Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Table 1. Revision list
Revision Figure number Page Date1. Power Defense MCP curves initial release 10/01/2019
4
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Table 2. Catalog number convention
* Applies to PDG2 ONLY.ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark .
This information is provided only as an aid to understand the catalog numbers .
It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available .
Poles
3 = 3 pole
Interruption capacity
PDG PDC
F = - 25kA @ 415V
G = - 36kA @ 415V
K = - 50kA @ 415V
M = Standard -
N = - 65kA @ 415V
Continuous current rating
# value # value
0003 = 3 A 0200 = 200 A
0007 = 7 A 0220 = 220 A
0015 = 15 A 0225 = 225 A
0025 = 25 A 0250 = 250 A
0030 = 30 A H250 = 250 A
0040 = 40 A 0300 = 300 A
0050 = 50 A H300 = 300 A
0063 = 63 A 0320 = 320 A
0070 = 70 A 0350 = 350 A
0080 = 80 A H350 = 350 A
0090 = 90 A 0400 = 400 A
0100 = 100 A H400 = 400 A
0125 = 125 A 0450 = 450 A
0150 = 150 A 0500 = 500 A
0160 = 160 A 0600 = 600 A
0175 = 175 A
Terminals included
N = No terminals
J = Standard terminals
S = Screw terminals / end cap kit
Calibration
S = Standard range
H = High range
L = Low range
R = Alternate standard range *
Style family
PDG = PD Global UL / CSA / CE / CCC
PDC = PD IEC / CE / CCC
Magnetic setting
A = Adjustable magnetic
Trip unit style
M= Motor protection
PDG 1 3 M 0015 M S A J
Frame size
1 = Frame PD1
2 = Frame PD2
3 = Frame PD3
5
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Table 3. Continuous current rating by frame
Continuous current rating by frame
PDG1 PDG2 PDG3 PDC1 PDC2 PDC3
0003 X X
0007 X X
0015 X X
0025 X
0030 X X
0040 X
0050 X X X
0063 X
0070 X X X
0080 X
0090 X
0100 X X X X
0125 X X
0150 X X
0160 X
0175 X
0200 X X
0220 X X
0225 X
0250 X
H250 X
0300 X
H300 X
0320 X
0350 X
H350 X
0400 X X
H400 X
0450 X
0500 X
Table 4. Curve notes
1. These curves apply for 50Hz and 60Hz applications.
2. The maximum voltage rating for the frame style is stated in curve.
3. These curves are comprehensive for Power Defense style motor circuit protectors including frame sizes, ratings and constructions stated.
4. The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current.
5. The end of the curve is determined by the application or the interrupting rating of the circuit protector.
6. All current values are in RMS amperes.
Cu
rren
t in
RM
S a
mp
eres
6
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
PD1 motor circuit protector curves
7
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 1. PD1 MCP 3 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ON
DS
TRIP CURRENT IN AMPERES
PD1 MCP, 3 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG13M0003MSAJ
Maximum Voltage Current Ra�ng600/347Vac (50/60Hz) 3A480Vac (50/60Hz) 3A250Vdc 3A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each se�ng on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrup�ng Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0003MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 9 AB 15 AC 21 AD 27 AE 30 AF 33 A
Maximum voltage
Current rating
600/347Vac (50/60Hz) 3 A480Vac (50/60Hz) 3 A250Vdc 3 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown by the
width of the box for each setting on the curve.
8
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 2. PD1 MCP 7 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ON
DS
TRIP CURRENT IN AMPERES
PD1 MCP, 7 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG13M0007MSAJ
Maximum Voltage Current Ra�ng600/347Vac (50/60Hz) 7A480Vac (50/60Hz) 7A250Vdc 7A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each se�ng on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrup�ng Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0007MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
9
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 3. PD1 MCP 15 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD1 MCP, 15 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG13M0015MSAJ
Maximum Voltage Current Rating600/347Vac (50/60Hz) 15A480Vac 15A250Vdc 15A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each setting on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrupting Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0015MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
10
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 4. PD1 MCP 30 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD1 MCP, 30 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG13M0030MSAJ
Maximum Voltage Current Rating600/347Vac (50/60Hz) 30A480Vac (50/60Hz) 30A250Vdc 30A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each setting on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrupting Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0030MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
11
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 5. PD1 MCP 50 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
SDN
OCES NI E
MIT
TRIP CURRENT IN AMPERES
PD1 MCP, 50 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG13M0050MSAJ
Maximum Voltage Current Ra�ng600/347Vac (50/60Hz) 50A480Vac (50/60Hz) 50A250Vdc 50A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each se�ng on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrup�ng Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0050MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
12
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 6. PD1 MCP 70 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SECO
NDS
TRIP CURRENT IN AMPERES
PD1 MCP, 70 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG13M0070MSAJ
Maximum Voltage Current Rating600/347Vac (50/60Hz) 70A480Vac (50/60Hz) 70A 250Vdc 70A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each setting on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrupting Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0070MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
13
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 7. PD1 MCP 100 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD1 MCP, 100 Amps, 3 Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG13M0100MSAJ
Maximum Voltage Current Rating600/347Vac (50/60Hz) 100A480Vac (50/60Hz) 100A250Vdc 100A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each setting on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrupting Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG13M0100MSAJ
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
14
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 8. PD1 MCP 100 amp high calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
1 10 100 1000 10000
TIM
E IN
SEC
ON
DS
TRIP CURRENT IN AMPERES
PD1 MCP, 100 Amps, High Calibra�on, 3-Pole
F
B
D
E
A
C
Time Current CurvePower Defense Circuit BreakersStyle: PD1 Motor Circuit ProtectorConfigura�on: 3 and 4 PolesTrip Unit Type: Motor Protec�on Curve: Instantaneous High Calibra�on Protec�onCatalog Numbers: PDG13M0100MHAJ
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 100A250Vdc 100A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are - 20%, +30% as shown by the width of
the box for each se�ng on the curve.
Adjustable Trip Setting RangeA - F
MaximumInterrup�ng Time
Time current curves Power Defense circuit breakersStyle: PD1 motor circuit protectorConfiguration: 3 and 4 polesTrip unit type: Motor protectionCurve: Instantaneous high calibration
protectionCatalog numbers: PDG13M0100MHAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 500 AB 750 AC 1000 AD 1250 AE 1375 AF 1500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 100 A250 Vdc 100 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
15
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
PD2 motor circuit protector curves
16
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 9. PD2 MCP 3 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 3 Amp, 3 Pole
F
H
B
C
D
E
G
Time Current CurvePower Defense Circuit BreakersStyle: PD2 3A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0003MRAJ, PDG23M0003MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 9AB 12AC 15AD 18AE 21AF 24AG 27AH 30A
Maximum Voltage Current Rating600Vac (50/60Hz) 3A250Vdc 3A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
A
Time current curves Power Defense circuit breakersStyle: PD2 3 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0003MRAJ,
PDG23M0003MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 9 AB 12 AC 15 AD 18 AE 21 AF 24 AG 27 AH 30 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 3 A250 Vdc 3 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
17
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 10. PD2 MCP 7 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 7 Amp, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 7A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0007MRAJ, PDG23M0007MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 21AB 28AC 35AD 42AE 49AF 56AG 63AH 70A
Maximum Voltage Current Rating600Vac (50/60Hz) 7A250Vdc 7A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 7 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0007MRAJ,
PDG23M0007MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 21 AB 28 AC 35 AD 42 AE 49 AF 56 AG 63 AH 70 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 7 A250 Vdc 7 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
18
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 11. PD2 MCP 15 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 15 Amp, 3 Pole
F
H
B
C
D
E
G
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 15A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0015MRAJ, PDG23M0015MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 45AB 60AC 75AD 90AE 105AF 120AG 135AH 150A
Maximum Voltage Current Rating600Vac (50/60Hz) 15A250Vdc 15A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
A
Time current curves Power Defense circuit breakersStyle: PD2 15 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0015MRAJ,
PDG23M0015MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 45 AB 60 AC 75 AD 90 AE 105 AF 120 AG 135 AH 150 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 15 A250 Vdc 15 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
19
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 12. PD2 MCP 30 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 30 Amp, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 30A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0030MRAJ, PDG23M0030MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 90AB 120AC 150AD 180AE 210AF 240AG 270AH 300A
Maximum Voltage Current Rating600Vac (50/60Hz) 30A250Vdc 30A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 30 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0030MRAJ,
PDG23M0030MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 90 AB 120 AC 150 AD 180 AE 210 AF 240 AG 270 AH 300 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 30 A250 Vdc 30 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
20
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 13. PD2 MCP 50 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 50 Amp, 3 Pole
F
H
B
C
D
E
G
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 50A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0050MRAJ, PDG23M0050MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 150AB 200AC 250AD 300AE 350AF 400AG 450AH 500A
Maximum Voltage Current Rating600Vac (50/60Hz) 50A250Vdc 50A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
A
Time current curves Power Defense circuit breakersStyle: PD2 50 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0050MRAJ,
PDG23M0050MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 150 AB 200 AC 250 AD 300 AE 350 AF 400 AG 450 AH 500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 50 A250 Vdc 50 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
21
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 14. PD2 MCP 70 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 70 Amp, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 70A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0070MRAJ, PDG23M0070MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 150AB 200AC 250AD 300AE 350AF 400AG 450AH 500A
Maximum Voltage Current Rating600Vac (50/60Hz) 70A250Vdc 70A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 70 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0070MRAJ,
PDG23M0070MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 150 AB 200 AC 250 AD 300 AE 350 AF 400 AG 450 AH 500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 70 A250 Vdc 70 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
22
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 15. PD2 MCP 100 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 100 Amp, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 100A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG23M0100MRAJ, PDG23M0070MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 300AB 400AC 500AD 600AE 700AF 800AG 900AH 1000A
Maximum Voltage Current Rating600Vac (50/60Hz) 100A250Vdc 100A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 100 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0100MRAJ,
PDG23M0100MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 300 AB 400 AC 500 AD 600 AE 700 AF 800 AG 900 AH 1000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 100 A250 Vdc 100 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
23
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 16. PD2 MCP 150 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
PD2 MCP, 150 Amp, 3 Pole
F
H
B
C
D
E
G
AdjustableTripSetting RangeA–H
MaximumInterrup�ng Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 150A Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG23M0150MRAJ or
PDG23M0150MSAJDial AdjustmentSe�ng
Instantaneous Pickup Se�ng
A 450AB 600AC 750AD 900AE 1050AF 1200AG 1350AH 1500A
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 150A250Vdc 150A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each se�ng on the curve.
A
Time current curves Power Defense circuit breakersStyle: PD2 150 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0150MRAJ,
PDG23M0150MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 450 AB 600 AC 750 AD 900 AE 1050 AF 1200 AG 1350 AH 1500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 150 A250 Vdc 150 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
24
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 17. PD2 MCP 150 amp high calibration motor circuit protector October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
PD2 MCP, 150 Amp, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrup�ng Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 150A Motor Circuit ProtectorConfigura�on: 3 and 4 PolesTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG23M0150MRAJ, PDG23M0150MSAJ High Mag Styles
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 150A250Vdc 150A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40% higher.
2. Pickup tolerances are -20%, +30% as shown by the width of the box for each se�ng on the curve.
F
H
B
C
D
E
G
AdjustableTripSetting RangeA–H
MaximumInterrup�ng Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 150A Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG23M0150MHAJ,
High Mag Style
Dial Dial tne tnemmtsujdA tsujdASe�ng
suo suoena enatna tnatsnI tsnIPickup Se�ng
A 750AB 1200AC 1250AD 1500AE 1750AF 2000AG 2250AH 2500A
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 150A250Vdc 150A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40% higher.
2. Pickup tolerances are -20%, +30% as shown by the width of the box for each se�ng on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 150 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG23M0150MRAJ,
high mag style
Dial adjustmentsetting
Instantaneous pickup setting
A 750 AB 1200 AC 1250 AD 1500 AE 1750 AF 2000 AG 2250 AH 2500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 150 A250 Vdc 150 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
25
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 18. PD2 MCP 25 amp low calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 25 Amp Low Magnetic Style, 3 Pole
F
H
B
C
D
E
G
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 25A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous Low Magnetic Calibration ProtectionCatalog Numbers: PDG23M0025MLAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 40AB 43AC 46AD 49AE 52AF 55AG 58AH 60A
Maximum Voltage Current Rating600Vac (50/60Hz) 25A250Vdc 25A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
A
Time current curves Power Defense circuit breakersStyle: PD2 25 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous low magnetic
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
26
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 19. PD2 MCP 50 amp low calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 50 Amp Low Magnetic Style, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 50A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous Low Magnetic Calibration ProtectionCatalog Numbers: PDG23M0050MLAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 80AB 87AC 93AD 98AE 103AF 109AG 115AH 120A
Maximum Voltage Current Rating600Vac (50/60Hz) 50A250Vdc 50A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 50 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous low magnetic
A 80 AB 87 AC 93 AD 98 AE 103 AF 109 AG 115 AH 120 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 50 A250 Vdc 50 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
27
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 20. PD2 MCP 70 amp low calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 70 Amp Low Magnetic Style, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 70A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous Low Magnetic Calibration ProtectionCatalog Numbers: PDG23M0070MLAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 115AB 122AC 130AD 139AE 145AF 153AG 160AH 170A
Maximum Voltage Current Rating600Vac (50/60Hz) 70A250Vdc 70A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 70 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous low magnetic
A 115 AB 122 AC 130 AD 139 AE 145 AF 153 AG 160 AH 170 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 70 A250 Vdc 70 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
28
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 21. PD2 MCP 100 amp low calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100 1000 10000
TIM
E IN
SEC
ONDS
CURRENT IN AMPERES
PD2 MCP, 100 Amp Low Magnetic Style, 3 Pole
F
H
B
C
D
E
G
A
AdjustableTripSetting RangeA–H
MaximumInterrupting Time
Time Current CurvePower Defense Circuit BreakersStyle: PD2 100A Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous Low Magnetic Calibration ProtectionCatalog Numbers: PDG23M0100MLAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 160AB 174AC 185AD 196AE 207AF 218AG 229AH 240A
Maximum Voltage Current Rating600Vac (50/60Hz) 100A250Vdc 100A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Time current curves Power Defense circuit breakersStyle: PD2 100 A motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous low magnetic
A 160 AB 174 AC 185 AD 196 AE 207 AF 218 AG 229 AH 240 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 100 A250 Vdc 100 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
29
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
PD3 motor circuit protector curves
30
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 22. PD3 MCP 100 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 100 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0100MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 500AB 565AC 625AD 690AE 750AF 810AG 875AH 935AI 1000A
Maximum Voltage Current Rating600Vac (50/60Hz) 100A250Vdc 100A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0100MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 500 AB 565 AC 625 AD 690 AE 750 AF 810 AG 875 AH 935 AI 1000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 100 A250 Vdc 100 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
31
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 23. PD3 MCP 125 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 125 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0125MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 625AB 700AC 780AD 860AE 940AF 1020AG 1090AH 1170AI 1250A
Maximum Voltage Current Rating600Vac (50/60Hz) 125A250Vdc 125A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0125MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 625 AB 700 AC 780 AD 860 AE 940 AF 1020 AG 1090 AH 1170 AI 1250 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 125 A250 Vdc 125 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
32
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 24. PD3 MCP 150 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 150 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0150MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 750AB 840AC 935AD 1030AE 1125AF 1220AG 1315AH 1410AI 1500A
Maximum Voltage Current Rating600Vac (50/60Hz) 150A250Vdc 150A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0150MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 750 AB 840 AC 935 AD 1030 AE 1125 AF 1220 AG 1315 AH 1410 AI 1500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 150 A250 Vdc 150 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
33
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 25. PD3 MCP 175 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 175 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0175MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 875AB 980AC 1090AD 1200AE 1310AF 1420AG 1530AH 1640AI 1750A
Maximum Voltage Current Rating600Vac (50/60Hz) 175A250Vdc 175A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0175MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 875 AB 980 AC 1090 AD 1200 AE 1310 AF 1420 AG 1530 AH 1640 AI 1750 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 175 A250 Vdc 175 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
34
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 26. PD3 MCP 200 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 200 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0200MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1000AB 1125AC 1250AD 1375AE 1500AF 1625AG 1750AH 1875AI 2000A
Maximum Voltage Current Rating600Vac (50/60Hz) 200A250Vdc 200A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0200MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1000 AB 1125 AC 1250 AD 1375 AE 1500 AF 1625 AG 1750 AH 1875 AI 2000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 200 A250 Vdc 200 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
35
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 27. PD3 MCP 225 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 225 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0225MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1125AB 1265AC 1410AD 1545AE 1690AF 1830AG 1970AH 2110AI 2250A
Maximum Voltage Current Rating600Vac (50/60Hz) 225A250Vdc 225A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0225MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1125 AB 1265 AC 1410 AD 1545 AE 1690 AF 1830 AG 1970 AH 2110 AI 2250 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 225 A250 Vdc 225 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
36
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 28. PD3 MCP 250 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ON
DS
TRIP CURRENT IN AMPERES
PD3 MCP, 250 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG33M0250MSAJ
Dial AdjustmentSe�ng
Instantaneous Pickup Se�ng
A 1250AB 1405AC 1560AD 1720AE 1875AF 2030AG 2185AH 2340AI 2500A
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 250A250Vdc 250A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each se�ng on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0250MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1250 AB 1405 AC 1560 AD 1720 AE 1875 AF 2030 AG 2185 AH 2340 AI 2500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 250 A250 Vdc 250 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
37
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 29. PD3 MCP 300 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 300 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0300MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1500AB 1690AC 1875AD 2060AE 2250AF 2440AG 2625AH 2810AI 3000A
Maximum Voltage Current Rating600Vac (50/60Hz) 300A250Vdc 300A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0300MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1500 AB 1690 AC 1875 AD 2060 AE 2250 AF 2440 AG 2625 AH 2810 AI 3000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 300 A250 Vdc 300 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
38
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 30. PD3 MCP 350 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 350 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0350MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1750AB 1970AC 2190AD 2410AE 2625AF 2845AG 3065AH 3285AI 3500A
Maximum Voltage Current Rating600Vac (50/60Hz) 350A250Vdc 350A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0350MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1750 AB 1970 AC 2190 AD 2410 AE 2625 AF 2845 AG 3065 AH 3285 AI 3500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 350 A250 Vdc 350 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
39
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 31. PD3 MCP 400 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 400 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0400MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 2000AB 2250AC 2500AD 2750AE 3000AF 3250AG 3500AH 3750AI 4000A
Maximum Voltage Current Rating600Vac (50/60Hz) 400A250Vdc 400A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0400MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 2000 AB 2250 AC 2500 AD 2750 AE 3000 AF 3250 AG 3500 AH 3750 AI 4000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 400 A250 Vdc 400 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
40
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 32. PD3 MCP 400 amp high calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 400 Amp High Calibration, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous High Calibration ProtectionCatalog Numbers: PDG33M0400MHAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 2250AB 2530AC 2810AD 3090AE 3375AF 3655AG 3935AH 4215AI 4500A
Maximum Voltage Current Rating600Vac (50/60Hz) 400A250Vdc 400A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -20%, +30% as shown by the width of the
box for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous high calibration
protectionCatalog numbers: PDG33M0400MHAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 2250 AB 2530 AC 2810 AD 3090 AE 3375 AF 3655 AG 3935 AH 4215 AI 4500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 400 A250 Vdc 400 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are - 20%, +30% as shown
by the width of the box for each setting on the curve.
41
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 33. PD3 MCP 600A frame 250 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame 250 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: High Instantaneous ProtectionCatalog Numbers: PDG33MH250MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1250AB 1405AC 1560AD 1720AE 1875AF 2030AG 2185AH 2340AI 2500A
Maximum Voltage Current Rating600Vac (50/60Hz) 250A250Vdc 250A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: High instantaneous protectionCatalog numbers: PDG33MH250MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1250 AB 1405 AC 1560 AD 1720 AE 1875 AF 2030 AG 2185 AH 2340 AI 2500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 250 A250 Vdc 250 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
42
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 34. PD3 MCP 600A frame 300 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 300 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: High Instantaneous ProtectionCatalog Numbers: PDG33MH300MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1500AB 1690AC 1875AD 2060AE 2250AF 2440AG 2625AH 2810AI 3000A
Maximum Voltage Current Rating600Vac (50/60Hz) 300A250Vdc 300A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: High instantaneous protectionCatalog numbers: PDG33MH300MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1500 AB 1690 AC 1875 AD 2060 AE 2250 AF 2440 AG 2625 AH 2810 AI 3000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 300 A250 Vdc 300 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
43
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 35. PD3 MCP 600A frame 350 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 350 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: High Instantaneous ProtectionCatalog Numbers: PDG33MH350MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 1750AB 1970AC 2190AD 2410AE 2625AF 2845AG 3065AH 3285AI 3500A
Maximum Voltage Current Rating600Vac (50/60Hz) 350A250Vdc 350A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: High instantaneous protectionCatalog numbers: PDG33MH350MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 1750 AB 1970 AC 2190 AD 2410 AE 2625 AF 2845 AG 3065 AH 3285 AI 3500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 350 A250 Vdc 350 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
44
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 36. PD3 MCP 600A frame 400 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 400 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: High Instantaneous ProtectionCatalog Numbers: PDG33MH400MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 2000AB 2250AC 2500AD 2750AE 3000AF 3250AG 3500AH 3750AI 4000A
Maximum Voltage Current Rating600Vac (50/60Hz) 400A250Vdc 400A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: High instantaneous protectionCatalog numbers: PDG33MH400MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 2000 AB 2250 AC 2500 AD 2750 AE 3000 AF 3250 AG 3500 AH 3750 AI 4000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 400 A250 Vdc 400 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
45
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 37. : PD3 MCP 600A frame 450 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ON
DS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 450 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfigura�on: 3 PoleTrip Unit Type: Motor Protec�on Curve: Instantaneous Protec�onCatalog Numbers: PDG33M0450MSAJ
Dial AdjustmentSe�ng
Instantaneous Pickup Se�ng
A 2250AB 2530AC 2810AD 3090AE 3375AF 3660AG 3940AH 4220AI 4500A
Maximum Voltage Current Ra�ng600Vac (50/60Hz) 450A250Vdc 450A
Notes:1. For DC applica�ons, pickup se�ngs are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each se�ng on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0450MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 2250 AB 2530 AC 2810 AD 3090 AE 3375 AF 3660 AG 3940 AH 4220 AI 4500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 450 A250 Vdc 450 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
46
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 38. PD3 MCP 600A frame 500 amp standard calibration motor circuit protector. October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 500 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0500MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 2250AB 2530AC 2810AD 3090AE 3375AF 3660AG 3940AH 4220AI 4500A
Maximum Voltage Current Rating600Vac (50/60Hz) 500A250Vdc 500A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0500MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 2250 AB 2530 AC 2810 AD 3090 AE 3375 AF 3660 AG 3940 AH 4220 AI 4500 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 500 A250 Vdc 500 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.
47
Technical Data TD012069ENEffective October 2019
Time current curves, Power Defense motor circuit protectors (MCP)
EATON www.eaton.com
Figure 39. PD3 MCP 600A frame 600 amp standard calibration motor circuit protector October 2019
0.001
0.01
0.1
1
10
100
1000
10000
100 1000 10000 100000
TIM
E IN
SEC
ONDS
TRIP CURRENT IN AMPERES
PD3 MCP, 600A Frame, 600 Amp, 3 Pole
Maximum Interrupting Time
Application Determines End of Curve.
I
H
G
F
E
D
C
B
A
Time Current CurvePower Defense Circuit BreakersStyle: PD3 Motor Circuit ProtectorConfiguration: 3 PoleTrip Unit Type: Motor Protection Curve: Instantaneous ProtectionCatalog Numbers: PDG33M0600MSAJ
Dial AdjustmentSetting
Instantaneous Pickup Setting
A 3000AB 3375AC 3760AD 4120AE 4500AF 4880AG 5250AH 5630AI 6000A
Maximum Voltage Current Rating600Vac (50/60Hz) 600A250Vdc 600A
Notes:1. For DC applications, pickup settings are approximately 40%
higher.2. Pickup tolerances are -/+ 20% as shown by the width of the box
for each setting on the curve.
Adjustable Trip Setting RangeA - I
Time current curves Power Defense circuit breakersStyle: PD3 motor circuit protectorConfiguration: 3 poleTrip unit type: Motor protectionCurve: Instantaneous protectionCatalog numbers: PDG33M0600MSAJ
Dial adjustmentsetting
Instantaneous pickup setting
A 3000 AB 3375 AC 3760 AD 4120 AE 4500 AF 4880 AG 5250 AH 5630 AI 6000 A
Maximum voltage
Current rating
600 Vac (50/60 Hz) 600 A250 Vdc 600 A
Notes: 1. For DC applications, pickup settings are approxi-
mately 40% higher.2. Pickup tolerances are -/+ 20% as shown by
the width of the box for each setting on the curve.