Operate PB-1 and PB-2 Seal Water Filter System Type CONTINUOUS Document No. TO-600-210 Rev/Mod L-7 Release Date 04/05/2018 Page 1 of 39 Tank Farm Plant Operating Procedure 242-A Evaporator USQ # EV-18-0526-D, Rev 0 CHANGE HISTORY ( LAST 5 REV-MODS ) Rev-Mod Release Date Justification: Summary of Changes L-7 04/05/2018 Address WRPS-PER-2017- 1808 Deleted requirement to initial and made columns "Check" blocks. Added signature at the end. Added a step just prior to step 5.1.2 that states "Personnel initialing valve line-up on Checklist 1, must record the required information on Signature Sheet 1." L-6 05/23/2017 Process improvement, PCA was a result of a periodic review. Updated a step regarding short term shutdown. Updated a referenced procedure title and pagination in this document. L-5 06/02/2016 Not closing valve 4-50A leaves the system pressurized Added closing valve 4-50A to system shutdown in step 5.10.7 Records section updated to standard. L-4 04/26/2016 Operational flexibility Changes give option to use F-RW-1 and/or F-RW-2 Raw Water Strainers in service. Pages 7 and 34 L-3 04/12/2016 Operational flexibility Correct component ID. Add alternate valving to isolate seal water flow to PB-2 pump. Table of Contents Page 1.0 PURPOSE AND SCOPE ................................................................................................................ 3 1.1 Purpose................................................................................................................................ 3 1.2 Scope ................................................................................................................................... 3 2.0 INFORMATION............................................................................................................................. 4 2.1 General Information ............................................................................................................ 4 3.0 PRECAUTIONS AND LIMITATIONS......................................................................................... 5 3.1 Personnel Safety.................................................................................................................. 5 3.2 Equipment Safety ................................................................................................................ 5 3.3 Radiation and Contamination Control ................................................................................ 5 3.4 Environmental Compliance ................................................................................................ 5 3.5 Limits .................................................................................................................................. 6 4.0 PREREQUISITES .......................................................................................................................... 6 4.1 Special Tools, Equipment, and Supplies............................................................................. 6
39
Embed
Tank Farm Plant Operating Procedure 242-A Evaporator USQ ... · This procedure provides instructions for operating and cleaning the PB-1 and PB-2 Seal Water System and filters. 1.2
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
1 of 39
Tank Farm Plant Operating Procedure 242-A Evaporator
USQ # EV-18-0526-D, Rev 0
CHANGE HISTORY ( LAST 5 REV-MODS )
Rev-Mod Release Date Justification: Summary of Changes
L-7 04/05/2018 Address WRPS-PER-2017-
1808
Deleted requirement to initial and made columns "Check"
blocks. Added signature at the end. Added a step just prior to
step 5.1.2 that states "Personnel initialing valve line-up on
Checklist 1, must record the required information on Signature
Sheet 1."
L-6 05/23/2017 Process improvement, PCA was
a result of a periodic review.
Updated a step regarding short term shutdown. Updated a
referenced procedure title and pagination in this document.
L-5 06/02/2016 Not closing valve 4-50A leaves
the system pressurized
Added closing valve 4-50A to system shutdown in step 5.10.7
Records section updated to standard.
L-4 04/26/2016 Operational flexibility Changes give option to use F-RW-1 and/or F-RW-2 Raw Water
Strainers in service. Pages 7 and 34
L-3 04/12/2016 Operational flexibility Correct component ID. Add alternate valving to isolate seal
water flow to PB-2 pump.
Table of Contents Page
1.0 PURPOSE AND SCOPE ................................................................................................................ 3
5.8.2 IF Process Condensate Seal Water System has previously been started,
GO TO Step 5.8.11.
Process Condensate Seal Water Initial Fill
5.8.3 CLOSE PDT-FC4/5 inlet valve 1-80A.
5.8.4 SET P-C106 (G18/10, F27/5) CONDSATE RECYCLE PUMP to CF-ON.
5.8.5 IF process condensate filter F-C-5 is to be placed in service,
PERFORM the following actions in the Condenser Room.
5.8.5.1 ENSURE outlet valve 1-85 is CLOSED.
5.8.5.2 CRACK OPEN Valve 1-83.
5.8.5.3 OPEN inlet valve 1-82.
5.8.5.4 AFTER a steady flow of water is seen coming from Valve 1-83,
CLOSE Valve 1-83.
5.8.5.5 SLOWLY OPEN outlet valve 1-85.
5.8.5.6 ENSURE the following Valves are CLOSED:
1-89
1-88.
5.8.5.7 CHECK for visible signs of leakage from F-C-5 AND
NOTIFY Shift Manager if leaks are observed.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
25 of 39
5.8 Switch Seal Water System from Filtered Raw Water to Process
Condensate (Cont.)
5.8.6 IF process condensate filter F-C-4 is to be placed in service,
PERFORM the following actions in Condenser Room:
5.8.6.1 ENSURE outlet valve 1-89 is CLOSED.
5.8.6.2 CRACK OPEN Valve 1-88.
5.8.6.3 OPEN inlet valve 1-86.
5.8.6.4 AFTER a steady flow of water is seen coming from Valve 1-88,
CLOSE Valve 1-88.
5.8.6.5 SLOWLY OPEN outlet Valve 1-89.
5.8.6.6 ENSURE the following Valves are CLOSED:
1-85
1-83.
5.8.6.7 CHECK for visible signs of leakage from F-C-4 AND
NOTIFY Shift Manager if leaks are observed.
5.8.7 PLACE the "In Service" and "Standby" signs on appropriate Process
Condensate filters.
5.8.8 OPEN Valve 4-51 for approximately 2 minutes to fill piping with process
condensate.
5.8.9 AFTER approximately 2 minutes, CLOSE Valve 4-51.
5.8.10 OPEN PDT-FC4/5 inlet Valve 1-80A.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
26 of 39
5.8 Switch Seal Water System from Filtered Raw Water to Process
Condensate (Cont.)
NOTE - If the Process Condensate Seal Water System has been previously started per
this section, then the F-C-5/F-C-4 filters do not need to be valved in.
5.8.11 IF Process Condensate Seal Water System has previously been started,
PERFORM the following:
5.8.11.1 IF switching back to Process Condensate after a filter change and
F-C-4 and F-C-5 valving has not changed, GO TO Step 5.8.11.4.
5.8.11.2 IF F-C-5 is in service, ENSURE Valve 1-85 is open.
5.8.11.3 IF F-C-4 is in service, ENSURE Valve 1-89 is open.
5.8.11.4 SET P-C106 (G18/10, F27/5) CONDSATE RECYCLE PUMP to
CF-ON.
Switch PB-1 and PB-2 seal water source to process condensate
CAUTION
Allowing process condensate to flow through booster pumps P-C-105
and P-C-105A for an extended period may damage seals.
NOTE - P-C-105 and P-C-105A must only be used with filtered raw water except when
switching between filtered raw water and process condensate.
5.8.12 ENSURE the following Valves are OPEN:
5-18A
5-18B.
5.8.13 SET HV-CA1-10 (G12/15, F6/14) SEAL WATER VALVE to CF-PC
position by clicking SPLY PC.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
27 of 39
5.8 Switch Seal Water System from Filtered Raw Water to Process
Condensate (Cont.)
5.8.14 IF seal water booster pumps are in operation, PERFORM the following:
5.8.14.1 SET P-C-105A (G12/13, F6) SEAL WATER PUMP to
MANUAL and CF-OFF status.
5.8.14.2 SET P-C-105 (G12/12, F6) SEAL WATER PUMP to MANUAL
and CF-OFF status.
5.8.14.3 POSITION the following valves as indicated:
Valve Number Pumps Position
5-16 P-C-105
CLOSED
5-18 CLOSED
5-17 P-C-105A
CLOSED
5-19 CLOSED
NOTE - Parameters may be monitored from current trend 8, on screen graphics or
locally.
5.8.15 NOTIFY Shift Manager if any of the following readings are not within
normal range: (OSD-T-151-00012)
Pump EPN Normal Range
PB-1 FI-CA1-1 (G12) 0.60 to 2.0 gpm
PI-CA1-9 (G12) 40 to 58 psig
PB-2 FI-CA1-2 (G15) 1.0 to 2.00 gpm
PI-CA1-10 (G15) 65 to 75 psig
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
28 of 39
5.9 Switch Seal Water System from Process Condensate to Filtered Raw
Water
Start Filtered Raw Water Booster Pumps
CAUTION
Allowing process condensate to flow through booster pumps P-C-105
and P-C-105A for an extended period may damage seals.
NOTE - P-C-105 and P-C-105A must only be used with filtered raw water except when
switching between filtered raw water and process condensate, or unless
otherwise directed by Shift Manager.
- If both seal water booster pumps are operable, either seal water booster pump
may be placed in MANUAL and used as the primary, and the “ALTERNATE”
pump placed in AUTO and used as a backup.
- If only one seal water booster pump is operable the “INOPERABLE” pump
will be left in OFF and MANUAL with the isolation valves for that pump
closed.
5.9.1 POSITION the following valves as indicated.
Valve Number Pumps Position
5-16 P-C-105
OPEN
5-18 OPEN
5-17 P-C-105A
OPEN
5-19 OPEN
Start P-C-105 Seal Water Pump
5.9.2 IF P-C-105 (G12/12, F6/1) SEAL WATER PUMP is to be used as the
primary seal water booster pump with P-C-105A (G12/13, F6/3) SEAL
WATER PUMP as backup, PERFORM the following:
5.9.2.1 SET P-C-105A to MANUAL.
5.9.2.2 SET P-C-105 to MANUAL and CF-ON status.
5.9.2.3 SET P-C-105A to AUTO.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
29 of 39
5.9 Switch Seal Water System from Process Condensate to Filtered Raw
Water (Cont.)
Start P-C-105A Seal Water Pump
5.9.3 IF P-C-105A (G12/13, F6/3) SEAL WATER PUMP is to be used as the
primary seal water booster pump with P-C-105 (G12/12, F6/1) SEAL
WATER PUMP as backup, PERFORM the following:
5.9.3.1 SET P-C-105 to MANUAL.
5.9.3.2 SET P-C-105A to MANUAL and CF-ON status.
5.9.3.3 SET P-C-105 to AUTO.
Switch PB-1 and PB-2 Water Source to Filtered Raw Water
5.9.4 SET HV-CA1-10 (G12/15, F6/14) SEAL WATER VALVE to CF-FRW
status.
NOTE - Parameters may be monitored from current trend 8, on screen graphics or
locally.
5.9.5 NOTIFY Shift Manager if any of the following readings are not within
normal range: (OSD-T-151-00012)
Pump EPN Normal Range
PB-1 FI-CA1-1 (G12) 0.60 to 2.0 gpm
PI-CA1-9 (G12) 40 to 58 psig
PB-2 FI-CA1-2 (G15) 1.0 to 2.00 gpm
PI-CA1-10 (G15) 65 to 75 psig
5.9.6 SET P-C106 (G18/10, F27/5) CONDSATE RECYCLE PUMP to CF-OFF
status.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
30 of 39
5.10 Shut Down Seal Water System
5.10.1 ENSURE P-C-105A (G12/13, F6/3) SEAL WATER PUMP is set to
MANUAL and CF-OFF status.
5.10.2 ENSURE P-C-105 (G12/12, F6/1) SEAL WATER PUMP is set to
MANUAL and CF-OFF status.
5.10.3 SET HV-CA1-10 (G12/15, F6/14) SEAL WATER VALVE to CF-FRW.
5.10.4 ENSURE P-C106 (G18/10, F27/5) CONDSATE RECYCLE PUMP is set to
MANUAL and CF-OFF status.
5.10.5 POSITION the following valves as indicated.
Valve Number Pumps Position
5-16 P-C-105
OPEN
5-18 OPEN
5-17 P-C-105A
OPEN
5-19 OPEN
5.10.6 ENSURE seal water system has run at least 10 minutes on Filtered Raw
Water to flush the seal water system before proceeding.
5.10.7 REQUEST Backside Operator to position the following valves as indicated.
Valve
Number Description Position
4-50A FRW isolation valve CLOSED
5-45A PB-1 isolation valve CLOSED
1-89 Outlet valve F-C-4 filter CLOSED
5-43 PB-2 isolation valve CLOSED
1-85 Outlet valve F-C-5 filter CLOSED
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
31 of 39
5.11 Short Term Shutdown of PB-1 and/or PB-2 Seal Water Systems
NOTE - With concurrence of 242-A Shift Manager either or both PB-1 and PB-2 seal
water systems may be put into short term shutdown by isolating seal water
flow to the respective pump(s).
- Seal water flow to PB-1 must not be isolated if the CA1 vessel has a volume of
greater than 96 inches as read on LI-CA1-3.
5.11.1 IF CA1 vessels volume is greater than 96 inches as read on LI-CA1-3,
ENSURE seal water flow to PB-1 is not isolated.
5.11.2 IF isolating both PB-1 and PB-2 seal water systems, SHUTDOWN seal
water booster pumps per Section 5.5.
5.11.3 IF isolating seal water flow to PB-1 pump, CLOSE valve 5-45A.
NOTE - Seal water flow to PB-2 must not be isolated if slurry out activities are in
progress whether by gravity slurry out, PB-2 pumping operation, or FARM
FLUSH.
5.11.4 IF isolating seal water flow to PB-2 pump, CLOSE valve 5-43 or valve 5-29
as specified by Shift Manager.
5.11.5 IF directed by Shift Manager, SET P-C106 (G18/10, F27/5) CONDSATE
RECYCLE PUMP to CF-OFF status.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
32 of 39
5.12 Return to Service from Short Term Shutdown of PB-1 and/or PB-2 Seal
Water Systems
NOTE - With concurrence of 242-A Shift Manager either or both PB-1 and PB-2 seal
water systems may be returned to service from short term shutdown by
restoring seal water flow to the respective pump(s).
- Seal water flow to PB-1 must be returned to service before the CA1 vessel is
filled to greater than 96 inches as read on LI-CA1-3.
5.12.1 IF returning seal water flow to PB-1 pump from short term shutdown and
before the CA1 vessel is filled to greater than 96 inches as read on LI-CA1-3,
OPEN valve 5-45A.
NOTE - Seal water flow to PB-2 must be returned to service before slurry flow is
initiated, whether by gravity slurry out, PB-2 pumping operation, or FARM
FLUSH.
5.12.2 IF returning seal water flow to PB-2 pump from short term shutdown,
OPEN valve 5-43 or valve 5-29 as specified by the Shift Manager.
5.12.3 IF seal water booster pumps are required due to operating conditions,
START seal water booster pumps per Section 5.4.
5.12.4 IF directed by Shift Manager, SET P-C106 (G18/10, F27/5) CONDSATE
RECYCLE PUMP to CF-ON status.
5.12.4.1 SET HV-CA1-10 (G12/15, F6/14) SEAL WATER VALVE to
CF-PC position.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
33 of 39
5.13 Records
5.13.1 PERFORM the following for records identified within this procedure.
5.13.1.1 RECORD the number of times the record was generated in
applicable column
OR
PLACE a check mark () in the N/A column.
5.13.1.2 SUBMIT the package to the central shift office.
Records Submittal Checklist
Number
of times
completed
N/A
()
4.3 Field Preparation Step 4.3.4
Checklists
Checklist 1
Signature Sheets
Signature Sheet 1
FWS/OE/Shift Manager SEND the completed records to the Central Shift Office for
records retention
/ /
Signature Print (First and Last) Date
FWS/OE/Shift Manager
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
34 of 39
Checklist 1 - Seal Water System Valve Lineup
Seal Water System Valve Lineup Date Started Time Started
Valve Location Position Description P&ID Location Operator Initial Date
HVAC Room
*H-1 H OPEN RW to F-H-3 98991/2/D7
H-1A H OPEN PDT-FH3-1 Isolation 99003/1/B8
H-2A H CLOSE F-H-3 Drain 99003/1/B8
H-2B H CLOSE F-H-3 Drain 99003/1/B8
HV-H-1C H OPEN PDT-FH3-1 Isolation 99003/1/B8
HV-H-3C H OPEN PDT-FH1-1 Isolation 99003/1/B7
H-3A H CLOSE F-H-1 Vent 99003/1/B7
H-4 H **OPEN/CLOSE F-H-1 Outlet Isolation 99003/1/B7
H-7 H OPEN PI-FH1-2 Isolation 99003/1/B7
HV-H-4A H OPEN PDT-FH1-1 Isolation 99003/1/B7
H-3 H **OPEN/CLOSE F-H-1 Inlet Isolation 99003/1/B7
H-3B H CLOSE F-H-1 Drain 99003/1/B7
H-6B H CLOSE F-H-2 Drain 99003/1/B6
H-5A H OPEN PI-FH1-1 99003/1/B7
H-5 H **OPEN/CLOSE F-H-2 Inlet Isolation 99003/1/B7
HV-H-5B H OPEN PDT-FH2-1 Isolation 99003/1/B6
H-6A H CLOSE F-H-2 Vent 99003/1/B6
HV-H-6C H OPEN PDT-FH2-1 Isolation 99003/1/B6
H-6 H **OPEN/CLOSE F-H-2 Outlet Isolation 99003/1/B6
Condenser Room
***1-82 1 OPEN/CLOSE F-C-5 Inlet 99003/1/F2
1-83 1 CLOSE F-C-5 Vent 99003/1/F2
1-84 1 CLOSE F-C-5 Drain 99003/1/F2
***1-85 1 OPEN/CLOSE F-C-5 Outlet 99003/1/F2
***1-86 1 OPEN/CLOSE F-C-4 Inlet 99003/1/F2
1-87 1 CLOSE F-C-4 Drain 99003/1/F2
1-88 1 CLOSE F-C-4 Vent 99003/1/F2
***1-89 1 OPEN/CLOSE F-C-4 Outlet 99003/1/F2
* Indicates Component Status Seal has been installed on the valve. Red indicates open, green indicates closed.
** If F-H-1 is to be valved in, open H-3 and H-4 and close H-5 and H-6
OR
If F-H-2 is to be valved in, open H-5 and H-6 and close H-3 and H-4.
*** If either F-C-5 or F-C-4 is to be valved in, open 1-82 and 1-85 and close 1-86 and 1-89
OR
Open 1-86 and 1-89 and close 1-82 and 1-85.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
35 of 39
Checklist 1 - Seal Water System Valve Lineup (Cont.)
Valve Location Position Description P&ID Location Operator Initial Date
Condenser Room (Cont.)
1-77 1 OPEN P-C106 Isolation 99003/1/F2
1-78 1 OPEN PI-C106-1 Isolation 99003/1/F2
1-79 1 OPEN PI-C106-1 Isolation 99003/1/F2
1-90 1 CLOSE Auxiliary Conn. 99003/1/F2
1-91 1 OPEN P-C106 Isolation 99003/1/F2
1-92 1 OPEN P-C106 Isolation 99003/1/F2
*HV-PA-
HY-CA1-
10
4 OPEN Process Air to HV-CA1-10 99001/1/F2
4-CA1-20 4 OPEN PT-CA1-20 Isolation 99003/1/C5
4-51 4 CLOSE Process Condensate Recycle
Prime Valve 99003/1/C5
4-52 4 CLOSE BFP-CA1-1 Test Ports 99003/1/D6
4-53 4 CLOSE BFP-CA1-1 Test Ports 99003/1/D6
4-54 4 CLOSE BFP-CA1-1 Test Ports 99003/1/D6
4-55 4 CLOSE BFP-CA1-1 Test Ports 99003/1/D6
*4-50B 4 OPEN BFP-CA1-1 Isolation 99003/1/C5
5-11 5 CLOSE Decon to P-C-105 & P-C-
105A 99003/1/C5
5-12 5 CLOSE Decon to P-C-105 & P-C-
105A 99003/1/C5
5-13 5 CLOSE Auxiliary Decon Connection 98996/1/C7
5-14 5 OPEN FRW to F-CA1-L/R 99003/1/C5
5-15 5 OPEN FRW to P-C-105 & P-C-105A 99003/1/B4
5-16 5 OPEN P-C-105 Isolation 99003/1/B4
5-17 5 OPEN P-C-105A Isolation 99003/1/B4
5-18 5 OPEN P-C-105 Isolation 99003/1/B4
5-18A 5 OPEN P-C-105/P-C-105A Bypass 99003/1/B4
5-18B 5 OPEN P-C-105/P-C-105A Bypass 99003/1/B4
5-19 5 OPEN P-C-105A Isolation 99003/1/B4
5-19A 5 OPEN PI-CA1-1/2 Isolation 99003/1/C4
*5-20 5 OPEN FRW to F-CA1-L/R 99003/1/D5
5-117 5 OPEN Sock Filters to PDT-CA1-3 99003/1/3C
5-118 5 OPEN Sock Filters to PDT-CA1-3 99003/1/3C
5-21 5 CLOSE F-CA1-R Drain 99003/1/C4
* Indicates Component Status Seal has been installed on the valve. Red indicates open, green indicates closed
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
36 of 39
Checklist 1 - Seal Water System Valve Lineup (Cont.)
Valve Location Position Description P&ID Location Operator Initial Date
Condenser Room (Cont.)
5-21A 5 CLOSE F-CA1-L Drain 99003/1/C5
5-21B 5 **F-CA1-L or F-
CA1-R F-CA1-L/R 3-way Inlet 99003/1/C5
5-21C 5 **F-CA1-L or F-
CA1-R F-CA1-L/R 3-way Outlet 99003/1/C5
5-22 5 CLOSE F-CA1-L/R Bypass 99003/1/C5
5-23 5 OPEN FIT-CA1-1 Isolation 99003/1/C4
5-26 5 CLOSE FIT-CA1-1 Bypass 99003/1/C4
5-27A 5 OPEN FIT-CA1-1 Isolation 99003/1/C4
5-29A 5 OPEN FIT-CA1-2 Isolation 99003/1/C4
5-29 5 OPEN FIT-CA1-2 Isolation 99003/1/C4
5-30 5 CLOSE FIT-CA1-2 Bypass 99003/1/C4
5-34 5 OPEN PI-CA1-2 Isolation 99003/1/C3
5-34A 5 OPEN PT-CA1-10 Line 99003/1/C3
5-35 5 OPEN PT-CA1-1 Isolation 99003/1/C3
5-35A 5 OPEN PT-CA1-9 Line 99003/1/C3
5-SW-1 5 CLOSE Tygon Tubing to Clean Sock
Filters 829563/2/D2
5-43 5 CLOSE FRW to PB-2 SEAL 98989/1/D4
*5-45 5 CLOSE Cooling Water to PB-1 (up
high) 98988/2/D5
5-45A 5 CLOSE Cooling Water to PB-1 98988/2/D5
5-69C 5 CLOSED C-A-1 Spray Down 99003/1/E7
5-71 5 CLOSE FRW to Lower De-
entrainment Pad Sprays 99003/1/E8
5-76 5 CLOSE FRW to Lower De-
entrainment Pad Sprays 99003/1/E8
5-97 5 CLOSE FRW to Upper De-
entrainment Pad Sprays 99003/1/E5
5-175 5 OPEN PT-CA1-10 Isolation 99003/1/D3
5-174 5 OPEN PT-CA1-9 Isolation 99003/1/D3
* Indicates Component Status Seal has been installed on the valve. Red indicates open, green indicates closed. ** Ensure 5-21B and 5-21C are on the same sock filter
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
37 of 39
Signature Sheet 1
Participating personnel enter their signature, printed name (first & last), and initials below.
Signature Printed Name (First & Last) Initials
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
38 of 39
Figure 1 - PB-1 and PB-2 Seal Water System
FIT-CA1-1 To PT-CA1-9
PI-CA1-15-35A
5-35
5-455-26
5-23 5-27A
¾ in. FRW-652-M9 to PB-1 seals
PCV-CA1-1
FIT-CA1-2 To PT-CA1-10
PI-CA1-25-34A
5-34
5-435-30
5-29A 5-29
¾ in. FRW-651-M9 to PB-2 seals
PCV-CA1-2
To TK-C1005-18A
5-18B
PCV-CA1-1/2
P-C-105A
RemovableSpool
5-19A
PI-CA1-1/2
5-175-195-185-16
P-C-105
CATCH PAN
5-21
5-21A
ToDrain
5-21B
5-21C
HV-CA1-10
5-20
5-135-11
5-22
5-14
5-15
From PC
From FRW
Ronnigen Peter Micropore Filters
Model D-1118-SS Fabric Filter
1-3 to 10 micron retention
1-½ in. FRW-650-M5
2 in. DECON-801-M9
ACME
METER
CO.
ACME
METER
CO.
ACME
METER
CO.
ACME
METER
CO.
Operate PB-1 and PB-2 Seal Water Filter System
Type
CONTINUOUS Document No.
TO-600-210 Rev/Mod
L-7 Release Date
04/05/2018 Page
39 of 39
Figure 2 - PB-1 and PB-2 Seal Water Filter Assembly