Project : PLN
INDUSTRIAL DIVISION
No
1 1 Set
1 "Aur ora" Horizontal Split Case
Model : 411-4x5x11D/Single Stage
Pump Material Design, Casing : Cast Iron, Impeller : Bronze,
Shaft : Carbon Steel with Bronze Sleeve, Shaft Seal : Gland Packing
1 "Western" Electric Motor 37 kW @ 2915 Rpm
With 380V/ 3Ph/ 50Hz
1 "Ronald" Electri c Fire Pump Controller
Auto On / Manual Off
2 1 Set
1 "Aur ora" Horizontal Split Case
Model : 411-4x5x11D/single stage
Pump Material Design, Casing : Cast Iron, Impeller : Bronze,
Shaft : Carbon Steel with Bronze Sleeve, Shaft Seal : Gland Packing
1 "CLARKE" Diesel Engi ne JU4H-NL14, 58 kW @ 3000 Rpm
Heat Exchanger Cooling System
Engine accessories: Batteries Cables, Silencer,
Flexible Exhaust Connector, Fuel Tank (Supplied by Local)
1 "Ronald" Diesel Fire Pump Controller
Auto On / Manual Off
3 1 Set
1 "Aur ora" Vertical Multistage In-Line
Model : PVM 5-13
Pump Material Design, Casing : Stainless Steel, Impeller : Stainless
Steel, Shaft : Stainless Steel, Shaft Seal : Mechanical Seal
1 "Factory Choice" Motor 2.2 kW @ 2915 Rpm
with 380V/ 3Ph/ 50Hz
1 "Ronald" Jockey Fire Pump Controller
DIESEL FIRE PUMP NFPA-20 STANDARD
Cap. 144 M3/H @ 54 Meter Total Head
JOCKEY PUMP
Cap. : 25 GPM @ 60 Meter Total Head
Qty Description
ELECTRIC FIRE PUMP NFPA-20 STANDARD
Cap. 144 M3/H @ 54 Meter Total Head
TECHNICAL REVIEW
Page 1 of 1
7/25/2019 Technical Data untuk project PLN.pdf
3/57
1
REFERENCE LIST AURORA PUMP
IN INDONESIA
NO PROJECT NAME LOCATION LINE DUTY YEAR
1 HINDOLI PALEMBANG BUILDING FIRE PUMP 1988
2 SEMEN CIBINONG CIBINONG INDUSTRY FIRE PUMP, TRANSFER PUMP 1999
3 MACRO DENPASAR BUILDING FIRE PUMP 1999
4 BATU HIJAU WTP SECTION I - MINING FIRE PUMP 1999
5 PLAZA DAGO BANDUNG BUILDING FIRE PUMP 1999
6 MAKRO JAKARTA BUILDING FIRE PUMP 1999
7 MAKRO MEDAN BUILDING FIRE PUMP 2000
8 SCHLUMBERGER BALIKPAPAN BUILDING FIRE PUMP 2000
9 BATU HIJAU WTP SECTION II - MINING FIRE PUMP 2000
10 MULAWARMAN UNIV. PACKAGED I - BUILDING FIRE PUMP 2000
11 MULAWARMAN UNIV. PACKAGED II - BUILDING FIRE PUMP 2000
12 MULAWARMAN UNIV.PACKAGED III - BUILDING FIRE PUMP 2000
13 GS BATTERY JAKARTA FACTORY FIRE PUMP 2000
14 AUTO 2000 TEBET JAKARTA SHOWROOM FIRE PUMP 2001
15 GLOBAL AGROTEK JAKARTA BUILDING FIRE PUMP 2002
16 MALL FANTASI BALIKPAPAN BUILDING FIRE PUMP 2002
17 TEMPO MEDAN WAREHOUSE FIRE PUMP 200218 SUSU CAIR INDOMILK - FACTORY FIRE PUMP 2002
19 PRESIDEN HOTEL JAKARTA BUILDING FIRE PUMP 2002
20 BINTARO TRADE CENTER JAKARTA BUILDING FIRE PUMP 2003
21 MALL KAREBOSI MAKASSAR BUILDING FIRE PUMP 2003
22 MULIA TOWER JAKARTA BUILDING FIRE PUMP 2003
23 BNI46 LADA JAKARTA BUILDING FIRE PUMP 2003
24 EXSPAN KAJI JAKARTA BUILDING FIRE PUMP 2003
25 WTC MANGGA DUA JAKARTA BUILDING PLUMBING 2003
26 TAMAN IMPIAN JAYA ANCOL JAKARTA BUILDING FIRE PUMP 2003
27 SEMEN CIBINONG CIBINONG CEMENT INDUSTRY SEWAGE PUMP 2003
28 PANGRANGO PLAZA BOGOR BUILDING FIRE PUMP 2003
29 ACA BANDUNG BUILDING FIRE PUMP 2003
30 ITC KEBON KELAPA BANDUNG MARKET FIRE PUMP 2003
31 PUPUK KUJANG CIKAMPEK WAREHOUSEWATER IN TAKE VERTICALTURBINE
2004
32 MATA PELANGI OFFICE JAKARTA BUILDING FIRE PUMP 2004
33 BSD MARKET TANGERANG BUILDING FIRE PUMP 2004
34 TOTAL INDONESIA - MINING PROCESS PUMP 2004
35 GRAND SOLO MALL SOLO BUILDING FIRE PUMP 2004
36 CIPUTRA SERAYA MALL PEKANBARU BUILDING FIRE PUMP 2004
7/25/2019 Technical Data untuk project PLN.pdf
4/57
2
37 PUSAT DAGANG INVESTASI BATAM BUILDING FIRE PUMP 2004
38 BELLAGIO RESIDENCE JAKARTA BUILDING FIRE PUMP 2004
39 PONDOK INDAH MALL 2 JAKARTA BUILDING FIRE PUMP, CHILLER PUMP 2004
40 SAN MIGUEL JAKARTA FACTORY FIRE PUMP 2004
41 BAYER MEDAN FACTORY FIRE PUMP 2005
42 BAYER SURABAYA FACTORY FIRE PUMP 2005
43 MEGA GLODOK KEMAYORAN JAKARTA BUILDING FIRE PUMP 2005
44 SEMEN PADANG PADANG CEMENT INDUSTRY COOLING TOWER 2005
45 SEMEN CIBINONG CIBINONG CEMENT INDUSTRY WATER INJECTION 2005
46 SEMEN CIBINONG CIBINONG CEMENT INDUSTRY WATER SPRAY 2005
47 PERTAMINA PRABUMULIH PRABUMULIH OIL & GAS FIRE PUMP 2005
48 - - - FIRE PUMP 2005
49 BG JUNCTION / BUBUTAN SURABAYA BUILDING CHILLER & BOOSTER 2005
50 BAYER JAKARTA FACTORYVERTICAL TURBINE FIREPUMP
2005
51 BPKP PRAMUKA JAKARTA BUILDING FIRE PUMP 2005
52 BATAM CITY SQUARE BATAM BUILDING FIRE PUMP 2005
53 MECOINDO CIKARANG FACTORY FIRE PUMP 2006
54 - - OIL & GAS FIRE PUMP 2006
55 GRIYA JENGGALA JAKARTA RESIDENTIAL FIRE PUMP 2006
56 SUDIRMAN PARK JAKARTA BUILDING FIRE PUMP 2006
57 PEARL GARDEN JAKARTA BUILDING FIRE PUMP 2006
58 MODERN GOLF APARTEMENT TANGERANG BUILDING FIRE PUMP 2006
59 CITY HOME KLP. GADING JAKARTA BUILDING FIRE PUMP 2006
60 ISLAMIC CENTER JAKARTA BUILDING FIRE PUMP 2006
61 INDONESIA NS FACTORY JAKARTA FACTORY FIRE PUMP 2006
62 PLAZA CIBUBUR JAKARTA BUILDING FIRE PUMP 2006
63 SUDIRMAN PLAZA JAKARTA BUILDING FIRE PUMP 2006
64 WISMA 76 JAKARTA BUILDING FIRE PUMP 2006
65 GRAND INDONESIA JAKARTA BUILDING FIRE PUMP, CHILLER PUMP,PLUMBING PUMP
2006
66 NUSA 2 GOLF RESIDENT BALI BUILDING FIRE PUMP 2006
68 PT. PJB UP MUARAKARANG JAKARTA POWER PLANT FIRE PUMP 2006
69 LAMONGAN INTEGRATEDSHORE BASE LAMONGAN SHORE BASE- WAREHOUSE FIRE PUMP 2006
70 UPH KARAWACI TANGERANG BUILDING FIRE PUMP 2006
71 XL PEKAN BARU PEKAN BARU BUILDING FIRE PUMP 2006
72 DSS PROJECT JAKARTA FACTORY FIRE PUMP 2006
73 SKF INDONESIA JAKARTA FACTORY FIRE PUMP 2006
74 JOHNSON & SON PROJECT JAKARTA FACTORY FIRE PUMP 2006
75 SENTRA GROSIR CIKARANG BUILDING FIRE PUMP 2006
76 SEMEN BASOWA SULAWESI CEMENT INDUSTRY REGENERATIVE TURBIN PUMP 2006
7/25/2019 Technical Data untuk project PLN.pdf
5/57
3
77 GRAND INDONESIA JAKARTA BUILDING FIRE PUMP 2006
78 KEDUTAAN BELANDA JAKARTA BUILDING FIRE PUMP 2006
79 HARDA BANK JAKARTA BUILDINGVERTICAL TURBINE FIREPUMP
2006
80 MENARA PRIMA JAKARTA BUILDING FIRE PUMP 2006
81 WISMA PONDOK INDAH JAKARTA BUILDING FIRE PUMP, CHILLER PUMP 2006
82 SEMEN PADANG PADANG CEMENT INDUSTRY HVAC PUMP 2006
83 ITC KOPO BANDUNG BUILDING FIRE PUMP 2006
84 THE EAST JAKARTA BUILDING FIRE & CHILLER PUMP 2006
85 PERTAMINA SAGATA KALIMANTAN OIL & GAS FIRE PUMP 2006
86 HOLCIM INDONESIA JAKARTA CEMENT INDUSTRY REGENERATIVE TURBINE PUMP2006
87 SPRING HILL GOLF RESIDENCE JAKARTA RESIDENTIAL FIRE PUMP 2006
88 HOLCIM INDONESIA JAKARTA CEMENT INDUSTRY REGENERATIVE TURBINE PUMP 2006
89 JACC JAKARTA BUILDING FIRE PUMP 2006
90 ETERNIT GRESIK GRESIK FACTORY FIRE PUMP 2006
91 PLAZA ASIA TASIKMALAYA TASIKMALAYA BUILDING CHILLER PUMP 2006
92 IPEKA SCHOOL JAKARTA BUILDING FIRE PUMP 2006
93 PLAZA ASIA TASIKMALAYA TASIKMALAYA BUILDINGPLUMBING PUMPSUBMERSIBLE PUMPDEEP WELL PUMP
2007
94 TOYOTA ASTRA MOTOR JAKARTA FACTORY FIRE PUMP 2007
95 CARREFOUR CIBINONG BANDUNG BUILDING FIRE PUMP 2007
96CARREFOUR KIARA CONDONGMALL
BANDUNG BUILDING FIRE PUMP 2007
97 PERFETI VAN MELLE JAKARTA FACTORY FIRE PUMP 2007
98 DATA CENTER SURABAYA BUILDING FIRE PUMP 2007
99 TOYOTA ASTRA MOTOR JAKARTA FACTORY CHILLER PUMP 2007
100 GRAND INDONESIA JAKARTA BUILDINGCHILLER PUMP APARTMENT,CONVENTION HALL 2007
101 CNOOC OFFCHORE OFFSHORE OIL RIGVERTICALTURBINESEA WATER FIRE PUMP
2007
102 PASAR BARU SQUARE BALIKPAPAN HOTEL AND MALL FIRE PUMP 2007
103 SEMEN PADANG PADANG CEMENT INDUSTRY HVAC PUMP 2007
104 NESTLE - PASURUAN PASURUAN FACTORY FIRE PUMP 2007
105 ST. REGIS BALI BALI BUILDINGFIRE PUMP, CHILLER PUMPPLUMBING PUMP, DEEP WELLPUMP
2007
106 CARREFOUR RUNGKUT SURABAYA BUILDING FIRE PUMP 2007
107 PABRIK SUGIZINDO CIBINONG FACTORY FIRE PUMP 2007
108 SEK-NEG DIKLAT CIPETE JAKARTA BUILDING FIRE PUMP 2007
109 THE CITY TOWER JAKARTA OFFICE FIRE PUMP 2007
110 KEM TOWER KEMAYORAN JAKARTA BUILDING FIRE PUMP 2007
7/25/2019 Technical Data untuk project PLN.pdf
6/57
4
111 WATERPLACE RESIDENCE SURABAYA BUILDING FIRE PUMP 2007
112 SEASON CITY JAKARTA BUILDING FIRE PUMP 2007
113 HOTEL MALEOSAN MANADO BUILDING FIRE PUMP 2007
114 APARTMENT BSB BALIKPAPAN BUILDING FIRE PUMP 2007
115 HOLCIM INDONESIA JAKARTA BUILDING WATER SPRAY 2008
116 GRAHA 165 JAKARTA BUILDING CHILLER PUMP 2008
117 ARKADIA OFFICE JAKARTA BUILDING FIRE PUMP 2008
118 SAINATH OFFICE JAKARTA BUILDING FIRE PUMP 2008
119 GRAND CITY SURABAYA SURABAYA BUILDING CHILLER PUMP 2008
120 KEM TOWER KEMAYORAN JAKARTA BUILDING
PLUMBING PUMP,CHILLER PUMP,SUBMERSIBLE PUMP
2008
121 THE ADHIWANGSA RESIDENCE SURABAYA RESIDENTIAL FIRE PUMP 2008
122 DAPENRA JAKARTA BUILDING FIRE PUMP 2008
123 LUCKY SQUARE MALL BANDUNG BUILDING FIRE PUMP 2008
124 BEST WESTERN BALI HOTEL BALI BUILDING FIRE PUMP 2008
125 ASTON VERANDA HOTEL JAKARTA BUILDING FIRE PUMP 2008
126 SEMEN PADANG PADANG CEMENT INDUSTRY HVAC PUMP 2008
127 HOLCIM INDONESIA CILACAP CEMENT INDUSTRY WATER SPRAY 2008
128 CYBER-2 JAKARTA OFFICE FIRE PUMP 2008
129 HOTEL HILTON BANDUNG HOTEL FIRE PUMP 2008
130 SUDIRMAN TOWER JAKARTA BUILDING FIRE PUMP 2008
131 FREEPORT IRIAN JAYA MINING CIRCULATION PUMP 2008
132 GRAHA PENA SURABAYA BUILDING FIRE PUMP 2008
133 BPK PENABUR - KELAPA GADING JAKARTA BUILDING FIRE PUMP 2008
134 FLOUR MILLS - CILEGON CILEGON FACTORY FIRE PUMP 2008
135 MEDCO ENERGI SUMATERA OIL & GAS FIRE PUMP 2008
136 PARAGON CITY SEMARANG BUILDING FIRE PUMP 2008
137 MENARA MTH JAKARTA BUILDING FIRE PUMP 2008
138 QATAR EMBASSY JAKARTA BUILDING FIRE PUMP 2008
139 CYBER-2 JAKARTA OFFICE HVAC PUMP, PLUMBING PUMP 2008
140 MEDCO II SUMATERA OIL & GAS FIRE PUMP 2008
141 CYBER ANNEX JAKARTA BUILDINGFIRE PUMP, HVAC PUMP,PLUMBING PUMP
2008
142RENOVASI GEDUNG MAHKAMAHAGUNG, RI
JAKARTA BUILDING FIRE PUMP 2008
143 W HOTEL SEMINYAK BALI HOTEL FIRE PUMP 2008
144 EQUITY TOWER JAKARTA BUILDING FIRE PUMP 2008
145 DEPO PERTAMINA BOJONEGORO OIL & GAS FIRE PUMP 2008
146 SEASON CITY JAKARTA BUILDING HVAC PUMP 2008
147 DUFAN ANCOL JAKARTA BUILDING FIRE PUMP 2008
7/25/2019 Technical Data untuk project PLN.pdf
7/57
5
148 TRANS KALLA MAKASSAR BUILDING FIRE PUMP 2009
149 PUPUK KUJANG CIKAMPEK FACTORY HYDROMATIC PUMP 2009
150 INDOSAT SUKABUMI BUILDING FIRE PUMP 2009
151 IT BATAM BATAM BUILDING FIRE PUMP 2009
152 SAMPOERNA STRATEGIC SQUARE JAKARTA BUILDING HOT WATER PUMP 2009
153KANTOR PERWAKILAN PEMDASULUT
JAKARTA BUILDING FIRE PUMP 2009
154 LOMBOK AIRPORT LOMBOK BUILDING FIRE PUMP 2009
155 LAN SAMARINDA SAMARINDA BUILDING FIRE PUMP 2009
156 CENTRAL PARK JAKARTA BUILDING HVAC PUMP 2009
157 OFFICE KRAMAT RAYA JAKARTA BUILDING FIRE PUMP 2009
158 BINUS BOARDING HOUSE JAKARTA BUILDING FIRE PUMP 2009
159 BANDARA KUALANAMU MEDAN BUILDINGFIRE PUMP, CHILLER PUMP,PLUMBING PUMP
2009
160 PPPK PETRA SURABAYA BUILDING FIRE PUMP 2009
161 PUSDIKLAT MAHKAMAH AGUNG JAKARTA BUILDING FIRE PUMP 2009
162 WILMAR NABATI INDONESIA GRESIK INDUSTRY FIRE PUMP 2009
163 PUSDIKLAT MAHKAMAH AGUNG BOGOR BUILDING FIRE PUMP 2009
164 PERTAMINA ACEH EP RANTAU ACEH OIL & GAS FIRE PUMP 2009
165DINAS PEMADAM KEBAKARAN-LEBAK BULUS
JAKARTA BUILDING FIRE PUMP 2009
166 TEMPO SCAN TOWER JAKARTA BUILDING FIRE PUMP, CHILLER PUMP,PLUMBING PUMP
2010
167 CIK DITIRO APARTMENT JAKARTA BUILDING FIRE PUMP 2010
168 CENTRAL PARK CGPP II JAKARTA BUILDING CHILLER PUMP 2010
169 CENTRAL PARK BALL ROOM JAKARTA BUILDING CHILLER PUMP 2010
170 SEASON CITY SCHOOL JAKARTA BUILDING FIRE PUMP 2010
171PERTAMINA UPMS IV DEPOTREWULU
SEMARANG OIL & GAS FIRE PUMP 2010
172 PERTAMINA UPMS VII MAKASAR OIL & GAS FIRE PUMP 2010
173 KEMANG VILLAGE SCHOOL JAKARTA BUILDING FIRE PUMP 2010
174 KEMANG VILLAGE JAKARTA BUILDING FIRE PUMP 2010
175 RUSUNAMI GADING ICON JAKARTA RESIDENTIAL FIRE PUMP 2010
176 MENARA ALLIANZ JAKARTA BUILDING FIRE PUMP 2010
177PERTAMINA UPMS VII DEPOTMAKASAR
MAKASAR OIL & GASVERTICAL TURBINE - FIREPUMP
2010
178PERTAMINA UPMS III UJUNGBERUNG
BANDUNG OIL & GAS FIRE PUMP 2010
179 DPPU AVIASI KUALANAMU MEDAN MEDAN OIL & GAS FIRE PUMP 2010
180 MEDCO ENERGY M-12 TARAKAN KALIMANTAN OIL & GAS FIRE PUMP 2010
7/25/2019 Technical Data untuk project PLN.pdf
8/57
6
181KEMANG VILLAGE KVR & RITZTOWER
JAKARTA BUILDING FIRE PUMP 2010
182 CIPUTRA WORLD SURABAYA BUILDING FIRE PUMP 2010
183PERTAMINA UPMS III - LPGBALONGAN
BALONGAN OIL & GAS FIRE PUMP 2010
184 PERTAMINA UBEP TARAKAN TARAKAN OIL & GAS FIRE PUMP 2010
185 DPPU SOEKARNO HATTA CENGKARENG OIL & GAS VEHRTICAL SUMP PUMP 2010
186 HOTEL SENTRA KELAPA GADING JAKARTA BUILDING PLUMBING 2010
187 ANCOL MENTION JAKARTA BUILDING FIRE PUMP 2010
188 GEDUNG LEMIGAS CIPULIR JAKARTA BUILDING FIRE PUMP 2010
189 MEDCO EOR RIMAU PALEMBANG OIL AND GAS FIRE PUMP 2010
190 PERTAMINA EP PENDOPO PRABUMULIH OIL AND GAS FIRE PUMP 2010
191 SUNTER OFFICE JAKARTA BUILDING FIRE PUMP 2010
192KAWASAN PERGUDANGANNARAGONG
NARAGONG BUILDING FIRE PUMP 2010
193 KRAFT FOOD INDONESIA CIKARANG BUILDING FIRE PUMP 2010
194 HANG LEKIR RESIDANCE JAKARTA BUILDING FIRE PUMP 2010
195 CIPUTRA WORLD SURABAYA BUILDING FIRE PUMP 2010
196 CENTRAL PARK JAKARTA HOTEL FIRE PUMP 2011
197 RS. ADVENT BANDUNG BANDUNG BUILDING FIRE PUMP 2011
198 MENARA CITICON JAKARTA BUILDING FIRE PUMP 2011
199 BINUS SERPONG 3 JAKARTA BUILDING FIRE PUMP 2011
200 NUSANTARA TURBINE PROPULSI BANDUNG INDUSTRYVERTICAL TURBINE FIREPUMP
2011
201 GEDUNG BERSAMA GRAMEDIA JAKARTA BUILDING FIRE PUMP 2011
202 TANGERANG CITY MALL TANGERANG BUILDING CHILLER PUMP 2011
203 BOILER YOGYAKARTA INDUSTRY BOILER PUMP 2011
204 GALERI MODECOR JAKARTA BUILDING FIRE PUMP 2011
205 MALL OF KEDIRI KEDIRI BUILDING FIRE PUMP 2011
206PERTAMINA UPMS V DEPOTBADAS
SURABAYA OIL & GASVERTICAL TURBINE FIREPUMP
2011
207 PERTAMINA EP RANTAU ACEH OIL & GAS FIRE PUMP 2011
208 MALL SERANG BANTEN BANTEN BUILDING FIRE PUMP 2011
209 WHITZ HOTEL SEMARANG HOTEL FIRE PUMP 2011
210 ST.MORITZ JAKARTABUILDING-PRESIDENTIAL
FIRE PUMP 2011
211 ST.MORITZ JAKARTABUILDING-AMBASSADOR
FIRE PUMP 2011
212 SWISS BELL HOTEL BALI HOTEL FIRE PUMP 2011
7/25/2019 Technical Data untuk project PLN.pdf
9/57
7
213 REGENT HOTEL BALI HOTEL HVAC 2011
214 KAMPUNG ITSB CIKARANG BUILDING FIRE PUMP 2011
215 BANK RIAU RIAU BUILDING FIRE PUMP 2011
216 THE STONE BALI BALI BUILDING FIRE PUMP 2011
217 WISMA PONDOK INDAH III JAKARTA BUILDINGFIRE PUMP, PLUMBING PUMP,CHILLER PUMP, SUBMERSIBLEPUMP
2011
218 HOTEL NOVOTEL GAJAH MADA JAKARTA HOTEL FIRE PUMP, CHILLER PUMP 2011
219APARTMENT NOVOTEL GAJAHMADA
JAKARTA RESIDENTIAL FIRE PUMP 2011
220APARTMENT RUSUNAMI SUNTERPARK VIEW JAKARTA RESIDENTIAL FIRE PUMP 2011
221APARTMENT RUSUNAMI PURI PARKVIEW TOWER A,B & C
JAKARTA RESIDENTIAL FIRE PUMP 2011
222APARTMENT RUSUNAMI PURI PARKVIEW TOWER E
JAKARTA RESIDENTIAL FIRE PUMP 2011
223 GAJAH MADA PLAZA JAKARTA BUILDING CHILLER PUMP 2011
224 GUDANG DHL JAKARTA BUILDING FIRE PUMP 2011
225 IRMC SHOWROOM & OFFICE JAKARTA BUILDING FIRE PUMP 2011
226 GREEN BAY PLUIT TAHAP I JAKARTA BUILDINGPLUMBINGPUMP, SUBMERSIBLEPUMP
2011
227 HOTEL TRANS & IBIS BANDUNG BUILDING FIRE PUMP, CHILLER PUMP 2011
228 PERTAMINA EP KTI PAPUA SORONG OIL & GAS FIRE PUMP 2011
229PERTAMINA JAYAPURA DEPOTSORONG
PAPUA OIL & GAS FIRE PUMP 2011
230 ASAM ASAM COAL MINING KALIMANTAN MINING FIRE PUMP 2011
231 LOGO OFFICE JAKARTA BUILDING FIRE PUMP 2011
232 HOLIDAY INN SUNTER JAKARTA HOTELFIRE PUMP, PLUMBING PUMP,CHILLER PUP
2011
233 HOLIDAY INN SUNTER JAKARTA RUKAN FIRE PUMP, PLUMBING PUMP 2011
234 GUDANG GARAM TOWER JAKARTA BUILDING FIRE PUMP 2011
235 MEDAN CENTER POINT MEDAN BUILDING FIRE PUMP 2011
236PERTAMINA UPMS V - LPGTANJUNG PERAK
SURABAYA OIL & GAS FIRE PUMP 2011
237 SUJ INDOCHEM CILEGON CILEGON FACTORY FIRE PUMP 2011
238 ARMADA JOHNSON CONTROL CIKAMPEK FACTORY FIRE PUMP 2011
239PERTAMINA MAKASAR MULTIDEPOT
MAKASAR OIL & GAS JOCKEY PUMP 2011
240 PLTA BRANTAS SURABAYA POWER PLANT FIRE PUMP 2011
241 PERTAMINA EP PENDOPO PRABUMULIH OIL & GAS FIRE PUMP 2011
242PERTAMINA UPMS V - DEPOTSEMAMPIR
SURABAYA OIL & GASVERTICAL TURBINE FIREPUMP
2011
7/25/2019 Technical Data untuk project PLN.pdf
10/57
8
243 PERTAMINA LPG TANJUNG PRIOK JAKARTA OIL & GAS FIRE PUMP 2011
244PERTAMINA UPMS V - DPPUKUPANG
SURABAYA OIL & GAS FIRE PUMP 2011
245 PERTAMINA UBEB TANJUNG KAL-SEL OIL & GAS FIRE PUMP 2011
246 PABRIK ROKOK GUDANG GARAM SEMARANG FACTORY FIRE PUMP 2011
247 GEDUNG AUDITORIUM PT. AHM CIKARANG FACTORY FIRE PUMP 2011
248 U RESIDENCE JAKARTA BUILDING FIRE PUMP 2011
249 CIKINI GOLD CENTER JAKARTA BUILDING FIRE PUMP 2011
250 WEST MARK APARTMENT JAKARTA RESIDENTIAL FIRE PUMP 2011
251 GREEN BAY PLUIT TAHAP-1A JAKARTA BUILDING FIRE PUMP 2011
252 GEDUNG EXIM MELATI JAKARTA BUILDING CHILLER PUMP 2011
253 APM ARMADA AUTO PARTS CIKARANG FACTORY FIRE PUMP 2011
254PERTAMINA EP REGION JAWAFIELD CEPU
CEPU OIL & GAS FIRE PUMP2012
255 SRC FACTORY KARAWANG KARAWANG FACTORY FIRE PUMP 2012
256 PT. TEMPO JL. KEMUNING JAKARTA FACTORY FLOOD PUMP 2012
257PERTAMINA SURABAYA-DEPOTMAUMERE
SURABAYA OIL & GAS VERTICAL TURBINE- FIRE PUMP 2012
258 OTTO PHARMACEUTIAL BANDUNG FACTORY FIRE PUMP 2012
259PERTAMINA JAYAPURA DEPOTDOBO, TUAL & MERAUKE
JAYAPURA OIL & GAS FIRE PUMP 2012
260 MEDCO M12 TARAKAN SUMATERA OIL & GAS FIRE PUMP 2012
261 PERTAMINA PERTAGAS SUMATERA SUMATERA OIL & GAS FIRE PUMP 2012
262 PERTAMINA PRABUMULIH SUMATERA OIL & GAS FIRE PUMP 2012
263PERTAMINA UPMS III JBB DEPOTTASIKMALAYA
TASIKMALAYA OIL & GAS FIRE PUMP 2012
264PERTAMINA MAKASSAR DEPOTGORONTALO
MAKASSAR OIL & GAS FIRE PUMP 2012
265 PERTAMINA BITUNG MAKASSAR OIL & GAS JOCKEY PUMP 2012
266PERTAMINA UPMS III - DEPOTPADALARANG
JAWA BARAT OIL & GAS FIRE PUMP 2012
267 CNG SEI GELAM JAMBI OIL & GAS FIRE PUMP 2012
268 PERTAMINA BIAK, JAYAPURA JAYAPURA OIL & GAS FIRE PUMP 2012
269 PERTAMINA SEMARANG CILACAP JAWA TENGAH OIL & GAS FIRE PUMP 2012
270 PERTAMINA REWULU JOGJA OIL & GAS JOCKEY PUMP 2012
271SUGAR REFINERY MARUNDAJAKARTA
JAKARTA FACTORY FIRE PUMP 2012
272 SUJ CILEGON CILEGON FACTORY FIRE PUMP 2012
273 INDOFOOD CIKUPA - TANGERANG TANGERANG FACTORY FIRE PUMP 2012
7/25/2019 Technical Data untuk project PLN.pdf
11/57
9
274 PERTAMINA BALIKPAPAN KALIMANTAN OIL & GAS JOCKEY PUMP 2012
275 REGENT HOTEL BALI BUILDING CHILLER PUMP 2012
276 BANK MEGA CARD CENTER JAKARTA BUILDING FIRE PUMP 2012
277 PUSAT TIKI-JNE JAKARTA BUILDING FIRE PUMP 2012
278 KEMANG VILLAGE INFINITY-TOWER JAKARTA BUILDING FIRE PUMP 2012
279KEMANG VILLAGE INTERCONTOWER
JAKARTA BUILDING FIRE PUMP 2012
280 DHARMAWANGSA 101 HOTEL JAKARTA BUILDING FIRE PUMP 2012
281 MENARA PRIMA II JAKARTA BUILDINGCHILLER PUMP, SUBMERSIBLEPUMP
2012
282 RS. AKADEMIKA UGM JOGYAKARTA BUILDING FIRE PUMP 2012
283 HOTEL AMARIS NUSA 2 BALI BUILDING FIRE PUMP 2012
284 TRANS STUDIO BANDUNG BUILDING CIRCULATION PUMP 2012
285 THE WINDSOR APARTMENT JAKARTA BUILDING FIRE PUMP 2012
286 STREET GALERY PONDOK INDAH JAKARTA BUILDINGFIRE PUMP, SUBMERSIBLEPUMP
2012
287 GREEN BAY TAHAP II - MALL JAKARTA BUILDING FIRE PUMP 2012
288 PULOMAS PARK CENTER JAKARTA BUILDING FIRE PUMP 2012
289 AKADEMI PERKERETAAPIAN MADIUN BUILDING FIRE PUMP 2012
290 BANDARA SULTAN THAHA JAMBI BUILDING FIRE PUMP 2012
291 BANDARA DEPATI AMIR BANGKA BELITUNG BUILDING FIRE PUMP, PLUMBING PUMP 2012
292 PASAR SINPASA BEKASI BUILDING FIRE PUMP 2012
293 HOLIDAY INN EXPRESS BALI BUILDING FIRE PUMP 2012
294 GREEN LAKE SUNTER-TAHAP I JAKARTA BUILDING FIRE PUMP 2012
295 DSO DJARUM TANDES SURABAYA SURABAYA FACTORY FIRE PUMP 2013
296 BALI DESA NUSA DUA BALI BUILDING FIRE PUMP 2013
297 BANDARA DJUANDA SURABAYA BUILDING FIRE PUMP 2013
298 SIMPRUG BOTANICA JAKARTA BUILDING FIRE PUMP 2013
299 MENARA PRIMA 2 JAKARTA BUILDING PLUMBING PUMP 2013
300 CONDOTEL AWANA BALI BUILDING FIRE PUMP 2013
301 SHANGRILA HOTEL BALI BUILDING FIRE PUMP 2013
302PERTAMINA BALIKPAPAN DEPOTSAMARINDA
BALIKPAPAN OIL & GAS JOCKEY PUMP 2013
303PERTAMINA BALIKPAPAN DEPOTPANGKALAN BUN, DEPOT PULAUPISAU, DPPU JUWATA
BALIKPAPAN OIL & GAS FIRE PUMP 2013
304PERTAMINA BALIKPAPAN DEPOTSINTANG
BALIKPAPAN OIL & GAS FIRE PUMP 2013
7/25/2019 Technical Data untuk project PLN.pdf
12/57
10
305PERTAMINA BALIKPAPAN DEPOTTARAKAN
BALIKPAPAN OIL & GASVERTICAL TURBINE FIREPUMP
2013
306PERTAMINA BALIKPAPAN DEPOTBANJARMASIN
BALIKPAPAN OIL & GASVERTICAL TURBINE FIREPUMP
2013
307 HOTEL SANTIKA CIKARANG CIKARANG BUILDING FIRE PUMP 2013
308BALI NUSA DUA CONVENTIONCENTER
BALI BUILDING FIRE PUMP 2013
309 GEDUNG BINA MULYA 1 JAKARTA BUILDING CHILLER PUMP 2013
310 TOWER PLN BEKASI BEKASI PLN CIRCULATION PUMP 2013
311 PERTAMINA TBBM SERUI PAPUA OIL & GAS FIRE PUMP 2013
312 FLOUR MILL CILEGON CILEGON INDUSTRI FIRE PUMP 2013
313 PERTAGAS JAMBI TEMPINO JAMBI OIL & GAS FIRE PUMP 2013
314 PERTAMINA SANGATTAKALIMANTANTIMUR
OIL & GAS FIRE PUMP 2013
315THE MANSION @ DUKUH GOLFKEMAYORAN
JAKARTA BUILDING FIRE PUMP 2013
316 PERTAMINA TJILIK RIWUTKALIMANTANTENGAH
OIL & GAS FIRE PUMP 2013
317 PERTAMINA LPG DUMAI RIAU OIL & GAS FIRE PUMP 2013
318PERTAMINA REGION IV SEMARANG TBBM LOMANIS CILACAP
JAWA TENGAH OIL & GAS FIRE PUMP 2013
319 PERTAMINA EP FIELD TAMBUN JAWA BARAT OIL & GAS FIRE PUMP 2013
320
PERTAMINA REGION IV
SEMARANG-TBBM LOMANISCILACAP
JAWA TENGAH OIL & GAS JOCKEY PUMP 2013
321 PERTAMINA TBBM KAIMANA PAPUA OIL & GAS FIRE PUMP 2013
322 PERTAMINA LABUHA PAPUA OIL & GAS FIRE PUMP 2013
323
PERTAMINA UPMS VII SULAWESI TBBM MOUTONG& TBBM BANGGAI,TBBM LUWUK & TBBM POSO, TBBMRAHA, TBBM POSO, TBBMMOUTONG & TBBM BANGGAI
SULAWESI OIL & GAS FIRE PUMP 2013
324 PGN LAMPUNG LAMPUNG OIL & GAS FIRE PUMP 2013
325 DSO DJARUM TANDES JAWA TIMUR INDUSTRI FIRE PUMP 2013
326PANTAI INDAH KAPUK MAL &HOTEL
JAKARTA BUILDING FIRE PUMP 2013
327 SAHID SUDIRMAN CENTER JAKARTA BUILDING FIRE PUMP 2013
328HARRIS HOTEL & YELLO HOTELHAYAM WURUK
JAKARTA BUILDING FIRE PUMP 2013
329HOTEL HOLIDAY INN EXPRESS -CIKINI
JAKARTA BUILDING FIRE PUMP 2013
330 MENTENG PARK JAKARTA BUILDING FIRE PUMP 2013
331 HOTEL AMARIS PASAR MINGGU JAKARTA BUILDING FIRE PUMP 2013
7/25/2019 Technical Data untuk project PLN.pdf
13/57
11
332 HOTEL 101 LEGIAN BALI BUILDING FIRE PUMP 2013
333 HOTEL 101 JOGYAKARTA JOGYAKARTA BUILDING FIRE PUMP 2013
334 UPH KARAWACI TANGERANG BUILDING FIRE PUMP 2013
335 BINTARO PARK VIEW JAKARTA BUILDING FIRE PUMP 2013
336 HOTEL ALILA SCBD JAKARTA BUILDINGVERTICAL TURBINE FIREPUMP, PLUMBING PUMP,SUBMERSIBLE PUMP
2013
337 SOHO PODOMORO CITY JAKARTA BUILDING FIRE PUMP 2014
338 WOLRD VISION INDONESIA JAKARTA BUILDING FIRE PUMP 2014
339 LOBP BATAKAN BALIKPAPANKALIMANTANTIMUR
OIL & GAS FIRE PUMP 2014
340 PERTAMINA TBBM NABIRE PAPUA OIL & GAS FIRE PUMP 2014
341 PERTAMINA TBBM MASOHI MALUKU TENGAH OIL & GAS VERTICAL TURBINE 2014
342PABRIK PENGOLAHAN DAGING DIPURWAKARTA
JAWA BARAT INDUSTRI FIRE PUMP 2014
343 HOTEL BEST WESTERN SOLO SOLO BUILDING FIRE PUMP 2014
344 ELPIS RESIDENCE JAKARTA BUILDING FIRE PUMP 2014
345 BANDARA SUPADIO PONTIANAK BUILDING FIRE PUMP 2014
346 HOTEL 101 BOGOR BOGOR BUILDING FIRE PUMP 2014
347 PURI INDAH FINANCIAL TOWER JAKARTA BUILDING FIRE PUMP 2014
348 ONE BELPARK MALL JAKARTA BUILDING FIRE PUMP 2014
349 BATULICINKALIMANTANSELATAN
OIL & GAS VERTICAL TURBINE 2014
350 SENORO SULAWESI TENGAH OIL & GAS FIRE PUMP 2014
351 CENTRAL KITCHEN THE DUCK KING TANGERANG INDUSTRI FIRE PUMP 2014
352 GEDUNG GIS JAKARTA BUILDING FIRE PUMP 2014
353THE MANSION @ TOWERBOUGENVILLE
JAKARTA BUILDING FIRE PUMP 2014
354 MENARA SENTRAYA JAKARTA BUILDING FIRE PUMP 2014
355 HOTEL BEDROCK BALI BUILDING FIRE PUMP 2014
7/25/2019 Technical Data untuk project PLN.pdf
14/57
12
356 GOR PKP CIRACAS JAWA BARAT BUILDING FIRE PUMP 2014
357GARDEN WING APARTMENTKARAWANG
JAWA BARAT BUILDING FIRE PUMP 2014
358HOTEL ASTON & TRAININGCENTER, SENTUL
JAWA BARAT BUILDING FIRE PUMP 2014
359PABRIK PRINTING FLEXO DISIDOARJO
JAWA TIMUR INDUSTRI FIRE PUMP 2014
360PERTAMINA TBBM KOTA BARU &DEPOT LPG BALIKPAPAN
KALIMANTAN OIL & GASVERTICAL TURBINE FIREPUMP
2014
361 PABRIK DUA BERLIAN JAKARTA INDUSTRI FIRE PUMP 2014
362 PERTAMINA ELNUSA DEPOPLUMPANG
JAKARTA OIL & GAS FIRE PUMP 2014
363PERTAMINA EP ASSET 1 LIRIKFIELD
RIAU OIL & GAS FIRE PUMP 2014
364 PERTAMINA TBBM SANANA MALUKU OIL & GAS VERTICAL TURBINE 2014
365 MAXX BOX KARAWACI BUILDING FIRE PUMP 2014
366 HOTEL HARRIS BENOA BALI BUILDING FIRE PUMP 2014
367 HOTEL TIJILI SEMINYAK BALI BUILDING FIRE PUMP 2014
368 MALL & HOTEL PIK JAKARTA BUILDING PLUMBING PUMP 2014
369 CONVENTION HALL SAMARINDA BUILDING FIRE PUMP 2014
370 KAMPUS ITB TAHAP II BANDUNG BUILDING FIRE PUMP 2014
371PERTAMINA AREA SULAWESI BITUNG
SULAWESI OIL & GAS VERTICAL TURBINE 2014
372PERTAMINA DPPU SAM RATULANGIMANADO
SULAWESI OIL & GAS FIRE PUMP 2014
373 PERTAMINA FIELD TARAKAN SULAWESI OIL & GAS FIRE PUMP 2014
374PERTAMINA SULAWESI KOLONEDALE
SULAWESI OIL & GAS JOCKEY PUMP 2014
375 PERTAMINA BALONGAN BALONGAN OIL & GAS VERTICAL TURBINE 2014
376 PABRIK ETERNA GELORAPUTRA CIKUPA INDUSTRI FIRE PUMP 2014
377 ANCOL DOUBLE DECKER JAKARTA BUILDING FIRE PUMP 2014
378 CENTENIAL TOWER JAKARTA BUILDING FIRE PUMP 2014
379 HOTEL ALILA SCBD JAKARTA BUILDINGVERTICAL TURBINE-JOCKEYPUMP
2014
7/25/2019 Technical Data untuk project PLN.pdf
15/57
13
380 OAK TOWER JAKARTA BUILDING FIRE PUMP 2014
381 ST. REGIS - HOTEL JAKARTA BUILDING FIRE PUMP 2014
382 ST. REGIS - OFFICE JAKARTA BUILDING FIRE PUMP 2014
383 HOTEL GUNUNG GEULIS BOGOR BUILDING FIRE PUMP 2014
384NPK GRANULAR II PT. PUPUKKUJANG
CIKAMPEK INDUSTRI FIRE PUMP 2015
385 PGN JAWA BARAT OIL & GAS FIRE PUMP 2015
386 PERTAMINA DEPOT SINTANG KALIMANTANBARAT
OIL & GAS FIRE PUMP 2015
387 PABRIK KERTAS CIKARANG BARAT INDUSTRI FIRE PUMP 2015
388 PERTAMINA SANGA SANGA KALIMANTAN OIL & GAS FIRE PUMP 2015
389 PABRIK ETERNIT GRESIK JAWA TIMUR INDUSTRI FIRE PUMP 2015
390 PABRIK VALEO PURWAKARTA INDUSTRIVERTICAL TURBINE & JOCKEYPUMP
2015
391 HOTEL ARCS JAMBULUWUK BALI BUILDING FIRE PUMP 2015
392MEDAN CENTER POINT APARTMENT CENTRUM & CENTRIA
MEDAN BUILDING FIRE PUMP 2015
393 MENARA PALMA II JAKARTA BUILDING FIRE PUMP 2015
394 ST. MORITZ II - OFFICE TOWER JAKARTA BUILDING FIRE PUMP 2015
395 PLAZA SADIRA PEKANBARU BUILDING FIRE PUMP 2015
396 PERTAMINA FIELD TANJUNGKALIMANTANSELATAN
OIL AND GAS FIRE PUMP 2015
397 APARTMENT LA CITY JAKARTA BUILDING FIRE PUMP 2015
398 HOTEL ARTOTEL SANUR BALI BUILDING FIRE PUMP 2015
399 MARVEL CITY HOTEL & MALL SURABAYA BUILDING CHILLED PUMP 2015
400 YAYASAN LIA CIBUBUR JAKARTA BUILDING FIRE PUMP 2015
401 MENARA PERTIWI JAKARTA BUILDINGFIRE PUMP, PLUMBING PUMP &HVAC PUMP
2015
402 PLAZA SADIRA PEKANBARU BUILDING FIRE PUMP 2015
403 PIK HOTEL NOVOTEL & IBIS JAKARTA BUILDING PLUMBING PUMP 2015
7/25/2019 Technical Data untuk project PLN.pdf
16/57
14
404 TAMANSARI HIVE OFFICE PARK JAKARTA BUILDING FIRE PUMP 2015
405 HOTEL IBIS LEGIAN BALI BUILDING FIRE PUMP 2015
406 JICT EXPANSION- PHASE 6,7,8 & 10 JAKARTA BUILDING FIRE PUMP 2015
407 CNG BANGKANAIKALIMANTAN
TENGAHOIL AND GAS FIRE PUMP 2015
408 TARJUNKALIMANTANSELATAN
INDUSTRI FIRE PUMP 2015
409 TERMINAL LPG BANYUWANGI JAWA TIMUR OIL AND GAS FIRE PUMP 2015
410 COAL FIRED POWER STATION,BABELAN
JAWA BARAT OIL AND GAS FIRE PUMP 2015
411 PERTAMINA BIAK PAPUA OIL AND GAS VERTICAL TURBIN PUMP 2015
412INDIAN OIL TANKING, KARIMUN,KEPRI
RIAU OIL AND GAS FIRE PUMP 2015
413 INDOFOOD NOODLE NEW CIREBON INDUSTRI FIRE PUMP 2015
414 GARDENIA CIBINONG JAWA BARAT INDUSTRI FIRE PUMP 2015
415COAL FIRED POWER STATION,BABELAN
JAWA BARAT OIL AND GAS ELECTRIC FIRE PUMP 2015
416EPCI FOR LIMA POWER ANDSAFETY SYSTEM UPGRADE
PROJECT
JAKARTA OIL AND GAS VERTICAL TURBIN PUMP 2015
417 PETRO KIMIA JAKARTA OIL AND GAS FIRE PUMP 2015
418PT. INDOFOOD CBP SUKSESMAKMUR
CIKAMPEK INDUSTRI CHILLER PUMP 2015
419 TRIVIUM APARTMENT CIKARANG BUILDING FIRE PUMP 2015
420 HOTEL AMARIS SATRIO KUNINGAN JAKARTA BUILDING FIRE PUMP 2015
421 HOTEL MAXONE BALI BUILDING FIRE PUMP 2015
422 GCNM TOWER JAKARTA BUILDING FIRE PUMP 2015
423 PONDOK INDAH HOTEL JAKARTA BUILDING FIRE PUMP 2015
424 RESIDENCE PONDOK INDAH JAKARTA BUILDING FIRE PUMP 2015
425 MENARA PERTIWI JAKARTA BUILDING BOOSTER PUMP 2015
426KEMENTERIAN KOMUNIKASI DANINFORMATIKA
JAKARTA BUILDING FIRE PUMP 2015
427 BINUS ANGGREK JAKARTA BUILDING TRANSFER PUMP 2015
7/25/2019 Technical Data untuk project PLN.pdf
17/57
15
428 CNG MARINE LOMBOK OIL AND GAS FIRE PUMP 2016
429 B-BRAUN INDO TAISEI CIKAMPEK INDUSTRI FIRE PUMP 2016
430 MORTAR UTAMA CIBITUNG INDUSTRI FIRE PUMP 2016
431 MORTAR UTAMA GRESIK INDUSTRI FIRE PUMP 2016
432EPCI PENGEMBANGAN DPPUSEPINGGAN
BALIKPAPAN OIL AND GAS FIRE PUMP 2016
433 PALEMBANG PALEMBANG INDUSTRI FIRE PUMP 2016
444 SORINI SURABAYA INDUSTRI FIRE PUMP 2016
445 WAREHOUSE MODERN MARKET CIKINI INDUSTRI FIRE PUMP 2016
446 PONDOK INDAH RESIDENCE JAKARTA BUILDING FIRE PUMP 2016
447 CHEVRON INDONESIA COMPANY BALIKPAPAN OIL AND GAS FIRE PUMP 2016
448 TANJUNG UBAN KEPULAUAN RIAU OIL AND GAS VERTICAL TURBINE PUMP 2016
449 PERTAGAS PALEMBANG PALEMBANG OIL AND GAS VERTICAL TURBINE PUMP 2016
7/25/2019 Technical Data untuk project PLN.pdf
18/57
INDUSTRIAL PUMPS
POWERWWW.PENTAIR.COM
7/25/2019 Technical Data untuk project PLN.pdf
19/57
Cooling Tower PumpsPentairs tradition as a leader in
vertical turbine and split case pumpscontinues with the rugged and heavyduty, family of Pentair vertical turbineand split case pump products,designed to successfully operate in a multitude ofwater sources such as raw water intake, liquid transfer,cooling water circulation, booster service, storm water,flood control, marine, process services, volatile fluids,condensate, fuel pumps and mine dewatering.
Circulating Water PumpsStrong. Dependable. Reliable.
Pentairs tradition of leadership continues with theseattributes in the manufacture of Vertical Mixed and AxialFlow Propeller Pumps. Designed for moderate to highvolume fluid movement from moderate to low dischargepressures, both product lines have excellent low NPHSrequirements and are only separated by the amount of heador pressure to be developed.
The advantages of mixed flow pumps include
minimum footprint, no priming required. In addition,vertical mixed flow pumps are easily adaptableto various design codes, can be modified for changinghydraulic conditions, and generally experience less weardue to the lower operating speeds they require.
Pentair vertical axial flow propeller pump applicationsare found in a variety of markets including urban andrural municipal water, government, industrial, irrigation,and more.
Boiler Feed PumpsWith the 7600 series turbine pump Pentair brings itscentury of experience to a pinnacle. The 7600 series pumpis a multistage, horizontal, radially split pump for highpressure service.
With 30-50% fewer stages, 10+ point higher efficienciesallowing for the use of smaller motors and less powerconsumption and available pressures up to 2000psi (1400 mlc),The 7600 series maximizes cost containment and otheroperational efficiencies for the user.
Applications
INDUSTRIAL PUMPS POWER
Contact your
local sales
representative
for availability.
Contact your
local sales
representative
or availability.
Cooling TowPentairs tradition as
vertical turbine and splicontinues with the ruggedduty, family of Pentair verticaland split case pump products,designed to successfully operate inwater sources such as raw water intacooling water circulation, booster servicflood control, marine, process services, volcondensate, fuel pumps and mine dewatering.
Circulating Water PumpsStrong. Dependable. Reliable.
Pentairs tradition of leadership continues with theseattributes in the manufacture of Vertical Mixed and AxialFlow Propeller Pumps. Designed for moderate to highvolume fluid movement from moderate to low dischargepressures, both product lines have excellent low NPHSrequirements and are only separated by the amount of heador pressure to be developed.
he advantages of mixed flow pumps include
minimum footprint, no priming required. In addition,vertical mixed flow pumps are easily adaptableto various design codes, can be modified for changing
ydraulic conditions, and generally experience less wdue to the lower operating speeds they require.
Pentair vertical axial flow propeller pump appliare found in a variety of markets including uural municipal water, government, indus
and more.
Boiler Feed PumpsWith the 7600 series turbcentury of experiences a multistage, horiressure service.
With 30-50%allowing foconsum
he 7op
App
7/25/2019 Technical Data untuk project PLN.pdf
20/57
WWW.PENTAIR.COM
ApplicationsFire Water PumpsPentair, with its Fairbanks Nijhuisand
Auroraline of products, is the world leaderin UL/FM, NFPA 20 fire pumps in the world.Vertical turbine, horizontal split case, verticallymounted split case, inline and end suctionlabeled fire pumps are available.
General Service PumpsThe Pentair Aurora line of end suction and ANSI Std. B73.1M pumps areone of the most comprehensive product line offerings available. Verticalmountings, in line mounting and even sump pumps are available withPentair Aurora pumps.
Both flanged and threaded connections are availabledepending upon model.
Ash Sluice PumpsPumping fly ash in water suspension is tough duty for a pump.Pentairs Fairbanks Nijhuis 4500/4600/4700series high chrome iron, recessed impellerpumps are up to the task.
They also can be used in other abrasiveservices which require a 600+ BrinellHardness to resist wear andpremature failure.
7/25/2019 Technical Data untuk project PLN.pdf
21/57
ApplicationsRaw Water Intake PumpsPentairs Fairbanks Nijhuisand Auroralines of
products have extensive experience in both verticalturbine and horizontal splitcase pumps in raw water intakeservices. High reliability andrugged constructionmaximize service lifewhile high efficienciesreduce powerconsumption.
Condensate and Heater Drain PumpsPentairs vertical pumps are up to the task of pumping hotcondensate efficiently and reliability. Broad material selection isbased on properties of the condensate.
Low NPSHA impellers are available on many sizes to minimizeinstallation costs and suction vessel length.
INDUSTRIAL PUMPS POWER
Product quality, dependability, and innovation are all part of the Pentaircommitment to excellence. Whatever your needs, Pentair has you covered!
7/25/2019 Technical Data untuk project PLN.pdf
22/57
WWW.AURORAPUMP.COM
AURORA
SPLIT CASE FIRE PUMPS
VERTICAL SPLIT CASE PUMPHORIZONTAL SPLIT CASE PUMP
Built Per NFPA 20
411SERIES
7/25/2019 Technical Data untuk project PLN.pdf
23/57
SPLIT CASE FIRE PUMPS
AURORA
Split Case Fire Pumps
Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:
Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
Aurora split case fire pumps are built per the rigid standards of
NFPA 20 and are listed by Underwriters Laboratories (UL) and
approved by Factory Mutual (FM).
Available in a broad range of operating pressures and flows
from a minimum of 250 GPM, Aurora split case pumps can bedriven by either an electric motor or diesel engine. Auroras
system controller, with a full range of options and accessories
In addition to horizontal split case pumps, Aurora also offers
split case performance in a vertical format. Vertical fire pumps
provide distinct advantages over horizontal pump constructions.
in most cases.
pump station is in a low area.
411SERIES
7/25/2019 Technical Data untuk project PLN.pdf
24/57WWW.AURORAPUMP.COM
SPLIT CASE FIRE PUMPS
Pump Features
1. Computer Machined major components with 360 degree registered
fits to assure concentricity of parts.
2.
Integral Bearing Arms eliminate bearing misalignment andsimplify maintenance.
3. Enclosed Impeller Designprovides high efficiency and performance.
4. Dynamically Balanced Impeller
shaft sleeves.
5. Double Suction Impeller balances hydraulic thrust loads.
6. Cast Iron Drip Rim Basedirects condensation and any stuffing box
7. Short Bearing Span holds shaft deflection to .002" at face of
stuffing box at maximum load.
8. Internal Water Seal Passagesbetween volute and stuffing box cannot
be damaged.
9.
Interwoven, GraphiteImpregnated T.F.E.
the pump shaft.
10. Stuffing Boxes
11. Double Row Thrust ball bearing.
12. Grease Seals
protect both bearings during pump operation
and washdown.
13. Bearings selected for 50,000 hour minimum life
at maximum load. Average bearing life
5 x minimum.
14. Split Case Design simplifies disassembly. The suction and
discharge piping and shaft alignment are
not disturbed.
15. O-Ring Sealed Shaft Sleeves prevent corrosion of the shaft. This eliminates
the need for stainless steel shafts.
16. Case Wearing Rings and throttle bushings protect the
casing from wear and are easily and
inexpensively replaced.
17. Bronze Shaft Sleeve prevents shaft wear, is slip fit over the shaft,
of the seal box.
18. Certified Performance Testwith Positive Suction Pressure
is provided for each fire pump for customerapproval. Pumps are also hydrostatically tested
per NFPA 20 at no less than 250 psi.
65
4
3
2
1
7
8
9
10
11
13
1415 16
17
1812
HORIZONTALSPLIT CASE
VERTICALSPLIT CASE
7/25/2019 Technical Data untuk project PLN.pdf
25/57
800 AIRPORT ROAD, NORTH AURORA, ILLINOIS 60542 WWW.AURORAPUMP.COM
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
AF-02-1033 11/26/12 2012 Pentair Ltd. All Rights Reserved.
Fire Pump Feature SelectorStandard
Optional
increasers and reducers, waste cones, and more.
HYDRAULIC
19
INSTITUTE
17
ISO
90
01
REGIS
TEREDQUAL
ITY
SYSTEM
SUCTION
STANDARDRIGHT-HAND ROTATION(TOP VIEW HORIZONTAL PUMP)
SUCTION
OPTIONALLEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP)
VERTICAL PUMPS PROVIDEIN-LINE PIPING IN ANY DIRECTION
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
7/25/2019 Technical Data untuk project PLN.pdf
26/57
qwertyuiopasdfghjklzxcvbnmqwerty
opasdfghjklzxcvbnmqwertyuiopasdfg
klzxcvbnmqwertyuiopasdfghjklzxcvb
nmqwertyuiopasdfghjklzxcvbnmqwe
yuiopasdfghjklzxcvbnmqwertyuiopa
dfghjklzxcvbnmqwertyuiopasdfghjklz
vbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyu
pasdfghjklzxcvbnmqwertyuiopasdfgh
klzxcvbnmqwertyuiopasdfghjklzxcvbmqwertyuiopasdfghjklzxcvbnmqwer
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzxvbnmqwertyuiopasdfghjklzxcvbnmrt
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzx
Spare Part List BookController Model : GPD
PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
Preparedby
:PT.
Roda
Nurmala
ELECTRIC FIRE PUMP NFPA-20
AURORA HORIZONTAL SPLIT CASE
Model : 411-4x5x11D/Single Stage
PLN
7/25/2019 Technical Data untuk project PLN.pdf
27/57
Pump Data Sheet - AURORA PUMPS
mpany: PT RODA NURMALA
me: PLN
e: 6/17/2016
Size: 4x5x11D
Type: 410 1 STG SPLIT CASE Speed: 2950 rpmSynch speed: 3000 rpm Dia: 8.25 in
Curve: PC-193673 Impeller: 444A476
Specific Speeds: Ns: 1060Nss: 8457
Dimensions: Suction: 5 inDischarge: 4 in
Temperature: 275 F Power: ---Pressure: 250 psi g Eye area: ---Sphere size: 0.56 in
Search Criteria:
Flow: 634 US gpm Head: 177 ft
Secondary Operating Point: 951 US gpm, 140 ft
Fluid:
Water Temperature: 68 FDensity: 62.32 lb/ft Vapor pressure: 0.3391 psi aViscosity: 0.9946 cP Atm pressure: 14.7 psi a
NPSHa: ---
Motor:
Size: 50 hpSpeed: 3000Frame: 324T
Standard: NEMAEnclosure: ODP
Sizing criteria: Max Power on Design Curve
Optimize 10.6.1.0 Selected from catalog: Aurora Pumps 50 Hz V
---- Data Point ----
low: 634 US gpm
ead: 179 ft
ff: 70%
ower: 40.4 hp
PSHr: 9.37 ft
---- Design Curve ----
hutoff head: 205 ft
hutoff dP: 88.7 psi
Min flow: ---
EP: 75% @ 854 US gpm
OL power:
48.8 hp @ 1298 US gpm
-- Max Curve --
Max power:
117 hp @ 1671 US gpm
Curve effic iencies are typical. For guaranteed values contact Aurora Pump or your local distr ibutor. Las eficiencias
curvas son tipicas. Para valores garantizados contacte a Aurora Pump o a su distribuidor local.
US gpmNPSHr-ft
1600140012001000800600400
0
200
25
50
Head
-ft
160014000
1200
50
1000
100
800
150
600
200
400
250
200
300
75
8.25 in
10.5 in
7.06 in
25 hp
30 hp
40 hp50 hp
60 hp75 hp
1
1
30
30
40
40
50
50
60
60
60
60
65
65
65
65
70
70
70
70
75
75
Performance Evaluation:
Flow Speed Head Efficiency Power NPSHr
US gpm rpm ft % hp ft
761 2950 165 74 42.8 11.7
634 2950 179 70 40.4 9.37
507 2950 190 64 37.7 7.6
380 2950 198 54 34.7 7.4
254 2950 203 41 31.3 7.4
EFP Cap. 144 M3/H @ 54 Meter Total Head
7/25/2019 Technical Data untuk project PLN.pdf
28/57
7/25/2019 Technical Data untuk project PLN.pdf
29/57
7/25/2019 Technical Data untuk project PLN.pdf
30/57
7/25/2019 Technical Data untuk project PLN.pdf
31/57
7/25/2019 Technical Data untuk project PLN.pdf
32/57
7/25/2019 Technical Data untuk project PLN.pdf
33/57
qwertyuiopasdfghjklzxcvbnmqwerty
opasdfghjklzxcvbnmqwertyuiopasdfg
klzxcvbnmqwertyuiopasdfghjklzxcvb
nmqwertyuiopasdfghjklzxcvbnmqwe
yuiopasdfghjklzxcvbnmqwertyuiopa
dfghjklzxcvbnmqwertyuiopasdfghjklz
vbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyu
pasdfghjklzxcvbnmqwertyuiopasdfgh
klzxcvbnmqwertyuiopasdfghjklzxcvbmqwertyuiopasdfghjklzxcvbnmqwer
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzxvbnmqwertyuiopasdfghjklzxcvbnmrt
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzx
Spare Part List BookController Model : GPD
PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
Preparedby
:PT.
Roda
Nurmala
DIESEL FIRE PUMP NFPA-20
AURORA HORIZONTAL SPLIT CASE
Model : 411-4x5x11D/Single Stage
PLN
7/25/2019 Technical Data untuk project PLN.pdf
34/57
Pump Data Sheet - AURORA PUMPS
mpany: PT RODA NURMALA
me: PLN
e: 6/20/2016
Size: 4x5x11D
Type: 410 1 STG SPLIT CASE Speed: 2950 rpmSynch speed: 3000 rpm Dia: 210 mm
Curve: PC-193673 Impeller: 444A476
Specific Speeds: nq: 21S: 164
Dimensions: Suction: 125 mmDischarge: 100 mm
Temperature: 135 C Power: ---Pressure: 1724 kPa g Eye area: ---Sphere size: 14.2 mm
Search Criteria:
Flow: 144 m/hr Head: 54 m
Secondary Operating Point: 216 m/hr, 43 m
Fluid:
Water Temperature: 20 CDensity: 998.3 kg/m Vapor pressure: 2.339 kPa aViscosity: 0.9946 cP Atm pressure: 101.4 kPa a
NPSHa: ---
Motor:
Size: 37 kWSpeed: 3000Frame: 324T
Standard: NEMAEnclosure: ODP
Sizing criteria: Max Power on Design Curve
Optimize 10.6.1.0 Selected from catalog: Aurora Pumps 50 Hz V
---- Data Point ----
low: 144 m/hr
ead: 54.8 m
ff: 71%
ower: 30.3 kW
PSHr: 2.85 m
---- Design Curve ----
hutoff head: 62.8 m
hutoff dP: 615 kPa
Min flow: ---
EP: 75% @ 194 m/hr
OL power:
36.7 kW @ 296 m/hr
-- Max Curve --
Max power:
87.4 kW @ 380 m/hr
Curve effic iencies are typical. For guaranteed values contact Aurora Pump or your local distr ibutor. Las eficiencias
curvas son tipicas. Para valores garantizados contacte a Aurora Pump o a su distribuidor local.
m/hr
NPSHr-m
350300250200150100
0
50
5
10
15
Head-m
35030010
250
20
30
200
40
50
150
60
70
100
80
90
50
100
75.1
210 mm
267 mm
179 mm
18.7 kW
22 kW
30 kW37 kW
45 kW
56 kW
7
9
30
30
40
40
50
50
60
60
60
60
65
65
65
65
70
70
70
70
75
75
Performance Evaluation:
Flow Speed Head Efficiency Power NPSHr
m/hr rpm m % kW m
173 2950 50.7 74 32.1 3.56
144 2950 54.8 71 30.3 2.85
115 2950 58.3 64 28.3 2.31
86.4 2950 60.6 54 26 2.26
57.6 2950 62.1 41 23.5 2.26
DFP Cap. 144 M3/H @ 54 Meter Total Head
7/25/2019 Technical Data untuk project PLN.pdf
35/57
7/25/2019 Technical Data untuk project PLN.pdf
36/57
FIRE PUMP ENGINES
MODEL
JU4H-NL
JU4H-NL
JU4H-NL
JU4H-NL50JU4H-NL22
JU4H-NL34JU4H-NL20
JU4H-NL24JU4H-NL14
159.5
146
126.5
91
78
119
109
94
68
58
3000
159.5
146
126.5
91
78
119
109
94
68
58
2960
159.5
146
114
88
77
119
109
85
66
57.5
2800
153
140
93.5
82.5
83
65
114
104
70
61.5
62
48.5
2600
138
140
93.5
80
80
61
103
104
70
60
60
46
2400
134
140
140
93.5
79
79
79
60.5
100
104
104
70
59
59
59
45
2350
RATED SPEED
106
56
2200
142
75
1431071371021239212190NL50
NL52
NL22
54
2100
7353
2000
7150
1800
67
NL54
NLK4
NL34
NL24
NL14
6649NL20
1760
JU4H
MODEL
NON-LISTED HEAT EXCHANGER COOLED ENGINES
GROSS POWER RATINGS KW/BHP
NL34 NL50/52
17.0:1
424 (935)
T
NL20/22 NLK4/54NL24
C07575Wiring Diagram DC
4Number of Cylinders
John Deere 4045 SeriesEngine Series
C07591Wiring Diagram AC
D525Installation Drawing
4.19 x 5.00 (106 x 127)Bore & Stroke mm (in.)
4 Stroke Cycle Inline ConstructionEngine Type
4.5 (275)Displacement l (cu. in.)
17.6:1Compression Ratio
413 (910)Weight kg (lb)
CWRotation*
NAAspiration
NL14
JU4H MODELSITEM
SPECIFICATIONS
Abbreviations: CW Clockwise NA Naturally Aspirated T Turbocharged
*Rotation viewed from Heat Exchanger / Front of Engine
CERTIFIED POWER RATING
Each engine is factory tested to verify power and performance.
Although ratings are shown at specific speeds, Clarke engines can be applied at any
intermediate speed. To determine the intermediate speed power; make a linear
interpolation from the Clarke certified power curve. Contact Clarke or your Pump
OEM Representative to obtain details.
ENGINE RATINGS BASELINES
Engines are not to be used for continuous duty. Engines are to be used only for stationary
emergency standby fire pump service.
Engines are rated at standard SAE conditions of 29.61 in. (7521 mm) Hg barometer and
77F (25C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the
testing laboratory (see SAE Standard J 1349).
A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
conditions shall be made for diesel engines for every 10F (5.6C) above 77F (25C)ambient temperature.
Power Rating: A 10% deduction in power must be made to determine the maximum allowable pump load
UK Purchased1275 mm
1156 mm
T-Models
1029 mmNA-Models
356 mm
OVERALL WIDTH
740 mm
Page 1 of 8
7/25/2019 Technical Data untuk project PLN.pdf
37/57
ENGINE EQUIPMENT
Specifications and information contained in this brochure subject to change without notice.C133457 revA14APR10
FIRE PUMP ENGINES
Fax +1-513-771-0726Tel +1-513-475-FIRE (3473)
www.clarkefire.com
United States of America
3133 E. Kemper Rd., Cincinnati, Ohio 45241
Fire Protection Products, Inc.
Fax +44-1236-427274Tel +44-1236-429946
www.clarkefire.com
United Kingdom
Grange Works, Lomond Rd., Coatbridge, ML5-2NN
UK, Ltd.
MODELS
Industrial with Clamped ConnectionsSilencer
12V-DC Energized to Run; 24V-DC Energized to Run; 24V-DC
Energized to Stop
12V-DC Energized to StopRun Solenoid
Adjustable Speed Control, Tamper ProofThrottle Control
Two (2) 12-V-DC; One (1) 24V-DC; Two (2) 24V-DCOne (1) 12V-DCStarters
Centrifugal Type, Single Poly-Vee Belt Drive with GuardCentrifugal Type, Dual Poly-Vee Belt Drive with GuardWater Pump
On Instrument Panel with Control Position Warning LightManual Stop LeverRun Stop Control
Automatic from Engine Controller and from Engine Instrument
Panel
Raw Water Solenoid Operation
Electronic with Reset and Test on Instrument PanelOverspeed Control
On Instrument Panel with Control Position Warning LightManual Start Control
Gear Driven, Gear TypeLube Oil Pump
Full Flow with By-Pass ValveLube Oil Filter
Engine Water Cooled, Plate TypeLube Oil Cooler
Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Junction Box
English and Metric, Tachometer, Hourmeter, Water Temperature,
Oil Pressure and Two (2) Voltmeters
Instrument Panel
Tube and Shell Type, 14 BAR (206 PSI), BSP(F) ConnectionsHeat ExchangerConstant Speed, MechanicalGovernor, Speed
240V-AC, 1500 Watt; 120V-AC, 1500 WattEngine Heater
Stanadyne Direct InjectionFuel Injection System
Primary Filter with Priming PumpFuel Filter
Fire Resistant Flexible Supply and Return LinesFuel Connections
11.5 SAE Industrial Flywheel ConnectionFlywheel Power Take Off
SAE #3Flywheel Housing
Stainless Steel Flex, Clamped Connection, 3 for NL14/20/22/24;
Stainless Steel Flex, Clamped Connection, 4 for NL34/50/52/K4/54
Exhaust Flex Connection
Centaflex; DriveshaftCoupling
Blankets on JU4H-NL14/20/22/24;
Metal Guards on Manifolds and Turbo on JU4H-NL34/50/52/K4/54
Exhaust Protection
12V-DC, 42 Amps with Belt Guard;
24V-DC, 40 Amps with Belt Guard
Alternator
Disposable, Drip Proof, Indoor Service Outdoor TypeDirect Mounted, Washable, Indoor Service with Drip ShieldAir Cleaner
OPTIONALSTANDARDEQUIPMENT
Abbreviations: DC Direct Current, AC Alternating Current, SAE Society of Automotive Engineers, BSP(F) British Standard Pipe Thread (Female)
JU4H-NL54
JU4H-NLK4
JU4H-NL52
JU4H-NL50JU4H-NL22
JU4H-NL34JU4H-NL20
JU4H-NL24JU4H-NL14
Page 2 of 8
7/25/2019 Technical Data untuk project PLN.pdf
38/57
GROSS kW
45
48.5
57.5
58
1750 2000 2250 2500 2750 3000 3250
35
40
45
50
55
60
65
RESTRICTED:
DATE CREATED
DRAWING NO. REVC
ENGINE MODEL JU4H-NL14
11/08/04
C131979
THIS DRAWING AND THE IN-FORMATION HEREIN ARE OURPROPERTY AND MAY BE USED BYOTHER ONLY AS AUTHORIZED BYUS. UNPUBLISHED -- ALL RIGHTSRESERVED UNDER THECOPYRIGHT LAWS.KEN WAULIGMAN 18SEP09
CREATED
USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS
FIRE PUMP MODEL: JU4H-NL14
Heat Exchanger
Naturally Aspirated
4.5L 4 Cylinder
ENGINE SPEED - RPM
STANDARD CONDITIONS: (SAE J1349, ISO 3046)77F (25C) AIR INLET TEMPERATURE29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE#2 DIESEL FUEL (SEE C13940)
ENGINE PERFORMANCE:Reduce published Gross kWs by 10% to determinemaximum pump load.
Page 3 of 8
7/25/2019 Technical Data untuk project PLN.pdf
39/57
CLARKE
Fire Protection Products
Basic Engine Descriptio
John Deere Co.
Compression (Diesel)
4
106 (4.19) x 127 (5.0)
4.5 (275)
17.0:1
Valves per cylinder - 1
1
Direct Injection
Rotary, 4 Stroke Cycle
Naturally Aspirated
1-3-4-2
Rotation (Viewed from Front) - Standard
Not Available
Open
D-545
Cooling System - 3 Pass 2350 2600 2800 3000
32 (30) 34 (32) 36 (34) 38 (36)
6 (6) 7 (7) 8 (8) 8 (8)
13 (12) 14 (13) 17 (16) 17 (16)
30 (8) 34 (9) 37 (10) 40 (11)
38 (10) 42 (11) 45 (12) 48 (13)
14 (203) (1400)
Flow - L/Min. (Gal./min.)........100 (26)
Thermostat, 86 (187)
91 (196)14 (15)
69 (10)
93 (200)
71 (160)
Electric System - DC
12 24
12 24
1 2
4D-640 4D-640
640 640
285 285
0.0012 0.0012
0 -120 m 00 00
121 - 160 m 000 000
161 - 200 m 0000 0000
40 40
380 250
JU4H-NL14
INSTALLATION & OPERATION DATA
*Positive and Negative Cables Combined Length
Engine Manufacturer....
Ignition Type.....................
Number of Cylinders.............
Bore and Stroke - mm (in.).........
Displacement - L(in.3)..........
Compression Ratio..........
Intake...........
Exhaust...........
Combustion System..........
Engine Type............
Aspiration.............
Firing Order (CW Rotation).........
Clockwise.......
Counter-Clockwise.....
Engine Crankcase Vent System........
Installation Drawing.........
Engine H2O Heat - kW (Btu/sec)........
Engine Radiated Heat (With Blanket) - kW (Btu/sec)....
Heat Exchanger Minimium Flow
Engine Radiated Heat (Without Blanket) - kW (Btu/sec).
Engine Coolant Capacity - L (qt.).........
Coolant Pressure Cap - kPa (lb./in.2)......
15C (60F) Raw H2O - L/min. (gal/min.)....
35C (95F) Raw H2O - L/min. (gal/min.)....
Heat Exchanger Maximum Cooling H2O
Max. Inlet Pressure - bar (lb./in.2)(kPa)
Voltage (Nominal)...........
Qty. per Battery Bank.........
SAE size per J537...........
UK Production
Maximum Engine H20 Temperature - C (F)......
Minimum Engine H20 Temperature - C (F).....
System Voltage (Nominal)........
Battery Capacity for Ambients Above 0C (32F)
Start to Open - C (F)......
Fully Opened - C (F)......
Starter Cranking Amps - @ 15C (60F).......
Circuit* Length.......
Circuit* Length..........
Circuit* Length..........
Charging Alternator Output - Amp.......
CCA @ -18C (0F)...........
Reserve Capacity - Minutes........
Battery Cable Circuit*, Max Resistance - ohm.........
Battery Cable Minimum Size
NOTE: This engine is Intendend For Indoor Installation Or In A Weatherproof Enclosure. (Continued)
Page 4 of 8
7/25/2019 Technical Data untuk project PLN.pdf
40/57
CLARKEFire Protection Products
Exhaust System 2350 2600 2800 3000
13 (469) 15 (531) 16 (581) 18 (630)
584 (1083) 568 (1055) 556 (1033) 543 (1010)
7.5 (30)
76 (3)
Fuel System
11.7 (3.1) 12.9 (3.4) 13.6 (3.6) 14.8 (3.9)
34.1 (9.0) 36.0 (9.5) 37.5 (9.9) 39.0 (10.3)
45.8 (12.1) 48.9 (12.9) 51.1 (13.5) 53.8 (14.2)
21-41 (3-6)
.50 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .033 (.848)
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter mm (in.).......... .026 (.675)
0.8 (31)
1.4 (4.5)
2
Heater System
1500
115 (+5%, -10%)
230 (+5%, -10%)
nduction Air System
Indoors Service Only - Washable
2.5 (10)1.2 (5)
4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
54 (130)
Lubrication System
Oil Pressure - normal - kPa (lb./in.2).... 241-345 (35-50)
In Pan Oil Temperature - C (F)....... 104-118 (220-245)
Oil Pan Capacity - High - L (qt.)....... 7.5 (8)
Low - L (qt.) 6.5 (7)
Total Oil Capacity with Filter - L (qt.).. 8.5 (9)
Performance
462 (67) 448 (65) 437 (63) 426 (62)597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m..........
pressure drop no greater than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 25C (77F)
JU4H-NL14
INSTALLATION & OPERATION DATA (Continued)
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
Exhaust Flow - m3/min. (ft.
3/min.)........
Exhaust Temperature - C (F)..........
Maximum Allowable Back Pressure - kPa (in. H20)...
Minimum Exhaust Pipe Dia. - mm (in.)**........
Minimum Line Size - Supply - (in.)......
Minimum Line Size - Return - (in.).....
Maximum Allowable Fuel Pump Suction
With Clean Filter - m H 20 (in. H20).......
Fuel Consumption - L/hr. (gal.hr.).......
Fuel Return - L/hr. (gal./hr.).......
Total Supply Fuel Flow - L/hr. (gal./hr.).......
Fuel Pressure - kPa (lb./in.2)......
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft.)..
Fuel Filter Micron Size..........
Jacket Water Heater
Wattage (Nominal)............
Dirty Air Cleaner - kPa (in. H 20)...........Clean Air Cleaner - kPa (in. H20).........
Voltage - AC, 1P............
Optional Voltage - AC, 1P.........
UK Production
Consult Factory
C131088Power Curve..............
BMEP - kPA (lb./in.
2
)............Piston Speed - m/min. (ft./min.).........
Engine Air Flow - m3/min. (ft.
3/min.)........
Maximum Allowable Temperature (Air To Engine Inlet) - C (F)***.
Air Cleaner Type.....
Air Intake Restriction Maximum Limit
C131253 revG
11FEB08 DSP
Page 5 of 8
7/25/2019 Technical Data untuk project PLN.pdf
41/57
CLARKE
Fire Protection Products
Air Cleaner Valves
Type.... .. Indoor Usage Only Type.. Poppet
Oiled Fabric Pleats Arrangement Overhead Valve
Material..... Surgical Cotton Number/Cylinder 1 intake
Aluminum Mesh 1 exhaust
Operating Mechanism Mechanical Rocker Arm
Air Cleaner - Optional Type of Lifter.. Large HeadTypeCanister Valve Seat InsertReplaceable
Material Pleated Paper
Housing..Enclosed Fuel Pump
Type Diaphragm
Camshaft Drive Cam Lobe
Material.. Cast Iron
Chill Hardened Heat Exchanger (USA)
Location.....In Block Type Tube & Shell
Drive...Gear, Spur Materials
Type of Cam..... Ground Tube& Headers Copper
Shell Copper
Electrode Zinc
Type.Raw Water Cooled
Heat Exchanger (UK)
Materials (in contact with raw water) Type Tube & Bundle
Tubes 90/10 CU/NI Materials
Headers 36500 Muntz Tube& Headers Copper
Covers 83600 Red Brass Shell. Aluminum
Plumbing 316 Stainless Steel/ Brass
90/10 Silicone
Coolant Pump Injection Pump
Type .Centrifugal Type. Rotary
Drive Poly Vee Belt Drive Gear
Coolant Thermostat Lubrication Cooler
TypeNon Blocking Type PlateQty 1
Lubrication Pump
Connecting Rod Type Gear
TypeI-Beam Taper Drive Gear
Material Forged Steel Alloy
Crank Pin Bearings Main Bearings
TypePrecision Half Shell Type Precision Half Shells
Number 1 Pair Per Cylinder Material Steel Backed-Aluminum Lined
Material Wear-Guard
Crankshaft Piston
Material Forged Steel Type and Material Aluminum Alloy with Reinforced
Type of BalanceDynamic Top Ring Groove
Cooling Oil Jet Spray
Cylinder Block
TypeOne Piece with Piston Pin
Non-Siamese Cylinders Type Full Floating - Offset
Material Annealed Gray Iron
Cylinder Head Piston Rings
Type.. Slab 2 Valve Number/Piston3
Material. Annealed Gray Iron Top Keystone Barrel Faced -
Plasma Coated
Cylinder Liners Second Tapered Cast Iron
Type.. Centrifugal Cast, Wet Liner Third Double Rail Type
Material... Alloy Iron Plateau, Honed w/Expander Spring
JU4H & JU6H ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0,
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0,
ADW8, ADX8, AD98 only)
C13615 19 NOV 09 DSPPage 6 of 8
7/25/2019 Technical Data untuk project PLN.pdf
42/57
Page7of8
7/25/2019 Technical Data untuk project PLN.pdf
43/57
7/25/2019 Technical Data untuk project PLN.pdf
44/57
VOLUME A B C D E F G H I J K L M N O DRY WEIGHT
(Liter) (Inch) (mm) (Inch) (mm) (Inch) (mm) (Inch) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) Approx. (kg)
100 1/2 250 1/2 480 1/2 60 1/2 3 420 620 580 680 50 480 - 45
200 1/2 250 1/2 500 1/2 60 1/2 3 820 1020 600 700 50 500 - 70
250 1/2 250 1/2 560 1/2 60 1/2 3 820 1020 660 760 50 560 - 80
300 1/2 250 1/2 560 1/2 60 1/2 3 920 1220 660 760 50 560 - 90
500 1/2 250 1/2 750 1/2 60 1/2 3 920 1220 850 950 50 750 - 120
750 1/2 250 1/2 870 1/2 60 1/2 3 920 1220 970 1070 50 870 - 140
1000 1/2 300 1/2 1050 1/2 60 1/2 3 920 1220 1150 1250 50 1050 30 170
1250 1/2 300 1 1150 1 60 1 3 920 1220 1250 1350 50 1150 30 200
1500 1/2 350 1 1130 1 60 1 3 1130 1530 1230 1330 50 1130 30 220
2000 1/2 350 1 1180 1 60 1 4 1430 1830 1280 1380 50 1180 30 260
7/25/2019 Technical Data untuk project PLN.pdf
45/57
7/25/2019 Technical Data untuk project PLN.pdf
46/57
qwertyuiopasdfghjklzxcvbnmqwerty
opasdfghjklzxcvbnmqwertyuiopasdfg
klzxcvbnmqwertyuiopasdfghjklzxcvb
nmqwertyuiopasdfghjklzxcvbnmqwe
yuiopasdfghjklzxcvbnmqwertyuiopa
dfghjklzxcvbnmqwertyuiopasdfghjklz
vbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyu
pasdfghjklzxcvbnmqwertyuiopasdfgh
klzxcvbnmqwertyuiopasdfghjklzxcvbmqwertyuiopasdfghjklzxcvbnmqwer
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzxvbnmqwertyuiopasdfghjklzxcvbnmrt
uiopasdfghjklzxcvbnmqwertyuiopasd
ghjklzxcvbnmqwertyuiopasdfghjklzx
Spare Part List BookController Model : GPD
PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
Preparedby
:PT.
Roda
Nurmala
JOCKEY PUMP
AURORA VERTICAL MULTISTAGE IN-LINE
Model : PVM 5-13
PLN
7/25/2019 Technical Data untuk project PLN.pdf
47/57
50Hz
PVM/PVMI
PVMXFLOW MANAGEMENT SOLUTIONS VERTICAL MULTISTAGE CENTRIFUGAL IN-LINE PUMPSINE PU PS
7/25/2019 Technical Data untuk project PLN.pdf
48/571
A LEADERIN WATER TECHNOLOGY
Pentair is one of the worlds leading
companies in the planning andmanufacture of innovative productsand systems suitable in any situationrequiring the treatment, transportationand storage of water. The activityand success of Pentair is based onvalues such as constant improvement,the continuous development ofnew products, high-performance,competence, business ethics andmarket leadership. Pentairs employeesshare personal values such asaccountability, deep respect for peopleand the environment and a candid andpractical work style. Strong customer
relationships and high quality standardsallow Pentair to rank amongst theleading producers of technology andinstruments for water treatment.
SAFE, CLEAN WATER
Providing clean, safe water to anever-growing portion of the populationis the Mission of Pentair: a validorganization is engaged to serve ourcustomers in an efficient mannerthrough production plants locatedin every corner of the world andspecialized sales and marketingnetworks.
FLOW TECHNOLOGIES
Vertical and horizontal centrifugalpumps; submersible pumps fordomestic, commercial, agricultural andindustrial use; pumps for the drainage of
clear and wastewaters; pressure boosterunits and fire-fighting systems.
WATER TREATMENT
Residential, commercial and industrialwater conditioning control valves; fibre-glass wound expansion tanks and vessels;water storage tanks.
FILTRATION
Industrial, residential and commercialfiltration systems; filter cartridges,components for the filtration of drinkingwater, pumps for mobile homes and
boats and pumps and accessories forapplications in industry and the cateringservice.
POOL AND SPA
A complete range of pool/spa equipmentand accessories: filters, pumps, heatingand lighting systems and cleaningaccessories; dosing and control systemsand products and accessories forfountains and ponds.
7/25/2019 Technical Data untuk project PLN.pdf
49/572
HIGH HYDRAULIC EFFICIENCY, MOTOR DESIGNED TO EN STANDARDS
The PVM, PVMI and PVMX are non-selfpriming vertical multistage pump ofin-line design, flange or with Victauliccoupling with equally sized suction anddischarge ports.
Stage construction with stainless steelimpellers, chambers and pressurecasing. Pump stub shaft and motorshaft of the IEC-standards motor are
directly close coupled.
All pumps are equipped with acartridge type mechanical seal for easymaintenance.
PVM, PVMI and PVMX pumps havedifferent pump sizes and variousnumbers of stages to provide the flowand the pressure required.
APPLICATIONS
VERTICAL MULTISTAGE CENTRIFUGAL PUMPSPVM/PVMI/PVMX
Water supply
Pressure boosting systems
Water treatment/filtration
Irrigation
High pressure washes
Liquid transfer
Firefighting systems
Boiler feed
7/25/2019 Technical Data untuk project PLN.pdf
50/574
VERTICAL MULTISTAGE CENTRIFUGAL PUMPSPVM/PVMI/PVMX
MOTOR
Asynchronous electric motorwith enclosed stator and external
ventilation
Main dimensions are in accordancewith DIN and IEC standards
Class F insulation
Level of protecion IP55
Maximum environmental temperature50C
Speed of rotation 2900 rpm
MOTOR TYPE -2 POLES NOMINAL CURRENT IN [A]
[HP] [KW] Flange Frame 3~230V 3~400V
0.5 0.37
B14
71 1.9 1.1
0.75 0.55 71 2.7 1.6
1 0.75 80 3.5 2.1
1.5 1.1 90S 5.2 3.0
2 1.5 90L 6.1 3.6
3 2.2 90L 9.8 5.7
4 3 100L 12.3 7.1
5.5 4 112M 15.0 8.7
B5
3~400V 3~690V
7.5 5.5 132S 12.1 6.910 7.5 132S 15.7 8.8
3~400V
15 11 160M 20.1
20 15 160M 27.2
25 18.5 160L 33.25
30 22 180M 39.4
40 30 200L 53.35
50 37 200L 65.4
60 45 225M 82.9
75 55 250M 96.75
100 75 280S 128.5
* The Nominal C urrent values indicated refer to a standard motor configuration.For detailed information, please contact your countrys Pentair office
7/25/2019 Technical Data untuk project PLN.pdf
51/575
PRODUCT DATA
VERTICAL MULTISTAGE CENTRIFUGAL PUMPSPVM/PVMI/PVMX
50Hz PVM, PVMI, PVMX
Nominal Flow (m3/h) 1 3 5 10 15 20
Flow Range (m3/h) 0.7-2.4 1.2-4.5 2.5-8.5 5-13 8.5-23.5 10.5-29
Max. Pressure (bar) 21,5 23 24 21.5 23 24.3
Fluid Temperature -15C to + 120C
Motor Power (kW) 0.37-2.2 0.37-3 0.37-5.5 0.37-7.5 1.1-15 1.1-18.5
Version
PVM: Cast iron and stainless steel EN 1.4301/AISI 304
PVMI: Stainless steel EN 1.4301/AISI 304
PVMX: Stainless steel EN 1.4401/AISI 316
Motor
Main connection 1~ (V/Hz) Permissible voltage tolerance 10% 220-240 V 50 Hz
Main connection 3~ (V/Hz) Permissible voltage tolerance 10% 0.37-7.5 kW 220-240/380-415 V 50 Hzfrom 11 kW 380-415 V 50 Hz
Insulation class F
Enclosure class IP 55
Ambient temperature 50C
PVM Pipe Connection
Flange DN 25/DN 32 DN 25/DN 32 DN 25/DN 32 DN 40 DN 50 DN 50
PVMI/PVMX Pipe Connection
Flange DN 25/DN 32 DN 25/DN 32 DN 25/DN 32 DN 40 DN 50 DN 50
Victaulic connection R DN32 R DN32 R DN32 R2 DN50 R2 DN50 R2 DN50
Mechanical Seals
SiC/SiC StandardSeals
EPDMStandard
Viton
5
7/25/2019 Technical Data untuk project PLN.pdf
52/577
PUMP CONSTRUCTION
VERTICAL MULTISTAGE CENTRIFUGAL PUMPSPVM/PVMI/PVMX
POS. NAME MATERIAL PVM 1, 3, 5, 10, 15, 20 PVMI 1, 3, 5, 10, 15, 20 PVMX 1, 3, 5, 10, 15, 20
36 Pump head Cast Iron EN-GJL-200 ; ASTM 25B EN-GJS-450-10 ; ASTM 65-45-12 EN-GJS-450-10 ; ASTM 65-45-12
56 Pump head cover Stainless Steel N/A 1.4301 ; AISI 304 1.4401 ; AISI 316
18 Impeller Stainless Steel 1.4301 ; AISI 304 1.4301 ; AISI 304 1.4401 ; AISI 316
37 Shaft Stainless Steel 1.4057 ; AISI 431 1.4057 ; AISI 431 1.4401 ; AISI 316
48 Outer sleeve Stainless Steel 1.4301 ; AISI 304 1.4301 ; AISI 304 1.4401 ; AISI 316
82 O-Ring for outer sleeve EPDM - - -
12 Chamber Stainless Steel 1.4301 ; AISI 304 1.4301 ; AISI 304 1.4401 ; AISI 316
24 Neck Ring PTFE - - -
59 BaseCast Iron EN-GJL-200 ; ASTM 25B N/A N/A
Stainless Steel N/A 1.4301 ; AISI 304 1.4401 ; AISI 316
62 Base plate Cast Iron N/A EN-GJL-200 ; ASTM 25B EN-GJL-200 ; ASTM 25B
44 Coupling Fe-Cu-C SINT C11 ; MPIF FC0525 SINT C11 ; MPIF FC0525 SINT C11 ; MPIF FC0525
57 Mechanical seal Cartridge type - - -
7/25/2019 Technical Data untuk project PLN.pdf
53/57
HYDRAULIC PERFORMANCE
VERTICAL MULTISTAGE CENTRIFUGAL PUMPS
PVM/PVMI/PVMX 5
Duty Point
7/25/2019 Technical Data untuk project PLN.pdf
54/57
PUMP DIMENSIONS
VERTICAL MULTISTAGE CENTRIFUGAL PUMPS
PVM/PVMI/PVMX 5
PUMP
TYPE
MOTOR
PVM PVMI - PVMX
DIMENSION [mm]
Net
Weight
[kg]
DIMENSION [mm] Net Weight [kg]
P2
DIN FlangeD1 D2 D3
DIN
Flange
Victaulic DIN FlangeD1 D2 D3 Victaulic
DIN
Flange[HP] [KW] H1 H2 H1 H2 H1 H2
PVM 5-2 0,5 0,37 279 474 141 115 23,3 257 452 282 477 141 115 19,2 20,1
PVM 5-3 0,75 0,55 306 501 141 115 24,2 284 479 309 504 141 115 20,3 21,2
PVM 5-4 0,75 0,55 333 528 141 115 24,8 311 506 336 531 141 115 20,8 21,8
PVM 5-5 1,0 0,75 366 601 141 115 27,4 344 579 369 604 141 115 23,4 24,3
PVM 5-6 1,5 1,1 393 628 141 115 29,1 371 606 396 631 141 115 25,1 26,0
PVM 5-7 1,5 1,1 420 655 141 115 29,6 398 633 423 658 141 115 25,6 26,5
PVM 5-8 1,5 1,1 447 682 141 115 30,1 425 660 450 685 141 115 26,1 27,1
PVM 5-9 2,0 1,5 490 781 177 141 39,3 468 759 493 784 177 141 35,4 36,4
PVM 5-10 2,0 1,5 517 808 177 141 39,9 495 786 520 811 177 141 36,0 36,9
PVM 5-11 3,0 2,2 544 835 177 141 43,2 522 813 547 838 177 141 39,3 40,3
PVM 5-12 3,0 2,2 571 862 177 141 43,7 549 840 574 865 177 141 39,9 40,8
PVM 5-13 3,0 2,2 598 889 177 141 44,2 576 867 601 892 177 141 40,4 41,4
PVM 5-14 3,0 2,2 625 916 177 141 44,8 603 894 628 919 177 141 41,0 41,9
PVM 5-15 3,0 2,2 652 943 177 141 45,2 630 921 655 946 177 141 41,5 42,5
PVM 5-16 3,0 2,2 679 970 177 141 45,8 657 948 682 973 177 141 42,1 43,0
PVM 5-18 4,0 3,0 737 1053 197 1 47 54,3 715 1031 740 1056 197 1 47 50,3 51,3
PVM 5-20 4,0 3,0 791 1107 197 1 47 55,5 769 1085 794 1110 197 1 47 51,6 52,5
PVM 5-22 5,5 4,0 845 1171 220 1 61 59,8 823 1149 848 1174 220 1 61 55,8 56,8
PVM 5-24 5,5 4,0 899 1225 220 1 61 60,8 877 1203 902 1228 220 1 61 56,9 57,8
PVM 5-26 5,5 4,0 953 1279 220 1 61 62,7 931 1257 956 1282 220 1 61 58,0 58,9
PVM 5-29 5,5 4,0 1 034 1360 220 161 64,6 1012 1338 1037 1363 220 161 59,7 60,6
PVM 5-32 7,5 5,5 1145 1507 235 197 300 90,1 1123 1485 1148 1510 235 197 300 84,9 85,8
PVM 5-36 7,5 5,5 1253 1615 235 197 300 92,6 1231 1593 1256 1618 235 197 300 87,1 88,1
7/25/2019 Technical Data untuk project PLN.pdf
55/5734
Pentair has been committed to the
design and production of electricwater pumps providing our customerswith quality products and concretesolutions for all their needs. Withinthe wide Pentair Water Supply range,engineering firms and plumbing andheating/cooling distributing centrescan find products and systems whichmeet any need with regards to watersupply and pressurization in the realmof residential and commercial building,irrigation and industry applications.
FIREFIGHTING SYSTEMS ANDPRESSURIZATION SYSTEMS
Vertical and horizontal centrifugalpumps. Complete systems for thetransfer and pressurization of water.
Fire-fighting systems.
ELECTRIC PUMPS FOR DRAINAGE
Pumps for the transfer of clear,dirty and wastewaters and sewage.Pumps for numerous applications(water in basins, tanks, pumpingstations etc.)
ELECTRIC PUMPS FOR RESIDENTIALUSE
Submersible pumps, self-primingpumps, multistage centrifugalpumps and compacting pumping
systems for domestic water supply,irrigation and the re-utilization ofharvested rainwater.
ELECTRIC PUMPS FOR OPEN ANDDRILLED WELLS
Submersible pumps for irrigationand pumping underground waters.
WE PUT ENERGY INTO YOUR WATER
WATER ENERGY
7/25/2019 Technical Data untuk project PLN.pdf
56/57
All Pentair trademarks and logos are owned by Pentair, inc. All other brand or product names are trademarks or registered marks of their respective owners.Because we are continously improving our products and serviceds, Pentair reserves the right to change specifications without prior notice.Pentair is an equal opportunity employer.01/2014 2014 Pentair, Inc. All Rights Reserved.
Avenue de Sevelin, 18 1004 LAUSANNE - SWITZERLAND WWW.PENTAIR.COM
7/25/2019 Technical Data untuk project PLN.pdf
57/57