Power Protection for Business-Critical Continuity

Tailored Solutions for Power Protection

Page 2: Tailored Solutions for Power Protection - SKY Automation

Trouble is Coming Down The LineAnd You Must BePrepared

Every operation in your business depends upon the instant, around-the clock availability of computers, servers and other electronic systems. If they aren’t working, neither is your company.

Unfortunately, every piece of this equipment your company possesses is subject to the whims of the electricity that powers it.

The first step in taking control of this situation is to understand the threats to your system reliability — and exactly what you can do about them.

The Ability ToTailor a PowerSolution Is WhatSets EmersonNetwork Power Apart

We Know The Importance Of Achieving Protection For Today…And Planning For TomorrowThe decisions you make now are going to impact your ability to efficiently grow into the future. As a power partner that truly understands the importance of genuine reliability, we can implement the best way to achieve it for your operations. Based on our years of experience, we know and understand your current needs for protection — and what it will take to increase your power capabilities as these demands grow. We can help you protect data, hardware and system availability in any combination.

No Matter How Deep Your Protection Needs To Be, We Have The Expertise To Make It HappenWe recognize that not everyone requires the same level of power protection. Liebert has the knowledge of critical facilities and equipment that is necessary to determine the exact needs of each application. An extensive range of power protection choices then enables us to match our equipment precisely to these parameters rather than force-fitting a few products to every situation. The result is our unique ability to deliver power solutions that are always on target for the depth of protection specified.

Page 3: Tailored Solutions for Power Protection - SKY Automation

No Organization In The Power Protection Business Has More Real-World Experience Than Emerson Network Power

Many years of experience allow us to properly respond to any power problem scenario. Our resources include knowledgeable leadership, as well as an outstanding staff of research, design, application and service engineers using the latest technological tools.

But the biggest difference in the way we approach your power requirements is the local Liebert Representative, Distributor or Reseller. We are the only company in this business that maintains such a strong local presence on a national and international basis. Specifying and maintaining a high availability power system requires someone who is knowledgeable in all phases of critical systems protection. This resource, coupled with our broad product line, gives Liebert the ability to create a “tailored solution” that will meet your protection needs precisely and efficiently. We don’t have to take the one or two items we happen to have and stretch them to come up with the answer. We give you the best answer every time.

Only Liebert can bring together all of the power protection solutions you need to create system availability that is as close to 100% reliability as possible.

There Is A Liebert Power Solution To Meet Every NeedNo one offers a more comprehensive selection of power products for critical applications than Liebert.

Liebert PS (400 VA/600 VA) 4-5A Reliable Power Protection For Your PC

Liebert Series 7400 M (10/30/40/60 kVA) 20-21Maximum Protection ForMission Critical Network Applications

Liebert iTrust 3-Phase UPS System 22-23True On-Line Sinewave UPS System ForThe Networked Economy

Liebert NX Series 24-25

The Next Generation UPS System

Liebert Hipulse UPS (30-150 kVA 1-Phase) 26-27

Digital UPS For The Digital World & Industrial Automation

Liebert Hipulse UPS (80-800 kVA 3-Phase) 28-29

Digital UPS For The High-End Digital World

ASCO Switch 34-35

Designed To Minimize Downtime OnCritical Systems

Liebert Powersure Panel 32-33

Transient Voltage Surge Supressor

Liebert ITON 600 VA /1000 VA 6-7

A Reliable Power Protection And Backup Solution For Your PC

TMLiebert UPStation GXT 2U 1 /2 /3 8-9

True Online Double Conversion UPS to Keep Your Business Up and Running

True On-line DSP Based UPS With Unity Power Factor

Liebert Super 400D (10/20 kVA) 18-19

Liebert Precision Power Center 30-31

Affordable Packaged Power ManagementFor Higher Power Quality

TMLiebert UPStation GXT 2 (4.5 kVA / 6 kVA) Series 10-11

The New Shape Of Network Power Protection

TMLiebert UPStation GXT-MT 1-2-3 kVA UPS 12-13

True Online Double Conversion UPS with Extended Runtime Capability

TMLiebert UPStation GXT-MT 6 /10 kVA UPS 14-15

Fit-And-Forget UPS System Power Protection And Power Source

TMLiebert UPStation GXT RT 1-3 kVA UPS 16-17

True Online Double Conversion UPS with Extended Runtime Capabilities with Rack & Tower Compatibility

Page 4: Tailored Solutions for Power Protection - SKY Automation

2

You Face ManyChallenges in the Pursuit of Uptime

Is There Really A Problem?“My computer can ride right through a short blip in the power — why do I need anything else?”

There Are No Simple Solutions“I have people telling me all I need to do is plug each workstation into a small UPS from the computer store . That’s good enough, isn’t it?”

Different Needs Require Different Power Protection

Configurations“Should I have a small UPS for each workstation or have everything on one large system . Which is best for my facility?”

A Lot Can Happen Between Your UPS And The Equipment

It Is Protecting“We have dozens of pieces of networking equipment. How can I make sure that each one is getting exactly the power it needs?”

Every Wire Carries The Potential For Trouble“An electrical surge came in through an outside phone line and knocked out our entire communications system. Is this going to happen again?”

A Single Source Of Power Simply May Not Be Enough“Adding a second power feed would certainly enhance our availability picture — but who can we talk to about getting it done right?”

Page 5: Tailored Solutions for Power Protection - SKY Automation

3

But There AreReal Solutions

You Need Protection From All Power ProblemsAn outage is just the problem you can see. There are many other more frequent power fluctuations — surges, spikes, sags — that you don’t see. Theseare the conditions that cause the “unexplained” lock-ups.

“Out-Of-The-Box” Can Put You Out Of BusinessBuying a simple off-line UPS down at the computer store may be a good solution for your home PC, but it just doesn’t make sense when your business and productivity are on the line. Protecting critical network and computing systems requires the expertise of someone who understands all the risks you face from poor power quality problems with critical equipment.

Centralized Vs. Distributed UPS ProtectionLiebert has the breadth of products that allows you to implement either a centralized or a one-on-one distributed power protection strategy depending on your requirements. Whatever configuration you choose, you can count on Liebert to make it the best it can be. Benefits, suchas increased system security, more efficient maintenanceand improved reliability, make a centralized strategy a better choice for larger operations.

Proper Power Depends On Proper DistributionIn network applications, there may be hundreds of different loads with various voltage requirements, a mix of AC and DC power, plus any number of other electrical Specifications This calls for adistribution system that is designed to maintain the highest levels of reliability and quality between the source of conditioned power and the protected equipment.

Power Conditioning And Surge Protection Throughout The FacilityRaw utility power is often far too “dirty” for sensitive systems, resulting in lost,or garbled data, unexpected software glitches or shutdowns, even hardware damage. The IEEE recommended practice is to install transient voltage surge suppression (TVSS) protection on every electrical conductor that penetrates a facility shell, including power lines, telephone and other communications links.

Maximum Reliability Demands Dual Power SourcesIf your needs require the highest level of system availability, Liebert has the knowledge and products to implement a dual-power strategy throughout your enterprise. UPS, transfer switching, power distribution and other equipment are all brought together to create the ultimate in reliability.

Page 6: Tailored Solutions for Power Protection - SKY Automation

4

Liebert PSA Reliable Power Protection For Your PC

Applications• TFT Monitors

• Personal Computers

• Printers

• Modems

• Routers

• Wireless Devices

• Non-critical passive devices

• Standalone Computers

Features• High Frequency Charger Design

• Input Fuse Protected

• Black Start Mode Available

• Separate Low Charge &

• Battery Indicator in AC mode

• Overload, Discharge

• and Overcharge Protection

• Output Cable Provided

Liebert PS (400 VA/600 VA)

A high-performance UPS designed especially to protect low voltage applications and is available in tower design

The Liebert PS' features and flexibility makes it the optimal solution for your small electronic devices both at home and office.

Page 7: Tailored Solutions for Power Protection - SKY Automation

5

Technical Data

Liebert PSA 400 Liebert PSA 600

VA/W

Voltage

Voltage Range

Voltage

Voltage Regulation(Batt.

Mode)

Frequency

Frequency Regulation

(Batt. Mode)

Output Waveform

Battery Type & Number

Back up Time (at a PC

load with 15" monitor) 5 minutes 8 minutes

Recharge Time

Typical

Green LED flashing every second

Red LED flashing every 2 seconds for 30

seconds

AC Mode

Battery Mode

Low Battery at Battery

Mode

Fault

Battery Weak at AC Mode

Battery Fault at AC

Mode Red LED flashing three times every 2 seconds

Sounding every second

Sounding every 2 seconds for 30 seconds

Battery Mode

Low Battery at Battery

Mode

Fault

Battery Weak at AC Mode

Battery Fault at AC

Mode Sounding three times every 2 seconds

Full Protection

Dimension, DXWXH (mm)

176.5x80x230

Net Weight (kgs)

Operating Environment

Noise Level

MODEL

CAPACITY

INPUT

OUTPUT

BATTERY

TRANSFER TIME

INDICATOR

AUDIBLE ALARM

PROTECTION

PHYSICAL

ENVIRONMENT

Continuously s ounding

400VA/200W 600VA/300W

220/230/240VAC

170-270VAC

220/230/240VAC

50Hz

Modified Sinewave

2-6ms

+/-1 Hz

±10%

12V/7AH x 1pc 12V/4.5Ah x 1pc

10 hours to 90% after complete discharge

Green LED lighting

Green LED flashing every 4 seconds

Red LED lighting

Sounding every 4 seconds

3.1 3.3

0- 40°C, 0-90 % relative humidity (noncondensing)

Less than 40dB

Discharge, overcharge, and overload protection

Page 8: Tailored Solutions for Power Protection - SKY Automation

6

Liebert ITONA Reliable Power Protection And Backup Solution For Your PC

Applications

Liebert ITON 600/1000

Features

A • uto

n est• sta R art

p eSlee Mod

I

r pr t o f r F / ePowe otec i n o ax Mod m

art n i g SSm Mo itor n oftware

art i r o s o o lSm M c opr ce s r c ntro

m rt echn loS a AVR T o gy

o i a o PoC mmun c ti n rt

v lo o ec n O er ad Pr t tio and alarm

• Home PC

• Printers

• Clustered network equipment: hubs, routers, bridges

• Remote telecommunications units

• Desktop Speakers

• Office Telecommunications systems

• Voicemail and e-mail servers

• Test and diagnostic equipment

A best-in-class UPS with proven reliability. ITON is an uptime solution for your personal computers & peripherals and is available in a compact tower design

A line interactive UPS that provides perfect power protection for Small Office & Home Office (SOHO) PC Systems

• Chargers

• Telecom Ports

Page 9: Tailored Solutions for Power Protection - SKY Automation

7

Technical Data

MODEL ITON 600 ITON 1000 CAPACITY VA/W 600 VA/360W 1000VA/600W

Voltage Range 140-300 VAC 160-270V

INPUT

Frequency 45-65 Hz (Auto sensing)

Voltage 230V

(Batt. Mode) Voltage Regulation

+/- 10% +/- 5%

Frequency 50Hz 50Hz or 60Hz

(Batt. Mode) Frequency Regulation

+/- 1Hz

Output Waveform Stepped Waveform

OUTPUT

Overload 110% for 5 minutes as “Mains” mode

Battery Type & Number 12V/7AH — 1 PC 12V/7AH — 2 Pcs Backup Time* (As per the loads)

15-22* mins 30 min typical* (with 1 PC)

BATTERY

Recharge Time 8 hours to 90% after complete discharge

TRANSFER TIME

Typical 4-8 ms 4-6 ms

INDICATOR (LED Bar Graph)

AC Mode Green Lighting

The 1st green lighting; The Green 2nd to 5th green gradually

Lighting lighting indicating load capacity

Backup Mode Green flashing Green

flashing

The 1st green flashing; The 2nd to 5th green gradually lighting indicating batteries capacity

Fault The red lighting

Backup Mode Sounding every 10 seconds Low Battery Sounding every second Overload Sounding every 0.5 seconds Battery Replacement Soundingevery 2 seconds

AUDIBLE ALARM

Fault Continuously Sounding

PROTECTION Full Protection Discharge, overcharge, and overload protection

PHYSICAL

ENVIRONMENT

Dimension (mm), DxWxH 330x100x140 369x141x181 Net Weight 6 kg 13.5 kg

Operating Environment 0-40 C, 0-90% relative humidity

(non-condensing) Noise Level Less than 40 dB

INTERFACE

RS-232 Support Windows 98/NT/ME/2000/2003/ XP, Linux, HP-UX, IBM AIX,

Sun Solaris, Unixware, Free BSD, Mac OS and Compaq True

Page 10: Tailored Solutions for Power Protection - SKY Automation

8

Liebert GXT 2UTrue Online Double Conversion UPSTo Keep Your Business Up And Running

Features• True on-line design

• Configurable as rack or tower

• Wide input voltage window allows• UPS support without going to battery,• extending systems availability

• Built-in Surge Suppression

• User replaceable batteries without• removing GXT 2U from rack

• Compatible with new SNMP / Web Card

• Compatible with Multiport 4 or 8

• Compatible with RelayCard INT

• Compatible with MultiLink

A high-performance UPS with proven reliability, custom configurability, hot-swap internal batteries and extendible runtime in a compact tower design.

The GXT2 features and flexibility make it the optimalsolution for small server room,networking and telecomapplications that requirereliable, continuous andquality power.

• LAN and WAN servers

• Clustered network equipment: hubs, routers, bridges

• Remote telecommunications units

• Office Telecommunications systems

• Voicemail and e-mail servers

• Test and diagnostic equipment

• Engineering network servers

• Factory floor protection of micro processor controlled equipment

• Mission critical devices

Applications

TMUPStation GXT 2U in Rack and Tower Mode

Page 11: Tailored Solutions for Power Protection - SKY Automation

9

Technical Data

Description 1 kVA 2 kVA 3 kVAUPStation GXT 2U UPStation GXT 2U UPStation GXT 2U1000 2000 3000

Input Parameters

Nominal Voltage 230 VAC

Voltage Range 119 - 280VAC ( Load Dependent )

Frequency Range 40 Hz - 70 Hz

Power Factor > 0.97

Output Parameters

Capacity 1 kVA / 0.7 kW 2kVA / 1.4 kW 3kVA / 2.1 kW

Voltage User Configurable 200 / 208 / 220 / 230 / 240 VAC

Voltage Regulation + / - 3% Steady state

+ / - 5% if synchronized to mains,

Frequency Regulation + / - 0.1 Hz free running or on battery operation ( when not synchronized to mains )

THD <=3% (100% Linear Load), <=5% (100% Non-Linear Load)

Overload Capability Upto 130% - 10 Secs

( with transfer to bypass ) 200% - 8 cycles

Efficiency > =88% (AC AC) minimum

Crest Factor 3:1 max

Battery Parameters

Type 21 V/7 AH Sealed, Lead/Acid. 12V / 9 AH Sealed,Lead/Acid

Maintenance Free Maintenance Free

Recharge Time Max.5 hours to 95% capacity (after full discharge into 100% Load)

Battery Back-up Time 13 mins 8 mins 8 mins

Environmental Conditions

O OStorage Temperature -15 C to +15 C

Humidity 0 to 95% Non Condensing

Noise Level <50 dBA

Electronic Discharge Compliant to ENC61000-4-2, LEVEL 4 (15 kV through air, 8 kV contract)

Dimensions ( Unit )

W x D x H 87 X 547 X 430 87 X 547 X 430 87 X 618 X 430

Weight 22.6 kg 24.7 kg 31.9 kg

Agency

Safety EN50091-1-1, CE compliance mark, for both Low Voltage and EMC Directives

RFI / EMI C-Tick, AS 62040-2, EN 50091-2, Class B

Surge Immunity EN 61000 4-2, 4-3, 4-4, 4-5

Transportation ISTA Procedure 1A

Typical Autonomy is calculated at approximately 80% load

Page 12: Tailored Solutions for Power Protection - SKY Automation

10

A high-performance UPS with proven reliability, custom configurability,hot-swap internal batteries and extendible runtime in a compact rack and tower design.

The GXT2 features and flexibility make it the optimalsolution for your small & medium server, data room, networking and telecom applications that require reliable, continuous and

Liebert GXT 2 (4.5 kVA / 6 kVA)The New Shape Of Network And Power Protection

Applications• LAN and WAN servers• Clustered network equipment: hubs, routers, bridges• Remote telecommunications units• Office Telecommunications systems• Voicemail and e-mail servers• Test and diagnostic equipment• Engineering network servers• Factory floor protection of micro processor controlled equipment• Mission critical devices

Features• True on-line design• Built-in PFC circuit• Wide input voltage window allows• UPS support without going to battery,• extending systems availability• Builtin Surge Suppression• Compatible with new SNMP / Web Card• Compatible with Multiport 4 or 8• Compatible with RelayCard INT• Compatible with MultiLink• External plug and play Battery cabinets available• Configurable as rack or tower Other product features of the Liebert GXT2 include• Self-diagnostics• Built-in serial communications for use with Liebert • TMMultiLink Automated Shutdown Software• TMIntellislot communications port• Built-in closure signals• Includes Windows-based configuration program

TMUPStation GXT 2 (4.5 kVA / 6 kVA)in Rack and Tower Mode

quality power.

Page 13: Tailored Solutions for Power Protection - SKY Automation

11

Technical Data

Output Ratings

Output Power 4.5 KVA/3.15Kw, 6 KVA/4.2KwNominal Output Voltage 230 VACOutput Voltage Regulation +/-2%Output Voltage Distortion-With 100% Linear Load < 3%Nominal Output Frequency 50 HzOutput Frequency Tolerance 46.5 Hz to 53.5Hz( Phase locked with Mains ) +/-3.5 Hz Synchronized to mainsOverload at 0.7 pf( Load is transferred to Bypass 125% for 10 SecAfter pre-determined timeLoad Power Factor Range 0.7 lagging to unity

Input Ratings

Nominal Input Voltage 220/230/240 VACPermissible Input VoltageVariation at Full Load 176-276 VACNominal Input Frequency 50 HzPermissible Input FrequencyVariation 40 to 70 HzPower Factor at Full load > 0.97

Battery Details (External)

Nominal DC Bus Voltage 240 VDCNumber of Blocks of SMFBatteries 20 blocks of 12 V eachTypes of Batteries Supported Sealed Maintenance Free (SMF)Recharge Time up to 100% Capacity 10 hours to 12 hours

Physical Parameters

Width X Depth X Height (mm) 221x547x430Weight 67 kg

Environmental Parameters

oOperating Temperature at Rated Load 0 to 40 CoStorage Temperature - 15 to + 50 C

Relative Humidity 0 to 95% RHNoise < 55 dB

Agency

Safety EN62040-1-1, TUV/GSRFI / EMI AS 62040-2, EN 50091-2, Class A CE EMC DirectiveSurge Immunity EN 61000 4-5 Level 3 criteria ATransportation ISTA Procedure 1B

Page 14: Tailored Solutions for Power Protection - SKY Automation

12

Liebert GXT-MT 1-3kVA UPSTrue Online Double Conversion UPS With Extended Runtime Capabilities

Applications• Small Size Data Center

• Telecommunication, VoIP

• Small Office Network

• Data Warehouses

• Medical Diagnostics

• Process Automation Equipments

Features• Extended Runtime Capabilities• Flexible (Site Specific) Battery Configuration• Compact Tower design.• Generator Compatible• Class B Electromagnetic interference (EMC)• compatible• Ultra wide input voltage range• High capacity Battery Charger for GXTL • High input power factor & low THDi

Liebert GXT-MT 1-3kVA UPS

Liebert GXT-MT features a comprehensive specification, satisfies safety criteria and electromagnetic compatibility standards, besides offering intelligent monitoring and network management functions. It isavailable in adaptable battery architecture & compact tower configuration.

• Small Research and Functional Laboratories

Note: Liebert GXT-MT standard model is provided with an internal battery. It is also available in long Back-up mode

Page 15: Tailored Solutions for Power Protection - SKY Automation

13

Technical Data

Input system

Rated voltage

Voltage range

Frequency

Power factor

Output system

Power factor

Voltage

Line regulation

Dynamic variation

Frequency

Frequency range

Crest factor

Bypass Operating Voltage

Transfer time

Model

Electrical

Rating

Charging current 1A 4A 1A 8A 1A 8A

1000VA/700W

Input

Output

Voltage harmonic distortion (rated input voltage, rated input frequency)

Inverter overload capability (in Normal mode, 25°C)

Inverter overload capability (in Battery mode, 25°C)

External battery voltage 36Vdc

Input THDi

3000VA/2100W

DC Component

96Vdc

Battery

Qty x Volts x Capacity 3x12Vx7.2Ah 8x12Vx7.2Ah 8x12Vx7.2AhManufacturer / Model CSB/GP 1272F2 or CSB/GP 1272F2 CSB/HRL 1234W Panasonic or Panasonic F2 or Panasonic Equivalent Equivalent EquivalentTypical Autonomy Time 12 Minutes 15 Minutes 9 MinutesAutonomy at Half Load 20 Minutes 26 Minutes 16 MinutesCharging Duration 80% of battery capacity in 4 hrs (standard type)Noise (within 1m) GXT1000L-MT, GXT2000L-MT, GXT3000L-MT: <45dbProtection IP20 (static state)

Environmental

Item Normal Range0 0Ambient Temperature 0 C-40 C

Relative Humidity Less than 90% CondensingAltitude Lower than 1000m; no derating; 1000~1500m; 1% derating for every 100m rise

0 0Storage temperature -0 C-40 C (excluding battery)

Frequency range

50 / 60 Hz ±0.02Hz

46-54 Hz

>150% 300ms

3:1

< _6%(0 ~100% non-linear load)

<5% in 20 ms

50 / 60 Hz

0.97 (conditions: rated voltage, full pure resistive load, fully charged battery)

1-phase, plus PE

0.7

1-phase, plus PE

>150% 300ms

220Vac / 230 Vac / 240 Vac ±2%

<_2%(0~100% linear load)

< _3%(0 ~100% linear load)

108%~150% 30s

220Vac / 230Vac / 240Vac

1. 160~300 Vac full load 2. 110 Vac half load

Normal<->Battery: 0ms

< 10%

300% for 5s

<_200mV

108%~150% 30s

200% for <_60 mins

46-54 Hz / 56-64 Hz

GXT 1000-MT GXT 1000-MT GXT 2000-MT GXT 2000L-MT GXT 3000-MT GXT 3000L-MT2000VA/1400W

Page 16: Tailored Solutions for Power Protection - SKY Automation

14

Liebert GXT-MT 6/10 kVA UPSFIT - AND - Forget UPS SystemPower Protection AndPower Source

Liebert GXT-MT 6/10 kVA UPS

Features•

Parallel up to 3modules

Extended Runtime Capabilities

Compact Tower design

Generator Compatible

Class B Electromagnetic interference (EMC)

compatible (EN50091-2)

Ultra wide input voltage range

High capacity Battery Charger for GXTL

High input power factor & low THDi

Applications

• Educational Institutes

• Small Retail Out lets

Small & Medium Size Data Center

Telecommunication, VoIP

Office Network

Data Warehouses

Process Automation EquipmentsLiebert GXT-MT features a comprehensive specification, satisfies safety criteria and electromagnetic compatibility standards, besides offering intelligent monitoring and network management functions.

This high performance UPS withproven reliability is available in compact tower design

Page 17: Tailored Solutions for Power Protection - SKY Automation

15

Technical Data

Input system

Rated voltage

Voltage range

Frequency

Power factor

Output system

Power factor

Voltage

Line regulation

Dynamic variation

Frequency

Frequency range

Crest factor

Bypass Auto retransfer

Transfer time

4.2A

Capacity 20 nos. of 12V

Charging duration

Model

Electrical

IP20(static state) Protection

Rating

Charging current

50 / 60 Hz ±0.05Hz

46-54 Hz

<55db

>105% 10sec,

3:1

Noise (within 1m)

< 6%(0 ~100% non-linear load)

±5% in 60 ms

50 Hz

> 0.98 (conditions: rated voltage, full pure resistive load, fully charged battery)

1-phase, plus PE

0.7

Battery

6000VA/4200W

1-phase, plus PE

Depends on battery capacity

>130% 1sec, transfer to bypass turnoff output

220Vac / 230 Vac / 240 Vac ±1%

<1%(0~100% linear load)

Input

Output < 2%(0 ~100% linear load)

105%~130% 10min, transfer to bypass

220Vac

180-270 V

Voltage harmonic distortion (rated input voltage, rated input frequency)

Inverter overload capability (in Normal mode, 25°C)

Inverter overload capability (in Battery mode, 25°C)

Normal<->Battery: 0ms

External battery voltage 240Vdc

GXT 6000L-MT

Input THDi < 10%

GXT 10000L-MT

10000VA/7000W

o0 - 40 COperating Temperature

< 1000 mInstallation Height

< 95%Relative Humidity

260 mm x 570 mm x 717 mmDimension (W x D x H)

Weight

Yes

6kVA / 90 kg 10kVA / 93 kg

Communication Port RS 232 as standard

Page 18: Tailored Solutions for Power Protection - SKY Automation

16

Liebert GXT- RT 1-3kVA UPS

Applications

• Extended Runtime Capabilities

• Flexible (Site Specific) Battery Configuration

• Rack / tower Adaptability

• DSP controlled Online double conversion

• Generator Compatible

• “Mute” design

• Class B Electromagnetic interference (EMC)

• compatible

• Ultra wide input voltage range

• High capacity Battery Charger

• High input power factor & low THDi

Features

Liebert UPStation GXT-RT 1-3kVA UPS

True Online Double Conversion UPS With Extended Runtime Capabilities With Both Rack & Tower Compatibility

• Small Size Data Center

• Telecommunication, VoIP

• Small Office Network

• Data Warehouses

• Medical Diagnostics

• Process Automation Equipments

• Small & Medium Functional & Research

• Laboratories

Liebert GXT-RT features a comprehensive specification, satisfies safety criteria and electromagnetic compatibility standards, besides offering intelligent monitoring and network management functions.

It is available in adaptable battery architecture and both rack and tower-mountable configuration to suit your specifications.

Page 19: Tailored Solutions for Power Protection - SKY Automation

17

Technical Data

Model GXT1000L-RT GXT2000L-RT GXT3000L-RT

Rated Out put 1kVA 2kVA 3kVA

Rectifier type

Input volta ge

Input volta ge range

Input frequenc y range

Input power factor

Battery type

Battery strin g rated voltage 36Vdc 72Vdc 72Vdc

Inverter type

Output active power 0.7k W 1.4kW 2.1k W

Output socket type I E C I E C IEC/Terminals

Output voltage

Output frequency

Output VTHD (Volta ge Total Harmonic

Load maximum crest factor

Step load capability

Efficiency >88% >89% >90%

Switching time (mains failure )

Noise <43dB

Panel dis play

Dimension (width x de pth x hei ght) in mm

Height in U 2U 2U 2U

Wei ght (long backu p time) 7.8kg 9.6kg 10kg

Safet y

EMC

Immunit y

Surge protection

Protection level

Interface type

Web /SNMP card

Operating temperature

Relative humidity

Altitude

Environment

0 to 40 Celsius degrees (UPS) and 25 Celsius degrees±5 (Batter y)

0 to 95% no-condensing

1500m (as per IEC 62040-3 )

IP21

Communication and mana gement

Serial port/dry contact / SNMP card

Optional parts

EN62040-1-1, CE Marked

EN50091-2, class B

EN50082-1

IEC60664-1, Level IV

System parameters and standard

0ms

LED

440 X 400 X 87

<45dB

<2% for linear load, <5% for non-linear load

3:1 (Comply with IEC62040-3 )

100%

Overload capability <105% continuous Operation

105% to 125% rated load for 5min

125% to 150% rated load for 1min

>150% rated load for 10s

Output Parameters

Uses most u p-to-date IGBT

220Vac, sin gle phase three-wir e

50Hz±2%

50Hz±2%, 5%, 7% and 10%, user settable

At least 0.99

Battery

Valve-re gulated lead-acid maintenance free batter y

Input Parameters

Uses most u p-To-date IGBT and PFC (power factor y correction )

220Vac, sin gle phase three-wir e

120 to 288Vac

Value-added Optional Parts

WEB/SNMP card ModBUS cardEquipment Room Signal Adapter UPSite Plus monitoring system

Page 20: Tailored Solutions for Power Protection - SKY Automation

18

Super 400D (10/20 kVA)True On-line DSP Based UPS With Unity Power Factor

Applications• Facility-wide networks

• Medical equipment

• Industrial processes

• Large computer rooms

Features & Benefits

Temperature compensated Battery

charging to enhance the Battery life

Battery test facility

Reverse Phase sequence operation

Auto retransfer facility

DSP and Dual microprocessor based system

The Liebert Super 400D is a true

On-line sine wave UPS system that

provides the user with clean

computer grade power for

continuous operation of his critical

load, regardless of any disturbance

on the upstream AC power. The

system offers many innovative

features to give the user maximum

reliability and flexibility at the lowest

operating cost. With Liebert Super

400D UPS system, you have

complete peace of mind.

10,20

Unity Input Power Factor

Low Input Current Harmonic Distortion of less than 5%

Super 400D (10/20 kVA)

Page 21: Tailored Solutions for Power Protection - SKY Automation

19

Technical Data

Input Parameters

Input VoltageInput Voltage Variation Input Frequency Input Frequency Variation Power walk in Power Factor at rated load Operation with Reverse Phase Sequence

Bypass Supply Voltage

Nominal DC bus voltagePermissible DC voltage variationDC bus OV tripEnd of discharge DC busTypes of batteries supportedNominal battery float voltageMax. batt.charging currentDC rippleD.C. Voltage Regulation

Output VoltageFrequencyPower rating at 0.8 p.f.Power rating at 1.0 p.f.Overload Rating

Max. Non-linear load permissibleOutput Voltage regulationTransient response for 100% load changeRecovery timeFreq. stability unsynchronized -synchronized -Max. rate of change of FrequencyOutput Voltage Distortion

Transfer time synchronized -unsynchronized -

Voltage limits for Inv. operationSMF battery Float Charge VoltageMax. Charging current

Height x Depth x WidthWeightVentilationCable entryColour / Panel finishBase castor wheels

Operating TemperatureStorage TemperatureRelative HumidityAltitudeTemperature DeratingAltitude Derating

415V, 3-Phase, 4 wire- 30%, +25 % 50 Hz +/- 10% Progressive over 10 seconds 1.0 (Unity) Possible

220/ 230/ 240V AC

356V 260V - 410V 410V 260V SMF 356V 7.0A< 2% rms ± 1%

220/ 230/ 240 VAC 1 Phase 50 Hz 10 kVA, 20 kVA 8 kW, 16 kW 110 % for 60 minutes 125 % for 10 minutes 150 % for 1 minute100 % with Crest Factor of 3:1 +/- 1% +/- 10% 10 millisecond +/- 0.1 % ± 1Hz, ± 2 Hz, ± 3 Hz 0.2 \0.4 hz/sec < 3 % at Non linear load < 2 % at linear load0 millisecond 20 millisecond

260V DC to 410V DC 26 Blocks of 12 V each 356 VDC 7.0 A

1150mm x 650mm x 450mm 275kg Forced - Air cooled Front end - Bottom Structured dark Grey Yes

o o0 C to 45 C, continuous

o o0 C to 70 C 95% RH 1000 Meters

o o1.5% per C between 40 & 50 C 1 % per 100m between 1000m - 2000m

Bypass Parameters

DC Parameters

Output Parameters

Parameters

Mechanical Parameters

Environmental Parameters

Page 22: Tailored Solutions for Power Protection - SKY Automation

20

Applications

Features

Series 7400 M (10/30/40/60 kVA)Maximum Protection For Mission Critical Network Applications

The Liebert Series 7400 M

addresses all the power

quality needs of today’s

networked economy by

providing a perfect sinewave

output voltage with stable

frequency, over and above

offering many other

important customer values.

Series 7400 M (10/30/40/60 kVA)in Rack and Tower Mode

•Information Technology

Servers (LAN, WAN, e-mail, ERP, Web, Digital Archives, IntraNet)

Networking (Routers, Hubs, Switches, Multiplexer, Bundler,

Unbundler, Modems)

Banks, Insurance and Financial Services

Telecommunications, Billing Computers

Medical Diagnostics, MRI, CT Scan, Cath Lab

Process Automation, Small processes, Light Robotics

••••

•On-line double conversion UPS: makes your load independent

from both main's voltage and frequency.

Ensures Server-grade high quality of power

IGBT technology PWM inverter switching technology:

provides your load with perfect sinewave voltage

High efficiency performances: lower cost of ownership

Excellent performance with either 100% unbalanced and

100% non-linear loads with crest factor upto 3:1 without

derating: no need to care about the distribution of your

single phase loads between output phases nor to oversize

the UPS

Super-servers, mini-computers and multi-processing systems

Advanced battery management systems with programmable

battery testing: constantly monitors the the health of the

battery pack keeping the battery ready to work for emergency

situations

Small footprint and convenient maintenance access: ease

of positioning and saving of floor-space

Inverter with high overload capability: no need to oversize

UPS; reduced initial investment

Inverter output protected against short-circuit: high

protection to the inverter hence more availability of the

systems; Investment protection

Zero footprint for optional tuned filter for the input: lower

cost of ownership because of space saving and reduced

electricity bill

••

••

Page 23: Tailored Solutions for Power Protection - SKY Automation

21

Technical Data

Model 10 30 40 60

Power 10kVA 30kVA 40kVA 60kVA

Output Power 8kW 24kW 32kW 48kW

Power factor 0.8

Input

Voltage 380/400/415 V

Frequency 50 or 60 Hz

Power Factor > 0.9 (Additional Filter)

THDi < 10%-15% with Battery charging

Voltage Window + 10%-20% without battery charging

Output

Voltage 380/400/415V

Frequency 50 or 60 Hz

Voltage stability

- static +_ 1%

- dynamic +_ 5%

Voltage distortion

- linear load 1% typical

- non-linear load 5% max (with 3:1 crest factor)

Overload capability three-phase: 110% for 60 mins,

125% for 10 Mins, 50% for 1 min

Single-phase: 200% for 30 secs

Maximum permissible non-linear load 100% (with 3:1 crest factor)

Physical

Weight 480kg 540kg 620kg

Width 710mm 710mm 710mm

Height 1420mm 1420mm 1420mm

Depth 800mm 800mm 800mm

20 kVA model also available on request.o oOperating Temperature is 40 C. However ratings can be selected for ambient temperature upto 50 C

Page 24: Tailored Solutions for Power Protection - SKY Automation

22

True On-Line Sinewave UPS System ForThe Networked Economy

Applications• Telecommunications Facilities• Data processing• Medical imaging equipment• Industrial process equipment

• Functional & Research Laboratories

The Liebert iTrust 3-phase is a true on-line 3 phase UPS system (sine wave output) that provides the user with clean computer grade power for continuous operation of his critical load, regardless of any disturbance on the upstream AC power. The system offers many innovative features to give the user maximum reliability and flexibility at thelowest operating cost. With Liebert iTrust 3-phase UPS system, you have complete peace of mind.

Liebert iTrust 3-Phase UPS System

• Parallel for Redundancy or Capacity for up to 4 units• Full Digital Signal Processing using the latest DSP technology• Wide Input Voltage Range• Low Current Harmonic Distortion of less than 3%• High Input Power Factor• High Overload and Short-Circuit Capacities• Intelligent Battery Management• Large LCD Display and Mimic Panel for Real-time information

Features

• Large Format Departmental Stores & Multiplexes

• MTBf over 5,00,000 hrs ensuring reliable power supply• Power supply efficiency over 97% through Bypass during good• mains supply thus minimizing operating cost

iTrust 3-Phase UPS

Page 25: Tailored Solutions for Power Protection - SKY Automation

23

Technical Data

Capacity 30kVA 40kVA 60kVARectifier InputInput Voltage 380/400/415v [line-to-line voltage]AC power input three-phase three-wirePower factor >0.99Harmonic current <3%Highest operating voltage +15%Lowest operating voltage -45%Input current limit When input current is smaller than 115%in, UPS can operate continuously; when input

Current is 115-140%in, the UPC can operate For 5 minutes; and when input current is 140-165%in, the UPC can Operate for 1 minute; current limiting function is activateWhen input Current is over 165%in [in the Rated output current at full load]

Frequency range 50hz+ -10%Bypass inputInput voltage 380/400/415v[line-to-line voltage]Input voltage range +-10%AC power input three-phase three-wireFrequency range 50hz +-10%OutputVoltage regulation 380/400/415v+1%[Balanced load] [+_5% adjustable]Voltage transient response +-5%[0 100% linear load]Voltage distortion [linear load] THD<1%[line-to-neutral voltage] [battery float charge state, rated Balance load]Voltage distortion [nonlinear THD<4%[line-to-neutral voltage] [battery float charge state, Load} rated balance load]Power factor 0.8 [lagged]Frequency syn. Range 50hz +-2hzFrequency regulation +-0.1%[Battery mode]Phase displacement 120 +-1 [balanced load or unbalance load][Three-phase]Overload capability [inverter] 105%<load<125%, transfer to bypass mode after 10+-0.1 min;

125%<load<150%, transfer to bypass mode after 1 minute;When load>150%, transfer to bypass mode after 200 ms

Overload capability [bypass] 135% rated current continuously135% 170% for 1 minute> 170, shutdown in 2s1000% rated current for 20 ms [a standard for selecting static switch]

Ratio of output current peak 3:1Value to RMS valueTransfer time [normal mode] 0[uninterrupted transfer], 15ms [interrupted transfer]SystemDisplay LCD + LEDEMC/EMI conduction EN 50091-2Radiation EN500919-2 CLASS-AHarmonic IEC 1000-3-4Immunity EN 61000-4-2,3,4,6,8,9,11 level III,

EN 61000-4-5 IVMTBF [single UPS] 150,000 hoursMTBF [1+1parallel operation System] 400,000 hoursAudible noise at 2m <60db <65dbCross current without <1ALoad [1+1]Cross current without <2ALoad [3+1]Current unbalance rate [1+1] <2%Current unbalance rate [3+1] <3%Insulation resistance >2m [500vdc]Dielectric strength [input to earth, output to earth] 2820vdc, leakage current lower than 3.5ma 1min without arcSurge immunity Satisfy the class IV requirements specified by IEC60664-1,

The ability to withstand 1.2/50us not lower than 6kv/3kaProtection Ip21

Installation Cable access mode top/bottom cable access modes optionalPhysical dimension [WxHxD] mm 600x1400x860 800x1800x860 800x800x860Weight [kg] 528 654 811

Page 26: Tailored Solutions for Power Protection - SKY Automation

24

Liebert NXNext GenerationUninterruptible PowerSystems

Applications•Server Rooms and Mid-sized Data Centers

•Telecommunication (Fixed, WiLL & Mobile) Billing & Reporting

Systems

•Networks (LAN, MAN & WAN), InfoCom and WiFi Hot Spots

•Industrial Process & Motion Automation for Mid-sized plants

•Medical Diagnostic / Imaging Equipment

Features•Stratified cooling techniques•Versatile and simultaneous communication facilities•Compact active and passive footprints•Capability to handle 0.9 leading power factor loads•Capability to handle 100% unbalanced loading•Backfeed protection•User f lexibility in selecting effective conÞ guration for the application•Large and user-friendly LCD display in twelve different languages•Compatibility to VRLA (SMF), LATB, Nickel Cadmium batteries•Black start facility

Benefits• Hi-Availability of Quality Power• Reduced Cost of Ownership• Upstream Green Power• Ease & Simplicity in Scalability & Redundancy• Investment Protection

Liebert NX – the next generation,true on-line, double conversion digital UPS – is designed to appropriately address the“Hi-Availability Quality Power”need of B2B and B2C businesses.Innovation, simplicity and low costof ownership have been delicatelyconverged in Liebert NX to offeryou the highest capital investment return. With the Liebert NX, you can rest assured that you havehigh nines quality power for yourcritical business applications.

Liebert NX comes in six popular ratings: 30, 40, 60, 80, 100 & 120 kVA.

Liebert NX

Page 27: Tailored Solutions for Power Protection - SKY Automation

25

Technical Data

Rated Power @ 0.8 PF [kVA] 10 15 20 30 40 60 80 100 120 140 160 200

Rectifier Type IGBT-based Vector Controlled PFC (PF Corrected)

Input Voltage [Vac] 380 / 400 / 415 (Accepted from 305 to 477 without batt. Use)

Input Frequency [Hz] 50 or 60 (Accepted range from 40 to 70)

Input Current THD <3% (without any Filter)

Input Power Factor =0.99 (without any Filter)

[s] 5 to 30 (selectable)

[Vac] 380 / 400 / 415

Battery Type VRLA (Valve Regulated Lead Acid) or Wet / Flooded or NiCd

End-Cell Voltage [Vdc/ Cell] Selectable from 1.60 to 1.90 (for VRLA)

DC Ripple Current

(float) <5% (of C10 AH capacity) RMS value

DC Ripple Voltage

(float & const V Ch) <1% (RMS value)

Temp. Comp. Charge Standard (where internal batteries 10, 15, 20, 30, 40 kVA)and Optional (for all other battery configurations)

Inverter Type IGBT-based Vector, Repetitive & PI Controlled

Output Power [kW] 8 12 16 24 32 48 64 80 96 112 128 160

Output Voltage [Vac] 380 / 400 / 415 +/- 0.5 Regulation (3-phase RMS average)

Output Frequency [Hz] 50 or 60 with +/- 0.05 Regulation

Output Voltage THD 1% (max)

Max. Load Crest Factor 3:1 (compliant with IEC 62040-3)

Transient Volt. Resp. [ms] 10 to recover ±5% of Nominal Voltage for 0% to 100% or 100% to 0% step load

Max. Leading PF Load Up to 0.9

Voltage Displacement [°el] 120°+/-10 el (with 100% unbalanced load)

110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute

up to 96

Width [mm] 600 600 700 1000

Depth [mm] 700 825 825 825

Height [mm] 1400 1600 1800 1800

Weight (approx.)

without batt. [kg] 180 204 204 312 341 401 445 720 720 1050 1200 1350

IP IP 20 (even with open front door)

IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1,IEC 61000-4-2, 4, 5, 6, 8,11, EN 50091-1-1, EN 50091-2,

EN 50091-3, EN 60950, EN 60529, ANSI C62.41 (IEEE 587)

Class-A (Applicable for both Radiated & Conducted)

Storage Temp. [°C] -20 to 70 (UPS) & -20 to 30 (Battery)

Operating Temp. [°C] 0 to 40 (UPS) & 25 +/-5 (Battery)

Relative Humidity 0 to 95% (non-condensing)

Maximum Altitude [m] 1000 (as per IEC 62040/3)above Mean Sea Level

Models Nxe Nxa

Rectifier Input

Power Walk-In

Bypass Input

Input Voltage

Battery

Output

Overload

Efficiency

AC-AC

Physical Parameters

UPS Enclosure

Standards

EMC Class

Environmental

Page 28: Tailored Solutions for Power Protection - SKY Automation

26

Applications• Facility-wide networks• Medical equipment• Industrial processes-Automation• Transport Automation

Features

From reliability to availability, from scalability to redundancy, from user-friendliness to maintainability, from parallelibility to connectivity, from investment protection to lower cost of ownership, whichever value you need, Hipulse addresses them allefficiently and effectively.

Hipulse is carefully designed to maximize the availability of your critical loads to ensure that your business is protected to the maximum extent possible against power quality problems as well as complete power failure.

• On-Line Double Conversion• IGBT-based PWM Inverter• Wide input voltage tolerance (+10/-15%)• Wide input frequency tolerance ( 5%)• Automatic battery testing• Common battery sharing kit (optional) with 1+1 configuration• Built-in maintenance bypass (Single and 1+N Models)• Modular design of inverter bridge for higher rated UPS modules like 600 & 800 kVA• UPS modules in Dual Bus configuration using optional HiSync on

the Upstream (with UPS), HiSwitch in the downstream (after UPS) and load-end SmartSwitches

• Provision to use any type of battery: Wet cells (Tubular or Plant ), Valve Regulated Lead Acid (VRLA) / Maintenance free and Nickel Cadmium

• Field settability of end-cell voltage of the battery• Intelligent web communications and automatic graceful computer

shutdown operations

Liebert Hipulse UPS (30-150 kVA 1-Phase)in Rack and Tower Mode

• N form software for full-scale and cost-effective monitoring• Site scan web solution tool for online monitoring

• Large Computer Rooms

Liebert Hipulse UPSDigital UPS For The Digital World & Industrial Automation

Page 29: Tailored Solutions for Power Protection - SKY Automation

27

Technical Data

Nominal rating [KVA](0.8 pf) 25 40 60 80 105 130 150

Depth[mm]

Width[mm]

Height[mm] 2110 2110 2110 2110 2110 2110 2110

Voltage 380/400/415V(+10/-15%)-3ph-3W

frequency 50 or 60 Hz +/- 5%

Power factor 0.8-0.92

Voltage stability 230/1 ph

Voltage stability -steady state (+/-)1.5%

100% load Step (+/-) 5%

Frequency Stability- Synchronized with the bypass supply (+/-)1%

- Auto -synchronized (+/-) 0.1%

Overload capacity from inverter at

nominal voltage 110% for 60 minutes,125% for 10 Minutes,135-150% For 1Minute

Short circuit current from inverter 1.5 in for 5 seconds(in accordance with EN50091-1-1)

Voltage distortion with linear load 2% max

Voltage distortion with 100% Non

linear load <5%Ph/N(distorted load as per En 50091-3)

Max deliverable Power with Non

linear load(CF=3:1) 100%

Output Voltage Dissymmetry with

100% Unbalanced load 2%

Operating

Continuous Max 40 to 8 Hrs

Storage (- 25C) to 70C

Relative Humidity 90% non condensing type at 20 C

Max operating altitude with derating 1000 meters from MSL

Acoustic noise at 1 meter from Panel

-Front 57 to 73 dbA (depending on the KVA)

Cable Entry Bottom

Front ,Rear ,Top Cover Structure White Epoxy Polyester

Front Door & Slide door Structure Black Epoxy Polyester

Degree of protection for enclosure IP 31 Standards

Ventilation forced Air Cooling with internal fans

HIPULSE UPS System

Physical characteristics

895 895 895 895 895 895 895

900 900 900 1250 1640 1640 1640

Input

Output

Frequency

Environment

Ambient Temperature **rating can be selected for ambient temperature upto 50C

0 to 40 C (**)

Cabinet Finish

Construction

Page 30: Tailored Solutions for Power Protection - SKY Automation

28

Applications• Facility-wide networks• Medical equipment• Industrial processes

Features

From reliability to availability, from scalability to redundancy, from user-friendliness to maintainability, from parallelibility to connectivity, from investment protection to lower cost of ownership, whichever value you need, Hipulse addresses them allefficiently and effectively.

Hipulse is carefully designed to maximize the availability of your critical loads to ensure that your business is protected to the maximum extent possible against power quality problems as well as complete power failure.

Liebert Hipulse UPS(80-800 kVA 3-Phase)

Liebert Hipulse UPS (80-800 kVA 3-Phase)in Rack and Tower Mode

• On-Line Double Conversion• IGBT-based PWM Inverter• Wide input voltage tolerance (+10/-15%)• Wide input frequency tolerance ( 5%)• Automatic battery testing• Common battery sharing kit (optional) with 1+1 configuration• Built-in maintenance bypass (Single and 1+N Models)• Modular design of inverter bridge for higher rated UPS modules like 600 & 800 kVA• UPS modules in Dual Bus configuration using optional HiSync on

the Upstream (with UPS), HiSwitch in the downstream (after UPS) and load-end SmartSwitches

• Provision to use any type of battery: Wet cells (Tubular or Plant ), Valve Regulated Lead Acid (VRLA) / Maintenance free and Nickel Cadmium

• Field settability of end-cell voltage of the battery• Intelligent web communications and automatic graceful computer

shutdown operations

Digital UPS For The High-EndDigital World

• Telecommunication• Data Centers in IT/ ITES/ BPOs• Server & Networking• Entertainment & Media• Server Farms

• N form software for full-scale and cost-effective monitoring• Site scan web solution tool for online monitoring

Page 31: Tailored Solutions for Power Protection - SKY Automation

29

Technical Data

Hipulse UPS System

Nominal Rating [kVA] (0.8pf) 80 120 160 200 300 400 500 600 800

Rectifier Type 6p 12p 6p 12p 6p 12p 6p 12p 6p 12p 6p 12p 12p 12p 12p

Physical Characteristics

Depth [mm] 875 1000

Width [mm] 900 1300 1250 1890 1250 1890 1250 1890 1640 2280 2460 2460 3200 3200 4400

Height [mm] 1900

Weight [kg] 750 1120 1000 1475 1200 1725 1350 2000 1850 2540 2400 3100 4200 4500 5050

Input

Voltage 380/400/415V (+10/-15%) 3Ph 4w

Frequency 50 or 60 Hz +/-5%

ITHD 4-10% with optional input filter

Power Factor 0.90- 0.94 with optional input filter

Output

Voltage Stability 380/400/415V 3Ph 4w

Voltage Stability

-Steady State +_ 1%

100% Load Step +_ 5%

Frequency 50 or 60 Hz

Frequency Stability

-Synchronised with the bypass supply +_1%

- Auto Synchronised +_0.1%

Overload capacity from inverter at nominal voltage

-3ph 10% for 60 minutes, 125% for 10 minutes, 135-150% for 1 minute

-1ph 200% for 30 seconds

Short circuit current from inverter

-3ph 1.5 In for 5 seconds 9in accordance with EN 50091-1-1

- 1 ph 2.9 In for 5 seconds 2.2 In for 5 seconds

Voltage Distortion With Linear Load <1%

Voltage Distortion With 100%

Non Linear Load <3% Ph/ Ph, < 5% Ph / N (distorted load as per EN 50091-3)

Max. Deliverable Power

With Non-Linear Load ( CF =3:1 ) 100%

Max Unbalanced Load 100%

Voltage Displacement Witho o100% Unbalanced Load 120 +_1 el

Output Voltage Dissymmetry

With 100% Unbalanced Load 2%

Page 32: Tailored Solutions for Power Protection - SKY Automation

30

Applications

Features

Liebert Precision Power Center

Liebert Precision Power Center

Liebert delivers the packaged power solution through precision power center (PCC), creating high quality power to protect the operation of a critical facility. It is a all in one power system at an affordable price that will close the power delivery loop in your critical facility.

Affordable and reliable operation of PCC ensures that power is distributed properly to each piece of your important equipment and you get maximum safety standards.

• Computer rooms• LANS/WANS • Communications facilities• Office areas• Medical imaging suits• Grouped workstations• Process control rooms• High-tech manufacturing power sites.

• Computer-Grade grounding • Handles non linear loads• Online communication tools • Compact single cabinet• Single input cable connections• Easy relocation• Expansion capabilities for future requirement• Onsite power monitoring• Secure distribution and circuit identification• Central monitoring interface• Space saving and easy to install• Optional system enhancement system• Circuit identification.

Affordable Packaged Power Management For Higher Power Quality

Page 33: Tailored Solutions for Power Protection - SKY Automation

31

Technical Data

Precision Power Center

Output

KVA 50 75 100 125 150 200 225

Input

Voltage 415 400 380 415 400 380 415 400 380 415 400 380 415 400 380 415 400 380 415 400 380

Input Circuit

Breaker (Amps) 100 100 100 150 150 150 200 200 200 250 250 250 300 300 300 400 400 400 400 400 400

Panel Board Poles

Std 24 24 48 48 72 96 96

Opt** 96 96 96 96 96 96 96

Dimensions (cm)

W 600 600 600 600 800 800 800

D 1000 1000 1000 1000 1200 1200 1200

H 2000 2000 2000 2000 2000 2000 2000

Weight

Kg 420 520 630 710 860 1045 1110

Dimensions (cm)

Output 2.0 2.55 3.3 4.06 4.5 6.0 6.75

• KVA : 50-225, 3 phase

• Input : 3 Phase 3-wire plus ground 380, 400 or 415 volts : 50 Hz (Transformer less system require 3 phase, 4w & G)

• Output : 3-phase, 4-wire plus ground220/380,230/400 or 240/415 volts: 50 Hz

• Alarm conditions : O/P & under voltages; O/P overload;neutral and ground over currents; o/p voltage THD;

Transformers over temperature; frequency deviation;phase sequence error; phase loss; 5 customer specifiedalarm conditioning

• •

• •• •

Ground : Single point reference on separately derived system

Distribution : Individually protected 125 Amps panel board with bolt on breaker and flexible output cables

Cooling system : convection / forced

Monitored parameters : I/P & O/P Voltages; o/p, Neutral & grounded currents / P voltage THD; K& crest factor; KVA;KW; PF; % load; KW Hrs; frequency; o/p current THD

Efficiency : 96-98%

Voltage Adjustment : 10% to + 5% of nominal in 2 ½ %increments

• •

Page 34: Tailored Solutions for Power Protection - SKY Automation

32

Liebert Powersure PanelTransient Voltage SurgeSuppressor

Applications

•Telecommunications and broadcasting Voice and data networks as well as television and radio

broadcasters rely on high quality power for f lawlesstransmission.

•Industrial electronics Factories require noise free voltage to keep process control

machines running at maximum productivity with minimum downtime.

•Computer equipment and networks Office, shops, superstores and other retail businesses need clean power to maintain the integrity of computers and data.•Telecommunications switchgear and cellular facilities

Reliable power is essential to ensure networks work reliably, 24 hours a day.

•Hospitals Closely controlled power is essential in critical areas such as

operating theatres and intensive care.

Liebert Powersure Panel utilizesPatent pending circuitry to monitorthe status of all protection modes,Including neutral to ground. Should protection be unavailable in any mode, the green LED will be out,and the red LED will illuminate andan audible alarm will sound. In addition, high isolation form C drycontacts for remote monitoringprovide indication of: suppressionsystem failure, under voltage, andphase or power loss. LiebertPowersure’s patent pending Suppression Integrity monitoringIndicates failure for both shorted oropened suppression components.

For Unparalleled Protection That Exceeds Industry Standards...

The Liebert Powersure Panel incorporates proven technology toprovide unparalleled protection from transient surges and electricalline noise (ELN).

Liebert Powersure Panel

Page 35: Tailored Solutions for Power Protection - SKY Automation

33

Features

• Compact module attaches directly to breaker panel• CE marked, complies with EMC and low voltage directives• Patent Pending Powersure Detection Circuitry• Easy, safe, maintenance free operation• Repeatable surge current capability• Can be retrofitted to existing panel boards• High isolation dry contacts for remote monitoring• Designed for maximum safety• 5 Year warranty

The Powersure Series At a Glance

• Connection means: Parallel connectedAgency listings: UL1449, Ul1283, CSA, CE,

BS6651 • Protection modes: All modes standard (L-N, L-G,

N-G, L-L); optional-any combinationEMI/RFI Attenuation: 60dB typical

• Response time: Less than .5ns• Operating Frequency: 47/63 Hz• Enclosure: Gray Noryl HS-1000, Rated 94-5V,

Nema, 12, 4, 4X, IP65, IP66Fault Current Rating: 300,000 AIC

• Line frequency: 47-63 Hertz• Temperature: -40 to +60 degrees C

Relative humidity: 0 to 95% noncondensingAltitude: 0 to 5500m

• Audible noise: Less than 45 dBa

Technical Data

Lower Exposure Medium Exposure

Connection Type Parallel Parallel

Operating Voltage Range -15% -15%

Surge Current Capacity 25kA, 50kA or 100kA 100kA or 160kA

Fault Current Rating ( A/C ) 14kA/C 65kA/C

Dimensions 4.72”x4.72”x2.36” (160 kA units) 8”x6”x4”

(100 kA units) 6”x4”x3”

Operating Frequency Range 47…63 Hz 47…63 Hz

Capacity Continuous Continuous

EMI/RFI Attenuation 40 dB typical 40 dB typical

Response Time <0.5 nanoseconds <0.5 nanoseconds

Dry Contract rating 125 VAC, 8.0A, 1.0pf 125 VAC, 8.0A, 1.0pfo o o oOperating Temperature -40 C to +50 C -40 C to +50 C

Operating Humidity 0% to 95% 0% to 95%

Status Indication LED, Dry Contacts LEDs, Dry Contacts

Certifications UL 1449, CUL (CE-optional) UL 1449, CUL

Low Exposure Medium Exposure

120 Volt systems 400 Volts all modes 400 Volts all modes

208 through 277 Volt systems 800 Volts all modes 800 Volts all modes

480 Volt systems 1500 Volts all modes 1500 Volts all modes

••

Page 36: Tailored Solutions for Power Protection - SKY Automation

34

ASCO SwitchDesigned To MinimizeDowntime On CriticalSystems

Applications•Healthcare Facilities•Commercial Buildings / Industrial Buildings•Web Hosting, Internet Data Centers•Telecom Central Offices•Process Manufacturing / Wafer Fabrication Plants / Distributed Power / Load Management

ASCO Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacitysize, is achieved by a reliable, Field proven solenoidoperating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPSs and microprocessor based systems.

7000 Series Power Transfer Switches are available open or enclosed, in ampacity sizes from 30 through 4000 amperes with the largest selection of optional accessories offered anywhere. All switching Configurations are available with an integrally mounted bypass- isolation switch and/ or rated for use in service entrance applications .

ASCO 7000 Series

Page 37: Tailored Solutions for Power Protection - SKY Automation

35

Applications•Healthcare Facilities•Commercial Buildings / Industrial Buildings•Web Hosting, Internet Data Centers•Telecom Central Offices

Features•The Series 300 is listed to UL 1008 standard for Transfer Switch Equipment and CSA standard C22.2 for

automatic transfer switches.•Meets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) Articles

700, 701 and 702.•30 through 3000 amps in a compact design, Available to 600 VAC, single or three phase. of loads, such as motors,•Rated up to 600 VAC, 30 through 4000 amperes.•True double- throw operation: The single solenoid design is inherently locked and prevents contacts from stopping between sources or from being in contact with both sources at the same time.•High withstand and close- on ratings•There’s no danger of the Series 300 ATS transferring loads to a dead source because the unique ASCO single- solenoid operator derives power to operate from the source to which the load is being transferred.•Solid, switched, or overlapping neutral conductor options.•Easy- to- read flush- mounted control and display panel provides LED indicators for switch position and

source availability.•It also includes test and time- delay bypass switches as standard features.•Standard engine exerciser for weekly automatic testing of engine generator set with or without load.•Adjustable time- delay feature•Supplied with solid neutral termination.•Standard ground conductor connections.•Optional switched neutral pole available.•Accessory kits available.•Meets IEC 60947-6-1

The ASCO Series 300 was designed for one purpose— to automatically transfer critical loads in the event of a power outage. The rugged construction and proven performance of the ASCO Series 300 assure the user of many years of complete reliability. The Series 300 is even designed to handle the extraordinary demands placed on the switch when starting or restarting stalled motors and switching high inrush loads.

ASCO Series 300

Page 38: Tailored Solutions for Power Protection - SKY Automation

36

Emerson NetworkPower Is the OneCompany That CanProvide A CompleteRange Of PowerProtection SolutionsDesigned For AnyFacility And Any Need

Poor power can affect every aspect of your criticaloperations. Critical equipment and processesthroughout your operations can be affected by poorpower quality, outages and other related problems.

Without Proper Power, Vital Processes JustCannot Function

Important computing, communications and industrialprocess control functions all depend on clean, continuouspower to maintain these operations. From a single desktopPC to a large data center, power quality is the commondenominator that must be maintained.

Differing Needs Require Different Solutions

Different parts of your operation have different needs forpower. Depending on the nature of the operation, powerneeds can range from simple surge protection all the wayup to redundant UPS systems and power feeds with back-up generating capabilities.

Threats To Your System’s Availability AreAround Every Corner

There are a number of points within a critical facility wherepower troubles can develop. Adding to this dilemma is thatoperations in one part of your facility can adversely affectthe power in another area of the building. Yourproductivity depends on critical electronic systems – canyou depend on your power to keep them operatingproperly?

Page 39: Tailored Solutions for Power Protection - SKY Automation

37

Remote FacilitiesEmerson Network Power’s High-reliability Liebert UPSsystems and DC power equipment are critical tomaintaining operations in telecommunications sheltersand other unmanned structures.

Telecommunications RoomsEmerson Network Power can provide a reliable flow of bothAC and DC power for telephone switching systems andother communications equipment.

Equipment Rack EnclosuresThese densely-packed equipment bays, housing servers orother essential communications devices require UPS back-upplus distribution to get uninterrupted, conditioned power toeach and every component in the rack.

Computer RoomsEmerson Network Power offers the full range of UPS,distribution systems and other power protection equipmentto meet the needs of the largest data centers and networkingfacilities.

Office LocationsWith many mission-critical computing systems locatedright in the office space, there is a need for UPS protectionthat can be placed nearby. Liebert offers a number of powersystems that are especially designed for use in business andoffice environments.

Process Control RoomsEmerson Network Power’s Liebert UPS, surge protectionand power distribution are all key to maintaining theproper operation of process control and othermanufacturing systems that utilize microprocessor andcomputer control.

A Power ProtectionSolution ForEvery Need

Page 40: Tailored Solutions for Power Protection - SKY Automation

38

Our End to End Solutions

Page 41: Tailored Solutions for Power Protection - SKY Automation

39

Power Is Just Part of The Reliability Story

Liebert Also Offers A Full Range Of Heat Removal Solutions

In addition to proper power, sensitive electronic computer and communications systems also require the correct environment in order to function reliably. Because this equipment produces heat, it is absolutely necessary to control and maintain the temperature and humidity levels where it is located in order to assure continuous operation.

The Widest Range Of Products Gives You An Infinite Range Of SolutionsAs network equipment gets smaller and packed tighter, it creates unprecedented heat densities that can result in thermal shutdown or total component failure. Precision air conditioning, specialized enclosures and rugged remote protection can assure network uptime against this threat.

From high-capacity units to compact above-ceiling systems there is a Liebert system designed to cool and protect your critical computing systems. We make the industry’s widest range of precision environmental control, including air conditioners, fluid chillers and heat rejection systems in capacities from one to more than 65 tons. These systems are available with a choice of cooling methods, including chilled water, air cooled and glycol cooled models, as well as ultra energy efficient GLYCOOL™ and Dual-Cool configurations.

We also offer specialized systems, including exterior mounted air-conditioning for telecommunications enclosures, supplemental cooling for high-density electronic applications.

End to EndSystem SolutionsWith EmersonNetwork Power

Page 42: Tailored Solutions for Power Protection - SKY Automation

24

Emerson NetworkPowerGlobal Services

FACTORY TRAINEDYou can be sure that the only people who deal with your Critical Air Equipment will be 100% Factory Trained Emerson Service Experts

ORIGINAL PARTSYou can be sure that the parts you will receive from our 100% Emerson Service Experts are 100% Original Parts. With our multi-tiered parts availability program, you are ensured that parts will be made available to you when and where you need them.

VERSION CONTROLYou are assured of 100% Version Control so that your critical business systems won’t have to experience downtime due to incompatibility.

SUPPORT NETWORKWe not only help you develop you Environmental Control System, but our 100% Emerson Service Experts also offer a Full Support Network so that your critical systems have a 100% Safety Net every step of the way.

QUALITY RESPONSEWe know it is important to get to your critical systems on time. With our 100% Emerson Service Experts you don’t just get prompt service; you also get 100% Quality Response. This means no useless tinkering, no wasted time-- just Quality Service, straight away.

100% Emerson Service Experts.Would you settle for anything less?

Page 43: Tailored Solutions for Power Protection - SKY Automation

41

Our Capability Literally Extends From “Grid to Chip”, Offering The Broadest Range of Solutions To The Market.

Emerson Network Power offers:

• DC Power Systems (Small, Medium, and Large Systems)

• Uninterruptible Power Systems (from 500VA to 1000 kVA)

• Precision Air Conditioning for Computer Rooms

• Automatic Transfer Switches Medium and Low Voltage

• Static Switches

• Shelter Air Conditioning for Telecommunications

• Specialized Enclosures to protect Critical Network Equipment

• Surge Suppression and Filtering

• Site Monitoring Equipment

• All Operating System associated Software

• Emerson Network Power Global Services (24X7X365 support for all our customers)

Our PortfolioShapes OurSolutions

Page 44: Tailored Solutions for Power Protection - SKY Automation

Emerson Network Power.

While every precaution has been taken to ensure accuracy and completeness in this brochure, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. © 2008 Emerson Electric Co.

TMThe global leader in enabling Business-Critical Continuity .

Voice of Customers UPS Awards 2006-07 for Product Line& Customer Service Awards in IT, Telecom,

Large Enterprise & Hospitals andCustomer Service Leadership Award in BFSI

Best IT Hardware CompanyMaharashtra IT Award 2006-07

2007R

Emerson Network Power1050, Dearborn Drive, P. O. Box: 29186Columbus, Ohio - 43229Tel.: 800.877.9222 (US & Canada Only)Tel.: 614.888.0246 (Outside US)Fax: 614.841.6022

Country OfficeEmerson Network Power (India) Private Ltd.Plot No. C-20, Road No. 19, Wagle Estate,Thane (w), Maharashtra - 400 604. India.Tel.: 91-22-67208000Fax: 91-22-25828358

City Offices

East ZoneKolkata : 033-40023100Jamshedpur : 0657-2227678Guwahati : 0361-2734486Bhubaneshwar : 0674-2586003/3299872

South ZoneBangalore : 080-41135670/770/870Secunderabad : 040- 27806771/772Cochin : 0484-2341985/86Chennai : 044-28151063/28152596Vishakapatnam : 0891-2505540/41/42Coimbatore : 0422-4387625

West ZoneGhatkopar : 022-67208800/67209000Pune : 020-66235000Baroda : 0265-2314296/2330383Nagpur : 0712-5634997Indore : 0731-4023806Ahmedabad : 079-27560230/40Vikhroli : 022-40780303

North ZoneNew Delhi : Chandigarh : 0172-5077531Lucknow : 0522-2237174

011-28753214/0774/2218

Gurgaon : 012-4470015/16/17Jaipur : 0141-4024774

Outside Plant

Power Switching & Controls

Precision Cooling

www.emersonnetworkpower.co.in

Racks & Integrated Cabinets

Services

Surge Protection

Embedded Computing

Embedded Power

Monitoring

AC Power

Connectivity

DC Power