Contents
Page
Circuit and people protection
MCBs
Miniature circuit breakers DPE06. .............................................................................................................................. 7
Miniature circuit breakers DS1 and DS. ................................................................................................................. 8
Miniature circuit breakers DH. ....................................................................................................................................... 10
Miniature circuit breakers TDH and accessories. ............................................................................................ 12
Electrical accessories for EcoPlus and TemDin2. .......................................................................................... 13
Mechanical accessories for EcoPlus and TemDin2. ..................................................................................... 14
RCDs
Residual current circuit breakers FIEP and ZFP. ............................................................................................ 15
Residual current circuit breakers ZFP and accessories. ........................................................................... 15
Residual current circuit breakers ZD06 Add-on-block for DS and DH. ........................................... 16
RCBOs
Residual current circuit breakers with overcurrent protection ZDH. .................................................. 17
Residual current circuit breakers with overcurrent protection ZDS. .................................................. 17
Residual current circuit breakers with overcurrent protection FCOP. .............................................. 18
Command and control
Contactors CDO and CDR. .............................................................................................................................................. 19
Contactors CDI and poles spacer CNCP. ............................................................................................................. 20
Motor operator ZFR. .............................................................................................................................................................. 21 Pushbuttons PD, PDL.......................................................................................................................................................... 21
Switches and changeover switches WDM. .......................................................................................................... 21
Mains disconnect switches DDF.................................................................................................................................. 22
Socket-outlet HD. .................................................................................................................................................................... 22
Programming and measurement
Time switches RDA, RDD. ............................................................................................................................................... 23
Staircase switch SDS016C.............................................................................................................................................. 24
Pilots LD. ....................................................................................................................................................................................... 24
Bell+buzzer+transformer TDB. ...................................................................................................................................... 24
Light sensitive switch RDA. ............................................................................................................................................. 24
Digital measurement instruments MDD. ................................................................................................................ 25
Active energy meter MDA................................................................................................................................................. 25
Analogue ammeters and voltmeters MDA. .......................................................................................................... 26
Current transformer TDC. ................................................................................................................................................. 26
Modular protection
Safety transformers TDS. .................................................................................................................................................. 27
Disconnector fuse holders FD. ...................................................................................................................................... 27
Surge arresters TM................................................................................................................................................................ 28
Permanent overvoltage protection TD2YD .......................................................................................................... 29
Permanent overvoltage protection and Transient surge protection solutions ........................... 30
Data subject to change without notice
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 6/56
6
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 7/56
7
In DIN Type C Type BPoles
(A) mod. Reference Reference
1 6 1 DPE06C10006 DPE06B10006
1 10 1 DPE06C10010 DPE06B10010
1 16 1 DPE06C10016 DPE06B10016
1 20 1 DPE06C10020 DPE06B10020
1 25 1 DPE06C10025 DPE06B10025
1 32 1 DPE06C10032 DPE06B10032
1 40 1 DPE06C10040 DPE06B10040
1 50 1 DPE06C10050 DPE06B10050
1 63 1 DPE06C10063 DPE06B10063
1+N 6 2 DPE06C11006 DPE06B11006
1+N 10 2 DPE06C11010 DPE06B11010
1+N 16 2 DPE06C11016 DPE06B11016
1+N 20 2 DPE06C11020 DPE06B11020
1+N 25 2 DPE06C11025 DPE06B11025
1+N 32 2 DPE06C11032 DPE06B11032
1+N 40 2 DPE06C11040 DPE06B11040
1+N 50 2 DPE06C11050 DPE06B11050
1+N 63 2 DPE06C11063 DPE06B11063
2 6 2 DPE06C20006 DPE06B20006
2 10 2 DPE06C20010 DPE06B20010
2 16 2 DPE06C20016 DPE06B20016
2 20 2 DPE06C20020 DPE06B20020
2 25 2 DPE06C20025 DPE06B20025
2 32 2 DPE06C20032 DPE06B20032
2 40 2 DPE06C20040 DPE06B20040
2 50 2 DPE06C20050 DPE06B20050
2 63 2 DPE06C20063 DPE06B20063
3 6 3 DPE06C30006 DPE06B30006
3 10 3 DPE06C30010 DPE06B300103 16 3 DPE06C30016 DPE06B30016
3 20 3 DPE06C30020 DPE06B30020
3 25 3 DPE06C30025 DPE06B30025
3 32 3 DPE06C30032 DPE06B30032
3 40 3 DPE06C30040 DPE06B30040
3 50 3 DPE06C30050 DPE06B30050
3 63 3 DPE06C30063 DPE06B30063
4 6 4 DPE06C40006 DPE06B40006
4 10 4 DPE06C40010 DPE06B40010
4 16 4 DPE06C40016 DPE06B40016
4 20 4 DPE06C40020 DPE06B40020
4 25 4 DPE06C40025 DPE06B40025
4 32 4 DPE06C40032 DPE06B40032
4 40 4 DPE06C40040 DPE06B40040
4 50 4 DPE06C40050 DPE06B40050
4 63 4 DPE06C40063 DPE06B40063
Short-circuit capacity
6kA (EN 60898)
Tripping characteristic
C and B
Miniature circuit breakers DPE06
TechnicalData
Rated voltage 230/400V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 1-25mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p 1p+N 2p 3p 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898
Miniature circuit breakers DPE06
Accessories on page 13.
Circuit and People Protection
EcoPlus
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 8/56
8
Rated voltage 230V/400V~, 240V/415V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 35mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p 1p+N 2p 3p 3p+N 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898, EN 60947-2
UNE 20317NOTE: Suitable for use at 240/415V. / Suitable for isolation.
TechnicalData
Short-circuit capacity
6kA (EN 60898)
Tripping characteristic
C, B and D
Rated voltage 230V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 16mm2 exible / 25mm2 rigid
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p+N
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898
TechnicalData
Tripping characteristic
C
Short-circuit capacity
6kA (EN 60898)
Miniature Circuit Breakers DS 6kA
In DIN Type
Poles (A) mod. C
1+N 6 1 DS041NC006
1+N 10 1 DS041NC010
1+N 16 1 DS041NC016
1+N 20 1 DS041NC020
1+N 25 1 DS041NC025 1+N 32 1 DS041NC032
1+N 40 1 DS041NC040
Note: Terasaki recommends
the Pozidrive 2 use.
In DIN TypePoles
(A) mod. C B D
1 0.3 1 - - DS06D100V3
1 0.5 1 - - DS06D100V5
1 0.75 1 - - DS06D100V7
1 1 1 - - DS06D10001
1 1.6 1 - - DS06D101V6
1 2 1 - - DS06D10002
1 2.5 1 - - DS06D102V5
1 3 1 - - DS06D10003
1 3.5 1 - - DS06D103V5
1 4 1 - - DS06D10004
1 6 1 DS06C10006 DS06B10006 DS06D10006
1 8 1 DS06C10008 DS06B10008 DS06D10008
1 10 1 DS06C10010 DS06B10010 DS06D10010
1 13 1 DS06C10013 DS06B10013 DS06D10013
1 16 1 DS06C10016 DS06B10016 DS06D10016
1 20 1 DS06C10020 DS06B10020 DS06D10020
1 25 1 DS06C10025 DS06B10025 DS06D10025
1 32 1 DS06C10032 DS06B10032 DS06D10032
1 40 1 DS06C10040 DS06B10040 DS06D10040
1 50 1 DS06C10050 DS06B10050 DS06D10050
1 63 1 DS06C10063 DS06B10063 DS06D10063
1+N 0.3 2 - - DS06D110V3
1+N 0.5 2 - - DS06D110V5
1+N 0.75 2 - - DS06D110V7
1+N 1 2 - - DS06D11001
1+N 1.6 2 - - DS06D111V6
1+N 2 2 - - DS06D11002
1+N 2.5 2 - - DS06D112V5
1+N 3 2 - - DS06D11003
1+N 3.5 2 - - DS06D113V5
1+N 4 2 - - DS06D11004
1+N 6 2 DS06C11006 DS06B11006 DS06D11006
1+N 8 2 DS06C11008 DS06B11008 DS06D11008
1+N 10 2 DS06C11010 DS06B11010 DS06D11010
1+N 13 2 DS06C11013 DS06B11013 DS06D11013
1+N 16 2 DS06C11016 DS06B11016 DS06D11016
1+N 20 2 DS06C11020 DS06B11020 DS06D11020
1+N 25 2 DS06C11025 DS06B11025 DS06D11025
1+N 32 2 DS06C11032 DS06B11032 DS06D11032
1+N 40 2 DS06C11040 DS06B11040 DS06D11040
1+N 50 2 DS06C11050 DS06B11050 DS06D11050
1+N 63 2 DS06C11063 DS06B11063 DS06D11063
Note: Terasaki recommends
the Pozidrive 2 use.
Accessories on page 13.
Accessories on page 13.
Circuit and People Protection
1+N in 1 module
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 9/56
9
Short-circuit capacity
6kA (EN 60898)
Tripping characteristic
C, B and D
Miniature Circuit Breakers DS 6kA
In DIN TypePoles
(A) mod. C B D
2 0.3 2 - - DS06D200V3
2 0.5 2 - - DS06D200V5
2 0.75 2 - - DS06D200V7
2 1 2 - - DS06D20001
2 1.6 2 - - DS06D201V6
2 2 2 - - DS06D20002
2 2.5 2 - - DS06D202V5
2 3 2 - - DS06D200032 3.5 2 - - DS06D203V5
2 4 2 - - DS06D20004
2 6 2 DS06C20006 DS06B20006 DS06D20006
2 8 2 DS06C20008 DS06B20008 DS06D20008
2 10 2 DS06C20010 DS06B20010 DS06D20010
2 13 2 DS06C20013 DS06B20013 DS06D20013
2 16 2 DS06C20016 DS06B20016 DS06D20016
2 20 2 DS06C20020 DS06B20020 DS06D20020
2 25 2 DS06C20025 DS06B20025 DS06D20025
2 32 2 DS06C20032 DS06B20032 DS06D20032
2 40 2 DS06C20040 DS06B20040 DS06D20040
2 50 2 DS06C20050 DS06B20050 DS06D20050
2 63 2 DS06C20063 DS06B20063 DS06D20063
3 0.3 3 - - DS06D300V3
3 0.5 3 - - DS06D300V5
3 0.75 3 - - DS06D300V7
3 1 3 - - DS06D30001
3 1.6 3 - - DS06D301V6
3 2 3 - - DS06D30002
3 2.5 3 - - DS06D302V5
3 3 3 - - DS06D30003
3 3.5 3 - - DS06D303V5
3 4 3 - - DS06D30004
3 6 3 DS06C30006 DS06B30006 DS06D30006
3 8 3 DS06C30008 DS06B30008 DS06D30008
3 10 3 DS06C30010 DS06B30010 DS06D30010
3 13 3 DS06C30013 DS06B30013 DS06D30013
3 16 3 DS06C30016 DS06B30016 DS06D30016
3 20 3 DS06C30020 DS06B30020 DS06D30020
3 25 3 DS06C30025 DS06B30025 DS06D30025
3 32 3 DS06C30032 DS06B30032 DS06D30032
3 40 3 DS06C30040 DS06B30040 DS06D30040
3 50 3 DS06C30050 DS06B30050 DS06D30050
3 63 3 DS06C30063 DS06B30063 DS06D30063
3+N 0.3 4 - - DS06D310V33+N 0.5 4 - - DS06D310V5
3+N 0.75 4 - - DS06D310V7
3+N 1 4 - - DS06D31001
3+N 1.6 4 - - DS06D311V6
3+N 2 4 - - DS06D31002
3+N 2.5 4 - - DS06D312V5
3+N 3 4 - - DS06D31003
3+N 3.5 4 - - DS06D313V5
3+N 4 4 - - DS06D31004
3+N 6 4 DS06C31006 DS06B31006 DS06D31006
3+N 8 4 DS06C31008 DS06B31008 DS06D31008
3+N 10 4 DS06C31010 DS06B31010 DS06D31010
3+N 13 4 DS06C31013 DS06B31013 DS06D31013
3+N 16 4 DS06C31016 DS06B31016 DS06D31016
3+N 20 4 DS06C31020 DS06B31020 DS06D31020
3+N 25 4 DS06C31025 DS06B31025 DS06D31025
3+N 32 4 DS06C31032 DS06B31032 DS06D31032
3+N 40 4 DS06C31040 DS06B31040 DS06D310403+N 50 4 DS06C31050 DS06B31050 DS06D31050
3+N 63 4 DS06C31063 DS06B31063 DS06D31063
4 0.3 4 - - DS06D400V3
4 0.5 4 - - DS06D400V5
4 0.75 4 - - DS06D400V7
4 1 4 - - DS06D40001
4 1.6 4 - - DS06D401V6
4 2 4 - - DS06D40002
4 2.5 4 - - DS06D402V5
4 3 4 - - DS06D40003
4 3.5 4 - - DS06D403V5
4 4 4 - - DS06D40004
4 6 4 DS06C40006 DS06B40006 DS06D40006
4 8 4 DS06C40008 DS06B40008 DS06D40008
4 10 4 DS06C40010 DS06B40010 DS06D40010
4 13 4 DS06C40013 DS06B40013 DS06D40013
4 16 4 DS06C40016 DS06B40016 DS06D40016
4 20 4 DS06C40020 DS06B40020 DS06D40020
4 25 4 DS06C40025 DS06B40025 DS06D40025
4 32 4 DS06C40032 DS06B40032 DS06D40032
4 40 4 DS06C40040 DS06B40040 DS06D40040
4 50 4 DS06C40050 DS06B40050 DS06D40050
4 63 4 DS06C40063 DS06B40063 DS06D40063
Rated voltage 230V/400V~, 240V/415V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 35mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p 1p+N 2p 3p 3p+N 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898, EN 60947-2
UNE 20317
NOTE: Suitable for use at 240/415V. / Suitable for isolation.
TechnicalData
Note: Terasaki recommends
the Pozidrive 2 use.
Accessories on page 13.
Circuit and People Protection
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 10/56
10
Note: Terasaki recommends
the Pozidrive 2 use.
Rated voltage 230V/400V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 35 mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p 1p+N 2p 3p 3p+N 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898
NOTE: Suitable for use at 240/415V.
TechnicalData
Short-circuit capacity
10kA (EN 60898)
Tripping characteristic
C, B and D
Miniature Circuit Breakers DH 10kA
Poles
In DIN Type(A) mod. C B D
1 0.3 1 - - DH06D100V3
1 0.5 1 - - DH06D100V5
1 0.75 1 - - DH06D100V7
1 1 1 - - DH06D10001
1 1.6 1 - - DH06D101V61 2 1 - - DH06D10002
1 2.5 1 - - DH06D102V5
1 3 1 - - DH06D10003
1 3.5 1 - - DH06D103V5
1 4 1 - - DH06D10004
1 6 1 DH06C10006 DH06B10006 DH06D10006
1 8 1 DH06C10008 DH06B10008 DH06D10008
1 10 1 DH06C10010 DH06B10010 DH06D10010
1 13 1 DH06C10013 DH06B10013 DH06D10013
1 16 1 DH06C10016 DH06B10016 DH06D10016
1 20 1 DH06C10020 DH06B10020 DH06D10020
1 25 1 DH06C10025 DH06B10025 DH06D10025
1 32 1 DH06C10032 DH06B10032 DH06D10032
1 40 1 DH06C10040 DH06B10040 DH06D10040
1 50 1 DH06C10050 DH06B10050 DH06D10050
1 63 1 DH06C10063 DH06B10063 DH06D10063
1+N 0.3 2 - - DH06D110V3
1+N 0.5 2 - - DH06D110V5
1+N 0.75 2 - - DH06D110V7
1+N 1 2 - - DH06D11001
1+N 1.6 2 - - DH06D111V6
1+N 2 2 - - DH06D11002
1+N 2.5 2 - - DH06D112V5
1+N 3 2 - - DH06D11003
1+N 3.5 2 - - DH06D113V5
1+N 4 2 - - DH06D11004
1+N 6 2 DH06C11006 DH06B11006 DH06D11006
1+N 8 2 DH06C11008 DH06B11008 DH06D11008
1+N 10 2 DH06C11010 DH06B11010 DH06D11010
1+N 13 2 DH06C11013 DH06B11013 DH06D11013
1+N 16 2 DH06C11016 DH06B11016 DH06D11016
1+N 20 2 DH06C11020 DH06B11020 DH06D11020
1+N 25 2 DH06C11025 DH06B11025 DH06D11025
1+N 32 2 DH06C11032 DH06B11032 DH06D11032
1+N 40 2 DH06C11040 DH06B11040 DH06D11040
1+N 50 2 DH06C11050 DH06B11050 DH06D11050
1+N 63 2 DH06C11063 DH06B11063 DH06D11063
2 0.3 2 - - DH06D200V3
2 0.5 2 - - DH06D200V5
2 0.75 2 - - DH06D200V72 1 2 - - DH06D20001
2 1.6 2 - - DH06D201V6
2 2 2 - - DH06D20002
2 2.5 2 - - DH06D202V5
2 3 2 - - DH06D20003
2 3.5 2 - - DH06D203V5
2 4 2 - - DH06D20004
2 6 2 DH06C20006 DH06B20006 DH06D20006
2 8 2 DH06C20008 DH06B20008 DH06D20008
2 10 2 DH06C20010 DH06B20010 DH06D20010
2 13 2 DH06C20013 DH06B20013 DH06D20013
2 16 2 DH06C20016 DH06B20016 DH06D20016
2 20 2 DH06C20020 DH06B20020 DH06D20020
2 25 2 DH06C20025 DH06B20025 DH06D20025
2 32 2 DH06C20032 DH06B20032 DH06D20032
2 40 2 DH06C20040 DH06B20040 DH06D20040
2 50 2 DH06C20050 DH06B20050 DH06D20050
2 63 2 DH06C20063 DH06B20063 DH06D20063
Accessories on page 13.
Circuit and People Protection
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 11/56
11
Miniature Circuit Breakers DH 10kA
Poles
In DIN Type(A) mod. C B D
3 0.3 3 - - DH06D300V3
3 0.5 3 - - DH06D300V5
3 0.75 3 - - DH06D300V7
3 1 3 - - DH06D30001
3 1.6 3 - - DH06D301V6
3 2 3 - - DH06D300023 2.5 3 - - DH06D302V5
3 3 3 - - DH06D30003
3 3.5 3 - - DH06D303V5
3 4 3 - - DH06D30004
3 6 3 DH06C30006 DH06B30006 DH06D30006
3 8 3 DH06C30008 DH06B30008 DH06D30008
3 10 3 DH06C30010 DH06B30010 DH06D30010
3 13 3 DH06C30013 DH06B30013 DH06D30013
3 16 3 DH06C30016 DH06B30016 DH06D30016
3 20 3 DH06C30020 DH06B30020 DH06D30020
3 25 3 DH06C30025 DH06B30025 DH06D30025
3 32 3 DH06C30032 DH06B30032 DH06D30032
3 40 3 DH06C30040 DH06B30040 DH06D30040
3 50 3 DH06C30050 DH06B30050 DH06D30050
3 63 3 DH06C30063 DH06B30063 DH06D30063
3+N 0.3 4 - - DH06D310V3
3+N 0.5 4 - - DH06D310V5
3+N 0.75 4 - - DH06D310V7
3+N 1 4 - - DH06D31001
3+N 1.6 4 - - DH06D311V6
3+N 2 4 - - DH06D31002
3+N 2.5 4 - - DH06D312V5
3+N 3 4 - - DH06D31003
3+N 3.5 4 - - DH06D313V5
3+N 4 4 - - DH06D31004
3+N 6 4 DH06C31006 DH06B31006 DH06D31006
3+N 8 4 DH06C31008 DH06B31008 DH06D310083+N 10 4 DH06C31010 DH06B31010 DH06D31010
3+N 13 4 DH06C31013 DH06B31013 DH06D31013
3+N 16 4 DH06C31016 DH06B31016 DH06D31016
3+N 20 4 DH06C31020 DH06B31020 DH06D31020
3+N 25 4 DH06C31025 DH06B31025 DH06D31025
3+N 32 4 DH06C31032 DH06B31032 DH06D31032
3+N 40 4 DH06C31040 DH06B31040 DH06D31040
3+N 50 4 DH06C31050 DH06B31050 DH06D31050
3+N 63 4 DH06C31063 DH06B31063 DH06D31063
4 0.3 4 - - DH06D400V3
4 0.5 4 - - DH06D400V5
4 0.75 4 - - DH06D400V7
4 1 4 - - DH06D40001
4 1.6 4 - - DH06D401V6
4 2 4 - - DH06D40002
4 2.5 4 - - DH06D402V5
4 3 4 - - DH06D40003
4 3.5 4 - - DH06D403V5
4 4 4 - - DH06D40004
4 6 4 DH06C40006 DH06B40006 DH06D40006
4 8 4 DH06C40008 DH06B40008 DH06D40008
4 10 4 DH06C40010 DH06B40010 DH06D40010
4 13 4 DH06C40013 DH06B40013 DH06D40013
4 16 4 DH06C40016 DH06B40016 DH06D40016
4 20 4 DH06C40020 DH06B40020 DH06D40020
4 25 4 DH06C40025 DH06B40025 DH06D40025
4 32 4 DH06C40032 DH06B40032 DH06D40032
4 40 4 DH06C40040 DH06B40040 DH06D40040
4 50 4 DH06C40050 DH06B40050 DH06D40050
4 63 4 DH06C40063 DH06B40063 DH06D40063
Short-circuit capacity
10kA (EN 60898)
Tripping characteristic
C, B and D
Note: Terasaki recommends
the Pozidrive 2 use.
Rated voltage 230V/400V~
Frequency 50/60Hz
Calibration temperature 30oC
Terminal capacity 35 mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles 1p 1p+N 2p 3p 3p+N 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60898
NOTE: Suitable for use at 240/415V.
TechnicalData
Accessories on page 13.
Circuit and People Protection
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 12/56
12
Rated voltage 240V/415V~
Frequency 50/60Hz
Rated insulation voltage 500V~
Calibration temperature 30oC
Terminal capacity max. 35mm2 exible conductor
max. 50mm2 rigid cable
Electrical endurance 10,000
Mechanical endurance 10,000
Poles 1p 2p 3p 4p
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards UNE-EN 60898 and IEC 947-2: 10kA
Suitable for isolation
TechnicalData
Short-circuit capacity
10kA (EN 60947-2)
Miniature Circuit Breakers TDHTripping curvesThe TDH series of Miniature Circuit Breakers are manufactured inaccordance with EN 60947-2.
- Curve C: magnetic trip threshold = 5 - 10 In- Curve D: magnetic trip threshold = 10 - 20 In
Poles
In DIN Trip(A) mod. C D
1 80A 1.5 TDHC1080 TDHD1080
1 100A 1.5 TDHC1100 TDHD1100
1 125A 1.5 TDHC1125 TDHD1125
2 80A 3 TDHC2080 TDHD2080
2 100A 3 TDHC2100 TDHD2100
2 125A 3 TDHC2125 TDHD2125
3 80A 4.5 TDHC3080 TDHD3080
3 100A 4.5 TDHC3100 TDHD3100
3 125A 4.5 TDHC3125 TDHD3125
4 80A 6 TDHC4080 TDHD4080
4 100A 6 TDHC4100 TDHD4100
4 125A 6 TDHC4125 TDHD4125
Miniature Circuit Breakers TDH 10kA80, 100 and 125A
Sensitivities 30, 300, 500 and 1000mA
Type AC
DIN modules width 6
Terminal capacity max. 35mm2 exible cable
max. 50mm2 rigid cable
Right side add-on TDH (80, 100, 125A)
RCD add-on blockTypes adjustable in time an sensitivity.
Poles
2
2
4
4
4
Sensitivity(mA)
30
Adjustable
300-500-1000
30
300
Adjustable300-500-1000
Timer(ms)
Instantaneous
Adjustable
0-60-150
Instantaneous
Instantaneous
Adjustable0-60-150
Reference
ZD1252030AC
ZD1252000AC
ZD1254030AC
ZD1254300AC
ZD1254000AC
DIN Description Reference mod.
1/2 1NO + 1NC TDHAUX
1/2 1NO + 1NC TDHAL
Alarm or auxiliary contact1/2 module device for monitoring the status of TDH breakers(open/closed), or trip condition on overload operation.
DIN mod. ½Max. rated current: 6A-230V~
Terminal capacity 0.5 to 4 exible cable
1 to 6 rigid cable.
Can be coupled on the left side of MCB TDH (80, 100, 125A).
Shunt trip (SHT) and Undervoltage release (UVT)Shunt trip allowing remote opening of the circuit via a push button orsimiliar device. Undervoltage release enables theautomatic trip of the MCB if the supply voltagedrops below 35~70% of Ue.
DINDescription Reference
mod.
1 230V~ TDHSHT230
1 230V~ TDHUVT230
DIN mod. 1
Terminal capacity 0.5 to 4 exible cable
1 to 6 rigid cable.
Can be coupled on the left side.
Circuit and People Protection
Note: Terasaki recommends
the Pozidrive 2 use.
Accessories for TDH series
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 13/56
13
Two change over contacts that include both funtions described below:AUX - Auxiliary contact: for monitoring the status of the protective
device (open/closed).
AL - Signal or auxiliary contact: for signalling the automatic trippingof the protective devices (overload or short-circuit for MCBs).
Accessories for TemDin2 DS and DH seriesMounted on to the left side of the MCB.
Rated voltage 230V/400V~
Rated current 6A
Frequency 50/60Hz
Calibration temperature 30oC
Performance
AC14 Ue 230V 400V
Ie 8A 5A
AC15 Ue 230V 400V
Ie 5A 3A
Terminal capacity 2.5 mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Standards EN62019
EN60947-5-1
YD alarm or auxiliary contact DIN
Description Reference mod.
1 Contact Aux/Al changeover YDA40
1 Contact Aux/AI NO YDA10
1 Contact Aux/AI NC YDA01
1 Contact Aux changeover YDX40
1 Contact Aux NO YDX10
1 Contact Aux NC YDX01
Auxiliary contact DPEAUX1
1/2 DIN module width
Double contact NO+NC signal
Terminal capacity 1-4mm2
Mounting left side
TechnicalData
Shunt trip DPESHT
1 DIN module width
Terminal capacity 1-25mm2
Mounting right side
Single phase overvoltage release with protection
against permanent overvoltage for MCB tripping.
For surge protection use, please refer to page 29.
YDO overvoltage release DINDescription Reference
mod.
Overvoltage release with protection against
1 phase-N 230Vac permanent overvoltage, YDO276
tripping voltage 276Vac.
Electrical accessories for EcoPlus and TemDin2
Accessories for EcoPlus DPE series
Auxiliary contact DIN
Description Reference mod.
1/2 Double aux contact NO+NC DPEAUX1
EcoPlus
Shunt trip DIN
Description Reference mod.
1 Shunt trip 230Vac DPESHT230
1 Shunt trip 48Vdc DPESHT48
EcoPlus
Undervoltage release YDU
Frequency 50/60Hz
Calibration temperature 30oC
Performance
Tripping voltage 0.55Ue(+/-10%)
Resetting voltage >=0.55Ue(+/-10%)
Tripping time adjustable 0-300mseg
Terminal capacity 2.5mm2
Standards EN 60947-1
YDU undervoltage releaseYDU undervoltage release enables the automatic trip of the MCB orRCBO if the supply voltage drops below 45~65% of Ue.
Type Rated voltage Consumption at the Rated voltage (mA)
YDU02 24Vac 23
24Vdc 25
YDU04 48Vac 14
48Vdc 19
YDU23 230Vac 5
230Vdc 6
Shunt trip YDS
Frequency 50/60Hz
Calibration temperature 30oC
Rated voltage Operating voltage
70-110% Ue
Terminal capacity 2.5mm2
Standards EN60947-1
YDS shunt trip YDS shunt trip allowing remote opening of the circuit via apushbutton or other control device.
Type Rated voltage Tripping current (A) 12Vac 2 24Vac 2.4 YDS04 48Vac 6.6 YDS01 12Vdc 2.2 24Vdc 3 48Vdc 7 110Vac 0.4
230Vac 0.7 YDS40 414Vac 1.2 YDS10 110Vdc 0.4 230Vdc 0.8 250Vdc 0.8
Circuit and People Protection
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 14/56
14
Mechanical accessories for EcoPlus and TemDin2
EcoPlus
Description Reference
Padlocking device YDKS
YDK padlocking device
This device allows the breaker to be padlocked either
in open or close positions, and also allows the MCB
trip being in close position.
Description Reference
Rotary handle ODR1
Rotary handle ODR
Insulated busbar
Poles DescriptionReference
Fork type Pin type
12 Fork/Pin type busbar 1p 210mm s=12mm2 G1L21012 s=10mm2 S1L21010
57 Fork/Pin type busbar 1p 1000mm s=20mm2 G1L100020 s=16mm2 S1L100016
6x2 Fork/Pin type busbar 2p 210mm s=10mm2 G2L21010 s=10mm2 S2L21010
28x2 Fork/Pin type busbar 2p 1000mm s=16mm2 G2L100016 s=16mm2 S2L100016
4x3 Fork/Pin type busbar 3p 210mm s=10mm2 G3L21010 s=10mm2 S3L21010
4x3 Fork/Pin type busbar 3p 210mm s=16mm2 G3L21016 s=16mm2 S3L21016
19x3 Fork/Pin type busbar 3p 1000mm s=16mm2 G3L100016 s=16mm2 S3L100016
3x4 Fork/Pin type busbar 4p 210mm s=16mm2 G4L21016 s=16mm2 S4L21016
14x4 Fork/Pin type busbar 4p 1000mm s=16mm2 G4L100016 s=16mm2 S4L100016
27x2 Fork/Pin type busbar 3p phase/N 1000mm s=16mm2 GRSTN100016 s=16mm2 SL123N100016
Fork/Pin type terminal s=25mm2 AS25GN s=25mm2 AS25SN
1 Protection cover pin/fork (5 units) CTPH5 CTPH5
End cap busbar 2p/10 EKC2 EKC2
End cap busbar 3p/10 EKC3 EKC3
End cap busbar 2p and 3p/16 EKC23 EKC23
End cap busbar 4p/16 EKC4 EKC4
Standards DE 0660 part 500
DIN EN 60439-1; 1994
Material busbars E-CU-F25
Material of insulation PC/ABS-Blend
UL 94-VO
Cross-section of busbars 10, 12, 16 and 20mm2
Maximum operating voltage 500V
Nominal voltage 415V
Surge voltage 4kV
Short-circuit strength 25kA
Climate stability DIN 40046 IEC 68-2
Group of insulation VDE0110, part 1; 4/1997 (IEC 664)
- overvoltage category III
- degree of soiling 2
TechnicalData
Current carrying capacity 1 pole 2, 3, 4 poles
Feed-in from the end
cross section mm2 10 12 16 20 10 16
max. current
IS/phase (A) 63 65 80 90 63 80
Feed-in from
the middle
max. current
IS/phase (A) 100 110 130 150 100 130
max. feed-in current
IE/phase Depends on the cross section for connection
If you feed-in from the middle you have to observe that the sum of the outgoings in not higher than the max. current of the
busbars Is/phase.
Circuit and People Protection
Rotary handle, external, lockable and depth
adjustable. Not necessary to cut the shaft.
Easy and fast mounting on the MCB front side, by
a “clic”, tools not needed.
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 15/56
15
RCCBs ZFP 2P No. In No. Mod. Sensitivity
Type Reference poles (A) DIN (mA)
2 16 2 10 AC ZFP162001AC
2 25 2 30 AC ZFP252003AC
2 40 2 30 AC ZFP402003AC
2 63 2 30 AC ZFP632003AC
2 80 2 30 AC ZFP802003AC
2 100 2 30 AC ZFP1002003AC
2 25 2 100 AC ZFP25201AC
2 40 2 100 AC ZFP40201AC
2 63 2 100 AC ZFP63201AC
2 25 2 300 AC ZFP25203AC
2 40 2 300 AC ZFP40203AC
2 63 2 300 AC ZFP63203AC
2 80 2 300 AC ZFP80203AC
2 100 2 300 AC ZFP100203AC
2 25 2 30 A ZFP252003A
2 40 2 30 A ZFP402003A
2 63 2 30 A ZFP632003A
2 80 2 30 A ZFP802003A
2 100 2 30 A ZFP1002003A
2 25 2 300 A ZFP25203A
2 40 2 300 A ZFP40203A
2 63 2 300 A ZFP63203A
2 80 2 300 A ZFP80203A
2 100 2 300 A ZFP100203A
2 40 2 300 A-S ZFP40203AS
2 63 2 300 A-S ZFP63203AS
2 40 2 30 Ai ZFP402003AI
2 63 2 30 Ai ZFP632003AI
2 40 2 300 Ai-S ZFP40203SAI
2 63 2 300 Ai-S ZFP63203SAI
Type AC Protection against sinusoidal leakage current.
Applied in domestic and commercial installations.
Type AProtection against sinusoidal and recti ed leakage currents with or without a DC component.
Applied in commercial and industrial installations.
Type «Ai » High Immunity
Earth leakage range designed to avoid nuisance tripping caused by high frequency currents, capacitivecurrents, overvoltages and transient currents. Developed to ensure the appropriate protection in electronicequipment, computers, inverters, electronic lightning and converters.
Residual Current Circuit Breakers FIEP and ZFP
Rated voltage 2 poles 230V/265V~
Frequency 50/60Hz
Types AC A A-S
Standard EN 61008
Terminal capacity Flexible cable conductor 35 mm2
and rigid cable 50 mm2, with a
degree of protection of IP20Tripping time < 30ms
Nuisance tripping resistance
Type AC, A - 250A 8/20 μs
Type A-S - 3000A 8/20 μs
0.5 μs -100kHz-200A
Type «Ai » - 3000A 8/20 μs
Type «Ai »-S - 5000A 8/20 μs
0.5 μs -100kHz-200A
TechnicalData
Type
AC, A, A-Selective and «Ai»
Sensitivity10, 30, 100 and 300mA
S
Circuit and People Protection
RCCBs FIEPType
AC
Sensitivity
30mA
Technical
Data
In DIN Sensitivity Reference Poles
(A) mod. (mA)
2 25 2 30 FIEP252003
2 40 2 30 FIEP402003
Rated voltage 230V~
Frequency 50/60Hz
Tripping time < 30ms
Terminal capacity 35mm2
Standards EN 61008
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 16/56
16
TechnicalData
Auxiliary contacts No. Mod.
Description
Referencia DIN
1/2 Changeover Aux AUXZF1
1/2 Changeover Aux/Al AUXZF2
AUXZF1: Provides the status of the protection device, OPEN-CLOSED (H)
AUXZF2: This auxiliary can operate as an auxiliary contact (function H) or a signal
contact (function S). The user can change the function at the moment of installation.
DIN module 1/2
Terminal capacity Flexible and rigid cable 2.5mm2
Rated current voltage 5A-240V~
Mounted on to the right side of ZFP RCCBs and FCOP RCBOs
Rated voltage 4 poles 400V/455V~
Frequency 50/60Hz
Types AC A A-S
Standard EN 61008
Terminal capacity Flexible cable conductor 35 mm2
and rigid cable 50 mm2, with a
degree of protection of IP20
Tripping time < 30ms
Nuisance tripping resistance
Type AC, A - 250A 8/20 μs
Type A-S - 3000A 8/20 μs
0.5 μs -100kHz-200A
Type «Ai » - 3000A 8/20 μs
Type «Ai »-S - 5000A 8/20 μs
0.5 μs -100kHz-200A
TechnicalData
Type
AC, A and A-Selective, «Ai»
Sensitivity
10, 30, 100, 300 and 500mA
S
Residual Current Circuit Breakers ZFP and ZD06
RCCBs ZFP 4P No. In No. Mod. Sensitivity
Type Reference poles (A) DIN (mA)
4 25 4 30 AC ZFP254003AC
4 40 4 30 AC ZFP404003AC
4 63 4 30 AC ZFP634003AC
4 80 4 30 AC ZFP804003AC 4 100 4 30 AC ZFP1004003AC
4 25 4 100 AC ZFP25401AC
4 40 4 100 AC ZFP40401AC
4 63 4 100 AC ZFP63401AC
4 100 4 100 AC ZFP100401AC
4 25 4 300 AC ZFP25403AC
4 40 4 300 AC ZFP40403AC
4 63 4 300 AC ZFP63403AC
4 80 4 300 AC ZFP80403AC
4 100 4 300 AC ZFP100403AC
4 63 4 500 AC ZFP63405AC
4 25 4 30 A ZFP254003A
4 40 4 30 A ZFP404003A
4 63 4 30 A ZFP634003A
4 80 4 30 A ZFP804003A
4 100 4 30 A ZFP1004003A
4 25 4 300 A ZFP25403A
4 40 4 300 A ZFP40403A
4 63 4 300 A ZFP63403A
4 80 4 300 A ZFP80403A
4 100 4 300 A ZFP100403A
4 40 4 300 A-S ZFP40403AS
4 63 4 300 A-S ZFP63403AS
4 40 4 30 Ai ZFP404003AI
4 63 4 30 Ai ZFP634003AI
4 40 4 300 Ai-S ZFP40403SAI
4 63 4 300 Ai-S ZFP63403SAI
Circuit and People Protection
In Sensitivity (A)
Poles (mA)
Reference
40 2 30 ZD06402003AC
40 2 300 ZD0640203AC
40 4 30 ZD06404003AC
40 4 300 ZD0640403AC
ZD06 RCD Add-on block
Frequency 50/60Hz
2 and 3 DIN module width
Terminal capacity 25mm2 exible
35mm2 rigid
Standards EN 61009
Sensitivity
30 and 300mA
Instantaneous. Mounted on to the right side of DS and DH MCBs.
Type
AC
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 17/56
17
TechnicalData
Residual Current Circuit Breakers withOvercurrent Protection ZDH and ZDS
Short-circuit capacity
10kA
Tripping characteristic
C and B
Type
AC and A
Sensitivity
30mA
Rated voltage 230V/240V~
Frequency 50/60Hz
Calibration temperature 30oC
Tripping curve C and B
Sensitivity 30mA
Type AC and A
Terminal capacity 16mm2 exible / 25mm2 rigid
Standards EN 61009
ZDH RCBO (single module RCBO + neutral tail) In DIN Sensitivity Type Trip curve
(A) mod. mA C B
6 1 30 AC ZDH41P06C003AC ZDH41P06B003AC
10 1 30 AC ZDH41P10C003AC ZDH41P10B003AC
16 1 30 AC ZDH41P16C003AC ZDH41P16B003AC
20 1 30 AC ZDH41P20C003AC ZDH41P20B003AC
25 1 30 AC ZDH41P25C003AC ZDH41P25B003AC
32 1 30 AC ZDH41P32C003AC ZDH41P32B003AC
40 1 30 AC ZDH41P40C003AC ZDH41P40B003AC
6 1 30 A ZDH41P06C003A ZDH41P06B003A
10 1 30 A ZDH41P10C003A ZDH41P10B003A
16 1 30 A ZDH41P16C003A ZDH41P16B003A
20 1 30 A ZDH41P20C003A ZDH41P20B003A
25 1 30 A ZDH41P25C003A ZDH41P25B003A
32 1 30 A ZDH41P32C003A ZDH41P32B003A
40 1 30 A ZDH41P40C003A ZDH41P40B003A
ZDS RCBO
Rated voltage 230/240V~
Frequency 50/60Hz
Calibration temperature 30oC
Tripping curve C
Sensitivity 30 and 300 mA
Type AC and A
Terminal capacity 25mm2 exible / 35mm2 rigid
Electrical endurance 20,000
Mechanical endurance 20,000
Standards EN 61009
Short-circuit capacity
6kA
Tripping characteristic
C
Type
AC
Sensitivity
30 and 300mA
In DIN SensitivityType Reference
Poles
(A) mod. mA
1+N 6 2 30 AC ZDS0462003AC
1+N 10 2 30 AC ZDS04102003AC
1+N 16 2 30 AC ZDS04162003AC
1+N 20 2 30 AC ZDS04202003AC
1+N 25 2 30 AC ZDS04252003AC
1+N 32 2 30 AC ZDS04322003AC
1+N 40 2 30 AC ZDS04402003AC
1+N 6 2 300 AC ZDS046203AC
1+N 10 2 300 AC ZDS0410203AC
1+N 16 2 300 AC ZDS0416203AC
1+N 20 2 300 AC ZDS0420203AC
1+N 25 2 300 AC ZDS0425203AC
1+N 32 2 300 AC ZDS0432203AC
1+N 40 2 300 AC ZDS0440203AC
Note: Terasaki recommends
the Pozidrive 2 use.
Accessories on page 13.
Circuit and People Protection
TechnicalData
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 18/56
18
Auxiliary contacts No. Mod.
Description
Referencia DIN
1/2 Changeover Aux AUXZF1
1/2 Changeover Aux/Al AUXZF2
AUXZF1: Provides the status of the protection device, OPEN-CLOSED (H)
AUXZF2: This auxiliary can act as an auxiliary contact (function H) or a signal contact
(function S). The user can change the function at the moment of installation.
DIN module 1/2
Terminal capacity Flexible and rigid cable 2.5mm2
Rated current voltage 5A-240V~
Mounted on to the right side of ZFP RCCBs and FCOP RCBOs
TechnicalData
Shunt trip (SHT) and Undervoltage trip (UVT) No. Mod. Rated
Reference DIN voltage
1 230V~ SHTZF230
1 230V~ UVTZF230
TechnicalData
DIN module 1
Terminal capacity Flexible and rigid cable 2.5mm2
Mounted on to the right side of FCOP RCBO
TechnicalData
Rated voltage 230/240V~
Frequency 50/60Hz
Calibration temperature 30oC
Tripping curve C and B
Sensitivity 30, 300mA
Type AC, A
Terminal capacity 25mm2 exible / 35mm2 rigid
Electrical endurance 20,000
Standards EN 61009
Type
AC, A
Sensitivity
30, 300mA
Tripping characteristic
C and B
Short-circuit capacity
6kA In DIN (mA) Curve Reference
(A) mod. Type A Type AC
6 2 30 C FCOPC6003A FCOPC6003AC
10 2 30 C FCOPC10003A FCOPC10003AC
16 2 30 C FCOPC16003A FCOPC16003AC
20 2 30 C FCOPC20003A FCOPC20003AC
25 2 30 C FCOPC25003A FCOPC25003AC
32 2 30 C FCOPC32003A FCOPC32003AC
40 2 30 C FCOPC40003A FCOPC40003AC
6 2 300 C FCOPC603A FCOPC603AC
10 2 300 C FCOPC1003A FCOPC1003AC
16 2 300 C FCOPC1603A FCOPC1603AC
20 2 300 C FCOPC2003A FCOPC2003AC
25 2 300 C FCOPC2503A FCOPC2503AC
32 2 300 C FCOPC3203A FCOPC3203AC
40 2 300 C FCOPC4003A FCOPC4003AC
6 2 30 B FCOPB6003A FCOPB6003AC
10 2 30 B FCOPB10003A FCOPB10003AC
16 2 30 B FCOPB16003A FCOPB16003AC
20 2 30 B FCOPB20003A FCOPB20003AC 25 2 30 B FCOPB25003A FCOPB25003AC
32 2 30 B FCOPB32003A FCOPB32003AC
40 2 30 B FCOPB40003A FCOPB40003AC
6 2 300 B FCOPB603A FCOPB603AC
10 2 300 B FCOPB1003A FCOPB1003AC
16 2 300 B FCOPB1603A FCOPB1603AC
20 2 300 B FCOPB2003A FCOPB2003AC
25 2 300 B FCOPB2503A FCOPB2503AC
32 2 300 B FCOPB3203A FCOPB3203AC
40 2 300 B FCOPB4003A FCOPB4003AC
Residual Current Circuit Breakers withOvercurrent Protection FCOP
FCOP RCBO
Circuit and People Protection
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 19/56
19
Rated current AC1 25A 32A
Rated voltage 250V
Frequency 50/60Hz
Min/max.ambient T atinstallation point -20/45oC
Terminal capacity 1.5mm2 min. / 10mm2 max.
Coil specifications
- Command voltage 230V~
- Supply voltage range %Un 85-110%
- Consumption AC (VA)
Coil power loss 4 4.5
Pick up power 4 4.5
- Maximum coil holding voltage time unlimited
Standards EN 60947-4-1
Contactors CDO and CDRCommand and Control
CDC main contact blockCDC main contact blocks are 2 pole and rated at 25 or 32A. If you t a CDC blockwith a CDR or CDO 1pole contactor, you get a 3 poles contactor and if you use a 2poles CDR or CDO contactor you get a 4 poles contactor. The CDC block is clippedon the left side of the contactor, without need of any screw or additional wiring.
Rated current AC1 25/32A
Rated voltage 400V~
Frequency 50/60Hz
Min/max.ambient T at installation point -20/45oC
Terminal capacity 1.5mm2 min. / 10mm2 max.
Standards EN 60947-4-1
TechnicalData
In DIN No.Reference
(A) mod. contacts
25 400V~ 1 2 NO CDC2520
32 400V~ 1 2 NO CDC3220
Used for the remote switching of circuits up to 32A, with double recti ed coil,ensuring silent operation whilst increasing electrical endurance. Visual indicationof the contactor switch position via front indication. Sealable clamping terminal withcaptive screw.Main contact and auxiliary contact blocks can be clipped on to the left-hand side ofthe contactor without any necessary tooling, in the following combination:
Auxiliary contact block + Main contact block + Contactor
TechnicalData
Rated current AC1 5A
Rated voltage 250V~
Frequency 50/60Hz
Min/max.ambient T at installation point -20/45oC
Terminal capacity 6mm2 max.
Standards EN 60669-2-2
TechnicalData
Contactor Main contact Total No. DIN Aux. contact
block CDC of mod. block CDA
1 Pole 2 Poles 2 Poles poles CDO or CDR+CDC (max)
1 - - 1 1 2
- 1 - 2 1 2
1 - 1 3 2 1
- 1 1 4 2 1
CDA auxiliary contact blockCDA ½ module auxiliary blocks allow additional contacts for signalling andsynchronisation with other devices. Auxiliary contact blocks can be tted toCDR, CDO contactors and ID impulse relays without any necessary tools. Amaximum of 2 blocks can be tted to the contactor depending on the type andnumber of main contact blocks.
In DIN No.Reference
(A) mod. contacts
5 250V~ 1/2 1NO+1NC CDA0520
STOP - Contacts permanently open AUTO - Normal operationPERM. - Contacts permanently closed
In DIN No.Reference
(A) mod. contacts
25 250V~ 1 2 NO CDO20325
32 250V~ 1 2 NO CDO20332
In DIN No.Reference
(A) mod. contacts
25 250V~ 1 1 NO CDR10325
32 250V~ 1 1 NO CDR10332
25 250V~ 1 2 NO CDR20325
32 250V~ 1 2 NO CDR20332
Contactor without manual operation
Contactor with manual operation
Combination table
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 20/56
20
Used in commercial and industrial applications for loads up to 20A and between63A, with visual indication of contactor position. Sealable clamping terminals withcaptive screws.
TechnicalData
Command and Control
Contactors CDIPoles spacer CNCP
Auxiliary contact blockCDI ½ module auxiliary blocks allow additional contacts for signalling andsynchronisation with other devices. Auxiliary contact blocks can be tted to CDIcontactors without any necessary tools.
Rated current AC1 3ARated voltage 230V~
Frequency 50/60Hz
Min/max.ambient T at installation point -20/45oC
Terminal capacity 2.5mm2 max.
Standards IEC 947-4-1, EN 60947-4-1, VDE 0660,
IEC 947-5-1, EN 60947-5-1
TechnicalData
CNP spacer ½ moduleCNP spacers can be tted on either side of the TemDin2 device and allow the safedissipation of heat when several devices are mounted side by sideon the same rail.
DINDescription Reference mod.
1/2 Spacer CNCP
In DINContacts Referencia
(A) mod.
3A 230V~ 1/2 1NO+1NC CDI0620
4 poles Total No. DIN mod. Block CDIcontactor of poles CDI+CDI (max)
1 4 2 or 3 + 1/2 1
In DINContacts
Reference
(A) mod.
20 230V~ 1 2 NA CDI22024
25 400V~ 2 4 NA CDI42524
40 400V~ 3 4 NA CDI44024
63 400V~ 3 4 NA CDI46324
CDI Contactor with coil at 24Vac
In DINContacts
Reference
(A) mod.
20 230V~ 1 1 NA CDI10620
20 230V~ 1 2 NA CDI20620
25 400V~ 2 4 NA CDI40625
40 400V~ 3 4 NA CDI40640
63 400V~ 3 4 NA CDI40663
CDI Contactor with coil at 230Vac
Rated current AC1 20A 25A 40A 63A
Rated voltage 230 V 400 V
Frequency 50 / 60 Hz
Min/max.ambient T at installation point -20 / 45oCTerminal capacity 1.5/10 mm2 max. 2.5/25mm2 max.
Coil specifications
- Command voltage 24, 220/240 V
- Supply voltage range % Un 85-110%
- Consumption AC (VA)
Holding 2.2-4.2 4-6 6-8
Inrush 7-9 14-18 33-45
- Fuse protection 35A 63A 80A
Standards IEC 947-4-1, EN 60947-4-1, VDE 0660,
IEC 947-5-1, EN 60947-5-1
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 21/56
21
TechnicalData
Poles 2, 4 poles
Dimensions ZFR 2 poles: 5 modules
ZFR 4 poles: 7 modules
Operating voltage 230/240V - 50/60Hz
Connection times 10, 20, 30, 60, 120, 600sec.
Motor operator for «A» and «Ai » types, please contact Terasaki.
Command and Control
RCD withmotor operator
Sensitivity
10, 30 and 300mA
Type
AC In SensitivityType Reference
Poles
(A) (mA)
2 16 10 AC ZFR162001AC
2 25 30 AC ZFR252003AC
2 40 30 AC ZFR402003AC
2 63 30 AC ZFR632003AC
2 80 30 AC ZFR802003AC
2 100 30 AC ZFR1002003AC
2 25 300 AC ZFR25203AC
2 40 300 AC ZFR40203AC
2 63 300 AC ZFR63203AC
2 80 300 AC ZFR80203AC
2 100 300 AC ZFR100203AC
4 25 30 AC ZFR254003AC
4 40 30 AC ZFR404003AC
4 63 30 AC ZFR634003AC
4 25 300 AC ZFR25403AC 4 40 300 AC ZFR40403AC
4 63 300 AC ZFR63403AC
4 80 300 AC ZFR80403AC
4 100 300 AC ZFR100403AC
Motor operator ZFRThe Motor operator ZFR allows the coupled RCCB automaticself-reclosing, in case of tripping. 6 reset operations are made,in the event that the leakage persists, before the earth leakageprotector stops. Dry contact included (remote signal).
TechnicalData
Rated current AC12 25A
Rated voltage 230/400V
Frequency 50/60Hz
Terminal capacity 1mm2 min. / 10mm2 max.
Insulation voltage 400V
Inpulse withstand test voltage 4KVStandards EN 60669-1
PD & PDL pushbuttonsTechnicalData
Rated current AC12 25A
Rated voltage 230V
Frequency 50/60Hz
Terminal capacity 1mm2 min. / 10mm2 max.
Insulation voltage 250V
Inpulse withstand test voltage 4KV
Standards EN 60669-1 / EN 60947-5-1
PD pushbutton
Description Contacts
DINReference
mod.
Pushbutton 1NO 1 PD11APushbutton 1NC 1 PD11B
Pushbutton 2NO 1 PD12A
Pushbutton 1NO/NC 1 PD12C
Double pushbutton 2NO 1 PD22A
Double pushbutton 1NO + 1NC 1 PD22C
PDL pushbutton with neon signal lamp
Description Contacts
DINReference
mod.
Pushbutton+ Pilot neon green 230V 1NO 1 PDL11AG
Pushbutton+ Pilot neon red 230V 1NO 1 PDL11AR
Pushbutton+ Pilot neon white 230V 1NO 1 PDL11AW
Pushbutton+ Pilot neon green 230V 1NC 1 PDL11BG
Pushbutton+ Pilot neon red 230V 1NC 1 PDL11BR
Pushbutton+ Pilot neon white 230V 1NC 1 PDL11BW
Motor operator ZFR, Pushbuttons PD and PDLSwitches and Changeover switches WDM
WDM switches and changeover switches
Description Contacts
DINReference
mod.
Switch 1 pole 1NO 1 WDM11A
Switch 2 pole 2NO 1 WDM12A
Switch 3 pole 3NO 1 WDM13A
Switch 4 pole 4NO 1 WDM14A
Changeover 1-2 1 pole 1 WDM21C
Changeover 1-2 2 pole 1 WDM22C
Changeover with zero position 1-0-2 1 pole 1 WDM31C Changeover with zero position 1-0-2 2 pole 1 WDM32C
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 22/56
22
Note: Terasaki recommends
the Pozidrive 2 use.
Rated voltage: 250V
Rated current In: 16A
No. of poles: 2P+ TTL
(side earth leakage degree of protection)
Terminal capacity: 6mm2
Degree of protection: IP20
Temperature: -20...+55oC
Screws: Pozidrive 2
Terminal capacity
min: 1x1mm2
max: 1x6mm2 or 2x2.5mm2
Mounting: 35mm symmetrical DIN rail
Standards: IEC 60884-1
BS EN C61112-1
NF C61-303 (86)
TechnicalData
Socket-outlet HD In Operating DIN Reference
(A) voltage (Ue) mod.
16 250V 2 HD16A
Command and Control
TechnicalData
DDF mains disconnect switches
Nominal current ratings from 32 to 100AMains disconnect switches allow switching and isolationof main circuits. They must be used in conjunction with aprotective device, i.e. a fuse or MCB, enabling protectionagainst overload orshort circuit conditions.
Poles In DIN Reference(A) mod.
1 32A 1 DDF1010032
1 63A 1 DDF1010063
1 100A 1 DDF1010100
2 32A 2 DDF1020032
2 63A 2 DDF1020063
2 100A 2 DDF1020100
3 32A 3 DDF1030032
3 63A 3 DDF1030063
3 100A 3 DDF1030100
4 32A 4 DDF1040032
4 63A 4 DDF1040063
4 100A 4 DDF1040100
Rated voltage 230V/400V~
Frequency 50/60Hz
Insulation voltage 660V~
DDF32A DDF63A DDF100A
Rated current In 32A 63A 100A
Rated making and breaking capacity 3Ie
Short-circuit capacity Icm 700A
Category AC-22
Temperature 30oC
Terminal capacity 35 mm2
Mounting 35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards EN 60947-3
Mains Disconnect Switches DDFSocket-outlet HD
Accessories on page 13. Suitable aux. contact only.
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 23/56
23
Programming and measurement
RDA24 analogue timer (daily) Analogue time switches allow the pre-programmed switchingof electrical circuits from user de ned settings. Programmingis made through manual adjustment of the timers slide tappet.Modular casing for din or wall mounted applications.Manual ON/OFF
TechnicalData
Description
DINReference
mod.
Analogue Time switch 24h 2 RDA24
Analogue Time switch 24h reserve time 2 RDA24R
RDD07A digital time switchDigital time switch with automatic summer and winter timesaving adjustment for set dates. Digital timers allow the preprogrammed switching of 1 or 2 electric circuits through a weeklytime programme. LCD display shows current program status,current date and time. Modular casing for Din or wall mountedapplications.
Rated voltage 230V
Frequency 50/60Hz
Max. Switched current rating 16(3)A/250V~
Change over contact voltage freeNumber of programs 20 On and 20 Off
Time intervals programmable 1sec. - 99 sec.
1min. - 59 min.
1h - 24 h
1day - 7 days
Variable and programs updated every minute
Channel activation end of minute
Precision +/- 0.5 sec./day
Quartz frequency 32.768Hz
Operating temperature 0/50oC
Storing temperature -10/50oC
Battery reserve (for date and hour) 15 days
Minimum recharge time 72 hours
Ingress protection degree - without clamps-cover IP20
- with clamps-cover IP30
- panel mounting IP40
Terminal capacity 1.5 mm2 min. / 2.5mm2 max.
TechnicalData
Description
DINReference
mod.
Digital weekly time switch auto 1 circuit 2 RDD07A
Digital weekly time switch auto 2 circuits 2 RDD07A2
Rated voltage 230V
Frequency 50/60Hz
Max. Switched current rating 16(3)A/250V~
Minimum ON/OFF setting 15 minutes
Precision +/- 0.5 sec/day
Quartz frequency 32.768Hz
Operating temperature 0/50oC
Storing temperature -10/50oC
Battery reserve (for date and hour) 15 days
Recharge time to needed save data 72 hours
Pretection degree IP40Terminal capacity 1mm2 min. / 2.5mm2 max.
RDD07 single module digital timer (weekly)Digital timers allow the pre programmed switching of electriccircuits through a weekly time programme. The LCD display showsthe present time, in year, month and day, programmed switchinginterval, relay ON / OFF status and manual operation. Key on relay’sfront panel is used for manual ON/ OFF.
TechnicalData
Description
DINReference
mod.Digital weekly time switch 1 circuit 1 RDD07
Rated voltage 230V
Frequency 50/60Hz
Max. Switched current rating 16(3)A/250V~
Minimum ON/OFF setting 30 minutes
Consumption 1.5 W
Time accuracy +/- 5 min/year
Temperature range -10/50oC
Ingress protection degree
- without clamps-cover IP20
- with clamps-cover IP30
- panel mounting IP40
Terminal capacity 1.5mm2 min. / 2.5mm2 max.
Analogue Time Switches RDADigital Time Switches RDD
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 24/56
24
RDA24P light sensitive switchLight sensitive switches allow the control of electric circuitsby measuring ambient light intensity. Detected via a separatephotocell, the switch changes state when the light intensitydrops below a preset level. Connected to the switch througha 4 ~9mm diameter wire, the photocell is suitable for IP65application.
The switch has an ON/OFF time delay avoidingnuisance operation via unstable light sources such asheadlights or lightning ashes. Modular casing for Dinor wall mounted applications.
TechnicalData
Rated voltage 230V
Frequency 50/60Hz
Max. Switched current rating 16(3)A/250V~
Maximum pilotable power
- tungsten lamp 2000w/230Vac /cos=1
- fluorescent lamp 720w/230Vac /cos=0,8
- DUO type lamp 200w/230Vac /cos=0,9
Activation threshold 2 ~ 100 lux
2 ~ 1000 lux
2 ~ 10000 lux
Delay time - switching ON 8 seconds - switching OFF 38 seconds
Operating temperature limit of the module 0/55oC
Operating temperature limit of the photocell -20/50oC
Terminal capacity 1mm2 min./2.5mm2 max.
Description
DINReference
mod.
Light sensitive switch 2 RDA24P
Photocell (spare unit) RDAP
LD pilotsUsed to signal the status of the electric circuits: motors, fan,pump, heater, etc. Available with different coloured lenses.
TechnicalData
Rated current AC12 20A
Rated voltage 230V
Frequency 50/60Hz
Lamp Neon 230V
Lamp power 0.6w
Insulation voltage 250V
Rated impulse voltage 4KV
Terminal capacity 1 mm2 min. / 10mm2 max.
Standards EN 60947-5-1
Description Reference
Pilot green neon 230V LD1G
Pilot red neon 230V LD1R
Pilot white neon 230V LD1W
Pilot double red&green neon 230V LD2C
Primary DINReference
voltage mod.
230 V~ 2 TDB23R
TechnicalData
TDB bell + buzzer + transformerTBD Bell/buzzer is used for audible signalling in domestic andcommercial installations. The device has a double insulatedenvelope by construction and complies with EN 60 742, whichcan be used be classi ed as ‘transformers for bells’. Thismeans it is conceived to power bells or similar intermittentwarning devices.
Primary voltage 230V~
Secondary voltage 12V~
Frequency 50/60Hz
Terminal capacity 4 mm2
Standars EN 60742
TechnicalData
Rated voltage 230V~
Frequency 50/60Hz
Max. Switched current rating 16A
Contact type NO (witch potential)
Time lag adjustable 20sec~10min
Nº máximo de pulsadores luminosos 40mA
Switching capacity
- incandescents lamps 2000w
- fluorescence serial compensated 750w
- fluorescence parallel compensated 750w
- resistive load cos=1 2000w
Terminal capacity 2.5mm2 min. / 4mm2 max.
SDS staircase switchesStaircase switches allow the timed management of lighting orventilation circuits used in stairwells or hallways.
SDS016B with 3 position handle for automatic, stop andpermanent duty. The switching function is contactor enabledand offers silent operation, high switching capacity and goodendurance values for incandescent or uorescent loads.
Suitable for 3 or 4 wire systems.
In DINReference
(A) mod.
16A 230V 1 SDS016C
Staircase SDS, Pilots LD, Bell + buzzer + ransformer TDBand Light sensitive switch RDAProgramming and measurement
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 25/56
25
Programming and measurement
Digital measurement instruments MDDActive energy meter MDA
Three-Phase LCD multimeterUsing buttons makes it possible to scroll through the measurementpages in a natural way.During programming, the instrument itself proposes the various settingpossibilities present in the model in question, so it is not necessary tohave the instruction manual always at hand.
The instrument can also be used as a priority relay.
Description DIN
Reference mod.
Three-phase LCD multimeter 4 MDD06P4
Rated voltage 63A/500V~
Frequency 50/60Hz
Description LCD display backlight white colour
8 + 8, 2 lines
Precision @ 25OC (%) 0.5% f.s.d. 2 digits
Relay contact NO contact max V... max I... max P
1000V 0.5A 20VA
Standards EN 61010-1, EN 60688
MDA Active energy meterSingle phase energy meter with 6-digit display and 0.1k w resolution.
Green LED indication for power input and ashing red LED for load
consumption (640 imp/kwh). Units have modular casing for Din or wall
mounted applications.
Description
DINReference
mod.
Active Energy meter 2 MDA00E
Rated voltage 230V~
Frequency 50/60Hz
Description Display mechanical 5+1 digit - h=4mm
Precision @ 25OC (%) 2% f.s.d. +/- 2 digit Cos0,7
Consumption 6VA 1.5w (capacitive)
Terminal capacity 1.5 mm2 min / 4mm2 max
Standards EN 61010-1, EN 50081-1, EN 50082-1
Digital frequency meterThis device allows the monitoring of frequencies from 1 to 999Hz and isequipped with automatic load selection.
Digital wattmeterMeasurement of active power circuits in single or three phase systems,with balanced / non-balanced load characteristics.Primary load selection by front dip switch, automaticdecimal point selection.
Frequency meter Wattmeter
Rated voltage 230V~
Frequency 50/60Hz
Description 3 digits red display LED 7 segments - h= 9mm
Precision @ 25OC (%) +/-0.2% f.s.d. +/- 2% f.s.d.
1 digit +/- 2 digit
Cos0.7
Power comsuption 4VA
Terminal capacity 1.5mm2 min./ 4mm2 max.
Standards EN 61010-1, EN 50081-1, EN 50082-1
Description
DINReference
mod.
Digital Frequency meter 2 MDD00F
Digital Wattmeter 2 MDD06W
Digital voltmeterModular digital voltmeter for AC voltage measurement with 3 digits LEDdisplay.
Digital ammeterModular digital ammeter for AC current measurement with 3 digits LEDdisplay.
TechnicalData
Voltmeter Ammeter
Rated voltage 230V~
Frequency 50/60Hz
Description 3 digits LED 7 segments - h= 10mm
Precision @ 25OC (%) 0.00 to 500V 0.05 to 5A
Power comsuption 1.5VA 2VA
Terminal capacity 1.5mm2 min./4mm2 max.
Standards EN 61010-1, EN 60688
Description
DINReference
mod.
Digital Voltmeter 2 MDD06V2
Digital Ammeter 2 MDD06A2
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 26/56
26
TDC current transformerCurrent transformers allow measurement of high line currents of upto 1000A with 5A secondary output ratios for use with low input rangemeters.The CT are cable/bus-bar type. The self-extinguish plastic case offersexcelent resistance to mechanical and thermal stress. Every CT enclose
a fastening system to rail DIN as standard.
Description Reference
Iprim=50A Class 3 - 1VA TDC050
Iprim=75A busbar: 20x5mm Class 1 - 1.5VA
TDC075 cable: ø 16mm Class 3 - 2.5VA
Iprim=100A
Class 1 - 2.5VATDC100
Class 3 - 3.75VA
Class 0.5 - 1.5VA
Iprim=150A Class 1 - 2.5VA TDC150
busbar: 30x10mm Class 3 - 3.75VA
cable: ø 22mm Class 0.5 - 2.5VA
Iprim=200A Class 1 - 3.75VA TDC200
Class 3 - 5VAClass 0.5 - 5VA
Iprim=250A Class 1 - 7.5VA TDC250
Class 3 - 10VA
busbar: 40x10mm Class 0.5 - 7.5VA
Iprim=300A cable: ø 30mm Class 1 - 10VA TDC300
Class 3 - 15VA
Class 0.5 - 10VA
Iprim=400A Class 1 - 15VA TDC400
Class 3 - 20VA
Class 0.5 - 15VA
Iprim=500A Class 1 - 20VA TDC500
busbar: 60x10mm Class 3 - 30VA
cable: ø 51mm Class 0.5 - 15VA
Iprim=600A Class 1 - 20VA TDC600
Class 3 - 30VA
Class 0.5 - 15VA
Iprim=800A Class 1 - 20VA TDC800
busbar: 80x10mm Class 3 - 30VA
cable: ø 65mm Class 0.5 - 15VA
Iprim=1000A Class 1 - 20VA TDC000
Class 3 - 30VA
Note: Fastening system to rail DIN included.
TechnicalData
Ammeter Voltmeter
Rated voltage —— 300 and 500 Vac
Rated current 15, 25 and 40A direct
50 to 1000A / CT ——
Frequency 15~100 HzPrecision @ 25ºC (%) 1.5 f.s.d.
Overload
- Permanent 1.5Ie 1.2Ve
- 5 seconds 10 Ie 2 Ve
Comsuption 0.3~1VA 1.5~3VA
Operating temperature -25/40oC
Testing voltage 2000V 50Hz during 1 minute
Standards IEC 51, VDE 0410, DIN 43780,
UNE 60051, BS 89, EN 50081,
EN 50082, CEI 1010, EN 61010
Programming and measurement
MDA analogue ammeters and voltmetersCurrent and voltage measurement for ac circuits. Easy scale changefor different transformer ratios.
Description
DINReference
mod. Analogue voltmeter 300V 3 MDA03V
Analogue voltmeter 500V 3 MDA05V
Analogue Ammeter 15A 3 MDA01A
Analogue Ammeter 25A 3 MDA02A
Analogue Ammeter 40A 3 MDA04A
Analogue Ammeter X/5A 3 MDA06A
Description Reference
Scale 50A MDC050A
Scale 75A MDC075A
Scale 100A MDC100A
Scale 150A MDC150A
Scale 200A MDC200A
Scale 250A MDC250A
Scale 300A MDC300A
Scale 400A MDC400A
Scale 500A MDC500A
Scale 600A MDC600A
Scale 800A MDC800A
Scale 1000A MDC1000A
MDA06A interchangeable scales for analogue meters
Analogue measurement instruments MDACurrent Transformer TDC
TechnicalData
Rated voltage 720V max.
Primary rated current from 50 to 1000A
Secondary rated current 5A
Frequency 50/60Hz
Test voltage 3kV (1min/50Hz)
Rated short-time thermal current Ith: limited to primary bar
Rated dynamic current Idin = 2.5 Ith
Continuous overload 1.2 In
Standars IEC 185, UNE 60064-1, VDE 0414, IEC 801/1-3,4
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 27/56
27
FD disconnector fuse holdersFuses guarantee a high level of protection againstoverload and short circuit conditions, in control, signallingand installation networks. FD disconnector fuse holdersare suitable for gL, gG and aM type fuses.
TechnicalData
FDS08/FDI08 FDS10/FDI10 FDS14 FDS22
Utilization category AC-22B AC-21B
Rated voltage 400V 690V
Rated impulse withstand voltage Uimp 8kV
Rated current 20A 25A 50A 100A
Rated making breaking capacity 60A 75A 150A 150A
Rated conditional short circuit current 50kA 100kA 100kA 100kA
Frequency 50Hz
Maximum power dissipation 2.6w 3w 5w 9.5w
Terminal capacity 25mm2 max. 35mm2 max. 50mm2 max.
Fuse size 8x31 10x38 14x51 22x58
Standards IEC 60947-1, IEC 60947-3
Modular protection
TDS safety transformersSafety transformers are used for the distribution of very low voltages: this guaranteeshigh protection against electrocution.Short-circuit proof and failsafe transformers offer great reliability in terms of theirgalvanic separation between primary and secondary circuits.Short-circuit proof transformers are protected from the over temperatures consequentin overload and short circuit conditions, by their own incorporated protective device.When normal operating conditions are returned and the transformer temperature is
returned to within operating limits, the transformer will function correctly.Failsafe transformers on the other hand can no longer function, following anomaloususe or fault.
TechnicalData
Primary voltage 230V~
Frequency 50/60Hz
Terminal capacity 4 mm2
Standars EN 60742
= F Failure-proof = R Short circuit proof
Primary Secondary Nominal DINReference
voltage voltage power mod.
230V~ 12V~ 15VA 2 TDS015F
230V~ 12/24V~ 15VA 2 TDS015R
230V~ 12/24V~ 40VA 4 TDS040R
Safety Transformers TDSDisconnector fuse holders FD
Poles
In Voltage DINIndicator Reference
(A) (V) mod.
1P 20A 400V~ 1 - FDS0810
1P+N 20A 400V~ 2 - FDS0811
2P 20A 400V~ 2 - FDS0820
3P 20A 400V~ 3 - FDS0830
3P+N 20A 400V~ 4 - FDS0831
1P 20A 400V~ 1 LED FDI0810
1P+N 20A 400V~ 2 LED FDI0811
2P 20A 400V~ 2 LED FDI0820
3P 20A 400V~ 3 LED FDI083 3P+N 20A 400V~ 4 LED FDI0831
1P 25A 690V~ 1 - FDS1010
1P+N 25A 690V~ 2 - FDS1011
2P 25A 690V~ 2 - FDS1020
3P 25A 690V~ 3 - FDS1030
3P+N 25A 690V~ 4 - FDS1031
1P 25A 690V~ 1 LED FDI1010
1P+N 25A 690V~ 2 LED FDI1011
2P 25A 690V~ 2 LED FDI1020
3P 25A 690V~ 3 LED FDI1030
3P+N 25A 690V~ 4 LED FDI1031
1P 50A 690V~ 1.5 - FDS1410
1P+N 50A 690V~ 3 - FDS1411
2P 50A 690V~ 3 - FDS1420
3P 50A 690V~ 4.5 - FDS1430
3P+N 50A 690V~ 6 - FDS1431
1P 100A 690V~ 2 - FDS2210
1P+N 100A 690V~ 4 - FDS2211
2P 100A 690V~ 4 - FDS2220
3P 100A 690V~ 6 - FDS2230
3P+N 100A 690V~ 8 - FDS2231
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 28/56
28
Surge Arresters TMModular protection
TM Main line and critical load protectionSurge arresters provide protection against destructive overvoltage sources in systems incorporating sensitive electrical or electronic
equipment. Overvoltages can be generated by lighting strike induced currents, electrical motors, frequency converters and power supply
switching operations.
Imax DINType Reference
Poles
(8/20 s) mod.
1 65kA 1 plug-in TM65I
1 65kA 1 plug-in TM65IS
Replacement module TM65IR
4 80kA 5 monoblock TM80IIIIS
1 35kA(10/350) 1 spark gap TM35SPI
TM20I TM20II TM20IIII
Rated voltage (V~) 230V 400/230V
Maximum voltage (V~) 270V 540/270V
Frequency 50/60Hz
Imax (8 20 s) 20kA
Protection level Vp(1) 960V
Poles 1 2 4
Type Single pole plug-in Multi-pole monoblock
Thermal fuse healty indication LED LED LED
Operating temperature -30oC / 70oC
Connection In parallel
Response time 5ns
Terminal capacity 50mm2
Replacement module TM20IR —— ——
Connected protection MCB C Type - 32A or 35A gL/gG fuse
TM45I TM45IS TM45II TM45IIIIS
Rated voltage (V~) 230V 400/230V
Maximum voltage (V~) 270 540/270V
Frequency 50/60Hz
Imax (8 20 s) 45kA
Protection level Vp(1) 1000V
Poles 1 1 2 4
Type Single pole plug-in Multi-pole monoblock
Thermal fuse healty indication LED LED + S(2) LED LED + S(2)
Operating temperature -30oC / 70oC
Connection In parallel
Response time 5ns
Terminal capacity 50mm2
Replacement module TM45IR TM45IR —— ——
Connected protection MCB C Type - 32A or 35A gL/gG fuse
DINType Reference
Poles
mod.
1 1 plug-in TM45I
1 1 plug-in TM45IS
Replacement module TM45IR
2 2 monoblock TM45II
4 5 monoblock TM45IIIIS
Note:(1) Vp: Residual voltage value when a transient current (8/20 s) is equal to the
rated current.
(2) References with «S» indicated that have double indication: LED + dry contact
(remote signal).
(3) Spark gap type: follow current=1,5kA, Insulation resistance 1000M.
TM65I TM65IS TM80IIIIS TM35SPI(3)
Rated voltage (V~) 230V 400/230V 230V
Maximum voltage (V~) 270V 540/270V 255V
Frequency 50/60Hz
Imax (8 20 s) 65kA 80kA 35kA(10/350)
Protection level Vp(1) 1200V <4kV
Poles 1 1 4 1
Type Single pole plug-in monoblockspark-gapThermal fuse healty indication LED LED + S(2) LED + S(2) —
Operating temperature -30oC / 70oC
Connection In parallel
Response time 5ns
Terminal capacity 50mm2
Replacement module TM65IR —- —- —-
Connected protection TM65 and TM80 MCB C type - 63A or 63A gL/gG fuse
Connected protection TM35SPI MCB C type - 100A or 125A gL/gG fuse
DINType Reference
Poles
mod.
1 1 plug-in TM20I
Replacement module TM20IR
2 2 monoblock TM20II
4 5 monoblock TM20IIII
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 29/56
29
Modular protection
Permanent overvoltage protectors with UVTfor TEMPORARY SUPPLY (emergency stopwith positive safety - NC contact)
YDO276 single phase OVT (Overvoltage
Release) with protection against permanent
overvoltage for MCB tripping, when network
voltage permanently exceeds 276V.
YDU single phase UVT (Undervoltage release)
enables the automatic trip of the MCB when
the supply voltage drops below 45-85% of Ue.
Equipments for single phase and three phaselines with integrated MCBs from 25A to 63A
The TD2YDO protects all the equipments
dowstream connected against permanent
overvoltage, induced by network voltage
increase.
YDO276 single phase OVT (Overvoltage
Release) with protection against permanent
overvoltage for MCB tripping, when network
voltage permanently exceeds 276V.
Permanent Overvoltage Protector In
Arrangement Reference (A)
20 TD2YDO220
25 TD2YDO225
32Main MCB 1P+N
TD2YDO232
40+
TD2YDO240
501 OVT YDO276
TD2YDO250
63 TD2YDO263
20 TD2YDO420
25 TD2YDO425
32Main MCB 3P+N
TD2YDO432
40+
TD2YDO440
503 OVT YDO276
TD2YDO450
63 TD2YDO463
TD2YDO Series
TD2YDU Series
Model TM20II TM20IIII
UC (50/60Hz) 275V - 50 ÷ 60Hz 275/400V - 50 ÷ 60Hz
UP (1,2/50)
≤ 1.2kV (L-N)1.2kV ÷ 1,5kV
≤ 1.5kV (N-PE)
IN (8/20) / Imáx. (8/20) / t A 5kA / 20kA / <25ns (L -N); <100ns (N-PE) 5kA / 20kA / <25ns
Dimensions An x Al x F 36 x 90 x 69mm 72 x 90 x 69mm
Transient Surge Protector When a transient surge is induced, the protector TM20 prevents the equipment downstream installed on
the electrical network damage. Transient protection will be of 20kA.
Permanent Overvoltage Protector with UVT In
Arrangement Reference (A)
20Main MCB 1P+N
TD2YDUO20
25+
TD2YDUO25
321 UVT YDU23
TD2YDUO32
40+
TD2YDUO40
501 OVT YDO276
TD2YDUO50
63 TD2YDUO63
20 TD2YDU20
25 TD2YDU25
32Main MCB 3P+N
TD2YDU32
40+
TD2YDU40
501 UVT YDU23
TD2YDU50
63 TD2YDU63
Indirect Permanent Overvoltage Protector
MCB 1P
6 + TD2YDO106
3 OVT YDO276
TD2YDO106
TD2YDU20
TD2YDUO40
Permanent Overvoltage Protection TD2YD
TD2YDO240
TD2YDO440
A complete protection solution can be achieved by the combination of Permanent overvoltage protectorsand Transient surge protectors. Please see the installation examples for single and 3-phase lines.
MCB breaking capacity 6kA at 400V~
UA Single phase element 255-275V
Response time 275V t ≤ 0.8s
400V t ≤ 0.3s
Operating voltage Ue Single phase 230V~
3-phase 230/400V~
MCB breaking capacity 6kA at 400V~
UA Single phase element 255-275V
Response time 275V t ≤ 0.8s
400V t ≤ 0.3s
Operating voltage Ue Single phase 230V~
3-phase 230/400V~
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 30/56
30
Permanent Overvoltage Protection + Transient Surge Protection
Single phase 3-phase
Permanent Overvoltage Protection with UVT + Transient Surge ProtectionSingle phase 3-phase
Modular protection
Permanent Overvoltage Protection TD2YDand Transient Surge Protection TM
Installation examples
I C P M
C B
( S p a n
i s h
S t a n d a
r d s )
M a i n M C B + P E R M A N E N T
P R O T E C T I O N
T D 2 Y D O 4 . . .
R C C B
R C C B
R C C B
MCB
T M 2 0 I I I I
MCBMCB
R S T N
R C C B
T M 2 0 I I
R C C B
M C B
M C B
L N L NN L
M a i n M C B + P E R M A N E N T
P R O T E C T I O N
T D Y D O 2 . . .
I C P M C B
( S p a n i s h
S t a n d a r d s )
L N
T M 2 0 I I
R C C B
M C B
M C B
M a i n M C B
+ P E R M A N E N T
P R O T E C T I O N T D
2 Y D U O . .
I C P M C B
( S p a n i s h
S t a n d a r d s )
L N
M u s h r o o m b u t t o n
1 N C
R C C B
R S T N
R C C B
R C C B
R C C B
MCBMCB MCB
T M 2 0 I I I I
I C P M C B
( S p a n i s h
S t a n d a r d s )
M u s h r o o m
b u t t o n
1 N C
M C B + P E R M A N E N T P R O T E C T I O N
T D 2 Y D O 1 0 6
M a i n M C B + U V T
T D 2 Y D U . .
M u
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 31/56
31
Technical Information
Page
Circuit Protection
General characteristics. ...................................................................................................... 32
Tripping characteristics. ...................................................................................................... 33
Power loss. ......................................................................................................................... 33
Let-throught energy I2t curves. ............................................................................................ 34
In uence of ambient temperature and height. .................................................................... 36
Selectivity. ........................................................................................................................... 36
The use of MCBs in special conditions. .............................................................................. 37
Technical characteristics for accessories YD. .................................................................... 38
General characteristics TDH. .............................................................................................. 39
People Protection
Technical classi cation. ...................................................................................................... 40
Technical characteristics: ZFP and FIEP. ........................................................................... 41
Technical characteristics: ZDH, FCOP and ZDS. ............................................................... 42
Command and Control
Contactors CDR, CDO and CDI. ........................................................................................ 43
RCCB with self-reclosing system ZFR. ............................................................................... 44
Pushbuttons, switches and changeover switches PD, PDL and WDM. ............................. 45
Programming and Measurement
Time switches RDA and RDD. ............................................................................................ 46
Staircase switch SDS and Light sensitive switch RDA. ...................................................... 47
Digital measurement instruments MDD. ............................................................................. 48
Analogue measurement instruments MDA. ........................................................................ 50
Modular Protection
Surge arresters TM. ............................................................................................................ 51
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 32/56
32
General Characteristics DPE, DS and DH seriesCircuit protection
Installation and Normal service conditions
Ambient temperature: -5oC to +40oC. For speci c applications at ambient temperatures values other thanthe ones mentioned above, please use the correction factors in table 5.
Humidity: 50% at a maximum temperature of +40oC.
Altitude: 2000 max.
Transport and storage ambient temperature: between -25oC and +70oC.
Mounting: directly on to 35mm DIN rail.
Connection: dual terminal for cable, busbar or crimp.
Cable terminations: stirrup type and the terminalscrew can be tightened using a Philips headscrewdriver or 5mm at blade screwdriver.
Wire section (rigid or flexible): 35mm2.
Torque: 1.7 to 2Nm.
TemDin2 breakers can be line fed from either thetop or bottom end of the device
Standards: Manufactured in accordance with EN 60898 and EN 60947 where applicable.Conforming with low voltage directive (72/23/CEE)
Rated Voltage (Ue): Single pole 230/400 V~ Single pole with neutral 230 V~ Two, three and four pole 400 V~
NOTE: Suitable for use at 240/415V. Degree of protection: IP20, as de ned in EN 60529.
Rated current (In):
Types B and C 6 - 8 - 10 - 13 - 16 - 20 - 25 - 32 - 40 - 50 - 63A
Type D 0.3 - 0.5 - 0.75 - 1 - 1.6 - 2 - 2.5 - 3 - 3.5 - 4 - 6 - 8 - 10 - 13 - 16 - 20 - 25 - 32 - 40 - 50 - 63A Tripping time: 8 to 20ms.
Impulse withstand test voltage U
imp:
Shock wave 1.2/50 s Rated insulation voltage (Ui): 660V AC.
Insulating distance: Clearance distances of 50mm have been established for the DS series, and 80mm for the DH MCB series
Energy limiting class: DS series Tripping curve B-C / Class 3 DH series Tripping curve B-C / Class 3
Breaking capacity: DS series B-C Standard EN 60898 6kA DH series Standard EN 60898 10kA MCBs to EN 60898: DS series: Breaking Capacity: 6kA of I
CN and I
CS with cos 0.65-0.7
DH series: Breaking Capacity: 10kA ICN
with ICS
7.5kA up to 32A and 6kA ICN
and ICS
for 40, 50 and 63A, in both cases cos =0.45-0.5
Endurance: Electrical - 30,000 operations. Mechanical - 40,000 operations
Mechanical shock and impact: The breakers have been subjected to accelerations of up to 22g without provoking the mechanical tripping.
Temperature rise:
Note: Terasaki recommends
the Pozidrive 2 use.
Motor protection: The protection of motors against the effectsof an internal short circuit must be ensured, allowing at the sametime the presence of short duration overcurrents (starting) withoutcausing tripping of the protection element.This element must also ensure protection of the line, of thecontactor and of the thermal relay associated to the motor.
Table 1
TemDin2 series selection table
for 4 pole squirrel cage motors.
Maximum permitted temperature as per EN 60898 Type B, C and DTerminals for external connections 60oC + ambient temperatureExternal parts which can be touched 40oC + ambient temperatureOther external parts 60oC + ambient temperature
380 / 415V 50/60Hz Type D Magnetic Kw HP In trip 0.37 0.5 1.6 20
0.55 0.75 2 250.75 1 2.5 31.51.1 1.5 3 37.51.5 2 4 502.2 3 6 753.7 5 10 1254 5.5 10 125
7.5 10 20 250
9 12 20 25010 13.5 25 31311 15 25 31315 20 32 400
18.5 25 40 50022 30 50 62525 34 50 62530 40 63 788
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 33/56
33
Tripping CharacteristicsCircuit protection
T e c h n i c a l D a t a
DPE, DS and DH series
DS and DH series
In Drop voltage Power loss Maximum power
loss by Standard
0.3 A 3.032 V 0.91 W 3 W
0.5 A 2.309 V 1.15 W 3 W 0.75 A 1.114 V 0.84 W 3 W 1 A 1.062 V 1.06 W 3 W 1.6 A 0.745 V 1.19 W 3 W 2 A 0.449 V 0.90 W 3 W 2.5 A 0.489 V 1.22 W 3 W 3 A 0.412 V 1.24 W 3 W 3.5 A 0.333 V 1.17 W 3 W 4 A 0.325 V 1.30 W 3 W 6 A 0.326 V 1.96 W 3 W 8 A 0.185 V 1.48 W 3 W 10 A 0.185 V 1.85 W 3 W 13 A 0.130 V 1.69 W 3.5 W 16 A 0.147 V 2.35 W 3.5 W 20 A 0.148 V 2.96 W 4.5 W 25 A 0.135 V 3.38 W 4.5 W 32 A 0.102 V 3.26 W 6 W 40 A 0.082 V 3.28 W 7.5 W
50 A 0.073 V 3.65 W 9 W 63 A 0.113 V 7.12 W 13 W
Table 2
DPE series EcoPlus
In R P
A m W
6 25.4 0.99
10 14.1 1.35
16 7.45 2.03
20 5.00 1.97
B, C 25 4.05 2.78
32 2.95 3.65
40 2.35 4.89
50 1.82 6.98
63 1.14 8.78
B, C and D tripping characteristics according EN 60898
Application selection for MCB tripping characteristicsType B characteristics are suitable for moderately inductive loads having that have little or no switching surges i.e. electric heating, water heating,ovens etc.
Type C characteristics MCBs can be used in general applications such as lighting, ring/ radial socket outlets and small motors.
Installations where the equipment is likely to produce abnormally high inrush currents, such as transformers, welding machines or induction motorsare suited to type D characteristics.
Power lossPower loss values as de ned by EN 60898. Per pole values shown.
Steady current value
Int = 1.13 In : t > 1h
Steady current value
It = 1.45 In : t < 1h
2.55 In: t < 1m (In 32A)
t < 2m (In > 32A)
2.55 In: t> 1s
Type B
3 In : t 0.1s
5 In : t < 0.1s
Type C
5 In : t 0.1s
10 In : t < 0.1s
Type D10 In : t 0.1s
20 In : t < 0.1s
1
2
3
4
5
6
7
8
9
10
Table 3
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 34/56
34
Values for isolated conductorK2 q2 (A2 s) Copper conductor (Cu)
mm2
0.5
0.75
1
1.5
2.54
6
10
16
25
35
PVC
K=115
3.306
7.439
13.225
29.756
82.656211.600
476.100
1,322.500
3,385.600
8,265.625
16,200.625
RubberK=141
4.970
11.183
19.881
44.732
124.256318.096
715.716
1,988.100
5,089.536
12,425.625
24,354.225
EPR K=143
5.112
11.503
20.449
46.010
127.806327.184
736.164
2,044.900
5,234.900
12,780.625
25,050.025
Table 4
Let-throught energy I2t curvesCircuit protection
Protection of conductors against the effects of an overcurrent is ensured when thefollowing is ful lled:
I²t < K²q²I = current r.m.s. (A) short circuit conditionst = breaking time (sec.)
K = material factor q = cable section (mm)
Example:K2q2 = 29,756A2s for an electrical line with a copper conductor (1.5 mm 2) PVCcovered. If we want to protect this line with a DS-B 6kA, its I 2t must be lower that theconductor K2q2, ; 6A at 16A
DS series DH series
Let-throught energy I2t curves
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 35/56
35
T e c h n i c a l D a t aLet-throught energy I2t curvesCircuit protection
DS1 series
I2t Curves
Amps
A 2 s
e c .
Amps
A 2 s
e c
.
Amps
A 2 s
e c .
DPE series EcoPlus
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 36/56
36
Influence of height (altitude)If the height of the installation site exceeds 2,000m, the reduction of thedielectric strength and the cooling effect of the air should be considered.NEMA and ANSI Standards establish some speci c values that can betaken as a reference:
Load compensation for breaker groupingBreakers mounted side by side and subject to near, or full loadingsimultaneously can generate high temperatures in small or poorlyventilated enclosures. Load reduction must be taken into account. Thefollowing tables are guidelines to prevent potential overloading:
- For a single row the table 5 can be used- In two-row distrubution boards the reduction is approximately of a 25%
- In three-row distribution boards the reduction is approximately of a 30%
DS and DH series
Ambient compensation At temperatures out with the breakers calibrated value +300C +/-50C,the load capacity of the device will vary inversely as a function of itsoperating ambient temperature. Therefore operation at temperatureshigher than 300C will reduce the MCB’s loading capacity.
Influence of ambient temperature and heightCircuit protection
Discrimination or selectivity exists between two protective devices
connected in series when the operation of the downstream device is
such that the fault condition is cleared without operation of the upstream
device
The characteristics of the downstream device should be that clearance
of the fault condition limits the current (let through value) to a value
below the magnetic threshold of the upstream device.
Partial selectivity is said to occur when the selective operation of the
downstream device is at a value between the threshold of the upstream
device’s magnetic trip setting but not exceeding the downstream
device’s rated breaking capacity. At values above this both devices may
operate.
Full selectivity is said to occur when it is selective up to a prospective
value of fault current equal to the downstream devices breaking
capacity.
Selectivity Limit value of the selectivity MCB/MCB
Type DS”C” up In (A) 6 10 16 20 25 32 40 50 63
6 8.0 8.0 8.1 8.1 8.2 8.2 8.3 8.3
10 7.1 7.1 7.5 7.5 7.6 7.6 7.7
16 7.0 7.0 7.5 7.5 7.6 7.6
Type 20 5.4 5.5 5.6 5.7 5.7
DS”B” 25 5.4 5.5 5.6 5.7
down 32 5.1 5.2 5.3
40 5.1 5.1
50 5.1
63
Table 8
Type DS”D” up
In (A) 6 10 16 20 25 32 40 50 63
6 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5
10 12.1 12.1 12.1 12.1 12.1 12.1 12.1
16 10.1 10.1 10.1 10.1 10.1 10.1
Type 20 10.1 10.1 10.1 10.1 10.1
DS”C” 25 10.2 10.2 10.2 10.2
down 32 10.2 10.2 10.2
40 10.2 10.2
50 10.2
63
Type DS”D” up
In (A) 6 10 16 20 25 32 40 50 63
6 10.2 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
10 10.0 10.2 10.5 10.5 10.5 10.8 10.8 10.8 10.8
16 10.0 10.2 10.5 10.5 10.8 10.8 10.8 10.8
Type 20 10.0 10.2 10.5 10.5 10.8 10.8 10.8
DS”B” 25 10.0 10.2 10.5 10.5 10.8 10.8
down 32 10.0 10.2 10.5 10.5 10.8
40 10.0 10.2 10.5 10.5
50 10.0 10.2 10.5
63 10.0 10.2
Table 9 Table 10
Non selective zone
For other tripping characteristics, please contact Terasaki.
The limit value of the selectivity is referred to the number of
times of the up breaker rated current value (In).
Example: Up DS-D 10A, Down DS-C 1A
corresponds to 10.9 10.9In x 10A = 109A
Table 5
Table 6
Height Permanent Clearance
max. I rated U < 2,000m 1.00 1.00
< 2,600m 0.99 0.95< 3,900m 0.96 0.80
Table 7
1 2 3 4 5 6 7 8
No. of breakers
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 37/56
37
T e c h n i c a l D a t a
The use of breakers in DC circuits
The thermal characteristics for TemDin2 breakers are unaffected by the type of current applied, that is either direct current or alternating current.The magnetic trip value increases by 40%. For example, in the case of a breaker of tri pping characteristic B and 10A rated current, its magnetictripping value will be between 30A and 50A in alternating current. The magnetic tripping value for this very same breaker in direct current will bebetween 42.4A and 70.7A.
Influence of non standard frequencies
For operational frequencies greater than 50/60Hz, the effect of these non-standard frequencies must be taken into consideration. Thermal
characteristics are independent from variation in frequency. Magnetic tripping values are directly affected by frequency. As a reference, forfrequencies of 100, 200, 300 and 400Hz, the values at which the magnetic tripping occurs become increased in a 10, 20, 30 and 40% respectively.
Use at other voltages
The maximum rated operational voltage for TemDin2 MCBs is 440V~ with a reduction in breaking capacity of 10%. Supply voltages lower than theassigned value can be applied.
Supply voltages up to 750V can be applied in special conditions of service and short circuit current rates. Please contact Terasaki for further details.
Phase Imbalance
In three phase circuits designed for single phase distribution through to nal load, consideration should be placed for protection of the neutralconductor. TemDin2 4 pole MCB’s have integral neutral pole protection and offers adequate protection against overloaded neutral conductors,when phase imbalance conditions are present. Commercial installations such as hotels, banks and public buildings are often subject to high neutralcurrents via equipment consuming non-linear loads and also require protection to be present in the neutral line.
Circuit protection
V 48V 48V < V 110V 110V < V 150V 150V < V 200V
1p 2p 3p 4p
The use of MCBs in special conditions
The breaking capacity of the breaker is also affected. The breaking capacity is maintained in 6kA (for the range DS06) and in 10kA (for the range DH06)for circuits with a constant time L/R = 0.015 sec., but bearing in mind the following table that indicates the number of poles that should participate inthe break.
The breaker poles distribution among the polarities depends on the type of system. According to the earth location, it should be analyzed the mostunfavourable fault that requires a larger number of poles in series for the short circuit voltage range that the table indicates. After that, apply the breakerwith the necessary number of poles.
When the source has a polarity put to earth, a supplementary pole in the said polarity can be used in order to carry out the load isolation.
Examples of different system types and faults (A, B or C) that cause consequences:
Example: Say, a source of 120V
Case 1) according to the table, 3 poles in series for the A and B fault are required. A 3-pole breaker in series should be put in the positive polarity ora 4-pole breaker with the fourth pole in the negative polarity to assure the isolation.
Case 2) 3 poles in series for the defect A are required (120V short circuit voltage) or 2 poles in series for the faults B or C (60V short circuit voltage) ineach polarity. In such a way that with a 4-pole breaker with 2 poles in series in each polarity the most unfavourable case is covered.
Case 3) 3 poles in series are required for the fault A. A 3-pole breaker in series in any polarity is required or 2 in one and the other pole in the otherpolarity.
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 38/56
38
Technical characteristics for accessories YDCircuit protection
Accessories for DS and DH series
Up to three accessories can be clipped together onthe left hand side of a breaker.
1. Under voltage release YDU2. Shunt trip YDS
3. Auxiliary contact and remote contact status indicator YD4. Breaker DS or DH
NOTE: Make sure that break out plate ‘A’ is removed and the dollies of both the auxiliary device and associated breaker are in the OFF positionbefore clipping them together.
The Under Voltage Trip release hastwo terminals, D1 and D2, betweenwhich it must be applied a voltage>=0.55Ue (+/-10%).
On the central-top hand of the frontalside there is a time delay functionpotentiometer that allows a delay ofup 300msec. User can manage it witha small size flat-end screwdriver.
Test device
On the low-left hand of the frontal side there is a test lever allowing11-13 contacts to be checked without tripping the main breaker.
With the main breaker in ON position by pushing the test lever fromthe bottom to the top, you can verify if contacts 11-13 open.
Shunt Trip is a main circuit breaker accessory that allows remote open-ing. There is a magnetic relay that when the coil is energized acts overits mechanism and it trips the main breaker.
There are 3 different terminals C1, C2 and 12
It is only possible to energize the relay(terminals C1 and C2) when the mainbreaker and the SHT are in ON position.There is a protection switch that after therelay is energized, the internal mechanism
trips it and the relay circuit becomes open(see diagram).
There is also, an auxiliary contact 12-C1that allows to show the status of SHT andthe main breaker.
Shunt trip YDS Undervoltage release YDU
Alarm or Auxiliary contact YDA
AUXILIARY operational mode
When the main breaker changes position (ON/OFF), either manually or because and automatictripping, always auxiliary contacts also change position.
When the main breaker is in ON position, auxiliary contacts 11-12 are in NO position, andauxiliary contacts 11-13 are in NC position.
When the main breaker is in OFF position, auxiliary contacts 11-12 are in NC position, andauxiliary contacts 11-13 are in NO position.
AUX/AL
There are 2 different operational mo-des. On the frontal side there is a shaftwith a cam that selects each functionmode (see picture). It must be used asmall size flat-end screwdriver. To be
fitted on the left side.AUX AL
ALARM operational mode
When the main breaker is in ON position, auxiliary contacts 11-12 are in NOposition, and auxiliary contacts 11-13 are in NC position.
When the main breaker is from ON position to OFF position manually changed,auxiliary contacts do not change position.
When the main breaker changes from ON position to OFF position, becausean automatic tripping, auxiliary contacts change position and there is a trippingindicator on the frontal side that shows red colour.
In this case auxiliary contacts 11-12 and 11-13 move to NC and NO positionrespectively.
OFF
TripOFF
ON
ON
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 39/56
39
Standards: 10kA, in accordance with UNE-EN 60898 and IEC 60947-2. Thermal calibration: 30°C. Suitable for isolation, shown by a green indicatoron the toggle. Simultaneous contacts closing independent of the handling speed.
Rated operational voltage Ue (V): 400V Insulation voltage Ui (V): 500V
Rated impulse voltage (Uimp (kV): 2500V
Power loss: MCB rated current (A)/Watts loss per pole (W) 80A/8W, 100A/10W
Temperature derating: If the circuit breaker is required to operate in a higher ambient temperature than 30°C it will require progressively lesscurrent to trip within the designated time/current zone.
General characteristics TDH seriesCircuit protection
T e c h n i c a l D a t a
TDH series
Accessories for TDH series
Correction factor
In (A) 30°C 35°C 40°C 45°C 50°C 55°C 60°C
80 80 76 72 68 64 60 56
100 100 95 90 85 80 75 70
Current limiting at 400V
Auxiliary contacts Shunt trip (SHT) Undervoltage trip (UVT)TDHAUX TDHAL TDHSHT230 TDHUVT230
1 x O 1 x C
230V~ 6A
AC-1
Consumption: 8VATolerance:
Un -15%
230V~
Consumption: 3VALatching voltaje Un 230~:
between 35-70%
230V~
Standards: In accordance with EN 61009-1 and EN 60947-2.
Rated voltage: -15 +10%. 2-pole 230V, 4-pole 230/400V
RCD add on block2 P 4 P
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 40/56
40
Residual current Tripping time
0.5 x In t = 1 x In t < 300 ms
2 x In t < 150 ms
5 x In t 40 ms
Technical classificationPeople protection
Tripping curvetype AC
RCCB classification
Type AC
Type AC RCCBs are designed to clear sinusoidal residualcurrent which occur suddenly or slowly rise in magnitude.
at point on wave 90o
0.25 x In t =
1.4 x In t < 300 ms
2.8 x In t < 150 ms
7x In t 40 ms
at point on wave 135o
0.11 x In t =
1.4 x In t < 300 ms
2.8 x In t < 150 ms
7 x In t 40 ms
Type Ai
High immunity to nuisance trippingElectric equipment incorporates more and more electronic components
which causes nuisance tripping to the conventional 30mA RCD’s type
A or AC (always in the most critical moment like weekends, areas with
no people presence…) due to overvoltages or high frequency currents
produced by atmospheric disturbances, lighting equipment (electronic
balasters), computers, appliances, connections to long cables which
induce a high capacity to ground, etc.
Some times the lter incorporated on the standard RCD’s type A or ACwhich are protected to prevent nuisance tripping against peak currents
up to 250A 8/20 μs, does not avoid 100% unwanted tripping.
Installations with lighting equipment incorporating electronicbalasters or computers.The most typical problem in these installations is the tripping of the RCD
when switching the equipment ON-OFF. It is recommended that, in
case several devices are installed in the same line, the sum of all leak-
ages shall not exceed 1/3 lDn since any disturbance in the line can trip
the RCD. For this kind of installation it is recommended either to split up
circuits or use RCD’s type Ai.
RCD’s type Ai have a tripping characteristic according to EN 61008/61009.
All RCD’s have a high level of immunity to transient currents, against
current impulses of 8/20 μs according to EN 61008/61009.
Type A, AC ........…...........250 A 8/20 s Type S ..............…..........3000 A 8/20 s Type Ai ...........................3000 A 8/20 s
RCD’s have a high level of immunity against alternating currents of high
frequency according to EN 61008/61009
Tripping curvetype A
Sinusoidal residual current
Residual current Tripping time
0.5 x In t =
1 x In t < 300 ms
2 x In t < 150 ms
5 x In t 40 ms
Residual pulsating direct current
at point on wave 0o
0.35 x In t =
1.4 x In t < 300 ms
2.8 x In t < 150 ms
7 x In t 40 ms
Type S SRCD’s type A or AC have instantaneous tripping. In order to providefull people protection in vertical installation with more than one circuit,as well as to ensure the service in the installation in case of earthleakage in one of the circuits or to avoid unwanted tripping because ofharmonics, high connection currents due to the use of motors, reactiveloads, or variable speed drives, we need to use selective RCD’s at thetop of the installation.
Any RCD type S is selective to any other instantaneous RCD installeddownstream with lower sensitivity.
1. Selective type RCCB’s.2. Standard type RCCB’s.
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 41/56
41
Technical characteristics for ZFP and FIEP SeriesPeople protection
Standards: In accordance with EN 61008 and suitable for isolation.
Sensitivities: 10, 30, 100 and 300A
ZFP RCCBs optional use for type A and type AC .For 300mA sensitivities available type A with selective time delay
function.
Resistant against unwanted tripping due to surge effect .
Rated current: Range from 16, 25, 40, 63, 80 and 100A
Rated voltage: 230/400V~ (2P) and 400/415V~ (4P) at a frequency of
50/60Hz
Mounting: 35mm symmetrical DIN rail (EN50022-DIN46277).
Operating temperature: Min. operating temperature -25°C.
Application: This range provides the protection against overload and short-circuit currents and protects people against earth fault currents: direct or
indirect contact, re...
AUXZF Auxiliary contacts
T e c h n i c a l D a t a
ZFP Series FIEP SeriesIn accordance with: EN 61008
Rated current: 25 and 40A
Rated voltage: 230V~
Sensitivities: 30mA
No. of poles: 2
Type: Type AC
Mounting: 35mm symmetrical DIN rail
(EN50022-DIN46277).
Dimensions: 2 DIN modules
(1 DIN module=17.8mm)
Tripping time: < 30ms.
Mechanical endurance: 20,000 operations.
Resistant against unwanted tripping due to
surge effect .
Residual making and breaking capacity:Im = Im = 500A
Power loss per pole
ZFP
In (A) 16 25 40 63 80 100
Z (mOhm) 9.95 3.75 2.15 1.30 1.3 0.9
Pw (W) 2.55 2.33 3.43 5.16 8.3 8.7
Rated current In 5A
Rated voltage AC Un 240V
Max. current AC 14 240V 5A
DC 12 60V 1A
48V 2A
24V 4A
Min. operating voltage AC 24V
DC 24V
Min. operating current AC 10mA
DC 200mA
Electrical endurance operations 10,000
Torque Nm 0.5
AUXZF1Auxiliary contact
AUXZF2Signal contact
S
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 42/56
42
Technical characteristicsPeople protection
ZDS I2t Curves
ZDH and FCOP Series
Standards: In accordance with IEC 61009.
Thermal setting In: 6, 10, 16, 20, 25, 32 and 40A
Residual current Im: 30 and 100mA
Tripping characteristic: C and B
Minimum operating voltage UBmin: 100VMechanical/electrical endurance: 20,000/10,000
Tropicalisation acc. to IEC 60068-2-28/2-30: 95% RH at 55oC
Terminal capacity flexible/rigid cable:ZDH - Bottom terminal: 16-25mm2
FCOP - Top: 16-25mm2 / Bottom: 25-35mm2
No. of poles:ZDH - 1+N (1 module)FCOP - 1+N (2 module)
Nuisance tripping resistance: 250A 8/20s
Ambient temperature: -5oC up to 55oC
Residual making and breaking capacity:ZDH - Im=10,000AFCOP - Im=7,500A
Short-circuit capacity: Icm=10,000 at 230V
Selectivity class: 3
Accessories for FCOP SeriesTo be added on the right side.
Auxiliary contacts, please refer to ZFP RCCBs Aux. contacts
Ref. AUXZF on page 41.
Shunt trip(SHT)
Undervoltage trip(UVT)
SHTZF230 UVTZF230
Nominal voltage AC 110/415V 230V
DC 110/125V 230V
Tripping voltage Un (±10%) 0.5V
Minimum voltage AC / DC Un 0.85V
Tripping time <10ms 0 – 300ms
Power consumption 3VA
Coil impedance 290
Electrical endurance (operations) 2000 2000
Torque 2Nm 2Nm
Power loss per pole
ZDH
In (A) 6 10 16 20 25 32 40 50 63
Z (mOhm) 45.8 16.4 10.6 7.3 5.4 3.2 2.6 1.9 1.4Pw (W) 1.65 1.7 2.7 2.9 3.3 3.4 4.2 4.8 5.6
Power loss per pole
FCOP
In (A) 6 10 16 20 25 32 40
Z (mOhm) 53 16.5 9.8 7.1 5.8 4.7 3.6
Pw (W) 1.9 1.6 2.5 2.8 3.5 4.8 5.8
ZDS Series
Standards: In accordance with IEC 61009.
Rated voltage: 230/240~
Frequency: 50/60Hz
Breaking capacity: 6kA - class 3 According to EN61009.
Sensitivities: 30 and 300mA.
Type: Type AC
Tripping characteristics: Type C.
No. of poles: I+N (neutral right side)
Rated current: from 6 to 40A
Resistant against unwanted trippingdue to surge effect
Terminals: Dual type bottom for cable or busbars connection (fork type).
Mounting: 35mm symmetrical DIN rail (EN50022-DIN46277).
No. of modules: 2
ZDH FCOP
ZDS
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 43/56
43
Contactors CDICommand and Control
T e c h n i c a l D a t a
1) Apropiados para sistemas de neutro, categorías de sobretensión I a IV, nivel de polución 3 (industria estándar): Uimp = 8kV.
2) Apropiados para sistemas de neutro, categorías de sobretensión I a III, nivel de polución 3 (industria estándar): Uimp = 8kV.
3) Sección de cable máx. con conductor preparado 4) AC7b motor 2 polos 230V 1,1kW
5) Frecuencia nominal 50/60Hz 6) Sobretensión máx. transitoria a la conexión <4kV 7) Ciclo de trabajo: 100%
Type
Main Contacts 5) 6) 7)
Rated insulation voltage Ui V AC
Rated operation voltage Ue V AC
Frequency of operations z AC1, AC3 1/hMechanical life S x 106
Utilization category AC1Rated operational current I
e (=I
th)
open at 60°C AContact life S x 106
Minimum Switch Voltage V/mAShort time current 10s-current APower loss per pole at I
e/AC1 W
Utilization category AC3Switching of three-phase motorsRated operational current I
e A
Rated operational power of three-phase motors 220V kW
50-60Hz 230-240V kW 380-415V kWContact life S x 106
Power consumption of coils AC operated inrush VA holding VA WOperation range of coilsin multiples of control voltage U
s (-40 to +40°C)
Short circuit protectionmax. fuse Coordination-type “1” gL (gG) ARated short circuit current “r” kA “Iq” kA
Cable cross-sectionsMain connector solid or stranded mm² exible mm² exible with multicore cable end mm²Clamps per poleMagnetic coil solid or stranded mm² exible mm² exible with multicore cable end mm²Clamps per pole
Auxiliary Contacts 5) 6) 7)
Rated insulation voltage Ui 1) V ACThermal rated current I
th 40°C A
Ambient temperature 60°C A
Utilization category AC15Rated operational current I
e 220-240V A
380-415V A 440V A
Utilization category DC13Rated operational current I
e 24-60V A
per pole 110V A 220V A
Short circuit protectionshort-circuit current 1kA,contact welding not acceptedmax. fuse size gL (gG) A
Switching time at controlvoltage U
s ±10%
make time ms
release time msarc duration ms
CDI Technical InformationDe acuerdo con IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
20A 25A 40A 63A Aux. Contact
440 2) 440 2) 440 2) 440 2) 440 2)
440 440 440 440 440
300 300 600 600 600 1 1 1 1 1
20 25 40 63 - 0.1 0.1 0.1 0.1 - 24/100 24/100 24/100 24/100 17/5 72 72 216 240 - 2 2 3 7 0.5
- 9 27 30 -
- 2.2 7.5 8 -
1.14)
2.5 8 8.5 - - 4 12.5 15 - - 0.15 0.15 0.15 -
7 - 9 14 - 18 33 - 45 33 - 45 - 2.2 - 4.2 4 - 6 6 - 8 6 - 8 - 0.8 - 1.6 1.6 - 3.2 2.6 2.6 -
0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 -
35 35 63 80 - 3 3 3 3 - 3 10 10 10 -
1.5 - 10 1.5 - 10 2.5 - 25 2.5 - 25 0.5 - 2.5 3)
1.5 - 6 1.5 - 6 2.5 - 16 2.5 - 16 0.5 - 2.5 3)
1.5 - 6 1.5 - 6 2.5 - 16 2.5 - 16 0.5 - 1.5 1 1 1 1 2 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 - 0.5 - 2.5 0.5 - 2.5 0.5 - 2.5 0.5 - 2.5 - 0.5 - 1.5 0.5 - 1.5 0.5 - 1.5 0.5 - 1.5 - 1 1 1 1 -
- - - - 440 2)
- - - - 10 - - - - 6
- - - - 3
- - - - 2 - - - - 1.6
- - - - 2 - - - - 0.4 - - - - 0.1
- - - - 10
7 - 16 9 - 15 11 - 15 11 - 15 -
6 - 12 4 - 8 6 - 13 6 - 13 - 10 - 15 10 - 15 10 - 15 10 - 15 -
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 44/56
44
Command and Control RCCB with self-reclosing system ZFR
ZFR Series
Operation modea) After a switch-off due to a residual current fault or a manual action,
the RCCB is automatically reclosed once the period of time between
successive reclosing actions has passed. It can also be reclosed by
means of an external electric command applied to (LI).
b) The manual switch (2) (yellow lever) can be locked with a padlock(6mm passing hole) at the position ON (I) or OFF (O). Fasten the
padlock through the hole (3).
- If the manual switch (2) is locked at the position I, then the ZFR is
ready for its regular use.
- If the manual switch (2) is locked at the position O, then the ZFR
is blocked and neither manual nor automatic reclosing actions are
allowed.
- The switch (2) (yellow lever) in the O position causes the internal
counter of reclosing attempts to be reset to zero - In case of switch lock, lower the yellow lever and put it up back
again.
Before executing any manipulation over the installation placeddownstream the ZFR unit, the self-reclosing ability must be
disabled by pulling down the manual switch (yellow lever).
c) ZFR type sets are equipped with a group of additional micro-switches
(H) which indicate the position of the RCCB (switched on or off)
regardless the cause of the trip (terminals No. 11, 12 and 14).
Motor
Dimensions 3p
Rated voltage 220/240V 50/60 Hz Reclosing
delay by means 0.3s < t < 1s
of external command
Auxiliary contact Imax: 2 A 250Vac / 2A 24Vdc
Imin: 20mA
Terminal for 2.5mm2 cable
Relay (built in the motor)
Reclosing actions
Allowable number 6
Delay Time 10, 20, 30, 60, 120 and 600s
Reset Time = Reclosing delay
RCCB device
Rated voltage (Un) 230/400Vac 50/60Hz
Current (In) 40 AacSensitivity (Ifm) 30 or 300mA according to model
Endurance to shock waves 250A 8/20ms and 200A 0.5ms
Endurance to short-circuit 6000A as per VDE 0664
Breaking and closing rated 500A
current
Tripping characteristics Type AC (other, please contact)
Test voltage 2p - between 140 and 230Vac
4p - between 190 and 400Vac
Poles 2 or 4
Connection terminals 35mm2
Protection degree IP40 (DIN 40050)
Storage temperature -55oC to +55oC
Working temperature -25oC to +55oC
Relevant standards EN 61008
Case colour RAL 7035
Specifications of ZFR Series
Specifications of ZFR Series
(1) Terminals for commands line:
N- L : Power supply at 230Vac
LI : External reclosing command (optional)
(2) Manual switch (yellow lever):
- Position I: Ready for regular use
- Position 0: All operations are locked.
(3) Passing hole for padlock:
Ability to lock at position 0 or I.
(4) Micro-switch terminals: Indication of the RCCB status: 11, 12 and 14.
Electrical wiring of ZFR series
(a) Connect the phases and/or neutral wire of the line to be protectedto the power terminals of the RCCB.
(b) Connect the power supply for the operation of the motorizeddriving system of the RCCB (voltage of 230Vac between theterminals marked as N and L).
3-phase system
1-phase system
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 45/56
45
T e c h n i c a l D a t a
Pushbuttons, Switches andChangeover switchesCommand and Control
5
86
7
1 3
2 4
1
2
1-2 UNIPOLAR
3 1
1-2 BIPOLAR
2
3 75
6
1
1-0-2 UNIPOLAR
2
3
2
1-0-2 BIPOLAR
31 5 7
6
5
86
7
1 3
2 4
1
2 2
1
6
5
1NA 2NA
2 4
3NA
1 3 5
6 4 62
4NA
3 51 7
8
5
86
7
1 3
2 4
1
2 6
5
2
1
6
5
2
1 5
6
7
8
5
6
1NA 1NC 2NA 1NA/NC 1NA+1NC
5
6
X1 X2
5
6
1NA
X1
X2
1NC
X2
X1
6
5
PD pushbuttons
PDL pushbuttons with neon signal lamp
WDM switches
WDM changeovers switches
Terminal numerical order
Terminal numerical order
Terminal numerical order
Terminal numerical order
1NO 1NC 2NO 1NO/NC 1NO+1NC
1NO 1NC
1NO 2NO 3NO 4NO
1-2 SINGLE POLE 1-2 TWO POLE 1-0-2 SINGLE POLE 1-0-2 TWO POLE
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 46/56
46
Time switches RDA and RDDProgramming and measurement
RDD07A digital time switch
RDD07 single module digital timer
RDA24 analogue timer
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 47/56
47
T e c h n i c a l D a t a
Staircase switch SDSLight sensitive switch RDAProgramming and measurement
RDD07A2 digital time switch
SDS016C Staircase switch
Diagram 3 wires Diagram 4 wires
RDA24P light sensitive switch
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 48/56
48
TechnicalData
Input
- Current TI/5Aac
- Voltage <500Vac
Overload 1,2 In/Vn
Position of the decimal point minidip switch
Power comsuption minidip switch
Power comsuption 4VA
Operating temperature 0/50oC
(R.H.<90% no condensation)
Storing temperature -10/60oC
(R.H.<90% no condensation)
TechnicalData
Input
- Current TI/5Aac
- Voltage <500Vac
Overload 1.2 In/Vn
Display LED + Segments
Power comsuption 2VA
Operating temperature 0/50oC
(R.H.<90% no condensation)
Storing temperature -10/60oC
(R.H.<90% no condensation)
Digital measurement instruments MDDProgramming and measurement
MDD06V2 voltmeter / MDD06A2 ammeter
MDD00F frequency meter
MDD06W wattmeter
TechnicalData
Input
- Voltage 10~500Vac
Overload 1,2 In/Vn
Position of the decimal point automatic
Power comsuption 4VA
Operating temperature 0/50oC
(R.H.<90% no condensation)
Storing temperature -10/60oC
(R.H.<90% no condensation)
Wiring diagram for voltmeter
Wiring diagram for ammeter
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 49/56
49
T e c h n i c a l D a t aDigital measurement instruments MDDProgramming and measurement
MDD06P4 three-phase LCD multimeter
TechnicalData
PARAMETERS DISPLAYED
- Phase-phase voltage L1, L2, L3
- Phase-neutral voltage L1-N, L2-N, L3-N
- Current I1,I2,I3,In (neutral)
- Total equivalent power factor total ind/cap
- Total active power (+/-) PW
- Total reactive power Pvar
- Total apparent power PVA
- Frequency Hz
- Total active energy (import)* +kWh
- Total active energy (export)* -kWh
- Total reactive energy* kvarh
- Total working time* hh:mm
- Partial working time* hh:mm
- Phase sequence
(square lighted=NO sequence)
N.O. contact 1000V-0.5A-20VA
*When used as a priority relay.
Voltmetric input Line-line voltage:
- direct connection max. 500 V
- permanent overload 120%
- thermal overload (1 s) 150%
- input impedance voltmetric circuits 2MΩL-N / L-L
Amperometric input
- rated current 63 A
- permanent overload 120%
- thermal overload (1 s) 200%
Voltage measurement
- range of measurement LN 0...290 V
(phase voltage with direct connection)
- precision 0.5% f.s ± 2 digit
Current measurement
- range of measurement 0.6 ... 63.0 A
- precision in the range of
measurement 0.6 ... 63.0 A 0.5% f.s ± 2 digit
Frequency measurement
- rated value 50/60 Hz
- range of measurement 45...80 Hz
- precision 0.3% vm ± 1 digit
- response time < 300ms
Active power measurement
- range of measurement 50 kW
- precision 1% f.s ± 2 digit
Reactive power measurement
- range of measurement 50 kvar
- precision 1% f.s ± 2 digit
Apparent power measurement
- range of measurement 50 kVA
- precision 1% f.s ± 2 digitActive energy measurement (Wh)
- resettable import / export hour meters Two separate
- calculating period 15 minutes
- energy count 999999.9 kWh
- precision with current 0.05...1.0 In 2% fs ± 2 digit
Reactive energy measurement (varh)
- resettable energy count 999999.9 kVarh
- calculating period 15 minutes
- precision with current 0.05...1.0 In 2% fs ± 2 digit
Power factor measurement
- range of measurement cos -1...0...+1
- precision with current 0.1...1.0 In
and voltage 0.8...1.2 Un 2% fs ± 2 digit
Working time
- Total working time hh:mm with presence of power supply
- Partial working time hh:mm from previous reset
Display
- display type LCD
- no. of characters 8+8 on two lines
Electrical characteristics options Galvanic insulation
- coil-contact alarm relay 3kV
Mechanical characteristics
- mounting type guide DIN50022/ ush DIN43700
- protection rating complete device IP20/ front panel IP30
Relay contact characteristics
- N.O. contact maxV..maxI..maxP 1000V 0.5A 20VA
Ambient conditions
- ambient temperature 0...+45 °C
- outer range -5...+55 °C
- storage temperature -10...+70 °C
- relative humidity 10...95 %- atmospheric pressure 70...110 kPa
Reference standards
- Safety EN 61010-1 300V CAT III
- Precision EN 60688
- Electromagnetic compatibility (immunity) EN 61000-6-2 (ex EN 50082-2)
- Electromagnetic compatibility (emission) EN 61000-6-4 (ex EN 50081-2)
- Protection rating of enclosures (IP Code) EN 60529
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 50/56
50
TechnicalData
Input
- Current 16Aac (48~62 Hz)
- Voltage 230Vac (+10/-15%) by voltimetric input
Overload 1,2 In/Vn
Operating temperature 0/50oC (H.R.<90% no condensation)
Storing temperature -10/60oC (H.R.<90% no condensation)
Programming and measurement
MDA00E active energy meter
MDA analogue ammeter and voltmeter
VOLTMETER AMMETER
Analogue measurement instruments MDA
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 51/56
51
T e c h n i c a l D a t aSurge arresters TMModular Protection
Protection against transient currents
Transients with high energy and short duration (<50ms) are the mostdangerous and destructive problems in distribution lines -low energyvoltage variations, electromagnetic noise, harmonics, power supplyinterruptions and ground faults-. Its random nature, short duration andhigh energy involved make them the most dif cult problem to solve.
Associated to lightning, either direct impact or induction are the most
destructive phenomenon.
Due to these surges or changeover operations, the transients’ origin indistribution lines is increasing and it causes serious cost damages tothe connected equipment. Furthermore, there is the substitution of thetraditional circuits with relay by printed circuits, which are easily affectedbecause of their high sensitivity, typical examples are operative lifereduction, malfunction of electronics’ logic and destruction.
Transient current at 250A (peak current) at point on wave8/20 s (VDE 0664)
Transient current at 200A (peak current) at minimised point onwave 0,5 s-100kHz (pr EN 61.1008)
Applications
Electronic equipment becomes more vulnerable to power disturbanceswith each new generation. Electronic damage, disruption and downtimecan be prevented.
Critical loads needing to be protected, with an increasing number ofelectronic loads are:
· Work stations· Telephone systems· Automated assembly· Medical diagnostic equipment· Industrial machine tools· Electronic gas pumps· Automated integrated controls· TV & radio broadcasting equipments· Telephone & communication equipments· Computers and networks· Domestic ...
Protection zones and surge arrester typesIn practice, it is very convenient to de ne four protection zones in a building.
Zone 0: Area with more risk, not protected. Direct lighting impact, usually occurred on the
external side of a building, with or without lighting conductor.
Zone 1: Part of the building protected by its external walls, normally provided with an earth
metal protection.
Zone 2: Inside either apartments or rooms from the building.
Zone 3: Equipment, protected by their own metal cover, to be directly protected.Zone 0
Zone 1Zone 2
Zone 3
Equipment
Distributionpanel
Supply
There is a suitable surge arrester type for each zone.
Type 1 High protection. Suitable for incoming supply boards with lighting protection, with wave 10/350µs. Residual voltage up to 4kV.
Zone 1
Type 2 Medium protection. Suitable for incoming supply boards without lighting protection and for secondary distr ibution boards in
general. Residual voltage under 1.5kV. Zone 1 and 2
Type 3 Accurate protection. Suitable for secondary boards located away from the distribution boards that feed them or for Category 1
sensitive equipment, with low insulation level. Zone 2 and 3
7/21/2019 Terasa Ki
http://slidepdf.com/reader/full/terasa-ki 52/56
52
When electrical distribution systems are TT or TN-S (neutral to ground and protection earth to ground), the surge arresters must be equipped with
phase-neutral and neutral-ground protection.
When electrical distribution systems are TN (neutral to ground and protection earth to neutral) or IT (isolated neutral and protection earth to
ground) must be protected, in addition, with phase-ground protection. To install a protection device –MCB or fuse– upstream of the surge arrester is
advisable. At the supply point, the surge arrester must be installed immediately downstream of the main breaker.
Connection of the Terasaki surge arresters range is very simple
because their internal elements are pre-wired.
Surge arrester application
Building with lighting protector or aerial supply incoming
UNDERGROUND SUPPLY
Type 1 Protector (high, 65kA, 4kV)
or Type 2 Protector (medium, 40kA, 1.5kV)
AERIAL SUPPLY
Type 1 Protector (high, 65kA, 4kV)
Building with underground supply and secondarydistribution in several floors
WITH LIGHTING PROTECTOR
SUPPLY BOARDType 1 Protector (high, 65kA, 4kV)
or
Type 2 Protector (medium, 40kA, 1.5kV)
DISTRIBUTION BOARDType 2 Protector (medium, 40kA, 1.5kV)
WITHOUT LIGHTING PROTECTOR
SUPPLY BOARDType 2 Protector (medium, 40kA, 1.5kV)
DISTRIBUTION BOARDType 3 Protector (accurate, 20kA, 1.5kV)
Type 1
TM65 1P. 65kA, 1,2kV, 5ns
TM80 4P. 80kA, 1,2kV, 5ns
TM35SP 1P. 35kA, 4kV, 5ns (wave 10/350µs)
Type 2 TM45 1, 2, 4P. 45kA, 1kV, 5ns
Type 3 TM20 1, 2, 4P. 20kA, 0,96kV, 5ns
Surge arresters TMModular Protection
L / N
GND GND
L / N
TM.....I surge arresters
GDNGDN
L N
L1
N
GDNGDN
N
L1
NL
TM.....II surge arresters
GDN
NL1 L2 L3
L3
N
L2
L1
GDN
L3
L2
L1
N
NL1 L2 L3
TM...IIII surge arresters