Top Banner
The All-Fiberglass Cooling Towers Closed Circuit Fluid Cooler HFC Series THERMAL PERFORMANCE CERTIFIED BY THE COOLING TECHNOLOGY INSTITUTE
16

The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

Jul 28, 2018

Download

Documents

trankhanh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

TheAll-Fiberglass Cooling Towers

Closed CircuitFluid Cooler

HFC Series

THERMAL PERFORMANCE CERTIFIED BY THE COOLING TECHNOLOGY INSTITUTE

Page 2: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers2

Features

■ Self contained heat transfer equipment.

■ Induced draft counter flow design.

■ CTI certified in accordance with Standard 201.

■ Built to last.

■ Over 100 different models.

■ Nominal Capacity: from 80 to 1,902 GPM @ Standard conditions: 95 ºF / 85 ºF / 78 ºF.

■ All construction materials are corrosion resistant.

■ Easy access for maintenance.

■ Simple economical assembly and installation.

Leader in “All-Fiberglass” Cooling TowersREYMSA´s success is the result of years of experience. Since 1969, we have been putting ideas into action by researching and developing the latest technologies. The Closed Circuit Fluid Coolers are manufactured to provide the highest performance and long service life, for those demanding the best.

FRP (Fiberglass Reinforced Polyester) Casing and Structure

■ Durable, heavy duty construction.

■ Life expectancy of 30+ years*.

■ Gel-coat finish with UV inhibitors provides superior protection from harsh environments, weather, and aggressive chemical treatment.

■ Thermally stable composition for hot or cold environments.

■ Light weight.

■ Corrosion resistant.

■ Low maintenance.

REYMSA´s complete line of Closed Circuit Fluid Coolers are certified by the Cooling Technology Institute in accordance with Standard 201.

*CTI Guideline 152, page 5 of 16, section 1.3: “Life of Structure - A reasonable anticipated life of 30 - 35 years can be expected from an FRP structure tower”.

Page 3: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 3

TheAll-Fiberglass Cooling Towers

Copper CoilThe heat transfer between process fluid and water takes place in the copper coil.

■ Copper’s thermal conductivity is at least 8 times greater than that of galvanized steel.

■ Corrosion resistance and durability.

■ Stainless steel casing.

■ Type L copper coil.

Excellent Thermal Performance

Direct Drive Fan SystemTypically a belt drive system requires quarterly service for checking and readjusting the tension of the belt, lubrication of fan shaft bearings, lubrication of the motor base adjusting screws and drive alignment to ensure maximum belt life.

Our direct drive motors eliminate the frequent service required by belt drives that have higher operational and maintenance costs.

Advantages

■ Minimum service required.

■ No belts to adjust, reliable operation.

■ Fewer parts between the motor and the fan.

Direct drive on all of our HFC Tower models, for a more reliable operation with much lower service and operation costs and minimal risk of failure.

Page 4: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers4

High Efficiency Components

Motors designed for the challengeAll of our towers feature motors that exceed the Cooling Tower duty characteristics:

■ Severe Duty.

■ Marine Duty.

■ Inverter Rated.

■ Premium efficient motor.

■ Cast iron construction.

■ Epoxy coated (internal and external).

■ Inpro/Seal VBX bearing isolator for added protection1.

The perfect protection1 The Inpro/Seal VBX Bearing Isolator is a non-contacting, non wearing, permanent bearing protection device, consists of a unitized stator and rotor that form a compound labyrinth seal with no wearing parts, manufactured in bronze for more extreme conditions. VBX ring blocks the transfer of vapor contamination created by heating/cooling of the bearing enclosure, maintenance free, zero energy consumption.

Minimal risk of failure

Over 51% of motor malfunctions are caused by bearing failure due to contamination ingress and lubrication loss. REYMSA motor bearings are protected by Inpro/Seal VBX to prevent the risk of failure.

Improved Design High Performance Fan BladeREYMSA has selected the “best choice” in fan assemblies to meet our commitment to quality. The fan assembly consist of a cast aluminum hub with adjustable pitch air foil or sickle blades molded with fiberglass reinforced polyamide. Ambient operating air temperatures may fluctuate from -50 °F to 250 °F. The materials used are spark and corrosive resistant.

Page 5: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 5

TheAll-Fiberglass Cooling Towers

Water Distribution SystemOur hot water distribution system is manufactured from PVC to eliminate corrosion, assuring a long service life and maximum reliability. After the water distribution system is assembled, REYMSA test it for leaks with 40 psig water pressure.

Spray Nozzles

REYMSA uses 2 ½” N.P.T. nozzle with interchangeable internal components for its non clogged design and its unique square water spray pattern.

The square spray pattern provides the best choice for a reliable fill coverage and results in an optimal thermal performance.

This industrial nozzle handles flow rates of 10 times per nozzle more than the typical cooling tower nozzle and has over 30 years of experience in power plant and large industrial cooling tower applications.

Recirculating Pump ■ The vertical inline recirculating pump is designed for optimum

performance, easy installation and simplified maintenance.

■ The close-coupled design results in improved alignment and increased seal life.

Page 6: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers6

■ Lower sound level.

■ Direct Drive system.

■ Adjustable pitch air foil or sickle blades molded with fiberglass reinforced polyamide.

■ Lower RPM motors / fan design for additional sound reduction.

■ Tower performance CTI certified.

Low Sound Solutions

Fill Media & Air Inlet LouversWe use high quality PVC fill that is UV stabilized, resistant to weather exposure, chemical degradation from alkali, acids and biological attack.

REYMSA provides triple pass PVC air inlet louvers, designed to:

■ Minimize direct sunlight to the water.

■ Reduce splash out - reduced make-up water and chemicals.

■ Reduce noise while having low pressure drop that results in less fan motor energy consumption.

■ The potential of algae growth is reduced, therefore reducing water treatment and maintenance cost.

■ UV stabilized - longer service life.

■ Additional characteristics are its durability by being corrosion-free and impervious to chemical attacks.

Page 7: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 7

TheAll-Fiberglass Cooling Towers

Easy Maintenance ■ Every REYMSA cooling tower includes a bolted access door for complete access to both the spray water

system and fill.

■ Removing the air inlet louvers gives the service people access to the water distribution pan for inspection & cleaning.

■ A wide access door is available for copper coil inspection.

Optimal Design System

Factory tests

Every tower is assembled and tested at our factory prior to shipment to ensure the tower is in optimal condition.

Easy Field Assembly ■ REYMSA ships their towers in a modular section design for fast assembly.

■ Assembly is reduced to placing and bolting the fan duct and the body section.

■ Easy assembly of all our towers results in lower installed cost.

Page 8: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers8

Optional Equipment

Flame Retardant ResinControls the spread of flame meeting the ASTM-E84 standard.

Access Ladders & HandrailsFor safe access to fan assemblies (In stainless or galvanized steel).

Air DeflectorsMade of a curved deflecting surface that redirects air and sound.

Davit / HoistFor motor removal where crane access is difficult.

Electric Water Level ControlIncludes water level controller, stilling chamber, and solenoid valve for make up water.

Basin HeatersDesigned to provide freeze protection during shutdown or standby conditions. Includes heater element, thermostat, and low water level safety cutoff.

Vibration Cutoff SwitchesVibration switch interrupts the power to the fan motor, when triggered by excessive vibration or shock.

Non-Skid CatwalkAccess platform for maintenance and servicing (in stainless or galvanized steel).

Grey TanLight grey

Colors

REYMSA towers are available in a variety of colors that match our customer’s need.

Centrifugal Separator: Water Filtration SystemMechanical device that uses the principle of centrifugal force and friction to cause the separation of suspended solids from liquids, effectively removing suspended particles larger than 40 microns form a variety of fluids.

Page 9: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 9

TheAll-Fiberglass Cooling Towers

Operation PrincipleA. Recirculating water is distributed over the fill media through

spray nozzles.

B. Tower fans draw ambient air into the tower, making contact with the water as it travels through the fill.

C. Heat transfer takes place between the water and the air resulting in latent and sensible cooling.

D. Water is distributed externally over the copper tube heat exchanger using gravity nozzles.

E. Process fluid circulates internally through the copper tube heat exchanger.

F. Heat transfer occurs between the outside exposed water and the contained process fluid. Protecting the integrity of the process fluid.

Air Out

Water

Outlet

Inlet

Water

Process Fluid

Air in

A

B

B

D

F

E

C

1. Fan Section

2. Drift Eliminator

3. Spray Nozzle Manifold

4. Body Section

5. Cellular Fill

6. Air Inlet Louvers

7. Basin Section

8. Water Distribution Pan

9. Process Fluid Inlet

10. Process Fluid Outlet

11. Copper Coil

12. Recirculating Pump

13. Drain

14. Purge

15. Water Make up

16. Overflow

17. Access Doors

1

2 3

4

5

6

8

9

10

17

17

15

14

1316

12

7

11

Construction Details

Page 10: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers10

810

505

606

707

808

HFC-505

HFC-606

HFC-707

HFC-808HFC-810

Coil Pressure Drop - Single Fan Models

Coi

l Pre

ssu

re D

rop

(PSI

) HFCModel

Flow (GPM)

Page 11: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 11

TheAll-Fiberglass Cooling Towers

HFC-510

HFC-612

HFC-714HFC-816

HFC-819HFC-822 HFC-827

Coil Pressure Drop - Double Fan Models

Coi

l Pre

ssu

re D

rop

(PSI

) HFCModel

Flow (GPM)

Page 12: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers12

HFC-1010

HFC-1212

HFC-1414HFC-1616

HFC-1622

HFC-1627

Coil Pressure Drop - Quadruple Fan Models

Coi

l Pre

ssu

re D

rop

(PSI

) HFCModel

Flow (GPM)

Page 13: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers 13

TheAll-Fiberglass Cooling Towers

Model** Nominal Capacity

Fans Pump Weight (lb) Dimensions (in) Copper Coil

HP Total CFM HP GPM Shipping OperatingLength

(L)Width

(W)Height

(H)Volume

(gal)

SIN

GLE

FA

N

505103 79.3 3 15,100 3 270 2,609 4500 61 61 196 22505105 88.6 5 16,300 3 270 2,609 4500 61 61 196 22505175 90.4 7.5 17,800 3 270 2,609 4500 61 61 196 22606105 123.6 5 21,200 3 350 4,020 7100 73 73 196 31606175 132.6 7.5 24,200 3 350 4,020 7100 73 73 196 31606110 139.5 10 26,400 3 350 4,020 7100 73 73 196 31*707175 173.2 7.5 32,300 5 480 4,220 8410 83 83 210.5 42*707110 185.7 10 34,700 5 480 4,220 8410 83 83 210.5 42*707115 195.8 15 37,000 5 480 4,220 8410 83 83 210.5 42*808175 249.1 7.5 36,500 5 600 4,815 10275 96 96 228 53*808110 264.2 10 40,900 5 600 4,815 10275 96 96 228 53*808115 285.6 15 46,100 5 600 4,815 10275 96 96 228 53*810175 294 7.5 41,400 7.5 780 7,555 15325 120.5 96 228 2 @ 42*810110 315 10 46,000 7.5 780 7,555 15325 120.5 96 228 2 @ 42*810115 354 15 54,200 7.5 780 7,555 15325 120.5 96 228 2 @ 42*810120 377 20 59,500 7.5 780 7,555 15325 120.5 96 228 2 @ 42*812110 348 10 50,000 7.5 860 8,705 17875 143 96 228 2 @ 46*812115 379.2 15 56,900 7.5 860 8,705 17875 143 96 228 2 @ 46*812120 415 20 64,300 7.5 860 8,705 17875 143 96 228 2 @ 46*812125 449.1 25 70,600 7.5 860 8,705 17875 143 96 228 2 @ 46

DO

UBL

E FA

N

510203 150.7 2 @ 3 30,980 5 470 5,218 9000 122 61 196 2 @ 22510205 168.3 2 @ 5 32,800 5 470 5,218 9000 122 61 196 2 @ 22510275 171.8 2 @ 7.5 36,000 5 470 5,218 9000 122 61 196 2 @ 22612205 234.8 2 @ 5 42,200 5 600 8,040 14200 146 73 196 2 @ 31612275 251.9 2 @ 7.5 48,800 5 600 8,040 14200 146 73 196 2 @ 31612210 265.1 2 @ 10 52,800 5 600 8,040 14200 146 73 196 2 @ 31*714275 329.1 2 @ 7.5 64,800 7.5 850 8,440 16820 177 92.5 216 2 @ 42*714210 352.8 2 @ 10 69,000 7.5 850 8,440 16820 177 92.5 216 2 @ 42*714215 372 2 @ 15 73,800 7.5 850 8,440 16820 177 92.5 216 2 @ 42*816275 473.3 2 @ 7.5 75,400 10 1000 9,630 20550 199.5 105 231.5 2 @ 53*816210 502 2 @ 10 84,600 10 1000 9,630 20550 199.5 105 231.5 2 @ 53*816215 542.6 2 @ 15 96,200 10 1000 9,630 20550 199.5 105 231.5 2 @ 53*819275 565 2 @ 7.5 81,400 15 1440 13,990 29295 232 99.5 257 4 @ 39*819210 610 2 @ 10 90,200 15 1440 13,990 29295 232 99.5 257 4 @ 39*819215 689 2 @ 15 104,000 15 1440 13,990 29295 232 99.5 257 4 @ 39*819220 724.5 2 @ 20 113,400 15 1440 13,990 29295 232 99.5 257 4 @ 39*822275 624 2 @ 7.5 87,600 15 1560 16,550 36600 268.5 99.5 257 4 @ 43*822210 670 2 @ 10 97,200 15 1560 16,550 36600 268.5 99.5 257 4 @ 43*822215 755 2 @ 15 112,800 15 1560 16,550 36600 268.5 99.5 257 4 @ 43*822220 818 2 @ 20 126,000 15 1560 16,550 36600 268.5 99.5 257 4 @ 43*827210 714 2 @ 10 104,200 2 @ 10 2 @ 920 18,170 40490 327.5 99.5 275.5 4 @ 49*827215 835 2 @ 15 128,200 2 @ 10 2 @ 920 18,170 40490 327.5 99.5 275.5 4 @ 49*827220 915 2 @ 20 144,400 2 @ 10 2 @ 920 18,170 40490 327.5 99.5 275.5 4 @ 49*827225 973 2 @ 25 157,200 2 @ 10 2 @ 920 18170 40490 327.5 99.5 275.5 4 @ 49

QU

AD

RUPL

E FA

N

1010403 285.5 4 @ 3 61,960 2 @ 5 2 @ 470 10,436 18000 122 122 196 4 @ 221010405 319 4 @ 5 65,600 2 @ 5 2 @ 470 10,436 18000 122 122 196 4 @ 221010475 325.4 4 @ 7.5 72,000 2 @ 5 2 @ 470 10,436 18000 122 122 196 4 @ 221212405 445 4 @ 5 84,400 2 @ 5 2 @ 600 16,080 28400 146 146 196 4 @ 311212475 477.4 4 @ 7.5 97,600 2 @ 5 2 @ 600 16,080 28400 146 146 196 4 @ 311212410 502.2 4 @ 10 105,600 2 @ 5 2 @ 600 16,080 28400 146 146 196 4 @ 31*1414475 623.5 4 @ 7.5 129,600 2 @ 7. 5 2 @ 850 16,880 33640 177 177 216 4 @ 42*1414410 668.5 4 @ 10 138,000 2 @ 7. 5 2 @ 850 16,880 33640 177 177 216 4 @ 42*1414415 704.9 4 @ 15 147,600 2 @ 7. 5 2 @ 850 16,880 33640 177 177 216 4 @ 42*1616475 896.8 4 @ 7.5 150,800 2 @ 10 2 @ 1000 19,260 41100 201 204 232 4 @ 53*1616410 951.1 4 @ 10 169,200 2 @ 10 2 @ 1000 19,260 41100 201 204 232 4 @ 53*1616415 1028.2 4 @ 15 192,400 2 @ 10 2 @ 1000 19,260 41100 201 204 232 4 @ 53*1619475 1090 4 @ 7.5 156,000 2 @ 15 2 @ 1440 27,980 58590 232 199 257 8 @ 39*1619410 1163 4 @ 10 173,200 2 @ 15 2 @ 1440 27,980 58590 232 199 257 8 @ 39*1619415 1335 4 @ 15 203,600 2 @ 15 2 @ 1440 27,980 58590 232 199 257 8 @ 39*1619420 1442 4 @ 20 224,400 2 @ 15 2 @ 1440 27,980 58590 232 199 257 8 @ 39*1622475 1158 4 @ 7.5 169,200 2 @ 15 2 @ 1560 33,100 73200 268.5 199 257 8 @ 43*1622410 1247 4 @ 10 189,200 2 @ 15 2 @ 1560 33,100 73200 268.5 199 257 8 @ 43*1622415 1478 4 @ 15 225,200 2 @ 15 2 @ 1560 33,100 73200 268.5 199 257 8 @ 43*1622420 1613 4 @ 20 253,200 2 @ 15 2 @ 1560 33,100 73200 268.5 199 257 8 @ 43*1627410 1406 4 @ 10 205,600 4 @ 10 4 @ 920 36,340 80980 327.5 199 275.5 8 @ 49*1627415 1630 4 @ 15 248,800 4 @ 10 4 @ 920 36,340 80980 327.5 199 275.5 8 @ 49*1627420 1770 4 @ 20 276,400 4 @ 10 4 @ 920 36,340 80980 327.5 199 275.5 8 @ 49*1627425 1902 4 @ 25 303,200 4 @ 10 4 @ 920 36,340 80980 327.5 199 275.5 8 @ 49

w

L

H

L

A

L

w

H

L

A

w

L

H

L

A

* Models available with low sound fan. For further information contact your local REYMSA Representative. ** Nominal capacity in GPM of water cooled from @ 95/85/78 °F.Physical dimensions of each tower are approximate and are subject to change.“A” Dimension is 19” for all models.

Engineering Data & Dimensions

Page 14: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

REYMSA Cooling Towers14

TOWER CAPACITY IN GALLONS PER MINUTE @ TEMPERATURE CONDITIONS IN °F

EWT, ºF 90 90 90 95 95 95 95 95 95 97 100 100 100 100 100 102 105 105 105 115 115

LWT, ºF 80 80 80 80 80 80 85 85 85 87 85 85 85 90 90 90 90 90 90 90 90

WBT, ºF 68 70 72 66 68 70 75 76 78 78 72 74 76 78 80 78 76 78 80 74 76

505103 114 97 81 88 78 64.7 107.6 98 79.3 102 91 78 65.3 136 118.1 113.3 102.7 90.7 78.7 68 61.6505105 122 103.9 87 93.5 83.5 69.6 115.1 104.9 88.6 109.1 97.4 84.5 72.8 145.5 126.3 123.1 113.4 100.6 85.6 77 67.4505175 128.8 109.9 92 99.4 88.1 73.5 121.6 110.7 90.4 115.3 102.8 89.3 76.8 153.7 133.4 130 119.8 106.2 90.4 81.4 71.2606105 172 148.2 126 130 114.7 98.8 164.6 152 123.6 157 133.3 117.3 101.3 207 180.9 172.5 155.3 138 120.6 102 93.2606175 184 159.9 135 137.5 122.7 106.6 176 162.6 132.6 168 142.7 125.5 108.4 221.5 192.1 184.6 166.2 147.7 128.1 109.2 99.7606110 194.4 169.5 142 146.9 129.6 113 185.7 171.8 139.5 177.4 150.7 132.6 114.5 233.9 204.8 194.9 175.5 155.9 136.5 115.3 105.3*707175 240 207.7 175 178.7 160 138.5 228.6 210 173.2 219.6 184.7 163.3 140 285.7 249.4 238.1 213.3 190.5 166.3 140.4 128*707110 256.8 222.3 187 191.2 171.2 148.2 244.4 226 185.7 233.3 197.6 174.8 150.7 307.6 266.6 256.3 229.1 205.1 177.7 150.2 137.4*707115 271.2 234.9 198 201.9 180.8 156.6 258.3 237.3 195.8 246.3 208.7 184.6 158.2 324.9 281.7 270.8 241.1 216.6 187.8 158.6 144.6*808175 338.8 291.2 249 253 225.9 194.1 323 297 249.1 309.1 264 231.7 198 403.7 354.7 336.4 302.9 269.1 236.5 199.3 181.7*808110 369.3 316.1 271 275.8 246.2 210.7 353.7 323.7 264.2 336.9 287.7 252.6 215.8 448.1 391.3 373.4 336.2 298.7 260.9 221.2 201.7*808115 393 336.5 288 299.2 262 224.3 378.5 344.5 285.6 358.6 306.3 268.8 229.7 496.6 420.5 413.8 372.5 331.1 280.3 245.2 223.5*810175 409.3 354.5 295 306.8 272.9 236.3 392.2 360.5 294 375.8 321.1 282.1 240.3 496.6 430.2 413.8 372.2 331.1 286.8 246.2 223.3*810110 438.2 380 315 329.2 292.1 253.3 420 384.3 315 399.2 342.7 300.8 256.2 527.7 459.3 439.8 395.9 351.8 306.2 262.2 237.5*810115 493.3 430 360 368.5 328.9 286.7 472 432.6 354 448.1 381.7 336.6 288.4 583.2 511.1 486 437.6 388.8 340.7 288.4 262.6*810120 525.2 451.5 379 393.7 350.1 301 497.2 458.7 377 474 407.5 357.3 305.8 626.2 543 521.8 468 417.5 362 309.7 280.8*812110 482.6 422 351 361.1 321.7 281.3 465 424.8 348 442 376 331.2 283.2 579.2 508.9 482.7 433.5 386.1 339.3 286.5 260.1*812115 529.4 462 385 395.4 352.9 308 509 465.5 379.2 484.5 412.4 363.3 310.3 636.7 557.9 530.6 475.7 424.5 371.9 314.3 285.4*812120 582.9 507.2 424 436.5 388.6 338.1 553 500 415 526.5 449.5 395.6 333.3 685.9 600 571.6 505.5 457.3 400 340.1 303.3*812125 623.8 548.2 456 466.9 415.9 365.5 594.5 545.8 449.1 566.1 480.8 424 363.9 735.5 640.1 612.9 549.1 490.3 426.7 363.1 329.5510203 216.6 184.3 154 167.2 148.2 122.9 204.4 186.2 150.7 193.8 172.9 148.2 124.1 258.4 224.4 215.3 195.1 172.3 149.5 129.2 117510205 231.8 197.4 165 177.7 158.6 132.1 218.7 199.2 168.3 207.4 185 160.6 138.2 276.5 240 233.8 215.5 191.1 162.6 146.4 128.1510275 244.8 208.8 174 188.9 167.5 139.6 231 210.4 171.8 219 195.4 169.6 146 292 253.5 246.9 227.6 201.8 171.8 154.6 135.3612205 326.8 281.6 239 247 217.9 187.7 312.7 288.8 234.8 298.3 253.3 222.9 192.5 393.3 343.7 327.8 295.1 262.2 229.1 193.8 177.1612275 349.7 303.8 256 261.3 233.1 202.5 334.4 309 251.9 319.2 271.1 238.5 206 420.9 365 350.7 315.8 280.6 243.4 207.5 189.4612210 369.3 322.1 271 279.1 246.2 214.7 352.8 326.3 265.1 337.1 286.3 251.9 217.6 444.4 389.1 370.3 333.5 296.2 259.4 219.1 200.1*714275 456 394.6 333 339.5 304 263.2 434.3 399 329.1 417.2 350.9 310.3 266 542.8 473.9 452.4 405.3 362 316 266.8 243.2*714210 487.9 422.4 356 363.3 325.3 281.6 464.4 429.4 352.8 443.2 375.4 332.1 286.3 584.4 506.5 487 435.3 389.7 337.6 285.4 261.1*714215 515.3 446.3 376 383.6 343.5 297.5 490.8 450.9 372 468 396.5 350.7 300.6 617.3 535.2 514.5 458.1 411.5 356.8 301.3 274.7*816275 643.7 553.3 472 480.7 429.2 368.8 613.7 564.3 473.3 587.3 501.6 440.2 376.2 767 673.9 639.2 575.5 511.3 449.4 378.7 345.2*816210 701.7 600.6 515 524 467.8 400.3 672 615.1 502 640.1 546.6 479.9 410 851.4 743.5 709.5 638.8 567.5 495.7 420.3 383.2*816215 746.7 639.4 548 568.5 497.8 426.2 719.2 654.6 542.6 681.3 582 510.7 436.4 943.5 799 786.2 707.8 629.1 532.6 465.9 424.7*819275 779.8 678.5 568 582.1 519.9 452.3 749.5 690.4 565 719.4 610.3 538.1 460.3 942.6 827.1 785.5 706.5 628.4 551.4 466.4 423.9*819210 846.3 737 618 631.2 564.2 491.3 812 746.9 610 776.8 659.2 581.6 497.9 1014.5 886.5 845.4 760.2 676.3 591 501.8 456.1*819215 942.2 821 691 702.9 785.2 547.3 902 828.7 689 860.3 729.3 643.9 552.5 119.4 978.4 932.8 836.6 746.3 652.3 552.2 502*819220 997.7 875 734 744.1 665.1 583.3 955 875.5 724.5 907.6 768.7 679.3 583.7 1175.2 1030.2 979.3 878.5 783.5 686.8 579.8 527.1*822275 852.9 740 618 637 568.6 493.3 823 752.4 624 783.8 668.2 588.2 501.6 1035.4 900.1 862.9 774.5 690.3 600.1 511.7 464.7*822210 923 802.4 674 688.4 615.3 534.9 890 813.9 670 847.4 718.8 634 542.6 1112.7 971.5 927.3 828.9 741.8 647.6 547.2 497.4*822215 1025.6 898 751 764.6 683.7 598.7 985 900.6 755 935.1 794.8 701.2 600.4 1223.9 1067.8 1019.9 913.1 815.9 711.8 602.9 547.8*822220 1109.5 970 815 827.3 739.7 646.7 1058 972.1 818 1007.4 855 755 648.1 1310.7 1142.3 1092.3 977.3 873.8 761.5 645.3 586.4*827210 997.2 864.5 717 746.9 664.8 576.3 955.5 878.8 714 918.3 783.9 688.7 585.9 1217.5 1053.7 1014.6 910.5 811.7 702.5 602.4 546.3*827215 1171.2 1018 845 876.5 780.8 678.7 1118.5 1022.1 835 1061.5 911.7 799.9 681.4 1411 1220.5 1175.8 1050.7 940.7 813.7 695.3 630.4*827220 1273.4 1110 925 953 848.9 740 1212 1109.4 915 1145.8 984.3 866 739.6 1504.6 1314.5 1253.8 1127.6 1003.1 876.3 746.3 676.6*827225 1353.2 1178 989 1012.1 902.1 785.3 1282 1179.7 973 1222.5 1041.3 917.7 786.5 1592.9 1382.1 1327.4 1188.2 1043.1 921.4 785.8 712.91010403 410.4 349.2 292 316.8 280.8 232.9 387.4 352.8 285.5 367.2 327.6 280.8 235.1 489.6 425.2 407.9 369.7 326.5 283.3 244.8 221.81010405 439.1 374 312 336.6 300.5 250.4 414.4 377.5 319 392.9 350.5 304.3 261.9 523.8 454.7 443 408.3 362.1 308.2 277.3 242.71010475 463.8 395.6 330 358 317.3 264.4 437.8 398.7 325.4 414.9 370.2 321.4 276.6 553.3 480.2 467.8 431.2 382.4 325.4 292.9 256.31212405 619.2 533.5 454 468 412.9 355.7 592.6 547.2 445 565.2 479.9 422.3 364.7 745.2 651.2 621 559.1 496.8 434.2 367.2 335.51212475 662.5 575.6 485 495 441.7 383.8 633.6 585.5 477.4 604.8 513.7 451.8 390.2 797.4 691.6 664.6 598.3 531.7 461.2 393.1 358.91212410 699.7 610.2 513 528.8 466.6 406.8 668.5 618.3 502.2 638.7 542.5 477.4 412.2 842 737.3 701.6 631.8 561.2 491.4 415.1 379.1*1414475 864 747.7 630 643.3 576 498.6 823 756 623.5 790.6 664.9 587.9 504 1028.5 897.8 857.2 767.9 685.8 598.7 505.4 460.8*1414410 924.5 800.3 674 688.3 616.3 533.5 879.8 813.6 668.5 839.7 711.4 629.3 542.5 1107.4 959.8 922.7 824.8 738.4 639.7 540.7 494.6*1414415 976.3 845.6 712 726.8 650.9 563.8 929.9 854.3 704.9 886.8 751.3 664.6 569.5 1169.6 1014.1 974.9 868 779.8 676.1 571 520.6*1616475 1219.7 1048.3 895 910.8 813.2 698.8 1162.8 1069.2 896.8 1112.8 950.4 834.1 712.8 1453.3 1276.9 1211 1090.4 968.8 851.4 717.5 654.1*1616410 1329.5 1138 976 992.9 886.3 758.5 1273.3 1165.4 951.1 1212.9 1035.7 909.4 776.9 1613.2 1408.7 1344.2 1210.3 1075.3 939.2 796.3 726.1*1616415 1414.8 1211.4 1,038 1077.1 943.2 807.5 1362.6 1240.3 1028.2 1290.8 1102.7 967.7 826.9 1787.8 1513.8 1489.7 1341 1192 1009.1 882.7 804.6*1619475 1507.2 1302 1,078 1130.7 1004.8 868 1456 1330.7 1090 1391.2 1190.4 1044.5 887.1 1851.6 1605.6 1543 1387.4 1234.4 1070.4 918.3 832.4*1619410 1633.8 1424 1,166 1227.1 1089.2 949.3 1575 1435.8 1163 1505.5 1286.9 1128.1 957.2 2003.1 1729 1669.3 1496.7 1335.4 1152.7 991.5 898*1619415 1864.5 1615 1,348 1396.7 1243 1076.7 1774 1628.5 1335 1694 1448.7 1272.8 1085.7 2231.1 1932.8 1859.3 1667.1 1487.4 1288.5 1103.9 1000.2*1619420 1995.4 1735 1,449 1494.2 1330.3 1156.7 1891 1739.7 1442 1806.8 1542.7 1357.4 1159.8 2365.8 2054.4 1971.5 1767.4 1577.2 1369.6 1169.8 1060.4*1622475 1631 1408 1,158 1221.7 1087.3 938.7 1569 1432.4 1158 1500 1289.1 1130.3 954.9 2008.7 1735.4 1673.9 1506.3 1339.1 1156.9 998.1 903.8*1622410 1789.6 1551 1,280 1342.8 1193.1 1034 1716.5 1569.8 1247 1638.9 1406.2 1233 1046.5 2182.9 1874.4 1819.1 1632.7 1455.3 1249.6 1081.5 979.6*1622415 2052.7 1782 1,486 1536.8 1368.5 1188 1955 1795.3 1478 1865.6 1594.8 1402.7 1196.9 2455.1 2128 2045.9 1834.8 1636.7 1418.7 1214.2 1100.9*1622420 2231.1 1941.5 1,623 1670.3 1487.4 1294.3 2120 1944.6 1613.5 2015.4 1721.9 1515.7 1296.4 2635.3 2289.4 2196.1 1969.5 1756.9 1526.3 1303.4 1181.7*1627410 1920.2 1702 1,408 1477.5 1313.5 1134.7 1886.5 1728.6 1406 1809.3 1550.8 1359.4 1152.4 2411.4 2076.9 2009.5 1803.8 1607.6 1384.6 1192.9 1082.3*1627415 2284.2 1973.5 1,645 1711.1 1522.8 1315.7 2176 1995 1630 2074.7 1777.5 1561.5 1330 2733.6 2372.1 2278 2049 1822.4 1581.4 1356.6 1229.4*1627420 2474 2149 1,796 1852.3 1649.3 1432.7 2345 2158.2 1770 2240.3 1914.5 1684.1 1438.8 2938.9 2548.3 2449.1 2195.4 1959.3 1698.9 1453.2 1317.2*1627425 2636.3 2292.5 1,924 1973.9 1757.5 1528.3 2490 2296 1902 2374.4 2029.8 1787.1 1530.7 3100.2 2691.1 2583.5 2317.1 2066.8 1794.1 1533.7 1390.3

* Models available with low sound fan. For further information contact your local REYMSA Representative. Certification applies only to units with water as process fluid.

Capacity Table

Page 15: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

TheAll-Fiberglass Cooling Towers

Sustainable Technology

Water ConservationFiberglass materials support water treatment with higher cycles of concentration resulting in less purging, water waste and cost.

Our Cooling Towers are designed to be sustainable and have a low environmental impact.

Life cycles

REYMSA all fiberglass towers have at least 2 times the life span of a galvanized steel tower. This construction also comes with lower annual maintenance cost.

Energy efficient

Our units exceed energy efficiency per ASHRAE Standard 90.1-2013 to reduce the unit’s operating cost.

REYMSA Cooling Towers 15

Page 16: The All-Fiberglass - Houston Commercial HVAC VFD ABB Water ...recohvac.com/wp-content/uploads/2015/10/HFC_series.pdf · The All-Fiberglass owers Water ... A. Recirculating water is

(Brochure/HFC/Eng/Jul15)

REYMSA COOLING TOWERS, INC.

Toll free: 1.866.445.2043, Ph: (956) 568.4062, Fax: (956) 717.2431 [email protected] www.reymsa.com