Techniques for establishing and Techniques for establishing and maintaining constant temperature in maintaining constant temperature in ICT systems in order to reduce ICT systems in order to reduce energy consumption energy consumption Mihail Radu C ătălin Truşcă , Ş. Albert, F. Fărcaş, M.L. Soran 1 National Institute for Research & Development of Isotopic and Molecular Technologies, e-mail: [email protected] INCDTIM
18

Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Dec 25, 2015

Download

Documents

Cory Gregory
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Techniques for establishing and maintaining Techniques for establishing and maintaining constant temperature in ICT systems in constant temperature in ICT systems in

order to reduce energy consumptionorder to reduce energy consumption

Mihail Radu Cătălin Truşcă,

Ş. Albert, F. Fărcaş, M.L. Soran

1National Institute for Research & Development of Isotopic and Molecular Technologies, e-mail: [email protected]

INCDTIM

Page 2: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Aim of work

Developping additional methods to monitor the operation of air conditioning equipments to prevent some damages that could occur in the cooling system, possible intervention can be so much faster and avoid the appearance of the defects.

For what do we need this monitoring system??

Monitoring and maintaining constant temperature in ICT systems in order to reduce energy consumption.

Page 3: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

3

Research teams in INCDTIM• Physics of multifunctional nanostructure

systems

• Isotope separation and labeled compounds

• Mass spectrometry, chromatography and ion physics– High-Tech Engineering in ATLAS experiment at LHC

Cern Geneva

• Molecular and Biomolecular physics– Numerical Modeling

– Structural Analysis in Solids

– Self-Assembled Molecular and Biomolecular Systems

INCDTIM

Page 4: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

4

INCDTIM Datacenter• Grid site RO-14-ITIM

– Core 250, Storage capacity: 100 TB, Technology 1U + Blade system (IBM & HP)

• MPI Cluster– 400 Core, 96 GB / Computer, 450 GB HDD

• Network Institute – Database server– Communication Server– Full functional Cisco system

INCDTIM

Page 5: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

5

Network abilities

• Switch Cisco 6509E

• ITIM – RoEduNet 10 GB from 1 Feb. 2011

• Nexus system– ~40 GB inside the Grid site– ~20 GB between Grid Site and Switch

INCDTIM

Page 6: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Practical implementation

The user frequency in the range [0.1 ... 60] second of the three monitored parameters for each component on controlled system.

The followed parameters: voltage power supply of the cooling units; temperature of the heat transfer of heat exchange circuit; state of rotation of the main outside fans that serves the unit, with their propeller motion detection.

The monitoring system obtained in this work, it will be applied in monitoring of the datacenter from INCDTIM

INCDTIM

Page 7: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

“Hardware” part

An electronic board with its "firmware" called "AVR_NET_IO"

A microcontroller ATmega32 type and completed with an adaptation electronic circuit needed to connect sensors.

Development board with eight digital outputs, four digital inputs and four analog inputs.

INCDTIM

Page 8: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

AVR_NET_IO electronic board

INCDTIM

Page 9: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Schema of the adaptation circuit

INCDTIM

Page 10: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

“Software” part

The virtual device is implemented in software, with a graphic interface, designed to:- read the watched parameters values- generates an alarm in case it is identified this need.- simulates the operation of warning lights panel on the display, - implements 2 mechanism: an abort command or trigger an alarm by authorized users.

Development board communicates with a computer by Ethernet connection

INCDTIM

Page 11: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

The program:

- generates commands for data acquisition from sensors attached; - control execution device that relays control panel display or digital multiplexer.

Graphic interface

INCDTIM

Page 12: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Refrigerant temperature at the inlet and outlet of the cooling unit, in two different days

29.04.2012

30.04.2012

INCDTIM

Page 13: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

_____ T1 (h = 2.20 m)_____ T2 (h = 1.80 m)_____ T3 (h = 1.30 m)_____ T4 (h = 0.50 m)

_____ T1 (h = 2.20 m)_____ T2 (h = 1.80 m)_____ T3 (h = 1.30 m)_____ T4 (h = 0.50 m) Ambient temperature

variation in Datacenter

INCDTIM

Page 14: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Test periods for reducing energy consumption

INCDTIM

Page 15: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

CONCLUSIONS The parameters controlled by complex automation system, will be adjusted to acceptable values while working even for relatively short periods of time. It is possible to detect the problems in the functioning of the cooling devices, with at least 10 minutes before recording by automatic fault protection thereof.

The alarm starts when the temperature is with minimum 3C above or below to established working range or / and fan damage.

Detect situations where the system works with some of the parameters changed significantly from the normal will help to easier system maintenance and ensure improved safety in operation.

INCDTIM

Page 16: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Refrigerant temperature increase especially at the outlet of the cooling unit, during normal working hours, when multiple tasks are launched.

In the future, in order to reduce the energy consumption we intend to stop some air conditioning systems and follow the variation of temperature at different times of day.

ACKNOWLEDGEMENTS

This work is supported by the Romanian Research and Development Agency through EU12/2009, EU15/2009, TE-76/2011 projects, and the development of the datacenter monitoring capabilities

Page 17: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Conference Invitation• INCDTIM is organizing between the 25-27

October 2012 the Fifth Romania Tier 2 Federation "Grid, Cloud & High Performance Computing Science" - RO-LCG Conference

• http://www.itim-cj.ro/rolcg2012

• Under the Regis of: IEEE Romania Section– Full paper submission: 15.08.2012– Notification of acceptance: 1.09.2012– Camera ready papers: 15.09.2012

17

Page 18: Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,

Thank you for your attention !