Top Banner
Tank Safety & Protection Devices Emergency Vent Cover 52 Vent Operation Construction The KSEP emergency pressure relief vent provides pressure relief only. Vacuum relief must be supplied by normal venting devices, or use our KSEV emergency pressure and vacuum relief vent covers. When excessive pressure builds within the storage tank the KSEP series emergency pressure relief vent begin to open at a predetermined set pressure relieving excessive pressure. When the overpressure has dissipated the cover reseat onto the base. The series KSEP is available in several materials that are corrosion resistant to most petroleum product applications. See Standard material of construction table for available material. Predetermined setting range is from a minimum of 50mm W.C to a maximum of 700mmW.C Sizes are 400, 450, 500 and 600mm with flange drilling according to ANSI 150lb or API650. The series KSEP is designed to provide emergency pressure relief for storage tanks when exposed to overpressures that are not handled by standard tank vents. These vents provide the capacity to meet API standard 2000 for emergency venting due to fire exposure when properly sized. These covers also provide quick easy access for tank inspection and maintenance. According to API 2000 Code : EMERGENCY PRESSURE RELIEF VENT COVER KSEP Section 4.1
2

Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSEP.pdf · Tank Safety & Protection Devices Emergency Vent Cover 52 ... These vents

Apr 14, 2018

Download

Documents

NguyễnKhánh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSEP.pdf · Tank Safety & Protection Devices Emergency Vent Cover 52 ... These vents

Tank Safety & Protection Devices Emergency Vent Cover

52

Vent Operation

Construction

The KSEP emergency pressure relief vent provides pressure relief only.

Vacuum relief must be supplied by normal venting devices, or use our KSEV emergency pressure and vacuum relief vent covers.

When excessive pressure builds within the storage tank the KSEP series emergency pressure relief vent begin to open at a predetermined set pressure relieving excessive pressure.

When the overpressure has dissipated the cover reseat onto the base.

The series KSEP is available in several materials that are corrosion resistant to most petroleum product applications.

See Standard material of construction table for available material.

Predetermined setting range is from a minimum of 50mm W.C to a maximum of 700mmW.C

Sizes are 400, 450, 500 and 600mm with flange drilling according to ANSI 150lb or API650.

The series KSEP is designed to provide emergency pressure relief for storage tanks when exposed to overpressures that are not handled by standard tank vents.

These vents provide the capacity to meet API standard 2000 for emergency venting due to fire exposure when properly sized.

These covers also provide quick easy access for tank inspection and maintenance.

According to API 2000 Code :

EMERGENCY PRESSURE RELIEF VENT COVER KSEP

Section 4.1

Page 2: Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSEP.pdf · Tank Safety & Protection Devices Emergency Vent Cover 52 ... These vents

Tank Safety & Protection Devices Emergency Vent Cover

53

EMERGENCY PRESSURE RELIEF VENT COVER KSEP

Unit = mm

16” 18” 20” 24”N.D 400 450 500 600

AAPI 650 597 635 660 762

ANSI 150# 597 635 700 815

APP.HMIN. 115 115 115 115MAX. 150 165 180 200

KSEP TYPE

APP.

H

A

N.D

5 6

3

1

2

4

7 2

KSEP FRONT CROSS SECTION VIEW

Materials of Construction

Dimension Table

ITEMNO COMPONENT

BODY ALUMINIUM C.S SS304 SS316TRIM SS304 SS304 SS304 SS316L

1 BODY B26-319.F A216-WCB A351-CF8 A351-CF8M2 COVER & PLATE SS304 SS304 SS304 SS316L3 GUIDE SS304 SS304 SS304 SS316L4 DIAPHRAGM TEFLON5 EARTH WIRE SS304 SS304 SS304 SS3046 HEX BOLT/NUT SS304 SS304 SS304 SS304

7 LOADING W’T C.S OR SS

Section 4.1