Push “SET” once (set point will be displayed flashing).

• Change the set point by pressing “UP” and “DOWN”.

• Confirm the changed set point with “SET”. Parameter programming (These parameters are factory set. Do not change them!) 1. To enter the parameters push the ‘’SET’’-button for at least 8 seconds. Value ‘’00’’ will appear, flashing. 2. Enter the correct code by pressing “UP” and “DOWN”. (this is factory-set to ‘’00’’) 3. Press ‘’SET’’ to confirm the code. If this is correct, the label of the first parameter will appear. 4. Using the “UP” and “DOWN” button, select the desired parameter. 5. Press ‘’SET’’ to see the value. 6. Change the parameter by pushing “UP” and “DOWN”. 7. Confirm with "SET". 8. To change more parameters, repeat step 4, 5 and 6. 9. The controller will return to its normal condition after 60 sec, or just press the ‘’SET’’ + ‘’DOWN’’ button. Parameter list

Parameter

Description

Factory-value

Comment

‘’SP1’’ Set point 1 18.0 Change possible between ‘’r4’’ and ‘’r6’’

‘’SP2’’ Set point 2 2.0 Change possible between ‘’r5’’ and ‘’r7’’

r0 Dependency SP1-SP2 Dep Dependency between SP1 and SP2

r1 SP1 differential 4.0 Differential on/off controller, this parameter may not be changed!

r2 SP2 differential 2.0 Differential on/off controller, this parameter may not be changed!

r3 Band differential 0.1

r4 Lowest value for SP1 10

r5 Lowest value for SP2 2.0

r6 Highest value for SP1 20.0

r7 Highest value for SP2 2.0

r8 Operating mode On1

A0 Alarm differential 0.1

A1 Maximum alarm probe 1 25

A2 Maximum alarm probe 2 0.1

A3 Minimum alarm probe 1

10

A4 Minimum alarm probe 2

0.1

A5 Alarm verification time 0.0

A6 Alarm probe 1 selection AHL

A7 Alarm probe 2 selection Ano

c0 Minimum relay stop time 0

c1 Operation relay 1 Dir

c2 Operation relay 2 Dir

c3 Default operation relay 1 oPn

c4 Default operation relay 2 oPn

Page 47: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 46

Parameter list

Parameter

Description

Factory-value

Comment

P0 Temperature scale selection

°C

P1 Calibration of probe 1 0

P2 Calibration of probe 2 0

P4 Decimal point Yes

P5 Probe to be displayed Sd1

P6 Number of probes 1

H0 Reprogramming 0

H1 Keyboard protection No

H2 Operation led OUT 1 Dir

H3 Operation led OUT 2 Dir

H4 Address for serial communication

0

H5 Access code for parameters

0

H6 Probe type PTC

DISPLAY MESSAGES: In normal operation the probe temperature selected by P5 will be displayed. But the following messages may also appear:

- ‘’Err’’ - Memory reading error - ‘’Erp’’ - Probe error, not viewed in display - ‘’Eri’’ - Internal parameter error. In this case, enter the above DTE-configuration - ‘’ALH’’ - High temperature alarm - ‘’ALL’’ - Low temperature alarm (temperature is 5 degrees lower then ‘’SET”) - ‘’ALE’’ - External alarm - ‘’AEL’’ - High and external alarm - ‘’000’’ - Probe open - ‘’---‘’ - Probe short-circuited - ‘’DON’’ - Defrosting activated - ‘’DOF’’ - Defrosting de-activated, or cannot be done - ‘’CON’’ - Continuous cold cycle - ‘’COF’’ - Continuous cold cycle de-activated, or cannot be done - ‘’-d-‘’ - Thermostat on defrosting - ‘’OFF’’ - Thermostat switched OFF, can be switched on by pressing the ‘’UP’’ and ‘’DOWN’’-button

simultaneously for at least 8 seconds

ONDERHOUD

- Cleaning:

Clean the surface of the controller with a soft, damp cloth. NEVER use abrasive detergents, alcohol or solvents

- Repairs/Programming All repairs and the programming of the thermostat must be carried out by authorised professional.

Page 48: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 47

1144..55 SSaaffeettyy iinnffoorrmmaattiioonn sshheeeettss

The refrigerant safety data sheet is sent separately as an attachment! MONOPROPYLENE GLYCOL USP

1. IDENTIFICATION OF THE PRODUCT AND THE COMPANY

Substance name: MONOPROPYLENE GLYCOL USP Substance type: Raw material Supplier: BREUSTEDT CHEMIE BV POSTBUS 721 7300 AS APELDOORN THE NETHERLANDS Tel. 055-5332844 Fax. 055-5429072

2. COMPOSITION OF AND INFORMATION ON THE INGREDIENTS

Official substance name: MONOPROPYLENE GLYCOL USP CAS no.: Annex 1 no.:

3. DANGER IDENTIFICATION

Not a dangerous product according to guideline 67/548/EEG

4. FIRST AID MEASURES

Swallowing: No harmful effects are expected in case of this type of exposure Eyes: Rinse extensively with water Skin: Rinse skin with plenty of water or shower Inhaling: No harmful effects are expected in case of this type of exposure, in association with the correct

professional usage.

5. FIRE FIGHTING MEASURES

Risks: Stability: Stable under normal circumstances Preventative measures: Extinguishing agents: Water spray, carbon dioxide, foam and extinguishing powder Fire: Incomplete incineration may lead to the formation of carbon monoxide and propionaldehyde

Page 49: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 48

6. MEASURES IN CASE OF UNWANTED RELEASE

Personal precautions Swallowing Do not eat, drink or smoke during work Eyes Safety glasses with side protection Skin Prevent skin contact, wear gloves Inhaling Ventilation, wear breathing protection if limit is exceeded Environmental precautions/cleaning methods Cleaning/waste If possible, recover or re-use, or dispose of waste in accordance with the applicable legislation.

7. HANDLING AND STORAGE

Storage In a ventilated, dry space, separate from strongly oxidizing substances

8. EXPOSURE MANAGEMENT/PERSONAL PROTECTION

Swallowing Do not eat, drink or smoke during work Eyes Safety glasses with side protection Skin Prevent skin contact, wear gloves Inhaling Ventilation, wear breathing protection if limit is exceeded Exposure details

ppm mg/m3 ceiling value Absorption through skin?

MAC-TGG 8 hours 50 10 No No

MAC-TGG 15 min No

WGW values No

WGD recommended values

No

BGW values No

9. PHYSICAL AND CHEMICAL CHARACTERISTICS

Description MONOPROPYLENE GLYCOL USP Blacklist substance? No Physical form Liquid Colour Colourless, clear Appearance form Liquid Odour None Molecular mass Not available Odour threshold Not available ppm Vapour pressure (mbar) 0.3 mbar Boiling point/pathway 188 °C Vapour pressure (bar) Not available bar Melting point/pathway Not available °C Density (water=1) 1.04 g/cm3 Sublimation

point/pathway Not available °C

Vapour density (air=1) 2.62 g/cm3 Flash point 103 °C Water solubility Completely Auto-ignition temp. 371 °C Soluble in Not available Dissolution temperature Not available °C pH N/a Lower explosion

threshold 2.6 Vol%

Viscosity Not available Upper explosion threshold

12.5 Vol%

As a standard temperature and standard pressure 20 °C and 1 atm. (=103,325 kPa) apply unless stated

otherwise

Other details Anti-freeze

10. STABILITY AND REACTIVITY

Reactivity Dangerous reactions: with caustic potash and caustic soda (T<200 C), oxidizing

substances

Stability Stable under normal circumstances Preventative measures

Page 50: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 49

11. TOXICOLOGICAL INFORMATION

Carcinogenic No Reprotoxic (for the reproduction of poisoning) No Sensitising No Special indication Mutagenic No Inhaling Coughing, headache, sore throat Skin Redness, pain Eyes Redness, pain Swallowing Abdominal pain, nausea Ingestion via Swallowing and inhaling, no hazardous effects are expected Other toxicological details LD50 oral, rat: > 5000 mg/kg LD50 dermal, rabbit: > 10000 mg/kg Skin irritation rabbit: not irritating, irritation of eyes rabbit: not irritating Sensitisation: causes no skin conditions

12. ECOLOGICAL INFORMATION

LC50 vis, 96 h: 4600-54900 mg/l EC50 Daphia Magna, 48h: 4850-34400 mg/l Biological degradation, 28 days 86% (BOD 28 > 60%) No long-term negative effects are expected in a watery environment

13. POINTS OF ATTENTION FOR REMOVAL

Cleaning/waste If possible, recover or re-use, or dispose of waste in accordance with the applicable legislation. BAGA KCA/KGA

14. INFORMATION WITH REGARD TO TRANSPORT

Transport This product has been classified as non-hazardous in accordance with international transport

regulation

UN no. Packaging group GEVI no. Other transport

codings

Class No. Edge no. TEC no. Sheet

no.

EMS

MFAG no. NFPA-code

Road ADR/VLG Water ADN

ADN(R)

IMDG Rail RID/VSG Air IATA/ICAO

15. INFORMATION WITH REGARD TO REGULATION

Chem. Identity MONOPROPYLENE GLYCOL USP EC no.

Contains Safety datasheet (VIB) according NEN-ISO 11014:2009

Page 51: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 50

16. OTHER INFORMATION

Comments Liability This safety data sheet (SDS) was drawn up in accordance with the NEN-ISO 11014:2009 guidelines. It was

drawn up with the utmost care and the data is based on current knowledge and experience. However, the responsibility for using this SDS rests with the employer. But we cannot accept liability for damage of any kind arising from the use of this data or use of the product. The safety data sheet describes products for their safety requirements. This information is no guarantee for product properties. It is the duty of the user to use this product with care and to comply with the applicable laws and regulations.

Page 52: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 51

MONO ETHYLENE GLYCOL

1. IDENTIFICATION OF THE PRODUCT AND OF THE COMPANY

Substance name MONO ETHYLENE GLYCOL Substance type Raw material Application Frost protective additive for liquid extinguishing agents Supplier BREUSTEDT CHEMIE BV POSTBUS 721 7300 AS APELDOORN THE NETHERLANDS Tel. 055-5332844 Fax. 055-5429072

2. COMPOSITION OF AND INFORMATION ON THE INGREDIENTS

Official substance name MONO ETHYLENE GLYCOL USP CAS no.: Annex 1 no.

3. RISKS

The vapour mixes well with air. Reacts strongly with oxidation agents and oxidising acids. The substance can be absorbed into the body through inhalation and swallowing. The substance is an irritant to eyes and skin. The substance has an effect on the nervous system. Liver, kidney, and brain damage may occur. In serious cases there is a risk of unconsciousness. Flammable substance: avoid open fire. Use in explosive safe environment, ensure there are earthing and spark-free tools. Do not consume any food or drink when using or processing, and do not smoke.

4. FIRST AID MEASURES

Swallowing Symptoms: Diarrhoea, stomach cramps, headache, dizziness, vomiting, sleepiness. Have

mouth rinsed, try to avoid vomiting and immediately transport to hospital

Skin and eye contact Symptoms: Redness. Rinse or shower with plenty of water. Rinse eyes for long time (if possible, remove contact lenses) Warn a doctor

Inhaling Symptoms: Headache, dizziness, sleepiness. Take the victim into the fresh air and allow him/her to rest

5. FIRE FIGHTING MEASURES

Suitable extinguishing agents Powder, alcohol proof foam, water spray, carbon dioxide Specific extinguishing methods None Specific exposure dangers None Protection in case of fire fighting Wear chemical-resistant clothing and respiratory protection

6. MEASURES IN CASE OF UNWANTED RELEASE

Personal precautions Wear chemical-resistant clothing and respiratory protection. Wear safety gloves and glasses.

Remove contaminated clothing and follow first aid measures

Environmental measures Dam in spilt product and carefully vacuum it up, clear it up. Absorb it with absorption grains Cleaning methods Remove residuals with water

Page 53: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 52

7. HANDLING AND STORAGE

Handling Use personal protection equipment Storage In a ventilated, dry space, separate from strongly oxidative substances

8. EXPOSURE MANAGEMENT/PERSONAL PROTECTION

Swallowing Do not eat, drink or smoke during work Eyes Safety glasses with side protection Skin Prevent skin contact, wear gloves Inhaling Ventilation, wear breathing protection if limit is exceeded Threshold value/MAC value 10 ppm / 26 mg/m3 in droplets (maximum not to be exceeded) Protected breathing Extraction. Filter mask A. processing or use in well-ventilated space Protection of hands Safety gloves Protection of eyes Safety glasses Protection of skin Protective clothing

9. PHYSICAL AND CHEMICAL CHARACTERISTICS

Description MONO ETHYLENE GLYCOL Blacklist substance? No Physical form Liquid Colour Colourless, clear Appearance form Liquid Odour None Molecular mass Not available Odour threshold Not available ppm Vapour pressure (mbar) 0,12 @ 25 °C mbar Boiling point/pathway 179 °C Vapour pressure (bar) Not available bar Melting point/pathway -13 °C Density (water=1) 1.1 g/cm3 Sublimation

point/pathway Not available °C

Vapour density (air=1) 2.1 @ 25 °C g/cm3 Flash point 116 °C Water solubility Completely Auto-ignition temp. 413 °C Solubility in water Fully soluble Dissolution temperature Not available °C pH N/a Lower explosion

threshold 3.2 Vol%

Viscosity Not available Upper explosion threshold

28 Vol%

As a standard temperature and standard pressure 20 °C and 1 atm. (=103.325 kPa) unless stated otherwise Other details Anti-freeze

10. STABILITY AND REACTIVITY

Circumstances to be avoided Keep separate from food Substances to be avoided Reacts strongly with oxidation agents and oxidising acids. Hazardous degradation products

Page 54: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 53

11. TOXICOLOGICAL INFORMATION

Carcinogenic No Reprotoxic (for the reproduction of poisoning) No Sensitising No Special indication Mutagenic No Inhaling Coughing, headache, sore throat Skin Redness, pain Eyes Redness, pain Swallowing Abdominal pain, nausea Ingestion via Swallowing and inhaling, no hazardous effects are expected Other toxicological details LD50 oral, rat: > 5000 mg/kg LD50 dermal, rabbit: > 10000 mg/kg Skin irritation rabbit: not irritating, irritation of eyes rabbit: not irritating Sensitisation: causes no skin conditions

12. ENVIRONMENTAL INFORMATION

Exotoxicity LC goldfish: > 5000 mg/l Persistence/degradation BOD: 0.47; COD: 1.24

13. POINTS OF ATTENTION FOR REMOVAL

Cleaning/waste If possible, recover or re-use, or dispose of waste in accordance with the applicable legislation.

14. INFORMATION WITH REGARD TO TRANSPORT

Transport UN no. Packaging group GEVI no. Other transport codings

Class No.

Edge no.

TEC no. Sheet

no. EMS MFAG no. NFPA-code

Road ADR/VLG Water ADN

ADN(R)

IMDG Rail RID/VSG Air IATA/ICAO

15. INFORMATION WITH REGARD TO REGULATION

Chem. Identity MONO ETHYLENE GLYCOL EC no.

Contains

Page 55: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 54

16. OTHER INFORMATION

Comments Liability This safety data sheet (SDS) was drawn up with the utmost care and the data is based on current knowledge

and experience. However, the responsibility for using this SDS rests with the employer. But we cannot accept liability for damage of any kind arising from the use of this data or use of the product. The safety data sheet describes products for their safety requirements. This information is no guarantee for product properties. It is the duty of the user to use this product with care and to comply with the applicable laws and regulations.

Page 56: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 55

1144..66 CCoommmmeennttss

Page 57: The Netherlands - DTEdte.eu/wp-content/uploads/2020/09/IO_Manual_CoolMaster_L... · 2020. 9. 28. · The CoolMaster (K)(N)(NF)(O)(OF)(L) may only be kept inside a cool, well-ventilated,

The Nether lands

www.dte.eu

Dutch Thermal Engineering n.v. Westerbroekstraat 18 7011 EX Gaanderen Phone : +31(0)315-328311 E-mail : [email protected]

Specialist in: Industrial ….Cooling ….Heating ….Tempering ….Heat Recovery

V00-08-2017 Page 56

1144..77 TTeecchhnniiccaall iinnffoorrmmaattiioonn

** SSppeecciiffiiccaattiioonn lliisstt

** MMaacchhiinnee ddrraawwiinngg

** PPaarrttss lliisstt

** FFllooww sscchheemmee

** EElleeccttrriiccaall sscchheemmee

** UUsseerr mmaannuuaall tthheerrmmoossttaatt

** SSaaffeettyy ddaattaa sshheeeett rreeffrriiggeerraanntt

** OOtthheerr

* Technical information is sent as an attachment to the technical operating instructions.