Testing and Design of Advanced Treatment Facilities to Remove

EDCs

2008 WEAU Mid-Year ConferenceJ. Clinton Rogers

[email protected]

Page 2: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

AcknowledgementsCoauthors:

Michael Luers, Snyderville BasinMichael Boyle, Snyderville BasinCraig Ashcroft Andy Salveson

Other Contributors:Keel Robinson, Applied Process Tech., Inc.Dr. Karl Linden, Duke UniversityDr. Shane Snyder, Southern Nevada Water Authority

Analytical Labs:Chemtech Ford, MWH Labs, Wisconsin State Hygiene Lab

Page 3: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

AP Story March 2008: Pharmaceuticals in Water

Page 4: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

SBWRD Is Concerned About the Possible Effects of EDCs on Downstream Fish

Brown Trout(Salmo trutta)Bonneville Cutthroat(Oncorhynchus clarki)

Page 5: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

What Is SBWRD’s Position Concerning EDC’s?

Currently there are no regulatory requirements to remove EDC’s.

The District has spent millions of dollars to improve water quality. It only makes sense to be proactive in addressing EDC’s.

The District has conducted pilot studies on how to remove EDC’s.

The District is working with the DWR Fisheries Experiment Station to conduct pathology studies of various species of fish to determine if estrogenicity is taking place.

Michael Luers, SBWRD General Manager - WEAU Annual Conference, St. George, Utah, April 2008.

Page 6: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Design Project for East Canyon WRF in Park City, Utah

Page 7: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

SBWRD Funded the Investigation of Three EDC Removal Technologies

GAC Filtration

Ozone/Peroxide

UV/Peroxide

Page 8: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Three Technologies Tested Using ECWRF Effluent

Developed Costs of Full-Scale Implementation

Recommendation on Technology of Choice

Identified a Potential Treatment Target for EDC Removal

Study Outcomes

Page 9: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Testing Methods and Results

Page 10: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Target EDC Analytes

USGS Method 2 – APCI Positive Ion Mode Only

natural hormoneTestosterone

natural hormoneProgesterone

synthetic hormoneEthinyl Estradiol

natural hormoneEstradiol

natural hormoneEstrone

pharmaceutical (epilepsy, bipolar)Carbamazepine

Page 11: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

E-Screen BioassayBreast cancer cell line, growth response to estrogen

Reported as Estradiol equivalents (MRL = 0.030 ppt)

Negative Control

Positive Control

Page 12: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Sample Collection

Page 13: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Sorption Pilot-Scale Apparatus

Page 14: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Sorption Pilot-Scale Apparatus

Page 15: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Carbamazepine Hits Min Max AvgPlant Eff 6 40 146 95

Column 1 4 5.1 12 7.9Column 2 3 20 37 27Column 3 4 5.0 19 10

Estradiol Hits Min Max AvgPlant Eff 3 1.6 2.2 1.8

Page 16: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Carbamazepine Hits Min Max AvgPlant Eff 6 40 146 95

Column 1 4 5.1 12 7.9Column 2 3 20 37 27Column 3 4 5.0 19 10

Estradiol Hits Min Max AvgPlant Eff 3 1.6 2.2 1.8

Page 17: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Carbamazepine Hits Min Max AvgPlant Eff 6 40 146 95

Column 1 4 5.1 12 7.9Column 2 3 20 37 27Column 3 4 5.0 19 10

Estradiol Hits Min Max AvgPlant Eff 3 1.6 2.2 1.8

Page 18: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Carbamazepine Hits Min Max AvgPlant Eff 6 40 146 95

Column 1 4 5.1 12 7.9Column 2 3 20 37 27Column 3 4 5.0 19 10

Estradiol Hits Min Max AvgPlant Eff 3 1.6 2.2 1.8

Page 19: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Carbamazepine Hits Min Max AvgPlant Eff 6 40 146 95

Column 1 4 5.1 12 7.9Column 2 3 20 37 27Column 3 4 5.0 19 10

Estradiol Hits Min Max AvgPlant Eff 3 1.6 2.2 1.8

Page 20: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Ethinyl Estradiol Hits Conc.Plant Eff 1 13

Column 1 1 2.6Column 2 1 4.5Column 3 1 3.0

E-Screen PE C1 C2 C3Estradiol Equivalents 0.77 <0.03 <0.03 <0.03

Page 21: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Ethinyl Estradiol Hits Conc.Plant Eff 1 13

Column 1 1 2.6Column 2 1 4.5Column 3 1 3.0

E-Screen PE C1 C2 C3Estradiol Equivalents 0.77 <0.03 <0.03 <0.03

Page 22: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Filtration Reduced EDC Concentrations in ECWRF Effluent

Ethinyl Estradiol Hits Conc.Plant Eff 1 13

Column 1 1 2.6Column 2 1 4.5Column 3 1 3.0

E-Screen PE C1 C2 C3Estradiol Equivalents 0.77 <0.03 <0.03 <0.03

Page 23: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Carbamazepine

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0 2000 4000 6000 8000 10000Bed Volumes

CEf

fluen

t/CIn

fluen

t

Column 1Column 2Column 3

8500 BV

Carbamazepine: A Tracer for Estimating GAC Bed Life

Page 24: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

GAC Treatment Improved Water Quality

0123456

Feb-14 Mar-20 Mar-27

TOC

(mg/

L)PlantEffluentColumn 1

Column 2

Column 3

TOC as a surrogate for real time filter performance?

Page 25: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Ozone Bench-Scale Apparatus

Courtesy of Applied Process Technology, Inc.

Page 26: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Ozone Treatment Effective for EDC/PPCP Removal

ConstituentPlant Eff

Conc (ng/L)

Conc after O3

(5 ppm)Estradiol Equivalents 0.92 <0.10Gemifibrozil 116 <1.0Ibuprofen 36 6.7Triclosan 13 <5.0Caffeine 45 <3.0Fluoxetine 20 <1.0Sulfamethoxazole 524 <1.0Trimethoprim 76 <1.0

#/100mLE. Coli. 12000 <1

Page 27: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Ozone/Peroxide Improved Removal of Ibuprofen

0

5

10

15

20

25

30

35

40

0.0 5.0 10.0 15.0

Ozone (ppm)

Ibup

rofe

n (n

g/L)

Ozone OnlyAOP MR=0.35AOP MR=0.70

80% Removal

90% Removal

93% Removal

Page 28: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

UV Bench-Scale Apparatus

Courtesy of Duke University Research Group

Page 29: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

UV/Peroxide: A Trend of EEQ Removal Seen at Highest UV Fluence

0.0

0.5

1.0

1.5

2.0

2.5

0 80 200 400

UV Fluence (mJ/cm2)

EEQ

s (n

g/L)

0 mg/L H2O22 mg/L H2O25 mg/L H2O210 mg/L H2O2

Page 30: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Costs and Recommendation

Page 31: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Cost Estimate Development

Assumptions:

Build new 7.2 mgd facility (AADF only)

Vendor quotes for equipment

$250/ sq ft. building cost

6% interest rate for 20 yr PW

GAC: 2 exchanges per year @ $350K

Ozone: 5ppm with H2O2, no CT basin

UV: 400mJ/cm2 low pressure lamps

Page 32: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Ozone Treatment of EDCs is the Most Economical Alternative

$0

$2

$4

$6

$8

$10

$12

GAC Ozone UV

Cap

ital &

Life

Cyc

le ($

Mill

ion)

$0.1

$0.3

$0.5

$0.7

$0.9

Ann

ual O

&M

Cos

ts ($

Mill

ion)Captial

Life CycleO&M

Page 33: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Advanced Oxidation with Ozone Recommended as Technology of Choice

Advantages:

Lowest cost alternative based on 20 year PW

Greater flexibility in treatment

Effective for a wide variety of chemicals

Vary the dose and/or add peroxide

Disadvantages:

Highest Capital Cost & Oxidation Byproducts

Page 34: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

EDC Removal Using Existing Infrastructure

Existing Granular Media Filter

(Parkson Dynasand)

GAC Contactor

Page 35: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Determine a Treatment Target

Source: National Drinking Water Clearing House, On Tap, Winter 2003.

Page 36: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

What Should the Treatment Target be in the Absence of a Permit?

Determined environmentally safe level for two most common constituents:

Estrogen Activity Carbamazepine

Page 37: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Carbamazepine is Not Suitable for Use as a Treatment Target

Published Ecotoxicity Values:

Acute Toxicity (EC50) – 15 to 60 ppm

(Jos et al, 2003., Ferrari et al, 2006., & Kim et al, 2007.)

Chronic Toxicity (LOEC) – 1 ppb(Triebskorn et al, 2003.)

ECWRF Highest Observed Conc. – 146 ppt(10 times lower than LOEC)

Page 38: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

A Reduction of Estrogenic Activity may be the best Treatment Target

Published Values for Measurable Effects:

Estrogenic Activity – 1 to 4 ppt

Observed Effects: Vitellogenin, Intersex, Feminization

(Purdom et al, 1994., Snyder et al, 2003., & Fent et al, 2006.)

ECWRF Highest Observed Conc. – 1.2 pptAverage Conc. 0.8 ppt

Treatment Target: Estrogenic Activity of less than 1 ppt E-Screen Bioassay

Page 39: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Conclusions

GAC Filtration and Ozone Oxidation were effective at reducing EDCs in ECWRF effluent

Ozone/Peroxide advanced oxidation most economical treatment technology

Best available treatment target is an estrogenic activity of 1.0 ppt or less

Page 40: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Future ResearchPhase II: Assess Impacts on Downstream Fish

Sex Ratio Investigation and Sentinel Study

Page 41: Testing and Design of Advanced Treatment Facilities to ...Parkson Dynasand) GAC Contactor. Determine a Treatment Target Source: National Drinking Water Clearing House, On Tap, Winter

Questions?