Top Banner

of 13

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Prep.Appr.Resp.dept.

    Document number Sheet

    No of sh.

    SEAPR/LAPP Lars Steiner SEAPR/LAPP

    Design DescriptionAdvant Controller 450 *2.3Task List

    SEAPR/LAPP Anders Wiberg 2000-02-16

    3BSE020440 1

    13

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without expressauthority is strictly forbidden. ABB3B

    SE00

    1270

    D000

    1/G

    ABB Automation ProductsFilename: TaskList23.fm; Modification date: 2001-01-18 08:26; Doc. skeleton: 3BSE001273/B

    Lang.en -

    Rev. ind.

    Advant Controller 450 2.3

    Task List

  • Document number Sheet23B

    SE00

    1270

    D000

    2/G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    1 INTRODUCTION

    1.1 Purpose and scope

    This document describes the operating system tasks included in the Advant Controller 450 system, release 2.3. The tasks are sorted in priority order -1..15, where 15 is the highest priority.

    1.2 Target group

    The document is meant for those who are programming or maintaining AC450 2.3 systems.

    1.3 Changes from release 2.2

    This document is based on the document 3BSE021173, Design Description, Advant Controller 450 2.2, Task List.

    Added tasks: CXPCKC0, CXPNSCn and CHVS0906

  • Document number Sheet33BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    2 TASK LIST

    Table 1 Task list for AC450*2.3

    Name Description Module a Prio In Chan. Out Chan. b

    CXKK340 Idle task BAS41 -1 - -

    CXDAXG0 DB lock function task BAS41 0 - -

    CXKK590 Memory supervision task BAS41 0 - -

    CXKK591 Auxiliary equipment supervision task(reads status from CI540 or PM150)

    BAS41 0 - -

    CXKK600 Prom board supervision task BAS41 0 - -

    CXNC320 Master Net init task BAS41 0 - -

    CXNUCM0 Master Bus init task BAS41 0 CXNUCH -

    YAPA000 Main startup task BAS41 0 - CLCHAN

    YEBC100 Controlled startup scan task BAS41 0 - -

    YEHA000 PIDCONA adaptation task LIB42 0 YEHGC1 DCBCF1

    CXNM200 Symbol translator task 1 OPF41 0 CXNMC2 -

    CXKK650 System clock comparison task BAS41 0 - -

    DAYIP10 PC utility task BAS41 1 - -

    IEASA50 System manager startup task BAT41 1 IEASHE -

    YAPB0040 BAT41 option module init task BAT41 1 - -

    YAPB006 LIB41 option module init task LIB41 1 - -

    YAPB008 LIB42 option module init task LIB42 1 - -

    YAPB0030 LOS41 option module init task LOS41 1 - -

    YEDP000 MV320 init task LOS41 1 - -

    YEDP01n MV320 presentation task n; n=1..4 LOS41 1 - CLCHANCXACSODCCC91DCCC92

    CXNM201 Symbol translator task 2 OPF41 1 MPCH02 -

    YAPB0020 OPF41 option module init task OPF41 1 - -

    YAPB0063 UDP41 option module init task UDP41 1 - -

    YAPB0071 COM41 option module init. task COM41 1 - -

    YAPB007 FUZ41 option module init. task FUZ41 1 - -

    CXCS050 Console communication accessor task BAS41 2 CXCCH2 CLCHAN

  • Document number Sheet43B

    SE00

    1270

    D000

    2/G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    CXNM510 Network management statistics and control point handler

    BAS41 2 CXNMSM CXNMTN

    CXNM530 Network management timer task in master BAS41 2 CXNMTN CXNMTN

    CXNM540 Network management forwarding task BAS41 2 CXNMFW -

    CXNM570 Network management startup task BAS41 2 CXNMSU -

    IEASA60 System manager close down task (cold) BAT41 2 IEASHF -IEASA61 System manager close down task (warm) BAT41 2 - -IEASA70 System manager cold start task makes a

    cold restart (activates IEASA60 & IEASA50) in process station

    BAT41 2 - -

    DCCA010 System message analyzer OPF41 2 SYSCHA -

    DCLA020 Status List search OPF41 2 DCLC20 DCLC20

    FAFA200 Statement description pre-processor UDP41 2 - -

    FAFA300 Code library pre-processor UDP41 2 - -

    CXAF000 EXCOM link handler A BAS41 3 CXARP0 -

    CXAF001 EXCOM link handler B BAS41 3 CXARP1 -

    CXAF010 EXCOM DB update BAS41 3 CXACND -

    IEAEAC0 Batch handling report collector BAT41 3 IEAEHSIEAEHT

    -

    IEAEAI0 Batch handling recipe receiver BAT41 3 IEAEHOIEAEHP

    -

    IEAEAO0 Batch handling operation sequencer BAT41 3 IEAEHIIEAEHJ

    -

    IEAEAS0 Batch handling section sequencer BAT41 3 IEAEHKIEAEHL

    -

    DCBAF00 PIDCONA object handler, event part LIB42 3 DCBCF1 DCSC96DCBAH00 PIDCON object handler, event part LIB42 3 DCBCH1 DCSC63DCBAJ00 MANSTN object handler, event part LIB42 3 DCBCJ1 DCSC75DCBAK00 RATIOSTN object handler, event part LIB42 3 DCBCK1 DCSC76DCBAB00 AI object handler, event part OPF41 3 DCBCB1 DCBCB1

    DCBCH1DCBCJ1DCBCK1DCBCF1DCSC53

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet53BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    DCBAD00 DI object handler, event part OPF41 3 DCBCD1 DCBCD1DCSC55

    DCBAG00 GROUP_ALARM object handler, event part

    OPF41 3 DCBCG4DCBCG3

    DCBCG4DCBCG2DCSC73

    DCBAG10 GROUP_ALARM utilities OPF41 3 - -

    DCBAI00 SEQ_CTRL object handler, event part OPF41 3 DCBCI1 DCSC65DCBAP00 GENOBJ object handler, event part OPF41 3 DCBCP1 DCSC67DCBAQ00 MMC-X object handler, event part OPF41 3 DCBCQ1 DCSCQ1DCBAX00 Dummy object handler OPF41 3 - -DCTA200 TTD primary memory logging OPF41 3 DCTC20 DCTC60

    DCTA500 TTD manipulation OPF41 3 DCTC50DCTC51

    DCTC60

    DCTA600 TTD subscription OPF41 3 DCTC60 -

    CHVMP40 Time-out supervision task (VFI) BAS41 3 - -CXAX000 Extended MVI data set communication BAS41 4 MVAPRQ -CXAX01ab Extended MVI data set communication,

    slave a, port b; a=1..5, b=1..2for a=5 exists only b=1

    BAS41 4 MVRCDMVRSPnMVUPSnCXAMMS

    -

    CXNM560 Network management network monitor task

    BAS41 4 CXNMACXNMLB

    -

    CXPC7C0 Scantask for retry sending to object handler BAS41 4 - -CXPCK20 PDC event handler task BAS41 4 CXPSC1 DCBCD1

    DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    CXPCKC0 LON event translator task BAS41 4 CXPSC2 DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1DCBCQ1

    CXRP100 Monitor task for redundant CPU BAS41 4 - -

    DAYIP30 PC init task BAS41 4 - -

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet63BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    DCCA910 Printer adaptation BAS41 4 DCCC90DCCC91DCCC92

    DCCC90

    YEBC010 Controlled startup execute task BAS41 4 - -

    YECB000 System supervision task BAS41 4 - -

    YECB0D0 Carrier board supervision task BAS41 4 - -

    IEACA40 Material and tank data supplier in process station

    BAT41 4 IEACH8IEACH9

    -

    IEAEAE0 Batch handling emergency report handler BAT41 4 IEAEHUIEAEHV

    -

    IEAEAR0 Batch handling address receiver BAT41 4 IEAEHQIEAEHR

    -

    DCSA0146 Subscription analyzer, reference type 46 (PIDCONA)

    LIB42 4 DCSC46NSTATUDCSC96

    -

    DCSA0113 Subscription analyzer, reference type 13 (PIDCON)

    LIB42 4 DCSC13NSTATUDCSC63

    -

    DCSA0125 Subscription analyzer, reference type 25 (MANSTN)

    LIB42 4 DCSC25NSTATUDCSC75

    -

    DCSA0126 Subscription analyzer, reference type 26 (RATIOSTN)

    LIB42 4 DCSC26NSTATUDCSC76

    -

    DCSA000 Subscription multiplexer OPF41 4 DCSC00 -

    DCSA013 Subscription analyzer, reference type 3 (AI)

    OPF41 4 DCSC03NSTATUDCSC53

    -

    DCSA014 Subscription analyzer, reference type 4 (AO)

    OPF41 4 DCSC04NSTATUDCSC54

    -

    DCSA015 Subscription analyzer, reference type 5 (DI)

    OPF41 4 DCSC05NSTATUDCSC55

    -

    DCSA016 Subscription analyzer, reference type 6 (DO)

    OPF41 4 DCSC06NSTATUDCSC56

    -

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet73B

    SE00

    1270

    D000

    2/G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    DCSA0115 Subscription analyzer, reference type 15 (SEQ_CTRL)

    OPF41 4 DCSC15NSTATUDCSC65

    -

    DCSA0117 Subscription analyzer, reference type 11,12,17,19,27,28,30,44,45(GENOBJ)

    OPF41 4 DCSC17NSTATUDCSC67

    -

    DCSA0123 Subscription analyzer, reference type 23 (GROUP_ALARM)

    OPF41 4 DCSC23NSTATUDCSC73

    -

    DCSA0136 Subscription analyzer, reference type 36,37,38,39,40,41(MMC-X)

    OPF41 4 DCSCQ0NSTATUDCSCQ1

    -

    DCSA0143 Subscription analyzer, reference type 43 (DAT)

    OPF41 4 DCSC43NSTATUDCSC68

    -

    DCSA0148 Subscription analyzer, reference type 48 (TEXT_DATA)

    OPF41 4 DCSC48NSTATUDCSC98

    -

    DCSA0220 Subscription analyzer, reference type 20 (simple data)

    OPF41 4 DCSC20 -

    DCTA100 TTD init OPF41 4 - DCTC20DCTC50DCTC60

    CXAA000 Data set communication BAS41 5 CXADSDCXADSP

    -

    CXAM000 MVI data set communication BAS41 5 CXAMSDCXAMSPCXAMMS

    -

    CXAPC0n Data set peripheral config task n; n=1..8 BAS41 5 - -

    CXAT000 Text set communication BAS41 5 CXATSDCXATSP

    -

    CXNU71n Master bus 300 handler n; n=1..6 BAS41 5 - -

    CXNU92n Master bus 300 handler n; n=7..15 BAS41 5 - -

    CXPCK00 PDC handling of service data BAS41 5 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet83BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    CXPHSCn AF100 and S800 Supervision task n; n=1..8

    BAS41 5 - -

    CXPNSCn LON supervision task, n=1..4 BAS41 5 - -

    DCWA010 System Status handler OPF41 5 DCWC10DCWC11DCWC13

    DCBCB0DCBCC0DCBCD0DCBCE0FCBCF0FCBCG0DCBCU0DCWC13DCBCR0DCBCS0

    CHVMP2n Slave dispatcher for VFI bus n BAS41 5 - -

    CHVMP3n Master receive task for VFI bus n BAS41 5 - -

    CHVMP51 Slave dispatcher for CI572/CI573 BAS41 5 - -

    CXPKSCn PROFIBUS_DP supervision task n; n=1..8 BAS41 5 - -

    CXAP000 Data set peripheral scan task BAS41 6 - -

    CXPC504 AI scan task ( >2s ) BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    CXPC510 AI scan task, slow temp BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    CXPC800 S100 and S400 supervision task BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    CXPCI20 CI570 Supervision task BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet93BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    CXPICF0 PDC configuration task BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    CXPIOP0 PDC init task BAS41 6 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    IEAEAD0 Batch handling object database handler BAT41 6 DCBCP1IEAEHNDCBCP0IEAEHM

    DCSC67

    IEAKAF0 Batch handling proevent analyzer BAT41 6 DCCC20IEAKH1IEAKH0

    -

    DCBAF01 PIDCONA object handler, dialogue part LIB42 6 DCBCF0 DCSC96DCBAH01 PIDCON object handler, dialogue part LIB42 6 DCBCH0 DCSC63DCBAJ01 MANSTN object handler, dialogue part LIB42 6 DCBCJ0 DCSC75DCBAK01 RATIOSTN object handler, dialogue part LIB42 6 DCBCK0 DCSC76DCBAB01 AI object handler, dialogue part OPF41 6 DCBCB0 DCBCB1

    DCBCH1DCBCJ1DCBCK1DCBCF1DCSC53

    DCBAC01 AO object handler OPF41 6 DCBCC0 DCSC54DCBAD01 DI object handler, dialogue part OPF41 6 DCBCD0 DCBCD1

    DCSC55

    DCBAE01 DO object handler OPF41 6 DCBCE0 DCSC56DCBAG01 GROUP_ALARM object handler, dialogue

    partOPF41 6 DCBCG1

    DCBCG2DCBCG4DCBCG2DCSC73

    DCBAI01 SEQ_CTRL object handler, dialogue part OPF41 6 DCBCI0 DCSC65DCBAL00 Simple data object handler OPF41 6 DCBCL0 DCSC20DCBAL043 DAT object handler OPF41 6 DCBCG0 -

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet103BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    DCBAP01 GENOBJ object handler, dialogue part OPF41 6 DCBCP0 DCSC67DCBAQ01 MMC-X object handler, dialogue part OPF41 6 DCBCQ0 DCSCQ1DCBAR00 Signal handler S6CI_STN OPF41 6 DCBCR0 -

    DCBAS00 Signal handler S800_INTF OPF41 6 DCBCS0 -

    DCBAT01 TEXT_DATA object handler OPF41 6 DCBCT0 DCSC98DCBAU00 OBJ_INTERFACE object handler OPF41 6 DCBCU0 -DCBAW00 Subscription handler for Syst.Status Dis-

    play. Object handler for commands to h/w.OPF41 6 DCBCW0 -

    FHVA100 Objectsupport via AF100, commandmonitor.

    COM41 6 OCHA14 -

    CXBH26n Basic I/O handler n; n=0..6 BAS41 7 CXBCHn -

    CXBH270 Basic I/O modem signals BAS41 7 CXBHMS -

    CXBH280 TC520 handler BAS41 7 - -

    CXKK380 Intermediate stall supervision BAS41 7 - -

    CXNC390 Master Net timer task BAS41 7 - -

    CXNM800 High precision time synch task BAS41 7 CXACSL -

    CXNM910 Task for routing function in the master BAS41 7 NMROUT NSTATU

    CXNT000 Master Net transport & network handler BAS41 7 - -

    CXNU810 MB300 transceiver task BAS41 7 - -

    DAXI002 PC interpreter C BAS41 7 DAXIAC DCBCI1DCBCH1DCBCJ1DCBCK1DCBCP1DCBCQ1DCBCF1

    CXPS100 DSBC174 supervision task BAS41 7 - -

    FAFA100 Command Monitor and Utilities UDP41 7 - -

    CXCS040 CC target system communication handler BAS41 8 CXCCH3SYSCHACXCCH0

    CXCCH2

    CXCS260 CC network handler BAS41 8 CXCCH4SYSCHACXCCH0

    CXCCH2

    CXND200 IEEE 802.3 MAC controller 1 BAS41 8 - -

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet113B

    SE00

    1270

    D000

    2/G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    CXND201 IEEE 802.3 MAC controller 2 BAS41 8 - -

    DAXI001 PC interpreter B BAS41 8 DAXIAB DCBCI1DCBCH1DCBCJ1DCBCK1DCBCP1DCBCQ1DCBCF1

    CXPC400 DI task BAS41 9 - DCBCD1DCBCB1DCBCH1DCBCJ1DCBCK1DCBCF1

    DAXI000 PC interpreter A BAS41 9 - DAXIABDAXIACDCBCI1DCBCH1DCBCJ1DCBCK1DCBCP1DCBCQ1DCBCF1

    CXAE000 Clock sync task BAS41 10 CXACSOCXACSMCXABRQCXABRPNSTATU

    CXACSOCLCHAN

    CXKK500 System message transfer task on master BAS41 10 CXKCH2 -

    CXLT100 Clock adjustment BAS41 10 CLCHAN -CXLT130 External time sync BAS41 10 - -

    CXPCI30 CI520, CI570 and CI572/CI573 watchdog and time sync task

    BAS41 10 - -

    CXPHS20 Utility task for CXPHS10 BAS41 11 - CXPSO0

    CXPHS30 Utility task for CXPHS10 BAS41 11 - CXPSO0

    CXPHS10 Switchover task for CI522 BAS41 12 CXPSO0 CXPSO0

    YEBC000 Controlled startup handling task BAS41 14 - -

    CXKK220 Timer task BAS41 15 - -

    CXKK550 System startup task BAS41 15 - -

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet123B

    SE00

    1270

    D000

    2/G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    CXRP110 Task for restart of HW handlers after take-over (redundant CPU)

    BAS41 15 - -

    a. Available modules are:BAS41, LIB41, LIB42, LOS41, OPF41, BAT41, UDP41, COM41 and FUZ41.

    b. Explicitly addressed signals are not included in this table.

    Table 1 Task list for AC450*2.3 (Continued)

    Name Description Module a Prio In Chan. Out Chan. b

  • Document number Sheet133BS

    E001

    270D

    0002

    /G

    ABB Automation ProductsLang.en -

    Rev. ind.3BSE020440

    REVISION

    Rev.Ind.

    Page (P)Chapt (C) Description

    DateDept./Init

    - New document.Based on 3BSE021173.

    2000-02-16APR/LAPP AW