SOLA Hydronic Control Commercial/Industrial Combustion Controls The Key to Integrated Hydronic Boiler Control
8

The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

Apr 15, 2018

Download

Documents

duongque
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

Sola Hydronic ControlCommercial/Industrial Combustion Controls

The Key to Integrated Hydronic Boiler Control

Page 2: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

10 Integrated Control Functions

• Primary flame safeguard control

• Igniter/spark generator

• High limit control: boiler outlet

• Operating control: central heating

• Pid load control: central heating

Reduce Installation, Wiring Time, Cabinet Space

• Replaces multiple devices with a single integrated, compact device

• Optional plug-in module enables back-up and cloning features

Algorithm Prioritization

• Burner demand: Central heating, domestic hot water and frost protection

• Firing rate limiting: Anti-condensate, stack, boiler delta-T, boiler slow start, boiler outlet

Expanded Diagnostics

• 11-item programmable first-out standard and expanded annunciation

• 15-item lockout condition history and 15-item alert condition history

Flexible

• User selectable parameters, features and program settings to meet individual requirements

• Boiler network can grow to meet future demands

Safety / Boiler Protection

• Frost protection, slow start, anti-condensate, boiler delta-T, stack high limit, boiler high limit, domestic hot water high limit,

outlet T-rise limit

Affordable

• Compare to purchasing, installing and maintaining 10 individual controls

• Pump control

• Outdoor reset control

• High limit control: domestic hot water

• Operating control: domestic hot water

• Pid load control: domestic hot water

The Honeywell Sola Hydronic Boiler Control combines ten control functions into onecompact device. Experiencereduced installation time,wiring time and increasedprogramming flexibility.Sola’S flexible programming, demand prioritization, boiler protection functions andHoneywell reliability are adrop in the bucket of itscontrol possibilities!

The Only Control You Need

Page 3: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

The Hydronic Boiler Control Solution

T

P

V

P P P

T

TT

T

T

DHWLoop

HeaderTemp

BoilerMix

Loop

BoilerInlet

Outlet

OutdoorTemp

Stack

Alarm

Fan

Ignitor

Pilot Valve

Main Valve(s)

24 Vac

L2

L1

Flame Signal

Interlock

PII

Limit Input(s)

Limit Annunciation (8)

Remote Reset

TOD

STAT

BuildingAutomation

System

SystemOperatorInterface

LocalKeyboardDisplayModule

Boiler

DomenticHot

WaterTank

T

CentralCooling

LoopV

V

Key

Valve Output

Pump Output

Temperature Input

Output

Input

Page 4: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

Singular ControlThe Sola Hydronic Control orchestrates multiple hydronic boiler functions, based on user programmable settingsand priorities. Each boiler has a dedicated control, with an optional local keyboard display module for monitoring and setpoint adjustment. Configuration is accomplished using a system operator interface. Central Heating is the mainheating loop, while Domestic Hot Water comprises the optional secondary heating loop. User assigned priorities foreach heat loop dictate which is addressed first.

Item R7910A1001 R7910A1019 R7910A1027

24 Vac Control Circuit • • •

24 Vac Load Circuit •

120 Vac Load Circuit • •

Plug Connections • • •

Modulation Output: PWM • •

Modulation Output: 4-20 mA • • •

Modulation Output: 0-10V dc • • •

High/Low Fire Switch Inputs •

Flame Rod Flame Detection • • •

UV Flame Detection • • •

Choose The Sola Hydronic Control for Your Application

Program ModulePM7910A1013

Display Options

Sola program back-up and cloning. Facilitates multiple controller setup. Order separately.

S7910A1008 Local Keyboard Display Module

S7999B1026 System Operator Interface

Typical ApplicationsThe Sola Hydronic Control works with hydronic low mass and commercial boilers of all types. Typical applications may include apartment buildings, hospitals, retail complexes, schools, universities and office complexes.

LCD for monitoring and setpoint adjustment of a local Sola and the boiler it controls. Communicates via Honeywell 3-wire protocol. Order separately.

Touchscreen display for individual and multiple boiler configuration, remote monitoring, fault history, diagnostics and trend analysis. Provides visual indication of normal operation, lockout condition, mode and communication errors. Required for commissioning, but not required for subsequent operation. Up to 8 Sola devices may be monitored with a single system operator interface. Communicates via 3-wire RS-485 Modbus™ protocol. Order separately.

Page 5: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

thinkGREEN

Keep green on the planet,keep green in your wallet.

The Sola Hydronic Control helps to save time, money and the planet!By using less fuel, less CO2 and other greenhouse gases are releasedinto the atmosphere. Also, reduced electrical energy use translates tofewer greenhouse gas emissions from utility companies.

Setback • Saves fuel by reducing boiler output temperatures for low use or unoccupied periods.

Outdoor Reset • Saves up to 10 percent on average fuel usage. • Adjusts boiler output temperature to compensate for outdoor air temperature changes, causing boiler to operate at lower temperatures during mild weather. • Reduces unnecessary boiler cycling.

Fan and Burner Modulation • Maximizes electrical energy savings and minimizes fuel use compared to fixed speed components. • Reduces fan speed and burner firing rate in response to modulation. • An ideal pairing with Premix components and Premix burner technology, which reduce NOx formation.

Money • Saves green with reduced installation, wiring and maintenance by integrating multiple control functions into a single device. • Keeps green in your wallet by reducing energy usage.

Page 6: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

The Honeywell SolutionGet the Honeywell advantage by combining the Sola Hydronic Control with compatible Honeywell components for a compact and powerful hydronic control solution. For more information, visit customer.honeywell.com.

Component Purpose

C7027, C7035, C7044

UV Sensors

Minipeeper® ultraviolet flame detectors. C7027A and C7044A are disposablemodels with integral threaded collar and bracket mounting, respectively. C7044has side or end flame monitoring capability. C7035 has integral threaded collarand field replaceable UV tube. Compatible with Sola integral amplifier.

C7007, C7008, C7009 / Q179A-B-C-D, C7005

Flame rod holders/pilot burner assemblies for rectified flame sensing. Reactsto ionization in and around the flame. Some gas pilot assemblies have integralignition electrodes. Compatible with Sola integral amplifier.

V4730/V4734/V8730C

Valves,VMU Venturi

Valve/Venturi compatible with modulating premix burners. Internal dual shutoff valves and regulator. A modulated combustion blower motor pulls the gas/air mixture through venturi, mixing in a 1:1 ratio for consistent burner operation. Modulation directed by Sola in response to firing rate requirements. Capacity range of 512-2,320kBTU, sizes from ½" to 1¼", 24 Vac and 120 Vac. No proof of closure switch.

Q624A, Q652B

Solid State Spark Generators

High voltage solid state spark generators, 120 Vac. Synchronized for use with UV sensors by sparking on one half of the ac cycle while UV sensors operate on the opposite half cycle. Prevents ignition interference.

V4046C/8046CV4295A/8295A

Gas Pilot Valves

24 Vac and 120 Vac gas pilot valves provide on/off control of pilot burners.They open within 1 second when energized and close within 1 second uponpower failure. The V4046C valves are magnetically operated, while the V4295A valves are solenoid operated. Fits various pipe sizes between 1/8" and 2½".

198799Z32003971-00232002971-003

Sensors

Single element 10K Ohm (at 25° C) NTC resistive temperature sensors.Temperature range of -40° F to 266° F. For use as inlet, header and outdoorsensors. -002 sensor has 6" leads and Molex® splice connector. -003 kitcontains 198799Z sensor with 42" leads and all necessary hardware forstrap-on or outdoor mounting.

50001464-006 50001464-007

Sensors

Dual element 10K Ohm (at 25° C) NTC resistive temperature sensors.Temperature range of -40° F to 266° F. For use as outlet and domestic hotwater operation/limit sensors. May be used for stack limit sensor if temperature specifications are not exceeded. -006 sensor has 6" leads and Molex spliceconnector. -007 sensor has 42" leads.

AT72DAT88AControl Transformer

24 Vac, Class 2 control transformer for powering the Sola control. AT72D is 40 VA and the AT88A is 75 VA. Various configurations available for each.

V5055C, V4055DValve, Actuator

Valve and on/off actuator. Used for double block safety shut-off. Available with integral proof of closure switch.

V5197A, ML7999BValve, Actuator

Modulating valve and actuator. Actuator accepts 4-20 mA signal from control.Valve not suitable for safety shut-off applications. Actuator accepts 100 to 240Vac, 50/60 Hz.

V51E, M7284, Q100Valve, Actuator, Linkage

Modulating valve, modulating motor and butterfly valve linkage. Actuator accepts 4-20 mA signal from control and are available in 24 Vac or 120 Vac. Valve notsuitable for safety shut-off applications.

Page 7: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

Sola Hydronic Control Condensed Specifications

Application

Modulating hydronic low mass or commercial boilers with central heating and domestic hot water loops. 24 Vac or 120 vac load circuit with 24 vac control circuit.All features are integral to control:•2Boilercontrolloops•Primaryflamesafeguardcontrol•Igniter/sparkgenerator•Highlimitcontrol:centralheating•Operatingcontrol:centralheating•PIDloadcontrol:centralheating•Frostprotection•Boilerdelta-Tprotection•Stackratelimitfunction

Required Components

•Controller:R7910A1001/R7910A1019/R7910A1027•Plugconnectors:SuggestedconnectorscanbefoundintheSolaProductDatasheet•Systemoperatorinterface:S7999B1026(configure/monitormultipleboilers)•UVsensors:C7027/C7035/C7044•Flamerodholders/pilotburnerassemblies:C7007,C7008,C7009/Q179A-B-C-D,C7005•Inlet/header/outdoortemperaturesensors:198799Zor32003971-002(purchasequantityneeded)•Headerandoutdoortemperaturesensors:32003971-003kit(purchasetwokitsifusingbothfunctions)•Outletanddomestichotwateroperation/limitsensors:50001464-006or50001464-007 (purchase two if using both functions)•Stacklimitsensor:50001464-006or-007.Maximum266°F(130°C)

Optional Components

•Localkeyboarddisplaymodule:S7910A1008(formonitoring,setpointadjustment)•Programmodule:PM7910A1013(back-up,cloning)•Controltransformer,24Vac,Class2:AT72D(40VA)orAT88A(75VA)

Electrical Ratings

•R7910A1001:24Vac(+25%,-16.6%),60(+-5%)Hzloadcircuit•R7910A1019/1027:120Vac(+10%,-15%),60(+-5%)Hzloadcircuit•AllR7910A:24Vac(+25%,-16.6%),60(+-5%)Hzcontrolcircuitvoltage; Requires Class 2 control transformer•S7910A1008:24Vac,obtainedfromSola3-wireinterface•S7999B1026:100-240Vac,50/60Hzpowerinputtoaseparatepowersupply(included)

Vibration •0.0to0.5Gcontinuousenvironment

Ambient Temperature Range

•R7910A:-4°Fto150°F(-20°Cto66°C)•S7910A1008:32°Fto120°F(0°Cto49°C)•S7999B1026:32°Fto122°F(0°Cto50°C)

Humidity Range

•R7910A:upto95%RelativeHumidity,non-condensing(maximumof14continuousdays)•S7910A1008:upto90%RelativeHumidity,non-condensing•S7999B1026:upto85%RelativeHumidity,non-condensing

Dimensions(W x H x D)

•R7910A:6"x9"x3"installed(152mmx229mmx76mm)•S7910A1008:5-9/16"x4"x2"(141mmx102mmx51mm)•S7999B1026:9-13/32"x6-21/32"x1-9/16"(239mmx169mmx40mm)

Approvals•R7910A:UL/cULComponentRecognized(fileno.MH20613;guideno.MCCZ),CSD-1 Acceptable, FCC (Part 15, Class B, Emissions)•S7999B1026:FCC(Part15,ClassAdigitaldevice),ULListed,CanadianICES-003

Communication•ECOM:Honeywell3-wireinterfaceforcommunicationwithdedicatedlocaldisplay•ModbusMB1:3-wireRS-485interfaceforModbusnetwork;Upto8deviceconnections•ModbusMB2:3-wireRS-485interfaceforModbusnetwork;Upto8deviceconnections

•3Pumpoutputs•Outdoorresetcontrol•Expandedannunciation•Highlimitcontrol:stack•Highlimitcontrol:domestichotwater•Operatingcontrol:domestichotwater•PIDloadcontrol:domestichotwater•Anti-condensationprotection•Slowstartfunction•Prioritizationfordemand,ratelimiting

Page 8: The Key to Integrated Hydronic Boiler Control · The Key to Integrated Hydronic Boiler Control. ... boiler protection functions and ... Interlock PII Limit Input(s)

63-9725December 2007© 2007 Honeywell International Inc.

Automation and Control Solutions