This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Število izmenjav zraka n (h-1, “na uro”) običajno za stanovanjske stavbe (brez večjega onesnaževanja) kolikokrat se mora zrak v prostoru ali stavbi zamenjati z zrakom iz okolice vsako uro
stalno: prostori za dnevno bivanje in spalnice 0,5 h-1
Glede na količino zraka, ki je potrebna N osebam v prostoru (m3 na uro); za velikeprostore, javne prostore … tudi za bivalne stavbe
gledališča, koncertne dvorane, kino, ... 20 m3 na osebo in uroposamezne pisarne, čitalnice 30 m3 na osebo in urogostinski lokali 40 m3 na osebo in urovelike, skupne pisarne 50 m3 na osebo in uro
Glede na količino zraka, ki je potrebna glede na vire onesnaževanja. Poznati moramo:
količino posameznega onesnažila, ki jih oddajo ljudje in naprave ali pa se sproščajo v časovni enoti G (kg/h) pri raznih tehnoloških postopkih predvsem za tehnološke prostore, kot so lakirnice, garaže, pralnice in podobno (npr. CO v garažah);
vsebnost onesnažila v zraku v okolici Ce s katerim prezračujemo stavbo (kg/m3; mg/m3)
dovoljeno vsebnost onesnažila (mejno dovoljeno koncentracijo MDK (kg/m3)); to je vsebnost, ki še ne škoduje zdravju ali vpliva na počutje
Glede na občuteno kakovost zraka. Količino onesnažil, s katerimi je onesnažen zrak ocenjujemo z olf-i (latinsko vonjave). 1 olf vonjav oddaja standardna sedeča oseba. Za povezavo kakovosti zraka in jakosti onesnaževanja je bila izbrana enota decipol (dp). En decipol ustreza kvaliteti zraka, če v nek prostor, kjer je vir onesnaževanja 1 olf, dovajamo 10 l/s svežega neonesnaženega zraka.
Sedeča oseba odda pri dihanju vsako uro ~ 25 kg CO2 (25.106 mg/h). V zunanjem zraku je vsebnost CO2 1080 mg/m3. Določite potrebno količino zunanjega zraka za prezračevanje, da vsebnost CO2 ne bo presegla 3000 mg/m3 (glede na navedbe WHO še ne vpliva na počutje in zdravje ljudi:
5 3 3
e
G 25 10 mg m mV 13
MDK C 3000 1080 h mg h
Sedeča oseba, aktivnost 1 -1.2 met 1 olf/oseboSedeča oseba, kadilec 5 olf/oseboKadilec – stalno 25 olf/oseboAtlet 30 olf/osebo
Prezračevanje stavb - mehansko z vračanjem toplote manjše stavbe
1700 W toplote
UN
I LJ, F
A, Tehnolo
gija insta
lacij;
pro
f. S
ašo M
edved
UN
I LJ, F
A, Tehnolo
gija insta
lacij;
pro
f. S
ašo M
edved
Prezračevanje stavb - mehansko z vračanjem toplote manjše stavbe
.
.
.
.
Da bi podaljšali uporabno dobo filtrom je potrebno v sistem vgraditi več filtrov, ki se jim postopoma zvišuje stopnja filtracije. Pozor redna menjava.
EU4/G4 grobi filter za prah (90% sintetičnih delcev);
EU8/F8 fini filter do 95% delcev v zraku, tudi cvetni prah;
HEPA in ULPA filtri se primarno uporabljajo v filtrirnih in klima sistemih, kjer se zahteva absolutno čist zrak (operacijske dvorane in bolnišnice, farmacevtska, laboratoriji; Odstranijo 99,999995% delcev in do velikosti 0,2 do 0,5 mm, torej tudi bakterije in viruse).
Kontrolirano mehansko prezračevanje: IR senzorji prisotnosti ali merilniki vsebnosti CO2 ali vlažnosti zraka
Pred vstopov v prezračevalni sistem lahko zrak predgrejemo (pozimi) ali pred-ohladimo (poleti) v zemeljske prenosniku toplote. Cevni prenosnik dolžine 60 do 80 m premera 120 mm (enodružinska stavba)
Concrete tube ground heat exchanger (U-tube type) with diameter of 800 mm and length 75 m for pre-heating of ventilation air in Shopping centre. Air flow rate 2800 m3/h.
Tubes are mounted under the small angle. This enables cleaning of inner surface and runaway of the (potential) water. Here difference in depth of channel can be notes at the beginning (left) and at the U-turn (right).
This is how the concrete tubes look likes. Two channel are connected in U-tube form.
UN
I LJ, F
A, Tehnolo
gija insta
lacij;
pro
f. S
ašo M
edved
Ground heat exchangers - examples
Ground heat exchanger of Office building. Six parallel polypropylene tubes with length of 35 m and diameter of 315 mm are connected with tube 500 mm in diameter. Special pipes with antibacterial inner layer (AWADUKT) produced by REHAU company are used for sanitary reasons. Configuration was optimized regarding to heat transfer surface area, heat transfer coefficient (air flow rate) and pressure drop (electricity demand for running the ventilator).
Six parallel tubes are connected with connection pipe (here intake side can be seen) and buried 1,5 m bellow finished surface.U
Prezračevanje stavb - senzibilni in latentni hranilniki toplote
Zrak v stavbah vodimo v ceveh ali kanalih8 m/s v glavnih ceveh ali kanalih4 m/s v stranskih kanalih2 m/s v ceveh ali kanalih iz katerih zrak izstopa v prostore
Velikost cevi ali kanalovprostor (delovni prostori) 2 m/s 50 m3/h f 90 mmenodružinska stavba (iz rekuperatorja) 4 m/s 500 m3/h f210 mmdvorana s 500 sedeži (iz klimata) 8 m/s 10000 m3/h f 660 mm
Svež zrak s katerim prezračujemo stavbe mora imeti ustrezno temperaturo:pozimi 22°C (max če tudi ogrevamo: 35 do 40 °C (Ti 20°C)poleti 24°C (min če tudi hladimo16 do 18 °C (Ti 26°C)
Z razporedom vpihovalnih rešetk (difuzorjev), indukcijo (vsrkom) toplega zraka s curkom hladnega, ki ga vpihujemo, moramo preprečiti lokalno toplotno neugodje zaradi previsoke hitrosti in turbulence. Hitrosti zraka v prostorih ne smejo presegati 0,15 do 0,2 m/s.. .
če ni mogoče izvesti naravnega prezračevanja za doseganje IAQ moramo vgraditi sistem hibridnega ali mehanskega prezračevanja.
pri manjših stavbah je potrebno preveriti možnost decentralnega prezračevanja.
ventilatorji (V > 150 m3/h) morajo biti opremljeni z najmanj tristopenjsko regulacijo.
električna moč ventilatorja za dovod svežega zraka mora biti manj kot 0,55 W na m3/h pretoka zraka, odvodnega pa 0,35 W za vsak m3/h.
izkoristek vračanja toplote mora biti vsaj 65%, v nizkoenergijskih stavbah vsaj 75%, pri decentralnih napravah vsaj 50%.
če je prezračevalni sistem namenjen klimatizaciji in priključen na centralno ogrevanje ali daljinsko toploto, je treba uporabiti adiabatsko ovlaževanje s svežo vodo.