Top Banner
Immediate Energy Efficiency with Power Factor Correction Power Quality Clean power, Efficient business
48

TDD Full load

Feb 12, 2017

Download

Documents

vuongxuyen
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: TDD Full load

Immediate Energy Efficiency with Power Factor Correction

Power Quality Clean power, Efficient business

Page 2: TDD Full load

Schneider Electric – Global PQ – June 2013 2 2

Outline

Power Factor:

●Definition & Examples

●Cost Savings

●Power Factor Correction Equipment

Harmonics:

●Introduction

●Harmonics and Power Factor Correction Capacitors

●IEEE 519 Standard

●Traditional Harmonic Mitigation Methods

●Active Filter Technology & Applications

Page 3: TDD Full load

Schneider Electric – Global PQ – June 2013 3 3

Definitions: ●kW = Active Power: It does the "work" for the system - providing the

motion, heat, or whatever else is required.

●kVAR = Reactive Power: It doesn't do useful "work." It simply sustains the electromagnetic field.

●kVA = Apparent Power: It is the vector addition of Working Power and Reactive Power.

●Power Factor : The ratio of Active Power (output) to Total Power (input). It is a measure of efficiency.

What is Power Factor?

Total Power (kVA)

θ

Active Power (kW)

Power Factor = Active (Real) Power Total Power = kW kVA = Cosine (θ)

Reactive Power (kVAR)

Page 4: TDD Full load

Schneider Electric – Global PQ – June 2013 4 4

Power Factor:The Beer Analogy

Mug Capacity = Apparent Power (kVA)

Foam = Reactive Power (kVAR)

Beer = Real Power (kW)

Power Factor = Beer (kW)

Mug Capacity (kVA)

Capacitors provide the Foam (kVAR), freeing up Mug Capacity so you don’t have to buy a bigger mug and/or so you can pay less for your beer !

kVAR Reactive Power

kW Active Power

kVA Apparent Power

Page 5: TDD Full load

Schneider Electric – Global PQ – June 2013 5 5

Why is Power Factor Important? ●Low power factor results in:

●Poor electrical efficiency ●Lower system capacity ●Higher utility bills

●Most utilities have power factor penalties to encourage power factor correction. Otherwise the utility may have to:

– Build more power plants – Purchase new transformers – Use larger cables

●Power factor correction ●Reduces power cost ●Releases system capacity ●Reduces power losses ● Improves voltage

Page 6: TDD Full load

Schneider Electric – Global PQ – June 2013 6 6

● The easiest solution to improve power factor is to add power factor correction capacitors to your electrical distribution system.

A2

Power Factor Correction

M

The Capacitor Supplies Reactive Current

Current that is drawn from the voltage source is then only used to do real work (kW) and not to create a magnetic field (kVAR). The source current is then minimized

» The customer only pays for the capacitor » Since the utility doesn’t supply the kVAR, the customer doesn’t

pay for it » In short, capacitors save money

Page 7: TDD Full load

Schneider Electric – Global PQ – June 2013 7 7

In this example, demand is reduced from 100 kVA to 80 kVA by installing a 60 kVAR capacitor.

Before: PF = kW/kVA = 80%

After: PF = kW/kVA = 100%

Transformer loading is reduced

Power Factor Correction

Page 8: TDD Full load

Schneider Electric – Global PQ – June 2013 8 8

● Reduced Power Costs: lower utility bills since utility no longer supplies the reactive current.

● Released System Capacity

●Capacitors off-load transformers and cables

● Improved Voltage

● Reduced losses

kW 100

kVAR 100

kW 100

kVAR 75

kW 100

kVA = 141 PF = 70%

kVA = 125 PF = 80%

kVA = 100 PF = 100%

Benefits of Power Factor Correction

Page 9: TDD Full load

Schneider Electric – Global PQ – June 2013 9 9

How do utilities charge for Power Factor?

Billing Actual Actual Possible Required Required % ReductionService Demand Power Demand Demand Cost Capacitor kVAR Capacitor kVAR of Transformer

Month kW Factor kVA kW Savings for 0.92 pf for 1.0 pf kVA Load05/14/11 900.0 0.8000 1,000.0 800.0 $550.00 259 600 20% 06/14/11 800.0 0.7950 888.9 706.7 $513.33 238 539 21% 07/16/11 850.0 0.7625 944.4 720.1 $714.24 304 611 24% 08/15/11 875.0 0.7511 972.2 730.2 $796.20 331 642 25% 09/16/11 910.0 0.7574 1,011.1 765.8 $793.01 334 660 24% 10/16/11 780.0 0.7722 866.7 669.2 $609.18 266 551 23% 11/16/11 890.0 0.7950 988.9 786.2 $571.08 265 600 21% 12/16/11 870.0 0.7950 966.7 768.5 $558.25 259 586 21% 01/16/12 760.0 0.7625 844.4 643.9 $638.61 272 546 24% 02/16/12 750.0 0.7511 833.3 625.9 $682.46 284 550 25% 03/16/12 690.0 0.7574 766.7 580.7 $601.30 253 501 24% 04/16/12 870.0 0.7722 966.7 746.5 $679.47 296 614 23%

0.0 0.0 Savings 2012 $7,707.13

Approximate cost of standard power factor correction equipment $12 to $15K === Payback about 2 years.

Approximate cost of filtered power factor correction equipment $18 to $21K === Payback about 3 years.

●Example with $5.50 per demand kW

Page 10: TDD Full load

Schneider Electric – Global PQ – June 2013 10 10

Power Factor Correction

●Capacitors: ● Low Voltage Power Factor Correction Capacitor Banks

●Fixed

●Standard Automatic

●Detuned

●Transient Free

●Medium Voltage Power Factor Correction Capacitor Banks

●Fixed

●Standard Automatic

●Detuned

●Active Filters ● LV and MV Hybrid VAR Compensation Products

Page 11: TDD Full load

Schneider Electric – Global PQ – June 2013 11 11

Page 12: TDD Full load
Page 13: TDD Full load

Schneider Electric – Global PQ – June 2013 13 13

Outline

Power Factor:

●Definition & Examples

●Cost Savings

●Power Factor Correction Equipment

Harmonics:

●Introduction

●Harmonics and Power Factor Correction Capacitors

●IEEE 519 Standard

●Traditional Harmonic Mitigation Methods

●Active Filter Technology & Applications

Page 14: TDD Full load

Schneider Electric – Global PQ – June 2013 14 14

Harmonic Basics ● What are harmonics?

●A harmonic is a component of a periodic wave with a frequency that is an integer multiple of the fundamental frequency

●Created by power semiconductor devices ●Converts power (AC to DC)

●Characteristic harmonics are the predominate harmonics seen by the power distribution system

●Predicted by the following equation:

– HC = characteristic harmonics to be expected

– n = an integer from 1,2,3,4,5, etc.

– p = number of pulses or rectifiers in circuit

Harmonic Frequency Sequence 1 60Hz + 2 120Hz - 3 180Hz 0 4 240Hz + 5 300Hz - 6 360Hz 0 7 420Hz + : : 19 1140Hz +

Fundamental

3 rd Harmonic

5 t1h Harmonic

7 th Harmonic

Waveform seen with oscilloscope

1±= npHc

Page 15: TDD Full load

Schneider Electric – Global PQ – June 2013 15 15

Harmonic Filtering

Page 16: TDD Full load

Schneider Electric – Global PQ – June 2013 16 16

Multi-pulse Converters

Harmonic Orders Present

Hn1 phase 4-pulse

2 phase 4-pulse

3 phase 6-pulse

3 phase 12-pulse

3 phase 18-pulse

3 x x5 x x x7 x x x9 x x11 x x x x13 x x x x15 x x17 x x x x19 x x x x21 x x23 x x x x25 x x x x27 x x29 x x x31 x x x33 x x35 x x x x x37 x x x x x39 x x41 x x x43 x x x45 x x47 x x x x49 x x x x

Harmonics present by rectifier designType of rectifier

Hn = np +/- 1

Hn = characteristic harmonic order present

n = an integer

p = number of pulses

Elimination of lower orders removes largest amplitude harmonics

AccuSine SWP

AccuSine PCS

Page 17: TDD Full load

Schneider Electric – Global PQ – June 2013 17 17

Harmonic Basics ●Nonlinear loads draw harmonic current from source

● Does no work

Inverter Converter

DC bus

M

A B C

Current: high TDD between 90-120%

Voltage: flat topping of waveform

Basic PWM VFD

Page 18: TDD Full load

Schneider Electric – Global PQ – June 2013 18 18

Harmonic Basics

●Why the concern? ●Current distortion

●Added heating = reduced capacity

●Equipment failures

– Transformers

– Conductors and cables

– Nuisance tripping of electronic circuit breakers (thermal overloads)

●Heating proportional to harmonic order in cables & bus bars ●Squared effect on transformers & AC

motors

Loads

Ih

hhh ZIV ×=

Page 19: TDD Full load

Schneider Electric – Global PQ – June 2013 19 19

Harmonic Basics

Voltage distortion

●Created as current harmonics flow

through the system

● Interference with other electronic loads ●Malfunctions to failure

● Induces harmonic currents in linear loads ●AC motor winding over heating & bearing failures

Loads

Ih

hhh ZIV ×=

Page 20: TDD Full load

Schneider Electric – Global PQ – June 2013 20 20

M M M

Utility

VFD

Harmonics and Standard Capacitors

●Capacitors absorb harmonics ●Overheating of PFC capacitors

●Tripping of PF protection devices

●Reduced life expectancy

●Magnification of harmonics by resonance ●Amplification of current between

capacitor and transformer

●Current distortion rises

●Voltage distortion rises

●Main transformer &/or capacitor fuses blow

●Equipment damage

Page 21: TDD Full load

Schneider Electric – Global PQ – June 2013 21 21

Capacitor Resonance

Page 22: TDD Full load

Schneider Electric – Global PQ – June 2013 22 22

Detuned Capacitors

Page 23: TDD Full load

Schneider Electric – Global PQ – June 2013 23 23

Conventional Switch Structure

HRC Fuses

Contactors

Optional De-tuned Inductor

L1 L2 L3 Electro- mechanical switching elements (contactors) are used to connect a capacitor group.

Page 24: TDD Full load

Schneider Electric – Global PQ – June 2013 24 24

IEEE 519-1992

●Defines current distortion as TDD (Total Demand Distortion) ● Largest amplitude of harmonic current occurs at maximum load of

nonlinear device – if electrical system can handle this it can handle all lower levels of amplitudes

● Always referenced to full load current ● Effective meaning for current distortion

●Defines voltage distortion as THD ● Total harmonic voltage distortion

●Does not use THD(I) ● Total harmonic current distortion ● Instrument measurement (instantaneous values) ● Uses measured load current to calculate THD(I)

fII

THDi h∑=2

)(

2

FLAfII

TDD h∑=fVV

THDv h∑=2

Page 25: TDD Full load

Schneider Electric – Global PQ – June 2013 25 25

IEEE 519-1992 ● Issues addressed:

● THD(V) delivered by utility to user (Chapter 11)

●THD(V) must be < 5% [< 69 KV systems]

●Defines the amount of TDD a user can cause (Chapter 10)

●Based upon size of user in relation to power source

●Table 10.3 for systems < 69 kV

●Defines limits for voltage notches caused by SCR rectifiers – Table 10.2

●Defines PCC (point of common coupling)

Page 26: TDD Full load

Schneider Electric – Global PQ – June 2013 26 26

IEEE 519-1992

Total I, rms

Fund I, rms

Harm I, rms THD(I) TDD

Full load 936.68 936.00 35.57 3.8% 3.8%836.70 836.00 34.28 4.1% 3.7%767.68 767.00 32.21 4.2% 3.4%592.63 592.00 27.23 4.6% 2.9%424.53 424.00 21.20 5.0% 2.3%246.58 246.00 16.97 6.9% 1.8%111.80 111.00 13.32 12.0% 1.4%

Measured

• TDD and THD(I) are not the same except at 100% load

• As load decreases, TDD decreases while THD(I) increases.

• Example:

Page 27: TDD Full load

Schneider Electric – Global PQ – June 2013 27 27

IEEE 519-1992 Table 10.3 Current Distortion Limits for General Distribution Systems (<69 kV)

Isc/Iload <11 11<=h<17 17<=h<23 23<=h<35 h>=35 TDD<20 4.0% 2.0% 1.5% 0.6% 0.3% 5.0%

20<50 7.0% 3.5% 2.5% 1.0% 0.5% 8.0%50<100 10.0% 4.5% 4.0% 1.5% 0.7% 12.0%

100<1000 12.0% 5.5% 5.0% 0.2% 1.0% 15.0%>1000 15.0% 7.0% 6.0% 2.5% 1.4% 20.0%

Isc = short circuit current capacity of sourceIload = demand load current (fundamental)

(TDD = Total harmonic current distortion measured against fundamental current at demand load.)

TDD = Total Demand Distortion

Page 28: TDD Full load

Schneider Electric – Global PQ – June 2013 28 28

•Designed to protect utility •Most harmonic problems are not at PCC with utility

•Occur inside the plant •Occur where nonlinear loads are concentrated •Occur with generators & UPS (high probability of problems) •Need to protect the user from self by moving the PCC to where harmonic loads are located.

•Apply principals of IEEE 519-1992 Table 10.3 inside the plant

•Assures trouble free operations •Assures compliance to standard

•We have the products to meet 5% TDD inside the plant

Harmonic Standards

Page 29: TDD Full load

Harmonic mitigation methods - (Applied per VFD)

Solution Advantage Disadvantage Typical %

TDD Typical Price

Multiplier* Increase short circuit capacity Reduces THD(V)

●Increases TDD ●Not likely to occur**

Dependent upon SCR***

Cost of transformer and installation change out

C-Less Technology

●Lower TDD ●Simplified design ●Less cost

●Compliance is limited ●Application limited ●Size limited 30 - 50% TDD 0.90 - 0.95

Impedance (3% LR or 3% DC choke)

●Low cost adder ●Simple ●Compliance difficult 30 - 40% TDD 1.05 - 1.15

5th Harmonic filter

Reduces 5th & total TDD

●Does not meet harmonic levels at higher orders^ 18 - 22% TDD 1.20 - 1.45

Broadband filter Reduces TDD (thru 13th)

●Large heat losses ●Application limited 8 - 15% TDD 1.25 - 1.50

12-pulse rectifiers ●Reduces TDD ●Reliable

●Large footprint/heavy ●Good for >100 HP 8 - 15 % TDD 1.65 - 1.85

18-pulse rectifiers ●Reduces TDD ●Reliable

●Large footprint/heavy ●Good for >100 HP 5 - 8% TDD 1.65 - 1.85

Active front end converter

●Very good TDD ●Regeneration possible

●Large footprint/heavy ●Very high cost per unit ●High heat losses < 5% TDD 2.0 - 2.5

* Price compared to a standard 6-pulse VFD. ** Utilities and users are not likely to change their distribution systems. *** Increasing short circuit capacity (lower impedance source or larger KVA capacity) raises TDD but lowers THD(V). ^ Can be said for all methods listed.

Page 30: TDD Full load

Schneider Electric – Global PQ – June 2013 30 30

Active Filter Concept

Source XFMR

Load(s)

Is

Ia

Il

Optional CT location

•Parallel connected

• includes 2nd to 50th harmonic current

• <5% TDD

las III

=+aI

sI

LOAD Sense

SOURCE Sense

Page 31: TDD Full load

Schneider Electric – Global PQ – June 2013 31 31

●Price (first cost) ●Footprint required ●Heat losses ●Cost to operate

●Site cooling required ●Net Present Value (NPV)

System solution Comparison of 18-P VFD to AccuSine PCS + standard VFD

Harmonic Mitigation Solutions

Page 32: TDD Full load

Schneider Electric – Global PQ – June 2013 32 32

Solutions by AccuSine Model

Page 33: TDD Full load

Schneider Electric – Global PQ – June 2013 33 33

Schneider Electric Offer

●AccuSine SWP ●20-120 Amps

●400 VAC

●Neutral correction

●AccuSine PCS ●50-300 Amps

●208-480 VAC/600 VAC/690 VAC

●AccuSine PFV ●50-300 Amps

●208-480 VAC/600 VAC/690 VAC

●No harmonics

●Use customized transformers for higher voltages (to 15 kV for harmonics & 35 kV for non-harmonic modes)

Page 34: TDD Full load

Schneider Electric – Global PQ – June 2013 34 34

AccuSine SWP

●The Schneider Electric solution for harmonic filtering in buildings.

Page 35: TDD Full load

Schneider Electric – Global PQ – June 2013 35 35

AccuSine PCS

●The Schneider Electric solution for active harmonic filtering in industrial installations.

● Most common – VFD sites ●Centrifugal pumps and fans

●Pumping Stations

– Potable

– Wastewater

●Wastewater Plants

●Water Purification (potable)

Page 36: TDD Full load

Schneider Electric – Global PQ – June 2013 36 36

AccuSine® PCS/PFV Power Diagram

+ C

E

C

E

C

E

C

E

C

E

C

E

C

Line Inductor

Filter Board

Pre-charge Contactor

Inductor

Fuse

Fuse

Fuse

AC Lines

S4

S5

S6

S1

S2

S3 DC Bus Capacitors

IGBT Module

Page 37: TDD Full load

Schneider Electric – Global PQ – June 2013 37 37

AccuSine® PCS Performance Summary - Harmonics ●Discrete Spectrum Logic (DSL)

●TDD <= 5%, if loads have =>3% Z installed ● 2nd to 50th orders, discrete ● <2 cycle response ●Resonance avoidance logic ●Adjustable trip limits per harmonic order ●On-board commissioning program

●Phase rotation (clockwise required) ●Automatic CT orientation (phase rotation/polarity/calibration) ●Run lockout if not possible to re-orient

●Oscilloscope feature built into HMI ● Load/source bar graphs

●Load balancing ●Can parallel up to 99 units of each size and mix sizes

Page 38: TDD Full load

Schneider Electric – Global PQ – June 2013 38 38

System Solution

AccuSine® PCS Sizing Example ●A 125 HP variable torque 6-pulse VFD with 3% LR

● Required AHF filtering capability = 47.5 amperes ●Two 125 HP VT 6-pulse VFD w/3% LR

● Required AHF size = 84.4 amps ●Three 125 HP VT 6-pulse VFD w/3% LR

● Required AHF size = 113.5 amps ●Six 125 HP VT VFD w/3% LR

● Required AHF size = 157.6 amps ● (not 6 x 47.5 = 285 amps)

Page 39: TDD Full load

Schneider Electric – Global PQ – June 2013 39 39

Product Package ●Standard (UL/CSA, ABS) ● Three current ratings ●Enclosed – NEMA 1/IP20

● 50 amp – 52”(1321mm) x 21”(533mm) x 19”(483mm)

●Weight – 250#(114 K\kg) ● 100 amp – 69”(1753mm) x 21”(533mm) x

19”(483mm) ●Weight – 350#(159 kg)

● 300 amp – 75”(1905mm) x 32”(813mm) x 20”(508mm)

●Weight – 775#(352 kg) ●Wall mount – 50 & 100 amp ● Free standing – 300 amp with disconnect

AccuSine® PCS/PFV

Page 40: TDD Full load

Schneider Electric – Global PQ – June 2013 40 40

Product Package

●Other enclosures (380 - 480VAC) ●NEMA 12, IP30, IP54

●50 amp – 75”(1905mm) x 31.5”(800mm) x 23.62”(600mm)

– Weight – 661Ib(300 kg) ●100 amp – 75”(1905mm) x 31.5”(800mm) x 23.62”(600mm)

– Weight – 771Ib(350 kg) ●300 amp – 75”(1905mm) x 39.37”(1000mm) x 31.5”(800mm)

– Weight – 1012Ib(460 kg) ●Free standing with door interlocked

disconnect ●CE Certified, C-Tick, ABS, UL, CUL

AccuSine® PCS/PFV

Page 41: TDD Full load

Schneider Electric – Global PQ – June 2013 41 41

AccuSine PCS 600/690 VAC

● Includes autotransformer & input fused disconnect

●Simple installation ● 600 VAC: UL/cUL/CE ● 690 VAC: CE ●Ratings: PCS 600V 690V 50 A 39 A 33 A 100 A 78 A 67 A 300 A 235 A 200 A

300A

50/100A

Height

Height

1000 mm

800 mm

800 mm

600 mm

1900 mm

1972 mm

Depth 800 mm

600 mm

Page 42: TDD Full load

Schneider Electric – Global PQ – June 2013 42 42

AS off AS on Order % I fund % I fund Fund 100.000%100.000% 3 0.038% 0.478% 5 31.660% 0.674% 7 11.480% 0.679% 9 0.435% 0.297% 11 7.068% 0.710% 13 4.267% 0.521% 15 0.367% 0.052% 17 3.438% 0.464% 19 2.904% 0.639% 21 0.284% 0.263% 23 2.042% 0.409% 25 2.177% 0.489% 27 0.293% 0.170% 29 1.238% 0.397% 31 1.740% 0.243% 33 0.261% 0.325% 35 0.800% 0.279% 37 1.420% 0.815% 39 0.282% 0.240% 41 0.588% 0.120% 43 1.281% 0.337% 45 0.259% 0.347% 47 0.427% 0.769% 49 1.348% 0.590% TDD 35.28% 2.67%

AccuSine Performance

AccuSine injection

Source current

At VFD Terminals

Page 43: TDD Full load

Schneider Electric – Global PQ – June 2013 43 43

700 HP Drive – AccuSine ON – OFF

Page 44: TDD Full load

Schneider Electric – Global PQ – June 2013 44 44

700 HP Drive – AccuSine ON – OFF

Page 45: TDD Full load

Schneider Electric – Global PQ – June 2013 45 45

700 HP Drive – AccuSine ON – OFF

Page 46: TDD Full load

Schneider Electric – Global PQ – June 2013 46 46

Ias = rms output current of AccuSine PCS

Ih = rms harmonic current

If = rms fundamental current

Ias Ih If100.0 10.0 99.5100.0 20.0 98.0100.0 30.0 95.4100.0 40.0 91.7100.0 50.0 86.6100.0 60.0 80.0100.0 70.0 71.4100.0 80.0 60.0100.0 90.0 43.6100.0 95.0 31.2

Examples

AccuSine® PCS Dual Mode Operation 22

fhas III +=

● Assignment of capacity ● Assign priority to Harmonic or PF/LB

(fundamental) modes ● Use % of harmonic mode to set split

●100% means capacity utilized for harmonic correction, then left over can be used for PF/LB ●0% assigns fundamental (PF correction/LB) current as primary mode, left over used for harmonic correction ●Can split to limit harmonic mode capacity, left over to PF correction/LB

Page 47: TDD Full load

Schneider Electric – Global PQ – June 2013 47 47

Power Factor & VAR Compensation

●HVC (AccuSine PFV + PF caps) ●Larger systems approach

●HVC is Hybrid VAR Control

– Combines AccuSine PFV with PF caps – Caps on line all the time

●AccuSine adjusts fundamental current to attain unity DPF ●Cycle-by-cycle response ●Voltages to 33 kV (6.6 kV shredder in France, 12.47 kV in US

automotive, 13.8 kV steel mill in Colombia) ●Fundamental current balancing (optional since 1 Nov 10))

●Sometimes critical – i.e. two phase loads

AccuSine® PFV

Page 48: TDD Full load

Schneider Electric – Global PQ – June 2013 48 48

Thank You

Questions?