Technical details -V-VAC Description Rated voltage Rated Frequency Rated busbar current Short time with stand current (3sec.) Insulation levels Width x Depth x Height Weight with circuit breaker (Appr.) Unit KV Hz A kA kAP KV/rms/KVp mm Kg Rating 36 50 up to 1600 26.3 66 70/170 1100X2370X2530 1300 Technical details -V-MAX circuit breaker Description Rated voltage Insulation Levels Normal current (40°C amb.) Breaking Capacity Making Capacity Short time withstand current Opening time Arcing time Total Break Time Making time Operating Sequence Weight Unit KV KVrms/kVp A kA kAP kA (3sec) ms ms ms ms - kg Rating 36 70/170 1250 31.5 80 31.5 60 (Max) 15 (Max) 75 (Max) 80 (Max) O-0. 3sec-CO-3min--CO 300 E-63, M.I.D.C., Ambad, Nashik - 422 010. INDIA TEL. : 0091- 253 - 6699841 / 835 WEBSITE : vibhacorporation.com E-MAIL : marketing@vibhacorporation.com / vibhaexport@yahoo.co.in Air Insulated Indoor Switchgear Cubical type V-VAC 36 with Vacuum Circuit Breaker type Vd4
3
Embed
Technical details -V-VAC Air Insulated Indoor Switchgear ... · PDF fileSalient Features - VD4 circuit breaker • The Vd4 circuit breaker is designed and type tested to meet requirements
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
• Metering compartment with numercal / static / electromagnetic relays, indicating meters, Lamps and control switches
• Protection and measuring apparatus customized as per requirement
• Cassette mounted breaker placed on elevated level with test position of breaker behind closed door
• Interlocks : - Racking in/out of breaker from test to service position and vice-versa with cubical door closed - To prevent racking in/out of breaker, when breaker in closed position - To prevent door from opening when breaker is in service position (optional)
• Multiple guides for safe and enduring alignment of fixed and moving power contacts
• Live parts covered by automatic polycarbonate shutters when breaker is racked out
• Removable fuses mounted on the PT
• Withdrawable line PT provided in the breaker panel
• EPOXY ENCAPSULATED PT Fuses in PT Trolley
Salient Features - VD4 circuit breaker
• The Vd4 circuit breaker is designed and type tested to meet requirements of IEC62271- 100 / IS : 13118
• Vacuum used as insulation and arc interruption medium
• Operationally safe and reliable in a wide range of ambient temperatures -5 to 40°C
• Capable of interrupting small magnetising and capactive currents
• Vacuum interrupters assembled in epoxy enclosure with insulated contact arms