Technical Review No.2·1988

Quantifying Draught Risk

Bruel & Kjcer +-

Page 2: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Previously issued numbers of Brtiel & Kjrer Technical Review 1-1988 Using Experimental Modal Analysis to Simulate Structural Dynamic

Modifications Use of Opej."ational Deflection Shapes for Noise Control of Discrete Tones

4-1987 Windows to FFT Analysis (Part II). Acoustic Calibrator for Intensity Measurement Systems

3-1987 Windows to FFT Analysis (Part I) 2-1987 Recent Developments in Accelerometer Design

Trends in Accelerometer Calibration 1-1987 Vibration Monitoring of Machines 4-1986 Field Measurements of Sound Insulation with a Battery-Operated

Intensity Analyzer Pressure Microphones for Intensity Measurements with Significantly Improved Phase Properties Measurement of Acoustical Distance between Intensity Probe Microphones Wind and Turbulence Noise of Turbulence Screen, Nose Cone and Sound Intensity Probe with Wind Screen

3-1986 A Method of Determining the Modal Frequencies of Structures with Coupled Modes Improvement to Monoreference Modal Data by Adding an Oblique Degree of Freedom for the Reference

2-1986 Quality in Spectral Match of Photometric Transducers Guide to Lighting of Urban Areas

1-1986 Environmental Noise Measurements 4-1985 Validity of Intensity Measurements in Partially Diffuse Sound Field

Influence of Tripods and Microphone Clips on the Frequency Response of Microphones

3-1985 The Modulation Transfer Function in Room Acoustics RASTI: A Tool for Evaluating Auditoria

2-1985 Heat Stress A New Thermal Anemometer Probe for Indoor Air Velocity Measurements

1-1985 Local Thermal Discomfort 4-1984 Methods for the Calculation of Contrast

Proper Use of Weighting Functions for Impact Testing Computer Data Acquisition from Brtiel & Kjrer Digital Frequency Analyzers 2131/2134 Using their Memory as a Buffer

3-1984 The Hilbert Transform Microphone System for Extremely Low Sound Levels Averaging Times of Level Recorder 2317

2-1984 Dual Channel FFT Analysis (Part II) 1-1984 Dual Channel FFT Analysis (Part I) 4-1983 Sound Level Meters- The Atlantic Divide

Design principles for Integrating Sound Level Meters

(Continued on cover page 3)

Page 3: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Technical Review

No.2 · 1988

Page 4: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)
Page 5: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Contents Quantifying Draught Risk by Arsen K. Melikov, Ph.D.

1

Page 6: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)
Page 7: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Quantifying Draught Risk By Arsen K. Melikou, Ph.D.

Abstract

Draught, defined as an unwanted local cooling of the human body caused by air movement, is one of the most common causes of complaints in venti­lated or air-conditioned spaces. The high ventilation rate required to es­tablish acceptable air quality, often leads to uncomfortably high air velocities.

Because of the high level of pollution in modern buildings, caused by increased internal loads from office machines (computers, printers, etc.), there will be an ever increasing demand for higher ventilation rates.

In most existing standards the requirements for the air velocity in a room are based on the mean air velocity limit, which depends on the exist­ing air temperature. New draught studies show, however, that high turbu­lent air flow causes more complaints of draught than low turbulent air flow at the same mean air velocity and temperature. Many field studies show that turbulence intensity in rooms varies from 10-70%, indicating that it should be taken into account during revision of the existing stan­dards. This paper discusses how to deal with the draught problem, and describes the measurements necessary for estimating draught risk.

Sommaire

Les refroidissements localises et indesires du corps par mouvement d'air sont l'une des plus frequentes causes de plainte dans les locaux ventiles ou avec air conditionne. Le taux de renouvellement de l'air, qui doit etre eleve pour maintenir une atmosphere de qualite suffisante, se traduit souvent par une vitesse de l'air trop elevee pour etre confortable.

1

Page 8: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

De nos jours, les sources de pollution (ordinateurs, imprimantes, etc.) sont de plus en plus nombreuses dans les bureaux et le taux de renouvelle­ment de l'air ne peut qu'aller en s'accroissant.

La plupart des normes actuelles portant sur la vitesse de l'air dans un local definissent sa vitesse moyenne limite en fonction de la temperature ambiante. Cependant, des etudes ont maintenant montre que pour une meme temperature et vitesse moyenne de l'air, un flux d'air tres turbulent provoque plus de plaintes qu'un flux d'air peu turbulent. L'etude de nom­breux cas pratiques montre que l'intensite de la turbulence dans des lo­caux varie de 10 a 70%, et que celle-ci devrait done etre prise en compte lors de la revision des normes existantes. Cet article indique comment traiter le probleme des courants d'air, et decrit les mesures necessaires pour estimer le risque de courant d'air.

Zusammenfassung

Zugluft, d.h. die unbeabsichtigte Ausktihlung des menschlichen Korpers an einzelnen Korperteilen durch Bewegung der Luft, ftihrt haufig zu Be­schwerden in Raumen mit Ventilation oder Klimaanlagen. Urn eine ak­zeptable Luftqualitat zu erreichen ist eine hohe Ventilationsrate erforder­lich, die wiederum oft unangenehm hohe Luftgeschwindigkeiten bewirkt.

Die Luft in modernen Gebauden wird immer starker durch Btiroma­schinen wie Rechner, Drucker usw. belastet, so dai3 immer hohere Ventila­tionsraten notwendig werden.

In den meisten gegenwartig vorhandenen Richtlinien und Normen ba­sieren die Anforderungen an die Luftgeschwindigkeit in einem Raum auf einem gemittelten Luftgeschwindigkeitsgrenzwert, der von der Raum­temperatur abhangt. Untersuchungen zur Zugluft haben nun gezeigt, dai3 bei gleicher mittlerer Luftgeschwindigkeit und Temperatur Luftstrome mit hohen Turbulenzen eher als Zugluft empfunden werden als Luftstro­me mit geringen Turbulenzen. In Untersuchungen vor Ort ist festgestellt worden, daf3 die Intensitat von Turbulenzen in Raumen zwischen 10-70% variiert. Diese Intensitat von Turbulenzen sollte daher auch schon bei den existierenden Richtwerten beachtet werden. Dieser Artikel untersucht, wie mit dem Problem der Zugluft umzugehen ist, und be­schreibt, mit welchen Mef3methoden die Wahrscheinlichkeit von Zugluft eingeschatzt wird.

2

Page 9: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Introduction Draught is defined as unwanted local cooling ofthe human body caused by air movement. It is a serious problem in ventilated or air-conditioned buildings, automobiles, trains and airplanes. Draught has been identified as one of the two most annoying environmental factors in workplaces and the most annoying factor in offices (Bolinder et al [1], Arbejdsmilj0grup­pen [2]). It may even cause people to stop ventilation systems or to plug up air diffusers. Serious draught complaints often occur despite measured ve­locities being within limits prescribed in existing standards. This is frus­trating for the ventilation engineer and a threat to the image of the venti­lation and air conditioning industry in general. In heated rooms without mechanical ventilation, draught may be caused by convective air currents along windows and other cold surfaces providing air-movement in the oc­cupied zone. In rooms where there are draught problems the occupants may increase the air temperature to counteract the draught, normally dur­ing the winter, and this will increase the energy consumption. Only one degree higher air temperature costs typically 5- 15% more energy.

The general thermal comfort concept and the local thermal discomfort has been discussed by Fanger [3, 4, 5, 6] and in earlier Technical Reviews by Olesen [7, 8]. In the following only the local discomfort caused by local con­vective cooling, namely draught, and how to measure and estimate the draught risk in spaces will be discussed.

Air flow in the occupied zone of rooms Typically the airflow in rooms is turbulent, e.g. velocity fluctuates ran­domly (Fig. 1). The turbulent airflow in the spaces may be characterized by the following magnitudes:

The instantaneous velocity, v = u + v', which is assumed to be the sum of the mean velocity, u, and the velocity fluctuations, v ', in the main direction of the flow. The mean velocity, v, is the average of the in­stantaneous velocity, v, over an interval of time, t 1

vdt m/s (1)

The bar denotes averaging over time.

3

Page 10: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

m/s ~---------------------------------------------------,

Mean Velocity v = 0,16 m/s Standard Deviation SD, = 0,05 m/s

0,40 Turbulence Intensity Tu = S~, · 100 = 0•05 · 100 = 31% v 0,16

€ 0,30 0

§!

0,20

0,10

0 2 4 6 8 1 0 12 14 16 18 20 22 24 26

Time

Fig. I. Record of instantaneous velocity in the occupied zone

871867

The standard deviation of the velocity, equal to the Root-Mean­

Square (RMS) of the velocity fluctuation, ~. provides information on the average magnitude of the velocity fluctuation over an interval of time.

The turbulence intensity, Tu, is the standard deviation divided by the mean velocity

Tu = V u'2 --=--. 100%

u

The energy spectrum of the velocity fluctuations

(2)

(3)

shows the density of distribution of iJ'2 in the range of frequencies, n. E ( n) is known as the spectral distribution function of iJ'2. It is often convenient (Hinze [9]) to consider the wave number k = 2 1r n /u instead of the frequency n and to introduce the energy spectrum function E ( k) instead of E(n). It appears suitable to define E(k) by

4

Page 11: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

u E(k) = 27r E(n) (4)

so that

(5)

which is similar to equation 3. It is possible to present the energy spectra, E ( k) /u72 = f( k ), as they are relatively independent of the mean velocity.

The eulerian integral time scale, T £, measures the longest connection of the turbulent behaviour of u '. It may be calculated from E ( n) when n approaches zero (Hinze [9]):

TE= E(n) 4 u f2

s (6)

Air flow in the occupied zone of rooms has been examined in several field studies [10, 11, 12, 13, 14, 15, 16, 17]. During some of the field studies [11, 12, 13, 16] and the draught study [25, 26] Brtiel & Kjrer Indoor Climate Analyzer 1213 was used extensively together with other instruments for measuring mean air velocity, standard deviation of the velocity, air tem­perature and radiant temperature asymmetry. Air velocity transducer MM 0038, temperature transducer MM 0034 and radiant temperature asymmetry transducer MM 0036 were used. The instrument and the sen­sors are described and discussed in [ 42, 43].

The Indoor Climate Analyzer Type 1213 and the Velocity Sensor MM 0038 were used for energy spectra measurements (Figs. 5, 6, 15). Dur­ing the measurements [12, 16, 26] the analog signal from the Indoor Cli­mate Analyzer was recorded on a tape recorder (B & K Type 7005) and later analyzed by B & K Dual Channel Signal Analyzer Type 2032. The energy spectra were used to calculate the integral time constant (Fig. 7) and some other turbulent characteristics of the airflow described in [12, 16]. Fig. 2 shows a diagram of the measuring and calculating equip­ment used.

A wide range of typical ventilated spaces [10, 11, 12, 13, 14, 15] and heat­ed rooms without mechanical ventilation [13, 16, 17] were included in these

5

Page 12: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Air Velocity

Air Temp.

Tape Recorder 7005

Radiant Temp.

Indoor Climate Analyzer

1213 ,_ Dual Channel Signal

Analyzer 2032

Tape Recorder 7005

-u

880084

Fig. 2. B & K instruments used for registration and analysis of the airflow characteris­tics during field studied [12, 16] and draught study [26]

field studies. The ventilated spaces were selected to cover typical loca­tions, types of outlets and exhaust devices. The heated rooms without me­chanical ventilation had different heating methods - floor and ceiling heating, as well as heating by radiators, convectors and skirting board. Rooms with a variery of window areas were investigated. This parameter is important because during the winter natural convective air currents down windows may create considerable velocities in the occupied zone. Mean velocity up to 0,4m/s and turbulence intensity from less than 10% to 70% were measured. Some results from the field study [12, 16] are shown in Fig. 3 (a and b). The figure compares a percentage distribution of the mean velocity and the turbulence intensity measured at two heights - 0,1 m and 1,1 m above the floor in spaces with and without mechanical ventilation. According to the ISO Standard 7726 [18] for sedentary person these two heights correspond to the feet and head level. Both the mean velocity and the turbulence intensity were lower in heated rooms without mechanical ventilation than in ventilated spaces. Relatively high veloci-

6

Page 13: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

% %1--

60 60 Level 1,1m Level 1,1m

1--40 40

~

20 20 -n-,_, ...........

0 0 0 0,1 0,2 0,3 0,4 m/s 0 0,1 0,2 0,3 m/s

% % r--

40 Level 0,1m 40 r--

Level 0,1m

~

20 ~

h 20

I--

0 h

0 0 0,1 0,2 0,3 0,4 m/s 0 0,1 0,2 0,3 m/s

Mean Air Velocity-Ventilated Spaces Mean Air Velocity-Unventilated Spaces Hanzawa et.al. [12] Melikov et.al. [16] 871874

% %

40 40 Level 1,1m

20

0 0 20 40 60 % 20 40 60 %

%

40 Level 0,1m Level 0,1m

20

0 0 20 40 60 % 20 40 60 %

Turbulence Intensity-Ventilated Spaces Turbulence Intensity-Unventilated Spaces Hanzawa et.al. [12] Melikov et.al. [16]

871876

Fig. 3. a) Histograms of the mean velocity (v) and b) turbulence intensity (Tu) in venti­lated spaces and heated rooms without mechanical ventilation (unventilated spaces)

7

Page 14: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

\ Hanzawa et.al [12] } Ventilated Spaces 60 --- Thorshauge [10]

% \ ---- Melikov et.al. [16] Unventilated Spaces

z. 50 \ "iii Level 0,1 m <:::

" \ ~

" \ " 40 <:::

" :; .c :; \ ,_

\\ 30

\ ....... \

20 "'-..... -----........ ---------------10

0 0,1 0,2 0,3 0,4 m/s

Mean Air Velocity

70

\ %

60 \

\ \ Level 1,1 m z. 50

\ "iii <:::

" ~ \ " \ ' " 40

~' <:::

" "\-___ :; -e " > ,_ \ ............... _

30 ' ....... , ------------20

10L-----~--~---~--~-----o 0,1 0,2 0,3 0,4 m/s

Mean Air Velocity 880649

Fig. 4. Relationship between turbulence intensity (Tu) and mean velocity (v) in venti­lated spaces and heated rooms without mechanical ventilation (unventilated spaces)

8

Page 15: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

c: 0

~ c:

" LJ._

c: .!2 ::; .0

~ iS

~ 0 "' 0. en

m

10-1

10-'

10-3

10_,

&/. %.,

• 0 "~ +

... ~ +k+ ~ ~~ ·~

8 v = 0,068 m/s, T" = 56,0% x v = 0,119 m/s, T, = 29,4% + v = 0,215 m/s, T, = 22,7%

* v = 0,144 m/s, T, = 24,3% o v = 0,134 m/s, T, = 37,3% • v = 0,240 m/s, T" = 23,3%

X 8+

~ "t

Unventilated Spaces Melikov et.al. [16]

Ventilated Spaces Hanzawa et.al [12]

0,1 m Above Floor

10-5 ,_ ________________________________________________________ __,

10-1 10

Wave Number 102 m-1

871880

Fig. 5. a. Energy spectra measured at ankle level (0,1 m above floor). Vertical axis repre­sents E(k) I v'2

ties (up to 0,25 m/s) were measured near to "the floor (0,1 m) in heated rooms with large windows and insufficient heat sources under the windows.

Although the turbulence intensity varied in wide ranges, it was found to decrease when the mean velocity increased. Fig. 4 compares this relation-

9

Page 16: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

c: g ti c: ::> "-c: .S! :; .0

~ i5

e ti (l) c. rn

m ,-----------------------------------------------------------,

10-1

10-2

10-3

10-"' .6. v = 0,115 m/s, T, = 42,4% } X v = 0,889 m/s, T, = 55,1% + v = 0,075 m/s, T, = 52,0%

1f v = 0,172 m/s, T, = 35,0% o v = 0,106 m/s, T, = 49,1% • v = 0,129 m/s, T, = 25,6% }

Unventilated Spaces Melikov et.al. [16]

Ventilated Spaces Hanzawa et.al [12]

1,1 m Above Floor

10-'+--------------.--------------.--------------.------------~

10 102

Wave Number 871881

Fig. 5. b. Energy spectra measured at head level (I, I m above floor). Vertical axis repre­sents E(k) I v'2

ship measured in ventilated spaces and heated rooms without mechanical ventilation at two heights- 0,1 m and 1,1 m above the floor. The results are from [12, 16].

The mean velocity and the turbulence intensity are not sufficient to characterize the nature of the air flow in the spaces. It is possible to find

10

Page 17: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

c .!2 u c " LL

c . !2 :; "" ·;:

'"

Sec x

1 -

i5 10-1

~ u Q) Q.

"'

10-2

X

X

X X

• • ••

10-1

X

X

X X

X

X x><x

X • "x

• 0 ••• 0 • • • •

Frequency

• Laminar Flow

x Turbulent Flow

• • •

• • X • •••• • • X • • X • ••

X •• •

X • XX

X

X X

X

XX XX

xxx X X

X

X

Hz 871920

Fig. 6. Comparison of energy spectra measured in laminar and turbulent flow. Vertical axis represents E(n) I v'2

two turbulent flows with the same mean velocity and turbulence intensity but with different frequencies of the velocity fluctuations. Therefore it is important to know the energy spectra of the velocity fluctuations. The energy spectra measured in ventilated rooms and heated rooms without mechanical ventilation are shown in Fig. 5 (a and b). The spectra curves do not indicate an energy concentration at any specific region of the spectra. The spectrum curves for the points 1,1 m above the floor follow "-5/3" law rather closely, while near the floor (Fig. 5 a) turbulent energy varies al-

11

Page 18: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

3,0

2,0

1,0

0

' ' .......

--- Ventilated Rooms

---- Unventilated Rooms

0,1 m Above Floor

....... __ ----------

0,1 0,2 0,3 m/s

Mean Air Velocity 871878

Fig. 7. Eulerian integral time scale as a function of the mean velocity

most according to k -l, thus indicating strong interaction between mean and turbulent flow [9]. Fig. 6 shows how different the spectral distribution of the turbulent energy is in the case of turbulent and laminar flows. The spectrum for the laminar flow was measured in a clean room. In the case of the laminar flow, the energy distribution remains at a low but approxi­mately constant value over a wide range of frequencies.

The integral time scale was found to be bigger in ventilated rooms than in heated rooms without mechanical ventilation (Fig. 7). It decreases as mean velocity increases.

Draught Studies There are a few draught studies available. Hough ten [19] studied ten male subjects exposed to a non-fluctuating, local velocity at the back of the neck and at the ankles. He found less than 10% dissatisfied at mean veloc­ity 0,3 m/s. Mcintyre [20] used a similar method where he exposed the head region of subjects to a nearly laminar airflow. At an air temperature of 21 oc and velocities up to 0,2 m/s no discomfort was registered. Howev­er, as discussed previously, the airflow in ventilated spaces typically is not laminar but turbulent, i.e. velocity fluctuates. Fanger and Pedersen [21] have shown that periodically fluctuating airflow is more uncomfortable than non-fluctuating (laminar) airflow. In a climate chamber sixteen sed­entary subjects (8 females and 8 males) were exposed at the back of the neck to a horizontal airflow with well defined periodic velocity fluctua-

12

Page 19: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

1,2

Uncomfortable 1,0

0,8

0,6

0,4

0,2

Not Uncomfortable 0

0,00625 0,025 0,1 0,2 0,4 0,8 Hz

Frequency 871866

Fig. 8. Mean values of the degree of discomfort expressed by 16 subjects being exposed to a fluctuating airflow as a function of the frequency. Mean velocity: 0,3 m/s. Constant stan­dard deviation 0,23 m!s

tions. The mean velocity and the amplitude of the velocity fluctuations were kept constant (i.e. the turbulence intensity) but the frequency of the velocity fluctuations was changed. The temperature of the airflow was close to the air temperature in the climate chamber which was kept at a level preferred by each individual subject (determined in a pre-test). They found that discomfort had a maximum at velocity frequencies around 0,3- 0,5 Hz (Fig. 8).

Fanger and Christensen [22] exposed 100 subjects to air velocities with fluctuations believed to be typical for ventilated spaces in practice. During their experiments the mean velocity was varied from 0,05 m/s to 0,4 m/s at air temperatures of 20, 23 and 26°C. They presented the results in a draught chart predicting the percentage of dissatisfied occupants as a function of mean velocity and air temperature (Fig. 9). The percentage may either be determined graphically from the draught chart or calculat­ed by the regression equation:

PD = 13800 [ ( ~-=-~'~,~ + 0,0293 )2 - 0,000857] (7)

The head region was found to be the most draught-sensitive part of the body for persons wearing normal indoor clothing. No significant differ­ences were found between the draught sensitivity of men and women.

13

Page 20: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

< c: ro

m/s

0,5

0,4

0,3

~ 0,2

0,1

Draught chart

Percentage of dissatisfied (PD) due to draught in ventilated spaces.

0%

a~-.-----.-----.-----.-----.-----.-----.----.-----.---~ 19 20 21 22 23 24 25 26 27

Air Temperature (t,) 872114

Fig. 9. Percentage of dissatisfied due to draught as a function of mean velocity and air temperature, Fanger and Christensen [22]

Berglund and Fobelets [23] made a study with 50 subjects. In their ex­periments the subjects were exposed to turbulent airflow approximately in the same range of mean velocities (0,05- 0,5 m/s) as in Fanger's and Christensen's study. Fig. 10 shows the results from this study. The per­centage experiencing draught is given by the equation:

PED = 113 ( v- 0,05) - 2,15 ta + 46 (8)

The comparison between the two studies (Fig. 11) shows higher per­centage of dissatisfaction in Fanger's and Christensen's study. The ques­tionaires and procedures were different in the two studies. An important difference was the turbulence intensity. In both experiments the turbu­lence intensity was decreasing when the mean velocity was increasing, but in Fanger's and Christensen's study it was between 65% and 30% while in the study of Berglund and Fobelets it was approximately from 40% down to 5%. Fig. 11 also shows the results from a draught study performed by Tanabe [24]. They register a significantly lower percentage of dissatisfied.

14

Page 21: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

%

0 20" c: Q)

E Q) > 0 60 ::;;

;;: 2 Q) ::J 0

.E 40 Ol ::J

"' 0 "' Ol c:

·c:; c: Q) 20 -~ c. X w

0 0,1 0,2 0,3 0,4 0,5 m/s

Nominal Air Velocity 812124

Fig. 10. Percentage of subjects experiencing draught (dissatisfied) as a function of nomi­nal air speed (mean velocity) and temperature, Berglund and Fobelets [23]

"0 .!! Ui ~ "' "' 0

%

60

40

20

0 0,1

Fanger & Christensen [22]

Berglund & Fobelets [23] Tanabe [24]

0,2 0,3

Mean Air Velocity

0,4 0,5 m/s

872126

Fig. II. Comparison of dissatisfied due to draught from different draught studies

15

Page 22: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Z;-·c:; 0 a; > ~ c:

"' C1> ::;:

m/s ---- Houghten [19[ -- - Fanger & Christensen [22] - · - · Berglund & Fobelets [23]

0,31-

0,2

-·--·--· --·----,

Air Temperature 21 "C 1 0% Dissatisfied

0,1 -- ------~---- ---, I

l i 0 10 20 30 40 50 60

Turbulence Intensity

%

872127

Fig. 12. Mean air velocity limits for 10% dissatisfied due to draught/constant air tem­perature 21°C) from different draught studies

The turbulence intensity during Fanger's and Christensen's and Tanabe's experiments (air temperature 26°C) was in the same range 55-30%. The clo value of the subjects' clothing was almost the same 0,58 and 0,6 respectively.

Fanger and Christensen [22] and Berglund and Fobelets [23] identified a much higher rate of dissatisfaction than previous draught studies of Houghten [19] and Mcintyre [20] (Fig. 12). The reason is most likely the differences in the turbulence intensity. In Houghten's and Mcintyre's studies the subjects were exposed to a low-turbulent airflow from a jet. Mcintyre measured the turbulence intensity to be 3%. As previously dis­cussed, the turbulence intensity is much higher in ventilated spaces.

The impact of the turbulence intensity on the sensation of draught has been investigated recently by Fanger et al. [25, 26]. Fifty subjects, dressed to obtain a neutral thermal sensation, were exposed to airflows with three different levels of turbulence intensity. The subjects were exposed to in­creasing mean velocity ranging from 0,05 m/s up to 0,40 m/s. Each subject was studied during three experiments at low turbulence ( Tu < 12%), at medium turbulence (20% < Tu < 35%) and at high turbulence (Tu >55%). The turbulence intensity range was selected to be the same

16

Page 23: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

~ ::f ""'"m '"''"'0"" ~

~ ~:;~f·~·~·::::-~~ ... _:_'A.:..:_,J.::_,.r.._:_,..!:'fir'V"J~· ::_'"_:"YY_·,.e_"i_"_~JJ_v_"_J'..Y_'*_.N._.""_'_""_~_J/1_~_~_~_~ ___ .. __

0,4~ Low Turbulence 0,3 0,2

0,1 ----0~

t ,.... .............

[c 5,5 min ,.[ Time

871869

Fig. 13. Samples of velocity fluctuations at six mean air velocities and three different turbulences

as measured in a normal office situation (Fig. 3 b). Fig. 13 shows typical samples of instantaneous velocity recorded during the draught study.

An important aim of these experiments was to expose the subjects to an airflow with the same nature as encountered in daily life. Instantaneous velocity recorded during the field measurements [12] and the draught ex­periments [26] are compared in Fig. 14. The samples are chosen from mea­surements with approximately the same mean velocity and turbulence in­tensity. Energy spectra of the velocity fluctuations for the three levels of turbulence intensity are compared in Fig. 15 (a, b, c). The comparisons in­dicate that the nature of the airflow during the draught experiments was the same as those found in practice. The air temperature was kept con­stant at 23°C. The subjects were asked whether and where they could feel air movement and whether or not it felt uncomfortable. As in [22] the head region which comprises the head, the neck and the shoulders was found to be the most draught sensitive part of the body.

Fig. 16 shows the percentage of subjects who felt draught at the head region as a function of the mean velocity at the neck. The results from

17

Page 24: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Draught experiment- v, = 0,40 m/s, T, = 9,2%

Ventilated room - Va = 0,37 m/s, T u = 4,3%

Draught experiment- Va = 0,14 m/s, Tu = 24%

Ventilated room - v, = 0,14 m/s, T, = 24,4%

Draught experiment - v, = 0,20 m/s, T, = 56,8%

Ventilated room - V8 = 0,20 m/s, T u = 61,5% 871877

Fig. 14. Records of instantaneous velocity at three levels of turbulence intensity. Figure compares records in ventilated spaces and draught study [26] at the same mean air velocity

18

Page 25: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

m

c: .S! j:j 10-2 :::>

u_

c: g 5 .c

~ Ci

~ ti "' fJi 10-3

Low Turbulence

)(.. v = 0,370 m/s, T, = 4,3%

o v = 0,407 m/s, T, = 9,3% D. v = 0,401 m/s, T, = 9,2% • v = 0,402 m/s, T" = 9,2%

Ventilated Space Hanzawa et.al. (12]

Draught Experiment Fanger et.al. [26]

1o-s +-------------~------------~------------~--------------10

Wave Number

102 m-'

872120

Fig. 15. a. Low turbulence airflow. Comparison of spectra of the velocity fluctuations measured by Fanger et. al. [26] during their draught study and in ventilated spaces measured by Hanzawa et. al. [12]. (See Fig. 15.a)

Fanger's and Christensen's draught study [22] are plotted as well. The lines in Fig. 16 are based on a pro bit analysis [27] of the percentage of sub­jects feeling draught versus the square root of the mean velocity. The

19

Page 26: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

m .-----------------------------------------------------------,

g 10-2

~ c

" LL.

c .~ "5 :§ u; i5 -e ~ 10-3

c. (/}

10-4 Medium Turbulence

>f ii = 0,294 m/s, T, = 32,0%

0 v = 0,308 m/s, T, = 22,1% ~ ii = 0,305 m/s, T, = 20,7% • v = 0,304 m/s, T, = 20,4% J. v = 0,301 m/s, T, = 22,6%

Ventilated Space Hanzawa et.al. (12]

Draught Experiment Fanger et.al. (26]

10-5 ~-------------,----L---------.--------------.--------------1 10 102

Wave Number 872121

Fig. 15. b. Medium turbulence airflow. Comparison of spectra of the velocity fluctuations measured by Fanger et. al. [26] during their draught study and in ventilated spaces measured by Hanzawa et. al. [12]. (See Fig. 15.a.)

square root was selected since heat transfer by forced convection is ap­proximately proportional to the square root of the mean velocity. The tur­bulence intensity had a significant impact on the occurrence of draught sensation.

20

Page 27: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

m

!?.

"' ~ lf-

10-1 11ft,..

61'. lf-o. ~ ~ ~ lf-~i~

c 00~

0 10-2 ~ c .. ~ ~

" LL 0 ~ c

f!>.J .!2 .¥ ... :; • .0

~ • i5 "-R• Iii .~tvf ti 10-3 Ql

o•~; ~ c. en

oo~ -~

• o• 10-4 High Turbulence ~

... v = 0,140 m/s, T, = 53,6% } Ventilated Space Hanzawa et.al. [12]

0 v = 0,155 m/s, T, = 54,8%

} A v = 0,152 m/s, T, = 53,9% Draught Experiment

• v = 0,157 m/s, T, =.56,1% Fanger et.al. [26]

"' v = 0,141 m/s, T, =· 46,1%

10-5

10-1 10 102 m·1

Wave Number 872122

Fig. 15. c. High turbulence airflow. Comparison of spectra of the velocity fluctuations measured by Fanger et. al. [26] during their draught study and in ventilated spaces measured by Hanzawa et. al. [12]. (See Fig. 15.a.)

Many subjects were able to sense air movements even at low velocities. As expected, the number of subjects sensing air movement increased with the mean velocity but surprisingly in [22] there was no influence from the air temperature. On the contrary the turbulence intensity was found to

21

Page 28: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

%

o ---Low Turbulence Intensity (T" < 12%) 0 ---- Medium Turbulence Intensity (20% < T" < 35%)

90 A - ·- High Turbulence Intensity (T" > 55%) --.,.---Fanger and Christensen, [22] (35% < T" <55%)

80

60

"C

-~ <;; 40

~ "' "' i5

20

10

5

0,1

0 0,05 0,1 0,2 0,3 0,4 0,5 m/s

Mean Air Velocity 872115

Fig. 16. Percentage of dissatisfied people due to draught at the head region as a function of the mean air velocity at three levels of turbulence intensity

have significant impact on the percentage of people sensing air movement [26]. Airflow with high turbulence intensity was sensed by more people than airflow with low turbulence intensity. Fig. 17 shows a relationship between percentage dissatisfied due to draught and percentage sensing the air movement at the same mean velocity, turbulence intensity and temperature.

More airflow fluctuations: more draught complaints -why? Fanger and Pedersen [21] found that periodically fluctuating airflow with frequencies 0,3 - 0,5 Hz are the most undesirable for the draught feeling (Fig. 8). The impact of a periodically fluctuating airflow on human being's cooling sensation was also registered by Assakai and Sakai [28].

22

Page 29: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

%

60

40

20

0 20 40 60 80 %

Sensing air movement 872128

Fig. 17. Relationship between percentage dissatisfied due to draught and percentage sensing air movement at the same mean air velocity and turbulence intensity

In a test chamber human beings were exposed to a constant airflow with the velocity at which they felt most comfortable. At the beginning the cooling sensation was evaluated as 3 on a 5 point scale. After five minutes the evaluation showed that the cooling sensation decreased to 2,6 due to adaptability of the human body with time. After that the subjects were exposed at the same airflow but pulsating. They could choose the most agreeable pulsating cycle. Evaluation at the beginning and after five min­utes indicated that the cooling effect increased with time up to 3,3. The pulsation cycle determined to be most comfortable was about 1,2 Hz. Fig. 18 demonstrates these results. The impact of periodically and ran­domly fluctuating air movement on man's thermal sensation and feeling of draught at different thermal conditions has been studied recently by Tan­abe [24]. As in previous studies it was found that fluctuating airflow had stronger impact on subjective thermal sensation and feeling of draught than non-fluctuating airflow.

Hensel [29] has studied and described the reaction of the skin and the thermoreceptors located at different layers below the skin surface to dif-

23

Page 30: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Cl .!: 0 0

" c "Ci c.

" .e 1ii " (ij > lU

5 With

pulsation

Q) Cl

"' c - Q)

" :;; Q.

0 ~-2~0~~40--~6~0----------~~2~0--4~0~~60' Percentage (%) Percentage (%)

0 3 4

Passage of time (Min)

60

Pulsation cycle desirable (Hz)

3

872116

Fig. 18. Changes in cooling effect with time. 1,2 Hz is the most comfortable pulsation. Asakai and Sakai [28]

ferent thermal influences. The thermoreceptors can be divided into the class of warm and cold receptors. The thermoreceptors have a static sensi­tivity to constant temperature ( t) and a dynamic sensitivity to tempera­ture changes ( dt I d T ), with a positive temperature coefficient for warm receptors and a negative coefficient for cold receptors. Irrespective of the initial temperature, a warm receptor will always show a transient increase in frequency on sudden warming and a transient inhibition of its discharge on sudden cooling, whereas a cold receptor will respond in the opposite way, namely, with an overshoot on cooling and an inhibition on warming. Besides this dynamic behaviour there are also typical differences in the static sensitivity curves of both types of thermoreceptors, in that the tem­perature of the maximum discharge is much lower for cold receptors than it is for warm receptors. The draught sensation, e.g. undesirable local cool­ing of the body, should be connected with the response of the cold recep­tors, as the receptors register the temperature changes at the skin surface.

Why is fluctuating airflow more uncomfortable than non-fluctuating airflow at the same conditions, e.g. mean air velocity and temperature? One suggestion made by Mayer [30, 31] is that the convective heat transfer increases with increasing turbulence intensity. This has certainly an im­pact but may not be sufficient to explain the dramatic effect of turbulence shown in Fig. 16. The velocity fluctuations will cause skin temperature fluctuations which will be reigstered by the receptors. The temperature changes will have an impact on the dynamic sensitivity of the receptors.

24

Page 31: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

25

20

(tj 15

"' .t::

~ 10

5

0,025 0,1 0,2 0.4 0,8 1,6 Hz Frequency 871858

Fig. 19. Maximum heat flow through thermal receptors simulated by an electrical ana­log model as a frequency of the input signals (from Madsen [34])

This theory has been studied by Madsen [32, 33, 34]. He simulated the hu­man skin including thermoreceptors by electrical model. In the model, temperature was simulated by voltage, heat flow by current, thermal ca­pacity corresponds to electrical capacitance and thermal resistance corre­sponds to electrical resistance. On the electrical model the maximum heat flow through the receptors was determined when the skin was exposed to a number of sine-shaped velocity changes, with constant amplitude, but with different frequencies. Fig. 19 shows the relationship between the heat flow and frequency from this experiment. The form of the curve is almost identical to the curve from Fanger and Pedersen's subjective study [21], Fig. 8. Both curves have a maximum around 0,5 Hz. Madsen hypothesised that for fluctuating airflow high sensitivity is a result of periodically high outputs from the cold receptors to the brain. This is caused by a corre­sponding high heat flow through the receptors following the moments of highest air velocity. The dynamic response of the thermoreceptors to the rate of change of the skin temperature is not simple. Although a non-zero dt I d T is necessary as a stimulus, it by itself does not account for many of the characteristics of the receptors discussed by Hensel [29]. Magnitude (size of temperature step) and frequency of the stimulus may play a role in the response of the receptors and in sensation. The fluctuation of the skin temperature with time, activates the receptors to initiate signals to the

25

Page 32: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

brain. They are probably warning signals, meant to provide an early modi­fication of human behaviour and of the regulatory mechanisms of the body to counteract a cooling process, which in the long run might be a threat to the human body. During exposure to velocity fluctuations this information is not useful and therefore undesired, but it may explain the nuisance called draught.

Model of draught risk Fanger and Christensen [22] studied the impact of the mean velocity

and air temperature on the sensation of draught. They measured the tur­bulence intensity but did not control it. Fanger et al [25, 26] studied the impact of the mean velocity and the turbulence intensity on man's sensa­tion of draught. They kept the air temperature constant.

The results of these two studies were used and a model of draught risk was developed by Fanger et al [26]. The model predicts the percentage of people dissatisfied due to draught as a function of air temperature, ta (°C), mean velocity, u (m/s), and turbulence intensity, Tu (%).The percent dis­satisfied, PD, is given by the equation:

PD = (34- ta) (u- 0,05)0·6223 (0,3696 · u · Tu + 3,143)

for u < 0,05 insert v = 0,05 m/s for PD > 100% use PD = 100%.

(9)

The model incorporates the convective heat transfer process to link tur­bulence to skin temperature fluctuations and Hensel's account of thermo­receptors to link thermal sensation to these temperature fluctuations. The two kinds of thermoreceptor responses, the static and the dynamic were assumed. As it was pointed the dynamic response depends on the rate of change of skin temperature while the static depends on the level of the skin temperature. Due to the free convection airflow along the warm hu­man body [35, 36], it was assumed that only velocities above 0,05 m/s would penetrate this layer. The exponent 0,6223 for the convective term in the model corresponds to the values in the literature [37]. The skin tem­perature was assumed to be 34 ° C. The ranges of the three parameters for the experimental data to which the model was fitted are:

20 < ta < 26°C, 0,05 < u < 0,4 m/s and 0 < Tu < 70%.

26

Page 33: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

30

~ .; 25 (i; c. E {!!. 20

< 15

mls

Mean Air

Velocity

0

Turbulence Intensity

871879

Fig. 20. A 3-dimensional representation of the draught risk model. The surfaces shown correspond to 10, 15 and 20% dissatisfied. The axes are turbulence intensity, mean air velocity and air temperature

It should also be noted that any u < 0,05 m/s counts as u = 0,05 m/s and although PD's bigger than 100% are mathematically possible they are not meaningful and should be counted as 100%.

Another way of presenting the model of draught risk is:

PD = 3,143 (34-ta) (v-0,05)0,6223 + 0,3696 (34-ta) (v-0,05)0,6223 v Tu (9a)

PD = (34-ta) (u-0,05)0,6223 (3,143 + 0,3696 · SD) (9b)

Equation (9b) can also be useful since some airflow instruments measure the standard deviation of the velocity fluctuations (SD) and not the tur­bulence intensity.

The main features of the model are shown in Fig. 20 which is a three dimensional drawing of surfaces of constant percentage dissatisfied (10, 15 and 20%) with the axes being, turbulence intensity, mean velocity and air temperature. Higher percentages of dissatisfied can be seen to be asso­ciated with higher Tu, higher u and lower ta-

27

Page 34: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

mls,---------------------------------------------------------,

10% Dissatisfied

0,4

"" '(; 0 0,3 a; >

< c: "' Q)

::;;

0,2

0,1

18 20 22 24 26 Air Temperature sne;o

Fig. 21. Combinations of mean air velocity, air temperature and turbulence intensity, which will cause 10% dissatisfied. Calculated from the model of draught risk, Fanger et. al. [26]

Figures 21 and 22 give more precisely the curves which result from inter­sections between planes of constant Tu and the surfaces of PD = 10% and 20% respectively. It can be seen from Fig. 21 that at the same air tempera­ture 23°C airflow with Tu = 60% will cause 10% dissatisfied at almost twice lower mean velocity (v = 0,11 m/s) than airflow with Tu = 0%

28

Page 35: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

mls~------------------------------~---------------------r--~

20% Dissatisfied

0,4

J':' "i)

0,3 0 a; > ;;;: <=

"' "' ::;;

0,2

0,1

18 20 22 24 26

Air Temperature 811871

Fig. 22. Combinations of mean air velocity, air temperature and turbulence intensity, which will cause 20% dissatisfied. Calculated from the model of draught risk, Fanger et al. [26]

(v = 0,19 m/s). Figs. 23 and 24 exhibit the way in which PD depends on Tu and vat ta = 23°C. It is obvious that the effect of the turbulence is signifi­cant and it increases with the mean velocity. It is possible, using the model of draught risk, to calculate the uniform (non-fluctuating) air velocity which will cause the same percentage of dissatisfied due to draught as a

29

Page 36: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

"0 -~ :§

%.-----------------------------------------------------~

Air Temperature 23"C

70

60

50

-m 40

"' Ci

30

20

10

Of-------,-------.-------.-------,-------.-------.-----~ 0 10 20 30 40 50 60 %

Turbulence Intensity 872125

Fig. 23. Percent dissatisfied as a function of turbulence intensity and mean air velocity calculated from the model of draught risk [26]. The diagram applies for an air tempera­ture 23°C

fluctuating airflow with the same mean velocity and temperature but dif­ferent turbulence intensity. Fig. 25 shows this relationship.

The feet and arms were found to be sensitive to draught as well. Normal­ly these parts of the body are covered by some clothing. The clothing layer will damp the thermal impact of velocity fluctuations on the risk and thus decrease the impact of turbulence on draught. The model of draught risk may be used for all heights in the occupied zone, although it may tend to

30

Page 37: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

%

Air Temperature 23'C

60

40

20

0 0,1 0,2 0,3 0,4 m/s

Mean Air Velocity 872129

Fig. 24. Percent dissatisfied as a function of mean air velocity and turbulence intensity calculated from the model of draught risk [26]. The diagram applies for an air tempera­ture 23°C

overestimate the draught risk at arms and feet level. For people with bare arms and ankles or with nylon stocking it is reasonable to use the model for the head.

Prediction of draught risk in rooms Draught risk in spaces for human occupancy may be quantified by the

model of draught risk. Measurements of three variables are necessary:

MEAN AIR VELOCITY - v (m/s) STANDARD DEVIATION - SD (m/s)

or TURBULENCE INTENSITY- Tu (%) AIR TEMPERATURE - ta (°C)

31

Page 38: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

m/s

1,8

1,6

1.4

.?:' '5 0

~ 1,2

<(

E "' 1,0 1n <:: 0 ()

E Q) 0,8 <ii > ·:; C'

UJ

0,6

0,4

0,2

0 0,1 0,2 0,3 0,4 m/s

Mean Air Velocity 872130

Fig. 25. Equivalent constant air velocity which will cause the same percentage of dissat­isfied due to draught as actual airflow with different mean velocity and turbulence inten­sity. Calculated from the model of draught risk [26]

The three airflow characteristics should be measured at 0,1 m, 0,6 m, 1,1 m and 1,7 m above the floor in the occupied zone of the spaces. The heights are recommended in the standards (ISO 7726 [18], ASHRAE, 55-81 [39]). For sedentary persons, 0,1 m, 0,6 m and 1,1 m correspond to the feet, the arms and the head. The height corresponding to the head region for standing person is 1,7 m above the floor.

32

Page 39: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Model of draught risk, standards and practice In the existing standards limits for the mean air velocity are recommend­ed. ISO 7730 [38], ASHRAE 55-8 [39], and NKB-guidelines [40] have agreed on the same limits:

WINTER SITUATION - operative temperature between 20 and 24°C, mean air velocity less than 0,15 m/s SUMMER SITUATION - operative temperature between 23 and 26°C, mean air velocity less than 0,25 m/s

Limits for turbulence intensity are not included in the standards. The values for the maximum mean velocity and minimum temperature recom­mended in the standards may be used to calculate maximum percentage of dissatisfied by the model of draught risk. This is shown on Fig. 26 for tur­bulence intensity up to 60% as it was measured in the field studies [10, 12, 14, 15, 16]. The maximum percentage of dissatisfied calculated with the limits for mean air velocity and temperature according to the German Standard DIN 1946 [41], are shown on Fig. 26 as well. The horizontal line

%

30

'C .!!! :§ 1ii <I> 20 <I>

i5

10

0

---- ISO 7730, NKB, ASHRAE 55·81

DIN 1946

10 20 30

Turbulence Intensity

40 50 %

872123

Fig. 26. Maximum percentage dissatisfied, based on the limits for the maximum mean air-velocity and minimum temperature recommended in the standards, as a function of the turbulence intensity. Calculated from the model of draught risk, Fanger et.al. [26]

33

Page 40: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

on the figure determines the values of the turbulence intensity up to which 15% or less of the occupants will be dissatisfied due to draught. For ISO, ASHRAE and NKB summer limits (0,25 m/s and 23°C) airflow with Tu > 7% will cause more than 15% dissatisfied occupants. For the winter limits (0,15 m/s and 20°C) this value of Tu is 25%. For DIN standard tur­bulence intensity is between them, Tu """ 17%.

Thus, the frequent complaints of draught occurring in practice, al­though mean velocity and air temperature may meet existing standards, may be explained by the significant impact of turbulence intensity on man's draught sensitivity. Values for the mean velocity and the air tem­perature are recommended in the standards but the turbulence intensity is not considered. Therefore there is a need to update the standards to in­clude this new insight in the draught risk.

What are the practical consequences of the velocity fluctuations' impact on man's draught sensitivity? Traditionally, ventilation systems are de­signed to establish good mixing of the supply air with the air in the room and low mean air velocity in the occupied zone. In order to fulfil these conditions, the outlets are located far from the occupied zone. The air comes into the space with relatively high velocity and creates high turbu­lent air flow.

But the strong impact of turbulence on draught risk would obviously provide an incentive to develop air distribution systems which produce low turbulence in the occupied zone. This has already been utilised to certain extent in the new displacement ventilation system (44,45). The main idea behind the displacement ventilation is that the contaminents are dis­placed out of, the occupied zone without any mixing. The clean air is sup­plied directly into the occupied zone from large outlets with low velocity. In order to promote an undirectional displacing flow of the air through the room the turbulence intensity must be as low as possible. For the supply air to cover all floor area and then rise to the ceiling its temperature should be lower than the room air temperature.

Discussion of Results The air flow in ventilated rooms is very complex and it should be investi­gated more. Air velocity measurements from different studies with differ­ent instruments have to be compared or analyzed together in order to un­derstand the nature of the airflow and to assess the indoor climate in the rooms. Because of these the accuracy of the velocity measurements be­comes an important factor.

34

Page 41: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

The ISO Standard 7726 [18] requirements for measuring the velocity are specified (see also previous issue of B & K Technical Review [8]). The measuring instrument should be able to measure air velocity as low as 0,05 m/s, to measure velocity fluctuations as fast as 1 Hz, to give a mean air velocity based on 3 min. measurement and to give the equivalent stan­dard deviation. A further requirement is that the velocity sensor should be omnidirectional, i.e. the air velocity should be measured correctly inde­pendent of the velocity direction relative to the sensor (except of course for a small angle around the support of the sensor).

Now the following questions about the accuracy of the velocity measure­ments connected with the calibration of the probes and their characteris­tics (static and dynamic) arise: - Is the period of 3 minutes integration time enough? Very often high ve­

locities occur in periods of more than 3 minutes. - Is the recommended 1 Hz in the standard enough to register mean veloc­

ity and standard deviation with acceptable accuracy? Velocity fluctua­tions with frequency higher than 1 Hz were registered in rooms and in some cases these fluctuations can contribute a lot to the high frequency range in the energy spectra;

- How far may the calibration of the probes typically made in nearly lami­nar flow be used in high turbulent flow where velocity changes its direc­tion and has fluctuating frequency?

- How much does the calibration of the probes made in different ways for different instruments affects the accuracy of the velocity measurements? The above questions regarding the low velocity measuring technique, in

general, need answering and they should be studied.

Conclusions Airflow in rooms is turbulent with turbulence intensity from less than 10 to 70%. Velocity fluctuations with frequency higher than 1Hz have been measured [12, 14, 15, 16].

A high turbulent airflow is felt as a draught by more people than low turbulent airflow with the same mean velocity and temperature [22, 25, 26].

A model of draught risk has been developed which predicts the percent­age of dissatisfied people due to draught as a function of air temperature, mean air velocity and turbulence intensity [26].

The model of draught risk may be used to estimate draught risk in rooms, by measuring mean air velocity, turbulence intensity and air tern-

35

Page 42: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

perature. B & K Indoor Climate Analyzer measures these three airflow characteristics.

Air distribution systems which create low turbulent airflow should be developed to diminish draught complaints.

There is a need to update existing standards to include the turbulence intensity in draught risk.

More investigations on the accuracy of velocity measuring technique, in general, are required.

The airflow in rooms has been investigated in several studies and more has to be done to understand its nature. Quite a few researchers are in­volved in this problem. Results from different studies must be compared and analyzed together. Air velocity measurements are important for esti­mation of draught risk in rooms. Therefore the problems with the low ve­locity measuring technique, in general, should be studied.

References

[ 1] Bolinder, E., Magnuson, E. & Nyren, E.

[ 2] Arbejdsmiljo­gruppen

[ 3] Fanger, P.O.

[ 4] Fanger, P.O.

[ 5] Fanger, P.O.

[ 6] Fanger, P.O.

36

"Risker i jobbet: LO-enkaten. LO-medlemensarms uppfattning om arbetsplatsens halsorisker ", Stock­holm: PRISMA) (in Swedish) 1970

"Arbejdsmiljoundersogelses rapport No.2", Copenha­gen (in Danish) 1972

"Thermal Comfort", (Copenhagen: DANISH TECH­NICAL PRESS, Reprinted 1972, New York: McGraw-Hill, Reprinted 1982, Malabar, Florida,: Rober E. Krieger)

" Thermal Comfort Requirements" For presentation at the meeting: Les Applications du thermocondition­ement ala Hurmique du batiment" Lyon, 9-11, May 1983

" The philosophy behind a comfort standard" Proc. of Indoor Air'84, August 20-24, 1984, Stockholm, Sweden

" Thermal Comfort in the built environment", Proc. of 1987 European Conference on Architecture, April 1987, Germany, pp.759-762

Page 43: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

[ 7] Olesen, B. W.

[ 8] Olesen, B.W.

[ 9] Hinze, T.O.

[10] Thorshauge, J.

[11] Hauzawa, H., Melikov, A.K. & Fanger, P.O.

[12] Hauzawa, H., Melikov, A.K., Fanger, P.O.

[13] Melikov, A.K., Hanzawa, H., Fanger, P.O.

[14] Sandberg, H.

(15] Kovanen, K., Seppanen, D., Siren, U., Majanan, A.

[16] Melikov, A.K., Hanzawa, H., Fanger, P.O.

[17] Olesen, B.W., Mortensen, E., Thorshauge, J., Berg-Munch, B.

" Thermal Comfort", Briiel & Kjrer Technical Review, No.2-1982

"Local Thermal Discomfort", Briiel & Kjrer Techni­cal Review No.1-1985

"Turbulence", New York: McGraw-Hill, 1985

"Air velocity fluctuations in the occupied zone of ven­tilated spaces", American Society of Heating, Refrig­erating and Air-conditioning Engineers Transactions, 88, 2, 1982, pp.753-764

"Field Measurements of characteristics of Turbulent Airflow in the Occupied Zome of Ventilated Spaces", Clima 2000, Vol. 4: Indoor Climate (Edited by P.O. Fanger, 1985, Copenhagen), pp. 409-414

"Airflow characteristics in the occupied zone of venti­lated spaces" American Society of Heating, Refriger­ating and Air-Conditioning Engineers Transactions, 93, 1, 1987, pp.524-539

"Mean velocity and turbulence intensity in ventilated and unventilated spaces", in Air distribution in ven­tilated spaces, session 2a, ROOMVENT-87, Stock­holm, 1987

" Velocity characteristics in mechanically ventilated office rooms", in Air distribution in ventilated spaces, session 2a, ROOMVENT-87, Stockholm 1987

"Air velocity, turbulence intensity and fluctuation frequency in ventilated spaces", in Air distribution in ventilated spaces, session 4, ROOMVENT-87, Stock­holm 1987

"Airflow characteristics in the occupied zone of heat­ed spaces without mechanical ventilation", American Society of Heating, Refrigering and Air-conditioning Engineers Transactions, 94, 1, 1988

" Thermal comfort in room heated by different meth­od", American society of Heating, Refrigerating and Air-conditioning Engineers Transactions, 86, 1, 1980, pp.34-48

37

Page 44: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

[18] ISO 7726

[19] Hougten, F.C.

[20] Mcintyre, D.A.

[21] Fanger, P.O., Pedersen, C.J.K.

[22] Fanger, P.O., Christensen, N.K.

[23] Berglund, L.G., Fobelets, A.P.R.

[24] Tanabe, Shin-ichi

[25] Fanger, P.O., Melikov, A.K., Hanzawa, H.:

[26] Fanger, P.O., Melikov, A.K., Hanzawa, H., Ring, J.

[27] Finney, D.J.

[28] Asakai, M., Sakai, K.

[29] Hensel, H.

38

" Thermal environments - Specifications relating to appliance and methods for measuring physical char­acteristics of the environment", Geneva, (in press)

"Draft temperatures and velocities in relation to skin temperature and feeling of warmth", American Soci­ety of Heating and Ventilating Engineers Transac­tions, 44, 1938, pp.289

" The effect of air movement on thermal comfort and sensation", In Indoor Climate (Edited by P.O. Fanger and 0. Valbjorn) (Copenhagen: Danish Building Re­search Institute), pp.541-560

"Discomfort due to air velocities in spaces", Proceed­ings of the Meeting of Commission B1, B2, E1 of the International Institute of Refrigeration, 4, 1977, pp.289-296

"Perception of draught in ventilated spaces", Ergo­nomics, 29, 2, 1986, pp.215-235

"Subjective human response to low-level air currents and asymmetric radiation", American Society of Heating, Refrigeration and Air-Conditioning Engi­neers Transactions, 93, 1987, pp. 497-523

" Thermal Comfort Requirements in Japan", Ph.D. Thesis, Waseda University, Japan 1987, 292

Draught and Turbulence", Proc. of "Indoor Air '87, "Berlin (west), 17-21 August 1987, Vol. 3, pp.404--408

"Air turbulence and sensation of draught", Energy and Buildings, 12, 1, 1988 pp ...

"Probit Analysis" Cambridge: The University Press, 1947

"Cooling effect of car ventilators", Bulletin of JSAE, 6, 1974, pp.75-82

" Thermo reception and temperature regulation", London: Academic Press), 1981

Page 45: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

[30] Mayer, E.

[31] Mayer, E.,

[32] Madsen, Th. Lund

[33] Madsen, Th. Lund

[34] Madsen, Th. Lund

[35] Fiedorovicz, J.

[36] Homa, H.

[37] Incropera, F.P., Dewitt, D.P.

[38] ISO 7730

[39] ASHRAE Standard 55-1981

"Entwicklung eines Messgertits zur getrennten und integrativen Erfassung der Physikalischen Raumkli­makomponenten" Dissertation, Technische Univer­stitat, Mtinchen, 1983

"Physical causes for draft: some new findings", American Society of Heating, Refrigerating and Air­Conditioning Engineers Transactions, 93, 1, 1987, pp.540-548

"Limits for draught and asymmetric radiation in re­lation to human thermal well-being" Proc. of the meeting of Commissions B1, B2, E1 of the Interna­tional Institute of Refrigeration, Belgrade, 1977, pp.297-305

"Definition and measurement of local thermal dis­comfort parameters", American Society of Heating, Refrigeration and Air-Conditioning Engineers Trans­action, 86, 1, 1980, pp.

" Why low air velocities may cause thermal discom­fort?" In Pro c. of the 3'd International Conference on Indoor Air-Quality and Climate, Indoor Air, 5, 1984, pp.331-336 (Swedish Council for Building Research, Stockholm).

"Boundary layer of air on a nude man (maximum) caused by free convective heat exchange" Report Thermal Insulation Laboratory, Technical University of Denmark, 1975

"Free convection caused by metabolic heat around hu­man body", Proc. of ROOMVENT'87, Session 20, Stockholm 1987

"Fundamentals of Heat and Mass Transfer", John Wiley & Sons, New York, 1982

"Moderate Thermal Environments - Determination of the PMV and PPD indices and specification of the conditions for thermal comfort", International Stan­dards Organisation, 1984, Geneva

"Thermal environmental conditions - Human Occu­pancy", (Atlanta ASHRAE)

39

Page 46: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

[40] NKB

[41] DIN 1946, Teil2

[42] Olesen, B.W.

[43] Johannessen, F.

[44] Skaret, E.

[45] Sandberg, M., Sjoberg, M.

40

"Indoor Climate (Stockholm)" The Nordic Commit­tee on Building Regulations, Report No.41, 1981

"Raumlufttechnik Gesundheitstechnische Anforder­unger" VDI-Ltiftungsregeln), Deutsches Institut ftir Normung, Berlin, 1983

"Assessment and measurement of the Indoor Thermal Environment", Energy and Building Envelope", Thessaloniki, July 1986, pp.46

"A new thermal annometer probe for indoor air veloci­ty measurements", B & K Technical Review No.2, 1985

"Displacement ventilation", Proc. of Roomvent'87, Session 5, Stockholm 1987

"A Comparative Study of the Performance of General Ventilation Systems in Evacuating Contaminants", Proc. of Indoor Air, Vol. 5, Stockholm, Sweden 1984, pp.59-64

Page 47: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Previously issued numbers of Briiel & Kjrer Technical Review (Continued from cover page 2)

3-1983 Fourier Analysis of Surface Roughness 2-1983 System Analysis and Time Delay Spectrometry (Part II) 1-1983 System Analysis and Time Delay Spectrometry (Part I) 4-1982 Sound Intensity (Part II Instrumentation and Applications)

Flutter Compensation of Tape Recorded Signals for Narrow Band Analysis

3-1982 Sound Intensity (Part I Theory). 2-1982 Thermal Comfort. 1-1982 Human Body Vibration Exposure and its Measurement. 4-1981 Low Frequency Calibration of Acoustical Measurement Systems.

Calibration and Standards. Vibration and Shock Measurements. 3-1981 Cepstrum Analysis. 2-1981 Acoustic Emission Source Location in Theory and in Practice. 1-1981 The Fundamentals of Industrial Balancing Machines and Their

Applications. 4-1980 Selection and Use of Microphones for Engine and Aircraft Noise

Measurements. 3-1980 Power Based Measurements of Sound Insulation.

Acoustical Measurement of Auditory Tube Opening. 2-1980 Zoom-FFT. 1-1980 Luminance Contrast Measurement. 4-1979 Prepolarized Condenser Microphones for Measurement Purposes.

Impulse Analysis using a Real-Time Digital Filter Analyzer. 3-1979 The Rationale of Dynamic Balancing by Vibration Measurements.

Interfacing Level Recorder Type 2306 to a Digital Computer. 2-1979 Acoustic Emission. 1-1979 The Discrete Fourier Transform and FFT Analyzers.

Special technical literature Brtiel & Kjrer publishes a variety of technical literature which can be obtained from your local Brtiel & Kjrer representative. The following literature is presently available:

0 Mechanical Vibration and Shock Measurements (English), 2nd edition 0 Modal Analysis of Large Structures-Multiple Exciter Systems (English) 0 Noise Control (English, French) 0 Frequency Analysis (English) 0 Catalogues (several languages) 0 Product Data Sheets (English, German, French, Russian)

Furthermore, back copies of the Technical Review can be supplied as shown in the list above. Older issues may be obtained provided they are still in stock.

Page 48: TECHNICAL REVIEW: No. 2 1988 Quantifying Draught Risk (bv0034)

Briiel & Kjcer +-DK-2850 Nffirum ·Denmark· Telephone: + 452800500 ·Telex: 37316 bruka dk Fax: + 45280 1405

ISSN007-2621

BV0034-11 Pr1nted 1n Denmark by Nrerum Oflset