TABLE OF CONTENTSWon-Door Design Manual
www.wondoor.com
Fire Doors
Won-Door FireGuard BrochureCase Studies
Fire Door Selection GuideAutomatic Closing System Selection Guide
Specifications - FireGuard 20, 60, 90, 180 2-1
Plan Views 2-6Elevations - Side Views 2-7Elevations - Front Views 2-8Instructions for Using the Pocket Depth Calculation Chart 2-9Pocket Depth Calculation Chart - FireGuard 20, 60, 90,180 2-10Pocket Cover Door Guidelines 2-11Pocket Cover Door Detail 2-12Pocket Mounted Motor Operator Assembly Wiring Diagram 2-13Large Door Motor Operator Assembly Wiring Diagram (> 300 sq. ft.) 2-14Curved Door Guidelines 2-15Multiple Exit Hardware (optional) 2-16Vision Panel (optional) 2-17Remote Control and Status Display PC Station (optional) 2-18Key Switch (optional) 2-19
Guidelines for Temperature Rise Doors 3-1Specifications - Won-Door FireGuard 90TR 3-2Instructions for Using the Pocket Depth Calculation Chart 3-5Pocket Depth Calculation Chart - Won-Door FireGuard 90TR 3-6
Color Selection Guide
(standard details for the most commonly specified doors- single parting, straight, < 300 sq. Ft.)
Specifications - FireGuard 20, 60, 90, 180 1-1Standard Head Detail - Straight Doors 1-4Plan View - Single Parting 1-5Elevation - Side View 1-6Elevation - Front View 1-7Instructions for Using the Pocket Depth Calculation Chart 1-8Pocket Depth Calculation Chart - FireGuard 20, 60, 90, 180 1-9Pocket Cover Door Guidelines 1-10Pocket Cover Door Details 1-11Pocket Mounted Motor Operator Assembly Wiring Diagram 1-12
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Movable Fire Walls
Folding Partitions
Won-Door FireGuard MFW
DuraFlex (non-acoustically rated)
DuraSound (acoustically rated)
DuraSound XL (acoustically rated)
Specifications - FireGuard MFW 1 & MFW 2 4-1Head Detail 4-4Plan View 4-5Elevations - Side View 4-6Elevations - Front View 4-7Instructions for Using the Pocket depth Calculation Chart 4-8Pocket Depth Calculation Chart 4-9Pocket Cover Door Guidelines 4-10Pocket Cover Door Details 4-11Pocket Mounted Motor Operator Assembly Wiring Diagram 4-12
Folding Partition BrochureColor Selection Guide
Specifications 5-1Head Details 5-3Plan Views 5-4Elevations - Side Views 5-5Elevations - Front Views 5-6
Specifications 6-1Head Details - Straight Doors - Manual Operation 6-3Head Details - Straight Doors - Motorized Operation 6-4Head Details - Curved Doors - Manual and Motorized Operation 6-5Plan Views - Under 14’-0” in Height - No Pockets 6-6Plan Views - Over 14’-0” in Height - No Pockets 6-7Plan Views - All Heights - Pocketed Doors 6-8Plan Views - Motorized Operation 6-9Elevations - Side Views 6-10Elevations - Front Views 6-11Curved Door Guidelines - manually operated doors under 12’ in height 6-12Curved Door Guidelines - motorized & manually operated over 12’ in height 6-13Configuration Options - 2-Way Meeting 6-14Configuration Options - 3-Way and 4-Way Meeting 6-15Motor Operator Assembly Wiring Diagram 6-16
Specifications 7-1Head Details 7-3Plan Views 7-4Elevations - Side Views 7-5Elevations - Front Views 7-6Motor Operator Assembly Wiring Diagram 7-7
ii
4
5
6
7
This guide will assist the specifier in selecting the most appropriate assembly and related options based on:1. Fire rating required2. Special requirements for access control / security.
1. Won-Door FireGuard is listed as a fire-rated door (ASTM E-152) with ratings up to 3 hours.
2. Won-Door FireGuard is also listed as a 250 temperature rise door (ASTM E-152) with 1½ hour rating for use instairwell enclosure applications.
3. Won-Door FireGuard is also listed as a moveable fire wall (ASTM E-119) in straight, single parting configurations.
Won-Door FireGuard MFW I 1 HourWon-Door FireGuard MFW II 2 Hours
A. Exit Hardware may be specified at multiple locations along the door assembly to allow exiting from a space where asingle exit device would not be sufficient. (see details on pg. 2-16)
B. Vision Panels may be specified to meet code requirements for smoke barriers. (see details on pg. 2-17)C. Access Control Options. Where required, the Won-Door FireGuard assembly can be equipped to provide two levels
of access control:
When the door is in the normal supervisory mode, the door’s exit hardware is programmed to be inactive (it is activein emergency mode ). In addition, the closing system will seek the closed position. If an attempt is made to forcethe door off its closed limit, it immediately re-closes and sounds an alarm. The alarm can sound locally or remotely.When the door re-closes, the clutch engages for approximately 5 minutes to resist further attempts to force it open.
For increased security, t
An electromagnetic locking clutch is added to the closing system and provides 400 to 500 pounds of resistance toopening.
In addition to the sliding jamb and jamb stop upgrades provided in Level 1, the lead posts of the FireGuard doorare reinforced with 10-gauge steel tubing for additional strength. An additional 1” of pocket depth is required.
In the access control applications, other types of operating devices can be added including numeric key pads, push buttonand infrared operating devices, providing they are capable of receiving a low voltage signal via stranded 18-gauge wire inconduit to the Won-Door automatic closing system control box. Additional operating device contacts can be added asrequired. These access devices should be defined, provided, and installed under the respective specification section.
The REMOTE CONTROL AND STATUS PC STATION will monitor and control up to 120 FireGuard assemblies andconsists of a dedicated personal computer and customized software designed to indicate door status information and toprovide remote operation of the doors. (See pg. 2-18)
1. Fire Ratings:
2. Special Requirements (Options):
3. Using Other Types of Access Devices (Optional)
4. Central Station Monitoring / Remote Control (Optional)
Door Model Fire Rating
Door Model Fire Rating
°
Door Model Fire RatingWon-Door FireGuard 90TR 1½ Hour Temperature Rise
:
only
A key-switch or other access device is required to open/close the door, therefore specifiers must determine the typeand location of the device(s) and specify the required boxes, conduit and wiring in the electrical section of thespecification (see pg. 2-13 or 2-14 for requirements).
he standard sliding jamb and “quick release” jamb stops are replaced with a heavy-gaugesteel sliding jamb and rigid Z-shaped fixed jamb stops. An additional 1” of pocket depth is required.
A key-switch or other access device is required to open/close the door, therefore specifiers must determinethe type and location of the device(s) and specify the required boxes, conduit and wiring in the electrical section ofthe specification (see pg. 2-13 or 2-14 for requirements).
inLevel 2
(Note: Access control is disabled when the door is in fire mode.)Level 1 Access Control - Disabled Exit Hardware
Level 2 Access Control - Electromagnetic Locking Device
Fire Door Selection Guide
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Won-Door FireGuard
www.wondoor.com
iii
Automatic Closing System Selection Guide
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
160 sq. ft.
200 sq. ft.
160 sq. ft.
320 sq. ft.
400 sq. ft.
Egress Conditions
Max. Square Footage
250 sq. ft.
300 sq. ft.
500 sq. ft.
600 sq. ft.
One motor at end of pocket.
One motor at end of pocket.
One motor at endof each pocket.
One motor at endof each pocket.
Single PartCurved
Single PartStraight
Bi-PartCurved
Bi-PartStraight
One motor at end of pocket.
One motor at end of pocket.
One motor at endof each pocket.
Single PartCurved
Single PartStraight
Bi-PartStraight
Bi-PartCurved
Bi-PartStraight
One motor at endof each pocket.
One motor at end of pocket.
DoorConfiguration Motor Operator Configuration
The chart below indicates the maximum door (in sq. ft.) that a standard pocket mounted motor caneffectively operate when considering the door’s configuration (curved or straight, single or bi-parting) and egressrequirements.
Large door motor operators requireadditional considerations (access, space to install the operator assembly, etc.)
size
If your door’s size requirements are larger than allowed with the standard pocket mountedmotor, see the LARGE DOOR motor operator assembly below.
Non-Egress Conditions
Standard Pocket Mounted Motor Operator
Large Door Motor Operator Assembly
This motor operator assembly is used when door sizes exceed the limits stated above. It is usually locatedabove the header at the stack end of the door. When installed in this position, a 3’ wide by 2' high fire ratedaccess door is required to service and install the equipment. A minimum of 24” between the top ofthe header and the deck above is required at the motor location. The operator assembly must be located withina 1 hour rated enclosure. The Large Door motor operator assembly may be mounted below the header, butrequires 8" of additional pocket depth. (See side elevation details on pg. 2-7.)
The control boxes must also be located within 25 conduit feet of the motor and within a 1 hour rated enclosure.Typical locations are storage closets, electrical closets, or above the header. Doors of up to 900 square feetrequire 1 control box. Those exceeding 900 square feet require an additional battery box. (See elevation detailFGEL3 on pg. 2-7)
For doors exceeding 20'-0" in height or 30'-0" in width, please consult with a Won-Door representative.
headroom
www.wondoor.com
Won-Door FireGuard
www.wondoor.com
iv
PART 1 - GENERAL
PART 2 - PRODUCTS
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and specified
herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors,
blocking and trim shall be furnished and installed by other sections.B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section.[C. All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color shall be
selected by the architect.]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Fire doors shall be listed by Underwriters Laboratories for ratings as indicated, when tested in accordance
with the requirements of UL 10B and ASTM E-152.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and Submittals.B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show
installation details, layout, and electrical requirements.
1.05 DELIVERY, STORAGE, AND HANDLINGA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb, and trim. Provide field dimensions for fabrication.
B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assureaccess to and proper clearance for motor operators.
C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the original positions.
1.07 WARRANTYA. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year
from the date of substantial completion.
2.01 MANUFACTURERA. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model [select one: 20, 60, 90, or
180] as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 FIRE RATINGA. Fire Doors shall be listed by Underwriters Laboratory as special purpose fire doors having a [select one: 20,
60, 90, or 180] minute fire-resistive rating in accordance with the requirements of UL 10B and ASTM E-152.
Supervise unloading and handling ofmaterials.
D. Store boxes flat (not more than three high) in dry area and protect from elements that may damagematerials. Replace damaged materials at no cost to the owner.
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
1-1Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
2.03 MATERIALSA. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no
pantographs or interconnections except at the lead-post.
(or .125 aluminum)
ACCESS CONTROL/MONITORING OPTIONS[L. Level 1 Access Control. The Exit Hardware shall not respond when pressed until activated by signal from
smoke detector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-guage steel sliding jamb and rigid Z-shaped jamb stops.] (Note: at least one key-switch required.)
B. Panels shall be formed of 24-gauge enamel coated steel V-grooved for strength and resilience. Panelsshall be connected by full height 24-gauge enamel coated steel hinges.
C. Suspension System: shall consist of two 14-gauge cold rolled steel tracks on 8" (.203)centers attached to the overhead structural support. Each lead post shall be suspended by a 8-wheel ballbearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearing roller.
D. Lead-posts: shall be of 24-gauge cold rolled steel and shall be connected by specially formed steel panels.An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operationand insure a tight fitting closure.
E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the firedoor to form a smoke and draft seal.
F. Hanging weight shall be 5.5 pounds per square foot.G. Automatic Closing System
Operation: closing system shall consist of an electronic control box, motor operator assembly and leadingedge obstruction detector. In case of fire, closing system shall be activated by the building's fire/smokedetection equipment and automatically close the Won-Door FireGuard doors. Motors shall be operated byDC power supplied from a 12-volt maintenance-free battery located in the electronic control box. Batteriesshall be continuously charged by the building's electrical service and be automatically maintained at capacity.Fire doors may be operated manually in either the conventional or emergency mode. Electronic control boxshall house the microprocessor logic board, interconnect board, 12-volt maintenance-free battery, powersupply charger, and motor control relays. The microprocessor shall initiate a loud audible signal should any ofthe following conditions arise:
1. High or low AC voltage2. High or low DC voltage3. Drive train malfunction4. Limit switch malfunction5. Key switch malfunction6. ROM or RAM check-sum error
Motor Operator Assembly shall consist of a DC gear-motor, limit switch, drive sprocket and clutch. The motorshall drive the fire door by means of a chain attached to the stabilizer bar trolley. Motor operator assemblyshall be located within a one (1) hour fire rated enclosure.
H. Leading Edge Obstruction Detector: fire doors shall be equipped with a pressure sensitive leading edgesuch that each contact with an obstruction shall cause the door to stop and pause before attempting to re-close. Fire doors can be manually opened at any time by pushing against the leading edge.
I. Exit Hardware shall be located on both sides of each fire door. In emergency mode a slight pressure on thehardware will cause the door to open a minimum of 32 inches, pause for 3 seconds, then automaticallyclose. The hardware shall be field programmable to allow automatic opening distances of up to the entireopening width. In the conventional mode, the hardware is used to open the door and move it back into thestorage pocket.
OPTIONS[J. Vision Panel shall consist of frame and clear glass assembly with listings from Underwriters Laboratory up to
1½ hours]. (Note: required only in smoke barriers in Group I occupancies.)[K. A Key switch module shall be provided.] (Note: required for doors with Large Door Motor Operators and doors
equipped with Access Control devices. See pg. 2-19 for details.)
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
1-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Won-Door FireGuard
www.wondoor.com
Brackets [ ] indicate specifier’s option.
Specifications FireGuard 20, 60, 90, 180
;specifier’snote
[M. Level 2 Access Control. An Electromagnetic locking clutch shall be added to the motor operator assembly toprovide 400-500 pounds of resistance to manual opening. Upgrades to the fire door for this level of accesscontrol shall include a heavy-guage steel sliding jamb, rigid Z-shaped jamb stops and 10-guage steel tubereinforcement to the lead post.] (Note: at least one key-switch required.)
[N. A Remote Control and Status Display PC Station shall continuously monitor the status and provide remoteoperation of up to 120 Won-Door FireGuard doors.] (See pg. 2-18 for details.)
2.04 COLORColor shall be manufacturers standard #55 Platinum.
[Color shall be selected from manufacturer's optional colors at additional cost.][Color shall be selected by architect and field painted by others.]
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor within +/- 1/16"(.002) tolerance over the entire length of the
opening.
3.02 INSPECTIONA. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect, in
writing, of any unacceptable conditions.
3.03 INSTALLATIONA. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings.B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of
applicable codes and regulations.C. Upon completion of the installation, general contractor shall protect fire doors from damage and shall replace
or repair subsequent damage so that doors are acceptable to the architect at no additional cost to the owner.
PART 3. EXECUTION
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
1-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Won-Door FireGuard
www.wondoor.com
Brackets [ ] indicate specifier’s option.
Specifications FireGuard 20, 60, 90, 180
;specifier’snote
1
2
3
7
4
6
5
18"
3 1/4"
Standard Head DetailStraight Doors
Won-Door FireGuard
1-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
1. 1/2" dia. threaded rod with nuts and washers by others. (18" O.C. in opening, 12" O.C. instack area)
2. Three layers ¾” x 18" plywoodTwo layers 5/8” x 18" gypsum board screwed to plywood by others.
3. Provide rated construction corresponding to rating required for opening by others.4. Motor operator unit. (Mounted at back of pocket. See pg. 1-6.)5. Minimum dimension required to meet U.L. labeling requirements. The dimension may be
increased to further recess the head condition if required.6. L-shaped trim piece of pre-finished off white color to match track by Won-Door. Provides
transition from track to gypsum soffit.7. Three layers ½ x 3 5/8" gypsum board terminating 12" into pocket. All gypsum to be
furnished, finished, and field painted by others.
glued and screwed together with staggered joints at 24"O.C. by others.
"
CAD FILE: FGHD1
5¾" 5¾"
Plan View - Single PartingPocketed
Won-Door FireGuard
1-5Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Pocket Depth* Clear Opening
12 5 4
7
6
43
4 1/16"
4 3/16"
5"
1. Exit Hardware.2. Sliding jamb assembly.3. Sliding jamb stops.4. Blocking by others.5. Pocket cover doors by others (optional). (See ppg. 2-11 & 2-12.)6. Provide rated construction corresponding to rating required for
opening by others.7. Recessed striker to be caulked by others.
CAD FILE: FGPL1
* To determine appropriate pocket depth, refer toon pg.1-9.
Pocket DepthCalculation Chart;specifier’s
note
ElevationSide View
Won-Door FireGuard
4
5
6
7
2
1
3
POCKET
1. Folding fire door.2. Ceiling line.3. Exit Hardware.4. Motor operator assembly.5. Electronic control box.6. Two 4x4 junction boxes surface mounted 12" from top of
finished floor. (Pocket Mounted Control Box Only)7. Top of door track.
CAD FILE: FGEL1
1-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
ElevationFront View
Won-Door FireGuard
2
3
1. Sub floor (Concrete, etc.)2. Finished floor (Carpet, tile, etc.)3. Fabrication height / field dimension height taken from
top of track to top of finished floor.
CAD FILE: FGEL4
1
Door Profile Widths:
Stacked Width: 13¾"Extended Width: 11½"
Stacked Extended
1-7Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
The term CLEAR OPENING WIDTH on the refers to the distance from thefront of the storage pocket to face of the striker. T
etermine the door’s CLEAR OPENING WIDTH, 2) find the appropriate range (, then 3) refer to the “SINGLE” (for single parting) column. Lastly, consult the OPTIONS EFFECTING
POCKET DEPTH below the chart to determine how optional equipment effects stack requirements.
: Pocket depth for FireGuard 60 door w/ (in the rangebetween 7’-9” and 8’-5”). Minimum pocket depth = ”
Pocket Depth Calculation Charto determine the pocket depth requirement of a door: 1)
d for that width FROM - TOcolumns)
Example below single parting 8'-4" clear opening33
Bi-part doors require two storage pockets. Instead of using the CLEAR OPENING WIDTH whenreferring to the stack chart, use of the CLEAR OPENING WIDTH (which is the distance from the front ofstorage pocket on one side to the center of the door opening),
For bi-parting doors,
: Pocket depth for FireGuard 60 b door with .Look up 7'-10" on stack chart (1/2 of 15'-8"). Min. pocket depth = 38" for
total1/2
then follow the same instructions listed in“single parting” (above) to determine the pocket depth requirement. a motor operatorcan be placed in each pocket to increase the maximum door size for a standard Pocket Mounted Motor. See
for details. For bi-parting, consult the factory.Automatic Closing System Selection Guide unequal
Example belowpocket.
i-Parting 15'-8" clear opening widtheach
Instructions for Using the Pocket Depth Calculation Chart
Single Parting Doors
Bi-Parting Doors
List of Options Effecting Pocket Depth:
Won-Door FireGuard
Once you depth requirements using the chart ,have determined the appropriate on the next page consult thebelow the chart. Note that the chart only applies to standard Pocket Mounted
Motor Operators with the size limitations listed in the Largerdoors will require a Large Door Motor Operator which will effect pocket depth requirements. Optionalequipment such as the access control sliding jambs, vision panels, pocket cover door bumpers and multipleexit hardware will also effect pocket depth as will pocket cover doors in excess of 2” thick.
Options Effecting Pocket DepthAutomatic Closing System Selection Guide.
From: To : Single Bi-Part7’-9” 8’-5” 33” 38”8’-6” 9’-2” 35” 40”9’-3” 9’-11” 36” 41”
Clear Opening Width Pocket Depth
From: To : Single Bi-Part7’-9” 8’-5” 33” 38”8’-6” 9’-2” 35” 40”9’-3” 9’-11” 36” 41”
Clear Opening Width Pocket Depth
1-8 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
OPTIONS EFFECTING POCKET DEPTH:Access Control sliding jamb - Add 1" to pocket depth.
bove cPocket cover door
Vision panel
Pocket cover door bumperAdditional exit hardware
- A harts allow for 2" thick cover door. Add appropriate amount ifcover door and door finish materials are thicker than 2". (See pg. 1-10)
- Add 5” to pocket depth (except when the vision panel is required to be closer tothe leading edge of the door than 48” on a straight door or 96” on a curved door.In these cases, contact the factory for details). (See pg. 2-17)
- Add 1” (See pg. 1-11).- Add 1" to pocket depth for each exit device (See page 2-16).
The above charts are for standard Pocket Mounted Motor Operators only. See for size limitations.Automatic Closing System Selection Guide
Please consult the factory for pocket depth requirements of doors exceeding 30'-0" in width or 20'-0" in height.
For doors inheight, if the MinimumPocket Depth shown onthe charts for the requiredwidth is than thatshown above use theappropriate value fromabove instead. If it is not,use the value shown onthe charts.
10’ inless
Height Single Bi-part
over 10’
less
height or
Pocket Cover Door Guidelines
Won-Door FireGuard
Pocket cover doors are not required, but may be used to aesthetically conceal Won-DoorFireGuard doors. When properly done, they add to the continuity of the project and provideanonymity to the installation.
Won-Door Corporation does not manufacture or install pocket cover doors. Therefore, theyshould be specified in a separate specification section. Unless specifically required by theAuthority Having Jurisdiction, pocket doors need not be fire-rated, but solid-core doors arepreferable for reasons of durability. The door thickness and covering material is at the discretionof the designer. Many covering materials have been successfully used including: plasticlaminates, wood veneers, vinyl, paint, bronze, stainless steel, and marble. If the aggregatethickness of the pocket cover door , however, the additional thickness must beadded to the calculation of the pocket depth (see ).
Some basic criteria for the successful design of pocket cover doors are listed below:1. Doors must be side hinge swinging and must swing at .
Designing “notches” on either side of thepocket opening to accommodate the cover door thickness will prevent this (see
on the following page).2. Cover doors must be operable with less than 50 lbs. of lateral force. As the Won-Door
FireGuard door is activated, the leading edge will make contact with the cover doorand push it open. 50 lbs. is the normal operating force required for egress-typeswinging doors and
3. W Pocket doors should remain in the open position so as not toobstruct the path of the Won-Door FireGuard door when it is closing.
4. Won-Door recommends specifying either (1) a spring-action hinge such as theHager #1257 (with reversed spring-action) to hold the cover door open whenactivated (2) a continuous
(1) The reversed spring-action in the Hager #1257 butt hinge makes thecover door self-opening rather than self-closing. Cover doors without spring-action hinges may swing back into the operating path of the Won-DoorFireGuard and cause damage or obstruct emergency operation.
(2) For aesthetic considerations, a continuous hinge is preferable because it notdoes protrude beyond the face of the pocket cover door and thereforepresents a “hingeless” appearance. When a continuous hinge is used,however, a “bumper” is required. The bumper prevents the pocket door fromswinging back into the operating path of the Won-Door FireGuard. Won-Door does not provide bumpers, but its design is shown on the next page.(See page 1-11.) A bumper adds 1” to the pocket depth requirement.
5. A magnetic catch not to exceed 30 lbs. can serve to keep the pocket cover doors inthe closed position when the Won-Door FireGuard door is not in use. Positive latchessuch as hooks or throw bolts are not permitted because they prevent the Won-DoorFireGuard door from pushing the cover door open during operation.
6. A door frame is not required although one may be used. For aesthetic considerations,however, a “frame less” design may be preferable because it leaves only two slightreveals at the door edges and provides a less noticeable pocket door installation.
Pocket Depth Calculation Chart
Whenin the open position, pocket doors may not encroach on the 18” clear minimumOpening width required for the pocket.
Pocket Cover Door Detail
least 90 degrees
or
exceeds 2”
only if the cover door is unusual heavy would specialconsiderations need to be taken.
hen activated,
hinge such as a Stanley #314.
1-10 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Pocket Cover Door Details
Won-Door FireGuard
1
2
3
4
56
1. Pocket cover door by others.2. Spring-action hinge or continuous hinge
by others.3. Bumper (mounted on inside of pocket cover
door 3” above finished floor) by others.4. Magnetic catch (not to exceed 30 lbs.)
by others.5. Blocking for sliding jamb stops centered at
5” from face of pocket by others.6. Provide fire rated construction corresponding
to rating required for opening by others(1-hour construction shown).
2"
5"
MATERIAL: 3/4" HARDWOOD
1'-4"
3"10"3"
3/4" R
Specifier’snote
Bumpers must be specified when non-spring-action hinges are used. Add 1”to pocket depth to allow for bumper.
1-11Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
COVER DOOR BUMPER
Pocket Mounted Motor Operator AssemblyWiring Diagram
CONDUIT FROM SURFACE MOUNTED "J" BOX TOTHE KEY SWITCH WITH 5 CONDUCTOR LOWVOLTAGE STRANDED HOOK-UP WIRE. 22 GA.MIN., 14 GA. MAX. BY OTHERS.
T1 T2
AUXILIARY RELAYS: RL1, RL2 & RL3, PROVIDE FORM C, DRY CONTACTSNORMALLY CLOSED OR NORMALLY OPEN. THESE OPTIONAL RELAYS ARE USEDTO INDICATE TO A CENTRAL BUILDING ALARM SYSTEM IF THE DOOR IS INALARM AND OR FAULT MODE AND IF THE DOOR IS OPEN OR CLOSED.CONTACTS ARE RATED FOR 1 AMP 120 VOLTS. TERMINALS WILL ACCEPT 22 GA.TO 14 GA. WIRE.
2 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UPWIRE FROM ALARM SYSTEM TO CONTROL BOX22 GA. MIN., 14 GA. MAX. POWER LIMITED NOTSUPERVISED. RECOMMENDED MANUFACTURERALPHA, PART NO. 1172. CONDUIT & WIRE PER NECBY OTHERS.
3 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UP WIREFROM CONTROL BOX TO KEY SWITCH. 22 GA. MIN., 14 GA.MAX. BY OTHERS
2 CONDUCTOR LOW VOLTAGESTRANDED HOOK-UP WIRE FROMCONTROL BOX TO EXTERNAL HORN.22 GA. MIN., 14 GA. MAX. BY OTHERS
RL1 RL3RL2ALARM FAULT DOOR
STATUS
SMOKE DETECTOR OR FIRE ALARM,NORMALLY OPEN, DRY CONTACT.FORM C REQUIRED FROM INITIATINGSOURCE BY OTHERS.
ALARM INPUT
MOTOR DRIVEASSEMBLY
BATTERYBOX
A
A
3'-0
"
FOLDING FIRE PARTITIONBY WON-DOOR
OPTIONAL FIRE EXIT HARDWARETYPICAL ON BOTH SIDES OF THEDOOR BY WON-DOOR
CARDALARM+ALARM-COMIN+COMIN-COMOUT+COMOUT-
ALA
RM
FA
ULT
STA
TU
SNONCW
NONCW
NONCW
KCLOSEKOPEN
KCOMMHORN+HORN-
+ 12 VOLTS
MOTOR / DOOR CONNECTOR
HAND HELD REMOTECONNECTOR
HORN
8 AMP
30 AMP
24
”
15"
15"x24" BATTERY BOX TO BE SURFACE MOUNTED AT THE BACKOF THE POCKET 48" FROM THE FLOOR BY WON-DOOR.
A
FLEX CONDUIT BY OTHERS
COLOR CODED 2 CONDUCTORS WITH GROUND 120 VOLTSA.C. 60/50 HZ., 1.5 AMP STRANDED SUPERVISED LINE BYWON-DOOR. BLACK-HOT, WHITE-COMMON, GREEN-GROUND
4"x4" "J" BOX SURFACE MOUNTED AT THE CENTER OF THEPOCKET 12" ABOVE THE FINISHED FLOOR BY OTHERS.
120 VOLT A.C. WIRING INTO "J" BOX WIRINGAND CONDUIT BY OTHERS
4"x4" "J" BOX AND PLASTER RINGBY OTHERS
OPTIONALONLYKEY SWITCH MODULE ASSEMBLY.
REQUIRED WITH .(LOCATED WITHIN LINE OF SIGHT OF THE PARTITION.)
ACCESS CONTROL OPTIONS
3 AMPFUSE
LOWVOLTAGE WIRING
OUT OF
"J" BOX TOCONTROL BOX
120
VO
LT
A.C
.W
IRIN
GO
UT
OF
"J"
BO
XT
OC
ON
TR
OL
BO
X
(2) 4x4 "J" BOXESBY OTHERS
KCKRKL
+HORN-HORN
48”
12”
1 - 12 Won-D oor Corporat ion 1865 S. 3480 W. Sal t Lak e Ci ty, U T 84104 (800) 453-8494, January 1999
www.wondoor.com
PART 1 - GENERAL
PART 2 - PRODUCTS
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and specified
herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors,
blocking and trim shall be furnished and installed by other sections.B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section.[C. All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color shall be
selected by the architect.]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Fire doors shall be listed by Underwriters Laboratories for ratings as indicated, when tested in accordance
with the requirements of UL 10B and ASTM E-152.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and Submittals.B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show
installation details, layout, and electrical requirements.
1.05 DELIVERYA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb, and trim. Provide field dimensions for fabrication.
B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assureaccess to and proper clearance for motor operators.
C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the original positions.
1.07 WARRANTYA. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year
from the date of substantial completion.
2.01 MANUFACTURERA. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model [select one: 20, 60, 90, or
180] as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 FIRE RATINGA. Fire Doors shall be listed by Underwriters Laboratory as special purpose fire doors having a [select one: 20,
60, 90, or 180] minute fire-resistive rating in accordance with the requirements of UL 10B and ASTM E-152.
Supervise unloading and handling ofmaterials.
D. Store boxes flat (not more than three high) in dry area and protect from elements that may damagematerials. Replace damaged materials at no cost to the owner.
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
2-1Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
2.03 MATERIALSA. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no
pantographs or interconnections except at the lead-post.
(Note: at least one key switch required.)
B. Panels shall be formed of 24-gauge enamel coated steel V-grooved for strength and resilience. Panelsshall be connected by full height 24-gauge enamel coated steel hinges.
C. Suspension System: shall consist of two 14-gauge cold rolled steel (or .125 aluminum) tracks on 8" (.203)centers attached to the overhead structural support. Each lead post shall be suspended by a 8-wheel ballbearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearing roller.
D. Lead-posts: shall be of 24-gauge cold rolled steel and shall be connected by specially formed steel panels.An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operationand insure a tight fitting closure.
E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the firedoor to form a smoke and draft seal.
F. Hanging weight shall be 5.5 pounds per square foot.G. Automatic Closing System
Operation: closing system shall consist of an electronic control box, motor operator assembly and leadingedge obstruction detector. In case of fire, closing system shall be activated by the building's fire/smokedetection equipment and automatically close the Won-Door FireGuard doors. Motors shall be operated byDC power supplied from a 12-volt maintenance-free battery located in the electronic control box. Batteriesshall be continuously charged by the building's electrical service and be automatically maintained at capacity.Fire doors may be operated manually in either the conventional or emergency mode.Electronic control box shall house the microprocessor logic board, interconnect board, 12-voltmaintenance-free battery, power supply charger, and motor control relays. The microprocessor shall initiate aloud audible signal should any of the following conditions arise:
1. High or low AC voltage2. High or low DC voltage3. Drive train malfunction4. Limit switch malfunction5. Key switch malfunction6. ROM or RAM check-sum error
Motor Operator Assembly shall consist of a DC gear-motor, limit switch, drive sprocket and clutch. The motorshall drive the fire door by means of a chain attached to the stabilizer bar trolley. Motor operator assemblyshall be located within a one (1) hour fire rated enclosure.
H. Leading Edge Obstruction Detector: fire doors shall be equipped with a pressure sensitive leading edgesuch that each contact with an obstruction shall cause the door to stop and pause before attempting to re-close. Fire doors can be manually opened at any time by pushing against the leading edge.
I. Exit Hardware shall be located on both sides of each fire door. In emergency mode a slight pressure on thehardware will cause the door to open a minimum of 32 inches, pause for 3 seconds, then automaticallyclose. The hardware shall be field programmable to allow automatic opening distances of up to the entireopening width. In the conventional mode, the hardware is used to open the door and move it back into thestorage pocket.
OPTIONS[J. Vision Panel shall consist of frame and clear glass assembly with listings from Underwriters Laboratory up to
1½ hours.] (Note: required only in smoke barriers in Group I occupancies.)[K. A key switch module shall be provided.] (Note: required for doors with Large Door Motor Operators and doors
equipped with Access Control devices. See pg. 2-19 for details.)
ACCESS CONTROL/MONITORING OPTIONS[L. Level 1 Access Control. Exit hardware shall not respond when pressed until activated by signal from smoke
detector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-guagesteel sliding jamb and rigid Z-shaped jamb stops.]
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
2-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Won-Door FireGuard
www.wondoor.com
Brackets [ ] indicate specifier’s option.
Specifications FireGuard 20, 60, 90, 180
;specifier’snote
[M. Level 2 Access Control. An electromagnetic locking clutch shall be added to the motor operator assembly toprovide 400-500 pounds of resistance to opening.
(Note: at least one key-switch required.)[N. A Remote Control and Status Display PC Station shall continuously monitor the status and provide remote
operation of up to 120 Won-Door FireGuard assemblies.] (See pg. 2-18 for details.)
2.04 COLORColor shall be manufacturers standard #55 Platinum.
[Color shall be selected from manufacturer's optional colors at additional cost.][Color shall be selected by architect and field painted by others.]
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor within +/- 1/16"(.002) tolerance over the entire length of the
opening.
3.02 INSPECTIONA. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect, in
writing, of any unacceptable conditions.
3.03 INSTALLATIONA. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings.B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of
applicable codes and regulations.C. Upon completion of the installation, general contractor shall protect fire doors from damage and shall replace
or repair subsequent damage so that doors are acceptable to the architect at no additional cost to the owner.
manual Upgrades to the fire door for this level of accesscontrol shall include a heavy-guage steel sliding jamb, rigid Z-shaped jamb stops and 10-gauge steel tubereinforcement to the lead post.]
PART 3. EXECUTION
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
2-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Won-Door FireGuard
www.wondoor.com
Brackets [ ] indicate specifier’s option
Specifications FireGuard 20, 60, 90, 180
;specifier’snote
1. ½" dia. threaded rod with nuts and washers by others. (18" O.C. in opening, 12" O.C. in stack area)2. Three layers 3/4" x 18" plywood with staggered joints, glued and screwed together at 24" O.C. and
by others.[OR]½" x 18" steel plate.
3. Provide rated construction corresponding to rating required for opening by others.4. Motor operator assembly. May be mounted above or below header. (See motor mountings on
ELEVATIONS pg. 2-7)5. Minimum dimension required to meet U.L. labeling requirements. The dimension may be increased
to further recess the head condition if required.6. L-shaped trim piece of pre-finished off white color to match track by Won-Door. Provides transition
from the track to gypsum soffit.7. Three layers ½" x 3 5/8" gypsum board terminating 12" into pocket. All gypsum to be furnished,
finished, and field painted by others.8. 24" x 36" 1-hour fire-rated access door by others. Doors in excess of
900 sq. ft. require a 48" x 24" access door and an additional battery box. (See detail on pg. 2-7)9. 4 5/8” x 4¼” gypsum soffit by others.
twolayers 5/8" x 18" gypsum board screwed to plywood
for motor installation and service
Head DetailsStraight Doors
Won-Door FireGuard
STANDARD HEAD w/ POCKET MOUNTED MOTOR
CAD FILE: FGHD1
1
2
3
7
4
6
5
18"
3 1/4"
1
2
3
7
4
6
5
18"
3 1/4"
24”
4
8
1
2
3
9
5
18"
8
4
1
2
3
7
53 1/4"
STEEL HEAD W/ POCKET MOUNTED MOTOR
CAD FILE: FGHD2
LARGE DOOR MOTOR ABOVE HEAD
CAD FILE: FGHD3
LARGE DOOR MOTORCAD FILE: FGHD4
ABOVE 20' IN HEIGHT
6
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-4
1. ½” dia. threaded rod with nuts and washers by others. (18" O.C. in opening, 12"O.C. in stack area)
2. Three layers 3/4" x 18" plywood, two layers 5/8" x 5 1/2" plywood with staggeredjoints, glued and screwed together at 24" O.C. by others.
3. Provide rated construction corresponding to rating required for opening by others.4. Motor operator unit. (Mounted at back of pocket typical)5. Minimum dimension required to meet U.L. labeling requirements. The dimension
may be increased to further recess the head condition if required.6. L-shaped trim piece of pre-finished off white color to match track by Won-Door.
Provides transition from track to gypsum soffit.7. Three layers ½” x 3 5/8" gypsum board terminating 12" into pocket. All gypsum to
be furnished, finished, and field painted by others.8. Two layers 5/8" x 7" gypsum board furnished, finished, and field painted by others.9. Two layers 5/8" x 6 3/4" gypsum board furnished and finished, by others.
10. 24” x 36” 1-hour fire-rated access door for motor installation and service by others.Doors in excess of 900 sq. ft. require a 48" x 24" access door and an additionbattery box (see detail on pg. 2-7).
Head DetailsCurved Doors
Won-Door FireGuard
1
2
3
4
7
8 9
6
53 1/4"
18"
10
4
2
3
7 6
53 1/4"
1
8 9
18"
CURVED HEAD
CAD FILE: FGHD5
POCKET MOUNTED MOTORCURVED HEAD
CAD FILE: FGHD6
W/ LARGE DOOR MOTOR*
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Specifier’snote
Refer to on pg. 2-15.
* Large Door motor may also be mounted below header (see pg. 2-7).
Curved Door Guidelines
1. Exit Hardware.2. Sliding jamb assembly.3. Sliding jamb stops.4. Blocking by others.5. Pocket cover doors by others (optional).6. Provide rated construction corresponding
to rating required for opening by others.7. Recessed striker to be caulked by others.8. Surface mounted striker to be caulked by
others.9. Jamb attached with anchors by Won-Door.10. Concrete, masonry, or steel construction
2-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Specifier’snote
*To determine pocket depth, see theon
pg. 2-10 and on pg. 2-9.**For single parting doors without
pockets (detail at bottom left), determinethe Stack Depth by using the
on pg. 2-10then subtract 6”. For bi-parting doorswithout pockets (detail at bottom right),determine the Stack Depth from thebi-parting column of the
then subtract 6” fromStack Depth.
Pocket Depth Calculation ChartInstructions
PocketDepth Calculation Chart
Pocket DepthCalculation Charteach
1. Folding fire door.2. Ceiling line.3. Exit Hardware.4. Motor operator assembly.5. Control Box (must be located within 25 wire feet of the motor and within
a 1-hour fire rated enclosure). Typical locations shown above.6. Two 4x4 junction boxes mounted within 24” of the control box by others.7. Top of door track.8. Key switch (must be located within visibility of door operation).
Required for doors using Large Door motors and/or Access Control.9. fire rated access door
by others. Doors in excess of 900 sq. ft. require a 48" x 24" access doorand an additional battery box.
10. T
36" x 24" 1-hour for motor installation and service
wo 4x4 junction boxes surface mounted side-by-side on back wall ofpocket 12" above top of finished floor by others.
ElevationsSide Views
Won-Door FireGuard
STANDARD POCKET MOUNTED MOTORCAD FILE: FGEL1
LARGE DOOR MOTOR BELOW HEADERCAD FILE: FGEL2
LARGE DOOR MOTOR ABOVE HEADERCAD FILE: FGEL3
4
5
10
7
7
2
22
1
3
POCKET
8
9
5
4
6
POCKET3
1
8
4
9 5 6
1
3
POCKET
2-7Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
ElevationsFront Views
1. Sub floor (Concrete, etc.)2. Finished floor (Carpet, tile, etc.)3. Fabrication height / field dimension height taken from
top of track to top of finished floor.
Door Profile Widths:
Stacked Width: 13¾"Extended Width: 11½"
STRAIGHT DOORCAD FILE: FGEL4
CURVED DOORCAD FILE: FGEL5
Stacked Extended
Won-Door FireGuard
1 1
2 2
3 3
2-8 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
The term CLEAR OPENING WIDTH on the refers to the distance from thefront of the storage pocket to face of the striker. T
etermine the door’s CLEAR OPENING WIDTH, 2) find the appropriate range (, then 3) refer to the “SINGLE” (for single parting) column. Lastly, consult the OPTIONS EFFECTING
POCKET DEPTH below the chart to determine how optional equipment effects stack requirements.
: Pocket depth for FireGuard 60 door w/ (in the rangebetween 7’-9” and 8’-5”). Minimum pocket depth = ”
Pocket Depth Calculation Charto determine the pocket depth requirement of a door: 1)
d for that width FROM - TOcolumns)
Example below single parting 8'-4" clear opening33
Bi-part doors require two storage pockets. Instead of using the CLEAR OPENING WIDTH whenreferring to the stack chart, use of the CLEAR OPENING WIDTH (which is the distance from the front ofstorage pocket on one side to the center of the door opening),
For bi-parting doors,
: Pocket depth for FireGuard 60 b door with .Look up 7'-10" on stack chart (1/2 of 15'-8"). Min. pocket depth = 38" for
total1/2
then follow the same instructions listed in“single parting” (above) to determine the pocket depth requirement. a motor operatorcan be placed in each pocket to increase the maximum door size for a standard Pocket Mounted Motor. See
for details. For bi-parting, consult the factory.Automatic Closing System Selection Guide unequal
Example belowpocket.
i-Parting 15'-8" clear opening widtheach
Instructions for Using the Pocket Depth Calculation Chart
Single Parting Doors
Bi-Parting Doors
List of Options Effecting Pocket Depth:
Won-Door FireGuard
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Once you depth requirements using the chart ,have determined the appropriate on the next page consult thebelow the chart. Note that the chart only applies to standard Pocket Mounted
Motor Operators with the size limitations listed in the Largerdoors will require a Large Door Motor Operator which will effect pocket depth requirements. Optionalequipment such as the access control sliding jambs, vision panels, pocket cover door bumpers and multipleexit hardware will also effect pocket depth as will pocket cover doors in excess of 2” thick.
Options Effecting Pocket DepthAutomatic Closing System Selection Guide.
From: To : Single Bi-Part7’-9” 8’-5” 33” 38”8’-6” 9’-2” 35” 40”9’-3” 9’-11” 36” 41”
Clear Opening Width Pocket Depth
From: To : Single Bi-Part7’-9” 8’-5” 33” 38”8’-6” 9’-2” 35” 40”9’-3” 9’-11” 36” 41”
Clear Opening Width Pocket Depth
2-9
;specifier’snote For doors without pockets, see specifier’s note on page 2-6 for stack formula.calculation
OPTIONS EFFECTING POCKET DEPTH:Large Door Motor - below header
Pocket cover door
Vision panel
Pocket cover door bumperAdditional exit hardware
- Add 8” to pocket depth. (See pg. 2-7)
- A harts allow for 2" thick cover door. Add appropriate amount ifcover door and finish materials are thicker than 2". (See pg. 2-11)
- Add 5” to pocket depth (except when the vision panel is required to be closer tothe leading edge of the door than 48” on a straight door or 96” on a curved door.In these cases, contact the factory for details). (See pg. 2-17)
- Add 1” (See pg. 2-12).- Add 1" to pocket depth for each exit device (See page 2-16).
Access Control sliding jamb - Add 1" to pocket depth.bove c
The above charts are for standard Pocket Mounted Motor Operators only. See or size limitations.Large doors require Large Door Motor Operators.
Automatic Closing System Selection Guide f
Please consult the factory for pocket depth requirements of doors exceeding 30'-0" in width or 20'-0" in height.
Clear Opening Width Min. Pocket Depth*
Won-Door FireGuard
2-10 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
For doors inheight, if the MinimumPocket Depth shown onthe charts for the requiredwidth is than thatshown above use theappropriate value fromabove instead. If it is not,use the value shown onthe charts.
10’ inless
Height Single Bi-part
over 10’
less
height or
Pocket Cover Door Guidelines
Won-Door FireGuard
Pocket cover doors are not required, but may be used to aesthetically conceal Won-DoorFireGuard doors. When properly done, they add to the continuity of the project and provideanonymity to the installation.
Won-Door Corporation does not manufacture or install pocket cover doors. Therefore, theyshould be specified in a separate specification section. Unless specifically required by theAuthority Having Jurisdiction, pocket doors need not be fire-rated, but solid-core doors arepreferable for reasons of durability. The door thickness and covering material is at the discretionof the designer. Many covering materials have been successfully used including: plasticlaminates, wood veneers, vinyl, paint, bronze, stainless steel, and marble. If the aggregatethickness of the pocket cover door , however, the additional thickness must beadded to the calculation of the pocket depth (see on pg 2-10).
Some basic criteria for the successful design of pocket cover doors are listed below:1. Doors must be side hinge swinging and must swing at .
Designing “notches” on either side of thepocket opening to accommodate the cover door thickness will prevent this (see
on the following page).2. Cover doors must be operable with less than 50 lbs. of lateral force. As the Won-Door
FireGuard door is activated, the leading edge will make contact with the cover doorand push it open. 50 lbs. is the normal operating force required for egress-typeswinging doors and
3. W ocket cover doors should remain in the open position so as not toobstruct the path of the Won-Door FireGuard door when it is closing.
4. Won-Door recommends specifying either (1) a reverse-action spring hinge such asthe Hager #1257 to hold the cover door open when activated (2) a continuous
(1) The reverse-action spring in the Hager #1257 butt hinge makes thecover door self-opening rather than self-closing. Cover doors without spring-action hinges may swing back into the operating path of the Won-DoorFireGuard and cause damage or obstruct emergency operation.
(2) For aesthetic considerations, a continuous hinge is preferable because it notdoes protrude beyond the face of the pocket cover door and thereforepresents a “hingeless” appearance. When a continuous hinge is used,however, a “bumper” is required. The bumper prevents the pocket door fromswinging back into the operating path of the Won-Door FireGuard. Won-Door does not provide bumpers, but the design is shown on the next page.(See page 2-12) A bumper adds 1” to the pocket depth requirement.
5. A magnetic catch not to exceed 30 lbs. can serve to keep the pocket cover doors inthe closed position when the Won-Door FireGuard door is not in use. Positive latchessuch as hooks or throw bolts are not permitted because they prevent the Won-DoorFireGuard door from pushing the cover door open during operation.
6. A door frame is not required although one may be used. For aesthetic considerations,however, a “frame less” design may be preferable because it leaves only two slightreveals at the door edges and provides a less noticeable pocket door installation.
Pocket Depth Calculation Chart
Whenin the open position, pocket doors may not encroach on the 18” clear minimumopening width required for the pocket.
Pocket Cover Door Detail
least 90 degrees
or
exceeds 2”
only if the cover door is unusual heavy would specialconsiderations need to be taken.
hen activated, p
hinge such as a Stanley #314.
2-11Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
1
2
3
4
Pocket Cover Door Detail
56
1. Pocket cover door by others.2. Reverse-action spring hinge or continuous
hinge by others.3. Bumper (mounted on inside of pocket cover
door 3” above finished floor) by others.4. Magnetic catch (not to exceed 30 lbs.)
by others.5. Blocking for sliding jamb stops centered at
5” from face of pocket by others.6. Provide fire rated construction corresponding
to rating required for opening by others(1-hour construction shown).
MATERIAL: 3/4" HARDWOOD
1'-4"
3"10"3"
3/4" R
COVER DOOR BUMPER
2"
5"
Specifier’snote
Bumper must be specified when non-spring-action hinges are used. Add 1”to pocket depth to allow for bumper.
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-12
Won-Door FireGuard
Pocket Mounted Motor Operator AssemblyWiring Diagram
2-13Won-D oor Corporat ion 1865 S. 3480 W. Sal t Lak e Ci ty, U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CONDUIT FROM SURFACE MOUNTED "J" BOX TOTHE KEY SWITCH WITH 5 CONDUCTOR LOWVOLTAGE STRANDED HOOK-UP WIRE. 22 GA.MIN., 14 GA. MAX. BY OTHERS.
T1 T2
AUXILIARY RELAYS: RL1, RL2 & RL3, PROVIDE FORM C, DRY CONTACTSNORMALLY CLOSED OR NORMALLY OPEN. THESE OPTIONAL RELAYS ARE USEDTO INDICATE TO A CENTRAL BUILDING ALARM SYSTEM IF THE DOOR IS INALARM AND OR FAULT MODE AND IF THE DOOR IS OPEN OR CLOSED.CONTACTS ARE RATED FOR 1 AMP 120 VOLTS. TERMINALS WILL ACCEPT 22 GA.TO 14 GA. WIRE.
2 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UPWIRE FROM ALARM SYSTEM TO CONTROL BOX22 GA. MIN., 14 GA. MAX. POWER LIMITED NOTSUPERVISED. RECOMMENDED MANUFACTURERALPHA, PART NO. 1172. CONDUIT & WIRE PER NECBY OTHERS.
3 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UP WIREFROM CONTROL BOX TO KEY SWITCH. 22 GA. MIN., 14 GA.MAX. BY OTHERS
2 CONDUCTOR LOW VOLTAGESTRANDED HOOK-UP WIRE FROMCONTROL BOX TO EXTERNAL HORN.22 GA. MIN., 14 GA. MAX. BY OTHERS
RL1 RL3RL2ALARM FAULT DOOR
STATUS
SMOKE DETECTOR OR FIRE ALARM,NORMALLY OPEN, DRY CONTACT.FORM C REQUIRED FROM INITIATINGSOURCE BY OTHERS.
ALARM INPUT
MOTOR DRIVEASSEMBLY
BATTERYBOX
A
A
3'-0
"
FOLDING FIRE PARTITIONBY WON-DOOR
OPTIONAL FIRE EXIT HARDWARETYPICAL ON BOTH SIDES OF THEDOOR BY WON-DOOR
CARDALARM+ALARM-COMIN+COMIN-COMOUT+COMOUT-
ALA
RM
FA
ULT
STA
TU
SNONCW
NONCW
NONCW
KCLOSEKOPEN
KCOMMHORN+HORN-
+ 12 VOLTS
MOTOR / DOOR CONNECTOR
HAND HELD REMOTECONNECTOR
HORN
8 AMP
30 AMP
24
”
15"
15"x24" BATTERY BOX TO BE SURFACE MOUNTED AT THE BACKOF THE POCKET 48" FROM THE FLOOR BY WON-DOOR.
A
FLEX CONDUIT BY OTHERS
COLOR CODED 2 CONDUCTORS WITH GROUND 120 VOLTSA.C. 60/50 HZ., 1.5 AMP STRANDED SUPERVISED LINE BYWON-DOOR. BLACK-HOT, WHITE-COMMON, GREEN-GROUND
4"x4" "J" BOX SURFACE MOUNTED AT THE CENTER OF THEPOCKET 12" ABOVE THE FINISHED FLOOR BY OTHERS.
120 VOLT A.C. WIRING INTO "J" BOX WIRINGAND CONDUIT BY OTHERS
4"x4" "J" BOX AND PLASTER RINGBY OTHERS
OPTIONALONLYKEY SWITCH MODULE ASSEMBLY.
REQUIRED WITH .(LOCATED WITHIN LINE OF SIGHT OF THE PARTITION.)
ACCESS CONTROL OPTIONS
3 AMPFUSE
LOWVOLTAGE WIRING
OUT OF
"J" BOX TOCONTROL BOX
120
VO
LT
A.C
.W
IRIN
GO
UT
OF
"J"
BO
XT
OC
ON
TR
OL
BO
X
(2) 4x4 "J" BOXESBY OTHERS
KCKRKL
+HORN-HORN
48”
12”
TB3
SWC
DB
PH2
PH1TLS
J15
+-
CONTROL BOX(CONTROL BOX AND AUXILIARY BOX [IF NEEDED] MUST BELOCATED IN A ONE HOUR FIRE RATED ENCLOSURE AND WITHIN25 FT. [SEE SPECIFIER�S NOTE BELOW] OF THE MOTOR.)
KEYSWITCH WITH EXTERNAL HORN5 CONDUCTOR LOW VOLTAGE STANDARD HOOKUP.WIRE FROM 4" x 4" "J" BOX AT KEYSWITCH LOCATION,BY OTHERS.
ALARM INPUTSMOKE DETECTOR OR FIRE ALARM, NORMALLYOPEN, DRY CONTACT. REQUIRED FROM INITIATINGSOURCE BY ELECTRICAL CONTRACTOR.
DC CONNECTIONS2 CONDUCTOR LOW VOLTAGE STRANDEDHOOKUP WIRE FROM ALARM SYSTEM.0.165" O.D. (POWER LIMITED NOT SUPERVISED).RECOMMENDED MANUF. ALPHA, PART NO. 117222 GA. MIN., 14 GA. MAX.CONDUIT AND WIRE PER NEC BY ELECTRICALCONTRACTOR.
EXTERNAL HORN 2 CONDUCTOR LOW VOLTAGESTRANDED HOOKUP WIRE FROM WALL MOUNTEDHORN. 22 GA. MIN., 14 GA. MAX.WIRE BY ELECTRICAL CONTRACTOR TO MEET NECREQUIREMENTS.
2 CONDUCTOR WITH GROUND, 120 VOLTS A.C.60 / 50 HZ. 1.5 AMP. SUPERVISED LINE WITH CONDUITBY ELECTRICAL CONTRACTOR.
(NOTE: 2 CONDUCTOR WITH GROUND REQUIRED TOAUXILIARY BOX LOCATION.)
2 CONDUCTOR 8 GA. STRANDED MOTOR CABLE0.424" O.D. FOR 12 VDC 30 AMP FOR RUNS UNDER 25FEET. (RECOMMENDED MANUFACTURER, BELDON*PART NO. 9412)
PIGTAILCONNECTIONS:
WHITE - NEUTRALBLACK - HOTGREEN - GROUND
9 CONDUCTOR LOW VOLTAGE HOOKUP WIRE, 0.379"O.D.. RECOMMENDED MANUFACTURER BELDON,PART NO. 8469. POWER LIMITED SUPERVISION (MAYONLY BE FOR OPEN FAULTS). CONDUIT REQUIRED IFCONTROL BOX AND MOTOR ARE NOT IN SAMEENCLOSURE. CONDUIT TO BE BY ELECTRICALCONTRACTOR. WIRE PROVIDED BY WON-DOOR.
D.C. MOTOR DRIVE UNIT
CABLE LENGTH REFERRED TO IN THIS NOTE AREACTUAL CABLE LENGTHS NOT STRAIGHT LINEDISTANCES. IF CABLE LENGTH EXCEEDS 25 FEET,CONSULT FACTORY.
KC
KR
KL
HORN +HORN +
HORN -HORN -
DBHS
PHSWC+
FLTD
ALRDKL
KR
KC+-
CLUCL
LC
OP+13.8
TLS
-
3 AMPSLOBLO
HORN
ALARM
Specifier�snote
Won-D oor Corporat ion 1865 S. 3480 W. Sal t Lak e Ci ty, U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-14
(REQUIRED FOR DOORS EXCEEDING 900 SQ. FT.)
Wiring Diagram
Curved Door Guidelines
Won-Door FireGuard
2
3
1
9” 9"
18"
1. Center line of header. (Radius of curved track is determined bymeasuring the center line of the header).
2. Center line of inside track.3. Center line of outside track.
1. Standard curves are 5’ radius and 10’ radius (measured from the center lineof the header). Optional custom radii may be specified.
2. Templates of header radii are supplied to the field upon request.3. Maximum height for curved FireGuard doors is 23’.
;specifier’snote
2-15Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Multiple Exit Hardware
Won-Door FireGuard
Pocket
12
3
4
1. Exit Hardware (in sets, one on of the door, one side only).2. Finished floor.3. Ceiling line.4. Top of track.
1. Up to three (3) sets of Exit Hardware may be specified atany horizontal locations on the door (example above shows twosets in front of a bank of elevators). U
a field-programable distance.2. Add 1” to stack or pocket depth for each set of Exit Hardware.
each side or
he FireGuard door will open topon activation of the Exit
Hardware, t
Elevator Elevator
;specifier’snote
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-16
Vision Panel
Won-Door FireGuard
1. 1½-hour U.L. listed Vision Panel. Required only for smoke barrierapplications in group occupancies. Maximum size is shown above.
2. Exit Hardware.3. Ceiling Line.
Add 5” to pocket depth for vision panel ( when the visionpanel is required to be closer to the leading edge of thedoor on a straight door or 96” on a curved door. In these cases,contact the factory for details).
I
exceptthan 48”
POCKET
2 5/8"
1
2
3
;specifier’snote
2-17Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Remote Control and Status Display PC Station
Won-Door FireGuard
1. PC computer.2. Mouse.
The PC-based remote display provides central control and monitoring capabilities for upto120 fire doors. The display screen monitors current status of each door (closed,closing, open, opening, stopped, blocked, access using fire exit hardware, or locked),battery voltage, and AC line voltage. The remotely located PC allows all monitoredWon-Door FireGuard doors to be opened or closed from a central control station. Doorsequipped with optional magnetic locks may also be remotely locked or unlocked.Changes in door status are displayed on the monitor when doors are in fire mode or amalfunction is detected. The Remote Control and Status Display Station is a dedicatedPC for use with Won-Door Fireguard assemblies .only
1
2
;specifier’snote
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-18
Key Switch
Won-Door FireGuard
1. Key switch module. (a high-decibel horn is integrated when. the key switch is specified in Access Control or Large Door
Motor applications.2. Plaster ring by others.3. 4” x 4” x 2½” electrical box by others.
;specifier’snote
1
2
3
2-19Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Key switches are for all applications except: 1) thosewith Large Door motor operator assemblies and 2) those withAccess Control options. For safety reasons, a key switch must beinstalled in a location within line-of-sight of the operation of theWon-Door FireGuard door.
optional
Guidelines for Temperature Rise Doors
Won-Door FireGuard TR
3-1Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Won-Door FireGuard TR (temperature rise) doors have been tested in accordancewith the ASTM standard for for 90 minutes and have qualified for the“temperature rise” label because the monitored back-face (unexposed side)temperature did not exceed 250° during the first 30 minutes of the fire test.
1½ hour fire-rated temperature rise doors are required in all current model buildingcodes as opening protectives for door penetrations in exit stairway enclosures.
The 90TR model is limited to a maximum height of 12 and a maximum width of 30 -5 .
This section includes a Specification and a Pocket Depth Calculation Chart that applyspecifically to . All TR model head details, plan views,elevations, pocket details, pocket cover door details, wiring diagrams and
are identical to otherWon-Door FireGuard models. Refer to the details in Section 2 of this designmanual entitled “Won-Door FireGuard” (pages 2-4 through 2-9, 2-11 through 2-16, and2-18 through 2-20).
fire doors
door
' ' "
E-152
Won-Door FireGuard TRaccessories
(except for the vision panel which is not allowed in TR doors)
Won-Door FireGuard TR
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire DoorsSpecifications FireGuard 90TR
3-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
PART 1 - GENERAL
PART 2 - PRODUCTS
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and specified
herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors,
blocking and trim shall be furnished and installed by other sections.B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section.[C. All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color shall be
selected by the architect.]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Fire doors shall be listed by Underwriters Laboratories for ratings as indicated, when tested in accordance
with the requirements of UL 10B and ASTM E-152.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and Submittals.B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show
installation details, layout, and electrical requirements.
1.05 DELIVERYA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb, and trim. Provide field dimensions for fabrication.
B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assureaccess to and proper clearance for motor operators.
C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the original positions.
1.07 WARRANTYA. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year
from the date of substantial completion.
2.01 MANUFACTURERA. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model 90TR as manufactured by
Won-Door Corporation, Salt Lake City, Utah.
2.02 FIRE RATINGA. Fire Doors shall be listed by Underwriters Laboratory as special purpose temperature rise fire doors having a
90 minute fire-resistive rating in accordance with the requirements of UL 10B and ASTM E-152.
Supervise unloading and handling ofmaterials.
D. Store boxes flat (not more than three high) in dry area and protect from elements that may damagematerials. Replace damaged materials at no cost to the owner.
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
3-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2.03 MATERIALSA. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no
pantographs or interconnections except at the lead-post.
(Note: at least one key switch required.)
B. Panels shall be formed of 24-gauge enamel coated steel V-grooved for strength and resilience. Panelsshall be connected by full height 24-gauge enamel coated steel hinges.
C. Suspension System: shall consist of two 14-gauge cold rolled steel (or .125 aluminum) tracks on 8" (.203)centers attached to the overhead structural support. Each lead post shall be suspended by a 8-wheel ballbearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearing roller.
D. Lead-posts: shall be of 24-gauge cold rolled steel and shall be connected by specially formed steel panels.An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operationand insure a tight fitting closure.
E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the firedoor to form a smoke and draft seal.
F. Hanging weight shall be 6.5 pounds per square foot.G. Automatic Closing System
Operation: closing system shall consist of an electronic control box, motor operator assembly and leadingedge obstruction detector. In case of fire, closing system shall be activated by the building's fire/smokedetection equipment and automatically close the Won-Door FireGuard doors. Motors shall be operated byDC power supplied from a 12-volt maintenance-free battery located in the electronic control box. Batteriesshall be continuously charged by the building's electrical service and be automatically maintained at capacity.Fire doors may be operated manually in either the conventional or emergency mode.Electronic control box shall house the microprocessor logic board, interconnect board, 12-voltmaintenance-free battery, power supply charger, and motor control relays. The microprocessor shall initiate aloud audible signal should any of the following conditions arise:
1. High or low AC voltage2. High or low DC voltage3. Drive train malfunction4. Limit switch malfunction5. Key switch malfunction6. ROM or RAM check-sum error
Motor Operator Assembly shall consist of a DC gear-motor, limit switch, drive sprocket and clutch. The motorshall drive the fire door by means of a chain attached to the stabilizer bar trolley. Motor operator assemblyshall be located within a one (1) hour fire rated enclosure.
H. Leading Edge Obstruction Detector: fire doors shall be equipped with a pressure sensitive leading edgesuch that each contact with an obstruction shall cause the door to stop and pause before attempting to re-close. Fire doors can be manually opened at any time by pushing against the leading edge.
I. Exit Hardware shall be located on both sides of each fire door. In emergency mode a slight pressure on thehardware will cause the door to open a minimum of 32 inches, pause for 3 seconds, then automaticallyclose. The hardware shall be field programmable to allow automatic opening distances of up to the entireopening width. In the conventional mode, the hardware is used to open the door and move it back into thestorage pocket.
OPTIONS[J. A key switch module shall be provided.] (Note: required for doors with Large Door Motor Operators and doors
equipped with Access Control devices. See pg. 2-19 for details.)
ACCESS CONTROL/MONITORING OPTIONS[K. Level 1 Access Control. Exit hardware shall not respond when pressed until activated by signal from smoke
detector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-guagesteel sliding jamb and rigid Z-shaped jamb stops.]
SECTION 08370 - Horizontal Sliding, Accordion-Type Fire Doors
3-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
[L. Level 2 Access Control. An electromagnetic locking clutch shall be added to the motor operator assembly toprovide 400-500 pounds of resistance to opening.
(Note: at least one key-switch required.)[M. A Remote Control and Status Display PC Station shall continuously monitor the status and provide remote
operation of up to 120 Won-Door FireGuard assemblies.] (See pg. 2-18 for details.)
2.04 COLORColor shall be manufacturers standard #55 Platinum.
[Color shall be selected from manufacturer's optional colors at additional cost.][Color shall be selected by architect and field painted by others.]
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor within +/- 1/16"(.002) tolerance over the entire length of the
opening.
3.02 INSPECTIONA. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect, in
writing, of any unacceptable conditions.
3.03 INSTALLATIONA. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings.B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of
applicable codes and regulations.C. Upon completion of the installation, general contractor shall protect fire doors from damage and shall replace
or repair subsequent damage so that doors are acceptable to the architect at no additional cost to the owner.
manual Upgrades to the fire door for this level of accesscontrol shall include a heavy-guage steel sliding jamb, rigid Z-shaped jamb stops and 10-gauge steel tubereinforcement to the lead post.]
The term CLEAR OPENING WIDTH on the refers to the distance from thefront of the storage pocket to face of the striker. T
etermine the door’s CLEAR OPENING WIDTH, 2) find the appropriate range (, then 3) refer to the “SINGLE” (for single parting) column. Lastly, consult the OPTIONS EFFECTING
POCKET DEPTH below the chart to determine how optional equipment effects stack requirements.
: Pocket depth for FireGuard 90TR , door w/ (in therange between 8’-2” and 8’-11”). Minimum pocket depth = ”
Pocket Depth Calculation Charto determine the pocket depth requirement of a door: 1)
d for that width FROM - TOcolumns)
Example below straight single parting 8'-4" clear opening52
Bi-part doors require two storage pockets. Instead of using the CLEAR OPENING WIDTH whenreferring to the stack chart, use of the CLEAR OPENING WIDTH (which is the distance from the front ofstorage pocket on one side to the center of the door opening),
For bi-parting doors,
: Pocket depth for FireGuard 90TR b door with .Look up 7'-10" on stack chart (1/2 of 15'-8"). Min. pocket depth = 54” for
total1/2
then follow the same instructions listed in“single parting” (above) to determine the pocket depth requirement. a motor operatorcan be placed in each pocket to increase the maximum door size for a standard Pocket Mounted Motor. See
(pg. ) for details. For bi-parting, consult the factory.Automatic Closing System Selection Guide iv unequal
Example belowpocket.
i-parting 15'-8" clear opening widtheach
Instructions for Using the Pocket Depth Calculation Chart
Single Parting Doors
Bi-Parting Doors
List of Options Effecting Pocket Depth:
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Once you depth requirements using the chart ,have determined the appropriate on the next page consult thebelow the chart. Note that the chart only applies to standard Pocket Mounted
Motor Operators with the size limitations listed in the (pg. ).Larger doors will require a Large Door Motor Operator which will effect pocket depth requirements. Optionalequipment such as the access control sliding jambs, vision panels, pocket cover door bumpers and multipleexit hardware will also effect pocket depth as will pocket cover doors in excess of 2” thick.
Options Effecting Pocket DepthAutomatic Closing System Selection Guide iv
From: To : Single Bi-Part8’-2” 8’-11” 52” 57”9’-0” 9’-9” 55” 60”9’-10” 10’-8” 59” 64”
Clear Opening Width Pocket Depth
From: To : Single Bi-Part49” 54”
8’-2” 52” 57”9’-9” 55” 60”
Clear Opening Width Pocket Depth
Won-Door FireGuard TR
Please consult the factory for stacking requirements of doors exceeding 30’-5" in width or 12’-0" in height.
Pocket Depth Calculation Chart
STRAIGHT DOOR CURVED DOORClear Opening Width Min. Pocket Depth* Clear Opening Width Min. Pocket Depth*
Won-Door FireGuard TR
The above charts are for standard Pocket Mounted Motor Operators only. See for size limitations.Large doors require Large Door Motor Operators.
Automatic Closing System Selection Guide
OPTIONS EFFECTING POCKET DEPTH:Large Door Motor - below header -Access Control sliding jamb
Add 8” to pocket depth. (See pg. 2-7)- Add 1" to pocket depth.
bove cPocket cover door
Pocket cover door bumperAdditional exit hardware
- A hart allows for 2" thick cover door. Add appropriate amount ifcover door and finish materials are thicker than 2". (See pg. 2-11)
- Add 1” (See pg. 2-12).- Add 1" to pocket depth for each exit device (See page 2-16).
For doors inheight, if the MinimumPocket Depth shown onthe charts for the requiredwidth is than thatshown above use theappropriate value fromabove instead. If it is not,use the value shown onthe charts.
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all horizontal sliding, accordion-type moveable fire walls shown on the drawings and
specified herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors,
blocking and trim shall be furnished and installed by other sections.B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section.[C. All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color shall be
selected by the architect.]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Moveable Fire Walls shall be listed by Underwriters Laboratories for ratings as indicated, when tested in
accordance with the requirements of UL 263 and ASTM E-119.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and Submittals.
1.05 DELIVERY, STORAGE, AND HANDLINGA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb, and trim. Provide field dimensions for fabrication.
B. Permanent power shall be in-place and ready for final connection when moveable fire walls are erected.Assure access to and proper clearance for motor operators.
C. After testing the fire alarm system, automatic-closing moveable fire walls shall be reset to the originalpositions.
1.07 WARRANTYA. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year
from the date of substantial completion.
2.01 MANUFACTURERA. Horizontal sliding accordion-type moveable fire walls shall be Won-Door FireGuard model [select one:
MFW 1(1 hour), MFW 2 (2 hour)] as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 FIRE RATINGA. Moveable fire walls shall be listed by Underwriters Laboratory as unit partition panels having a [select one:
1 hour, 2 hour] fire-resistive rating in accordance with the requirements of UL 263 and ASTM E-119.
B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Showinstallation details, layout, and electrical requirements.
Supervise unloading and handling of thematerials..
D. Store boxes flat (not more than three high) in dry area and protect from elements that may damagematerials. Replace damaged materials at no cost to the owner.
2.03 MATERIALSA. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no
pantographs or interconnections except at the lead-post.
[I. A key switch module shall be provided.] (Note: required for doors with Large Door Motor Operators and doorsequipped with Access Control devices. See pg. 2-19 for details.)
[J. Level 1 Access Control. Exit hardware shall not respond when pressed until activated by signal from smokedetector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-guagesteel sliding jamb and rigid Z-shaped jamb stops.] (Note: at least one key switch required.)
[K. Level 2 Access Control. An electromagnetic locking clutch shall be added to the motor operator assembly toprovide 400-500 pounds of resistance to manual opening. Upgrades to the fire door for this level of accesscontrol shall include a heavy-guage steel sliding jamb, rigid Z-shaped jamb stops and 10-gauge steel tubereinforcement to the lead post.] (Note: at least one key-switch required.)
B. Panels shall be formed of 24-gauge enamel coated steel V-grooved for strength and resilience. Panels shallbe connected by full height 24-gauge enamel coated steel hinges.
C. Suspension System: shall consist of two 14-gauge cold rolled steel tracks on 8" (.203) centers attached tothe overhead structural support. Each lead post shall be suspended by a 8-wheel ball bearing trolley.Each panel shall be suspended by a steel hanger pin and a 1¼" diameter ball bearing roller.
D. Lead-posts: shall be of 24-gauge cold rolled steel and shall be connected by specially formed steel panels.An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operation andinsure a tight fitting closure.
E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the firedoor to form a smoke and draft seal.
F. Hanging weight shall be 6.5 pounds per square foot.G. Automatic Closing System
Operation: closing system shall consist of an electronic control box, motor operator assembly and leadingedge obstruction detector. In case of fire, closing system shall be activated by the building's fire/smokedetection equipment and automatically close the Won-Door FireGuard assemblies. Motors shall beoperated by DC power supplied from a 12-volt maintenance-free battery located in the electronic controlbox. Batteries shall be continuously charged by the building's electrical service and be automaticallymaintained at capacity. Moveable Fire Walls may be operated manually in either the conventional oremergency mode.Electronic control box shall house the microprocessor logic board, interconnect board, 12-voltmaintenance-free battery, power supply charger, and motor control relays. The microprocessor shall initiate aloud audible signal should any of the following conditions arise:
1. High or low AC voltage2. High or low DC voltage3. Drive train malfunction4. Limit switch malfunction5. Key switch malfunction6. ROM or RAM check-sum error
Motor Operator Assembly shall consist of a DC gear-motor, limit switch, drive sprocket and clutch. The motorshall drive the moveable fire wall by means of a chain attached to the stabilizer bar trolley. Motor operatorassembly shall be located within a one (1) hour fire rated enclosure.
H. Leading Edge Obstruction Detector: moveable fire walls shall be equipped with a pressure sensitive leadingedge such that each contact with an obstruction shall cause the door to stop and pause before attempting tore-close. Moveable Fire Walls can be manually opened at any time by pushing against the leading edge.
OPTIONS
ACCESS CONTROL/MONITORING OPTIONS
4-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
[L. A Remote Control and Status Display PC Station shall continuously monitor the status and provide remoteoperation of up to 120 Won-Door FireGuard assemblies.] (See pg. 2-18 for details.)
2.04 COLORColor shall be manufacturers standard #55 Platinum.[Color shall be selected from manufacturer's optional colors at additional cost.][Color shall be selected by architect and field painted by others.]
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor within +/- 1/16"(.002) tolerance over the entire length of the
opening.
3.02 INSPECTIONA. Inspect openings prepared for moveable fire walls and surrounding conditions. Immediately notify the
architect, in writing, of any unacceptable conditions.
3.03 INSTALLATIONA. Install moveable fire walls in accordance with manufacturer's instructions for clearance and fastenings.B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of
applicable codes and regulations.C. Upon completion of the installation, general contractor shall protect moveable fire walls from damage and
shall replace or repair subsequent damage so that doors are acceptable to the architect at no additional costto the owner.
PART 3. EXECUTION
4-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
1. ½” diameter threaded rod with nuts and bolts by others.(18” on center in opening, 12” on center in stack area)
2. Three layers ¾” x 20” plywood
3. Provide rated construction corresponding to rating required for opening by others.(1-hour rated shown)
4. Motor operator assembly. (Mounted below header at the back of the pocket. Seedetail on pg. 4-6.)
5. 3¼” represents the minimum dimension required to meet U. L. labelingrequirements. The dimension may be increased to further recess the headcondition if required.
6. L-shaped trim piece pre-finished off-white color to match track by Won-Door.Provides transition from track to gypsum soffit.
7. Three layers ½” x 3-5/8” gypsum board termination 12” into pocket. All gypsum tobe furnished and finished by others.
Three layers 5/8” x 20” gypsum board screwed to plywood byothers.
glued and screwed together with staggered joints at24” O. C. by others.
20”
5 3/4"5 3/4"
3 1/4"
5 3/8" 5 3/8"
1
2
3
4
5
67
4-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CAD FILE: MFWH1
;specifier’snote Maximum height is 9’-0”.allowable
Won-Door FireGuard MFW
Pocketed
Pocket Depth* Clear Opening**
1 4 3
6
5
32
4 1/16"
4 3/16"
5"
1. Sliding jamb assembly.2. Sliding jamb stops.3. Blocking by others.4. Pocket cover doors by others (optional). (See pg. 2-11 & 2-12.)5. Provide rated construction corresponding to rating required for
opening by others.6. Recessed striker to be caulked by others.
Plan View
CAD FILE: FGPL1
;specifier’snote * To determine appropriate pocket depth, refer to
on pg. 4-9.** Maximum Clear Opening width allowable is 20 -0 .
Pocket DepthCalculation Chart
' "
4-5Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Won-Door FireGuard MFW
CAD FILE: FGEL1
3
5
6
1
2
4POCKET
1. Moveable fire wall.2. Ceiling line.3. Standard Pocket Mounted motor operator assembly.4. Control box.5.
6. Top of door track.
Two 4x4 junction boxes surface mounted side-by-side on back wallof pocket 12” above top of finished floor.
ElevationsSide Views
4-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Won-Door FireGuard MFW
ElevationFront View
1. Finished floor (carpet, tile, etc.).2. Sub floor (concrete, etc.).3. Fabrication height / field dimension is height taken
from top of the track to top of finished floor.
1
2
3
4-7Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Won-Door FireGuard MFW
The term CLEAR OPENING WIDTH on the refers to the distance from thefront of the storage pocket to face of the striker (see example below). T
etermine the door’s CLEAR OPENING WIDTH, 2) find the appropriate range( , then 3) refer to the “SINGLE” (for single parting) column. Lastly, consult the
OPTIONS EFFECTING POCKET DEPTH below the chart to determine how optional equipment effects stackrequirements.
: Pocket depth for FireGuard MFW1 , door w/ (inthe range between 8’-2” and 8’-11”). Minimum pocket depth = ”
Pocket Depth Calculation Charto determine the pocket depth
requirement of a door: 1) d forthat width FROM - TO columns)
Example below straight single parting 8'-4" clear opening52
Instructions for Using the Pocket Depth Calculation Chart
Single Parting Doors(FireGuard MFW can be specified in single parting confirguration)only
List of Options Effecting Pocket Depth:Once you depth requirements using the chart ,have determined the appropriate on the next page consult the
below the chart. Note that the chart only applies to standard Pocket MountedMotor Operators. Optional equipment such as access control sliding jambs, pocket cover door bumpers, andpocket cover doors in excess of 2” thick will effect the pocket depth.
Options Effecting Pocket Depth
From: To: Single8’-2” 8’-11” 52”9’-0” 9’-9” 55”9’-10” 10’-8” 59”
Clear Opening Width Min. Pocket Depth
Won-Door FireGuard MFW
4-8 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
The above chart is for standard Pocket MountedMotor assemblies.
OPTIONS EFFECTING POCKET DEPTH:Access Control sliding jambPocket cover door and frame
- Add 1" to pocket depth.- Above chart allows for a 2” thick cover door. Add appropriate
amount if cover door and finish materials are thicker than 2”.(See pg. 4-10)
NOTE:Moveable Fire Walls are limited toa maximum length of 20’-0” andmaximum height of 9’-0”. Theyare not available in Bi-Parting orCurved configurations.
*
Won-Door FireGuard MFW
4-9Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Pocket cover doors are not required, but may be used to aesthetically conceal the Won-DoorFireGuard MFW (Moveable Fire Wall). When properly done, they add to the continuity of theproject and provide anonymity to the installation.
Won-Door Corporation does not manufacture or install pocket cover doors. Therefore, theyshould be specified in a separate specification section. Unless specifically required by theAuthority Having Jurisdiction, pocket doors need not be fire-rated, but solid-core doors arepreferable for reasons of durability. The door thickness and covering material is at the discretionof the designer. Many covering materials have been successfully used including: plasticlaminates, wood veneers, vinyl, paint, bronze, stainless steel, and marble. If the aggregatethickness of the pocket cover door , however, the additional thickness must beadded to the calculation of the pocket depth (see on pg. 4-9).
Some basic criteria for the successful design of pocket cover doors are listed below:1. Doors must be side hinge swinging and must swing at .
Designing “notches” on either side of thepocket opening to accommodate the cover door thickness will prevent this (see
on the following page).2. Cover doors must be operable with less than 50 lbs. of lateral force. As the Won-Door
moveable fire wall is activated, the leading edge will make contact with the cover doorand push it open. 50 lbs. is the normal operating force required for egress-typeswinging doors and
3. W ocket cover doors should remain in the open position so as not toobstruct the path of the moveable fire wall when it is closing.
4. Won-Door recommends specifying either (1) a reverse-action spring hinge such asThe Hager #1257 to hold the cover door open when activated (2) a continuous
(1) The reverse-action spring in the Hager #1257 butt hinge makes thecover door self-opening rather than self-closing. Cover doors without spring-action hinges may swing back into the operating path of the Won-DoorFireGuard and cause damage to the door or obstruct emergency operation.
(2) For aesthetic considerations, a continuous hinge is preferable because it notdoes protrude beyond the face of the pocket cover door and thereforepresents a “hingeless” appearance. When a continuous hinge is used,however, a “bumper” is required. The bumper prevents the pocket door fromswinging back into the operating path of the moveable fire wall.Won-Door does not provide bumpers, but the design is shown on the nextpage (see page 4-11). A bumper adds 1” to the pocket depth requirement.
5. A magnetic catch not to exceed 30 lbs. can serve to keep the pocket cover doors inthe closed position when the Won-Door FireGuard MFW is not in use. Positivelatches such as hooks or throw bolts are not permitted because they prevent themoveable fire wall from pushing the cover door open during operation.
6. A door frame is not required although one may be used. For aesthetic considerations,however, a “frame less” design may be preferable because it leaves only two slightreveals at the door edges and provides a less noticeable pocket door installation.
Pocket Depth Calculation Chart
Whenin the open position, pocket doors may not encroach on the 20” clear minimumopening width required for the pocket.
Pocket Cover Door Detail
least 90 degrees
or
exceeds 2”
only if the cover door is unusual heavy would specialconsiderations need to be taken.
hen activated, p
hinge such as a Stanley #314.
Won-Door FireGuard MFW
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
4-10
1
2
3
4
Pocket Cover Door Detail
56
1. Pocket cover door by others.2. Reverse-action spring hinge or continuous
hinge by others.3. Bumper (mounted on inside of pocket cover
door 3” above finished floor) by others.4. Magnetic catch (not to exceed 30 lbs.)
by others.5. Blocking for sliding jamb stops centered at
5” from face of pocket by others.6. Provide fire rated construction corresponding
to rating required for opening by others(1-hour construction shown).
MATERIAL: 3/4" HARDWOOD
1'-4"
3"10"3"
3/4" R
2"
5"
Specifier’snote
Bumpers must be specified when non-spring-action hinges are used. Add 1”to pocket depth to allow for bumper.
COVER DOOR BUMPER
Won-Door FireGuard MFW
4-11Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Pocket Mounted Motor Operator AssemblyWiring Diagram
Won-D oor Corporat ion 1865 S. 3480 W. Sal t Lak e Ci ty, U T 84104 (800) 453-8494, January 1999
www.wondoor.com
4-12
CONDUIT FROM SURFACE MOUNTED "J" BOX TOTHE KEY SWITCH WITH 5 CONDUCTOR LOWVOLTAGE STRANDED HOOK-UP WIRE. 22 GA.MIN., 14 GA. MAX. BY OTHERS.
T1 T2
AUXILIARY RELAYS: RL1, RL2 & RL3, PROVIDE FORM C, DRY CONTACTSNORMALLY CLOSED OR NORMALLY OPEN. THESE OPTIONAL RELAYS ARE USEDTO INDICATE TO A CENTRAL BUILDING ALARM SYSTEM IF THE DOOR IS INALARM AND OR FAULT MODE AND IF THE DOOR IS OPEN OR CLOSED.CONTACTS ARE RATED FOR 1 AMP 120 VOLTS. TERMINALS WILL ACCEPT 22 GA.TO 14 GA. WIRE.
2 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UPWIRE FROM ALARM SYSTEM TO CONTROL BOX22 GA. MIN., 14 GA. MAX. POWER LIMITED NOTSUPERVISED. RECOMMENDED MANUFACTURERALPHA, PART NO. 1172. CONDUIT & WIRE PER NECBY OTHERS.
3 CONDUCTOR LOW VOLTAGE STRANDED HOOK-UP WIREFROM CONTROL BOX TO KEY SWITCH. 22 GA. MIN., 14 GA.MAX. BY OTHERS
2 CONDUCTOR LOW VOLTAGESTRANDED HOOK-UP WIRE FROMCONTROL BOX TO EXTERNAL HORN.22 GA. MIN., 14 GA. MAX. BY OTHERS
RL1 RL3RL2ALARM FAULT DOOR
STATUS
SMOKE DETECTOR OR FIRE ALARM,NORMALLY OPEN, DRY CONTACT.FORM C REQUIRED FROM INITIATINGSOURCE BY OTHERS.
ALARM INPUT
MOTOR DRIVEASSEMBLY
BATTERYBOX
A
A
3'-0
"
FOLDING FIRE PARTITIONBY WON-DOOR
OPTIONAL FIRE EXIT HARDWARETYPICAL ON BOTH SIDES OF THEDOOR BY WON-DOOR
CARDALARM+ALARM-COMIN+COMIN-COMOUT+COMOUT-
ALA
RM
FA
ULT
STA
TU
SNONCW
NONCW
NONCW
KCLOSEKOPEN
KCOMMHORN+HORN-
+ 12 VOLTS
MOTOR / DOOR CONNECTOR
HAND HELD REMOTECONNECTOR
HORN
8 AMP
30 AMP
24
”
15"
15"x24" BATTERY BOX TO BE SURFACE MOUNTED AT THE BACKOF THE POCKET 48" FROM THE FLOOR BY WON-DOOR.
A
FLEX CONDUIT BY OTHERS
COLOR CODED 2 CONDUCTORS WITH GROUND 120 VOLTSA.C. 60/50 HZ., 1.5 AMP STRANDED SUPERVISED LINE BYWON-DOOR. BLACK-HOT, WHITE-COMMON, GREEN-GROUND
4"x4" "J" BOX SURFACE MOUNTED AT THE CENTER OF THEPOCKET 12" ABOVE THE FINISHED FLOOR BY OTHERS.
120 VOLT A.C. WIRING INTO "J" BOX WIRINGAND CONDUIT BY OTHERS
4"x4" "J" BOX AND PLASTER RINGBY OTHERS
OPTIONALONLYKEY SWITCH MODULE ASSEMBLY.
REQUIRED WITH .(LOCATED WITHIN LINE OF SIGHT OF THE PARTITION.)
ACCESS CONTROL OPTIONS
3 AMPFUSE
LOWVOLTAGE WIRING
OUT OF
"J" BOX TOCONTROL BOX
120
VO
LT
A.C
.W
IRIN
GO
UT
OF
"J"
BO
XT
OC
ON
TR
OL
BO
X
(2) 4x4 "J" BOXESBY OTHERS
KCKRKL
+HORN-HORN
48”
12”
PART 1 - GENERAL
PART 2 - PRODUCTS
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all accordion-type folding partitions shown on the drawings and specified herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, pocket doors, field painting, blocking and
wood trim as required shall be furnished and installed by other sections.
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained or authorized personnel.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and SubmittalsB. Indicate required stacking depth, pocket width, if applicable, and height of header above finished floor.
Show installation details and layout.
1.05 DELIVERY, STORAGE AND HANDLINGA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb and trim. Provide field dimensions for fabrication.
1.07 WARRANTYA. Materials shall be warranted against defects and workmanship for a period of one (1) year from the date of
substantial completion.
2.01 MANUFACTURERA. Folding partitions shall be DuraFlex as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 MATERIALSA. Operation: Shall be top supported and manually operated.B. Construction: Shall consist of a single accordion-type wall of panels suspended from a single overhead
track. Panels shall be connected by full height extruded vinyl hinges. Panels shall be formed of vinyl clad 24-gauge steel V-grooved for strength and resilience. Vinyl shall be permanently bonded to the face of thesteel panels with a heat and pressure process before the panels are formed.
C. Suspension system: Shall consist of a single extruded aluminum track attached to the overhead structuralsupport. Each panel shall be suspended by a 1" (.025) nylon-tired ball bearing roller. Each lead-post shall besuspended by a 4-wheel trolley.
D. Lead-posts: Shall be extruded aluminum and include standard grip-type handles and a sliding latch toeffect closure. [Key locks shall be provided.]
E. Perimeter Seals: Shall consist of continuous extruded vinyl sweep strips attached to the top and bottom ofthe partition. Leading edges of the lead-posts and receiver posts shall be cushioned by extruded vinylinterlocking seals.
F. Hanging weight shall be 1.9 pounds per square foot.
B. Supervise unloading and handling. Store boxes flat (not more than three high) in a dry area and protect fromelements that may damage materials. Replace damaged materials at no additional cost to the owner.
DuraFlexSpecifications
SECTION 10655 - Accordion Folding Partitions
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
2.03 COLORSA. Colors shall be selected by the architect from manufacturer's standard colors.
PART 3 - EXECUTION
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be in the dimensions specified, plumb, and level.B. Headers shall be leveled with the finished floor to within +/- 1/4" (.006) tolerance over the entire length of
the opening.
3.02 INSPECTIONA. Contractor shall inspect prepared opening and immediately notify the architect, in writing, of any
unacceptable conditions.
3.03 INSTALLATIONA. Install partitions in accordance with manufacturer's printed instructions.B. Upon completion of the installation, the General Contractor shall protect partitions from damage and
replace or repair subsequent damage so that partitions are acceptable to the architect, at no additionalcharge to the owner.
DuraFlexSpecifications
SECTION 10655 - Accordion Folding Partitions
5-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
1. 3/8" All thread rod with nuts and washers by others. (24" O.C. in opening,12" O.C. in stack area.)
2. Two (2) layers 3/4" x 6" x Continuous plywood to be parallel with floor withmaximum tolerance of ±1/4" by others.[OR]One number 1 grade 2"x 6" x continuous to be parallel with floor withmaximum tolerance of ±¼" by others.
3. Ceiling by others. (Ceiling not to be supported by Won-Door PVC Soffit.)4. 1¼" x 2 1/8 wood trim by others."
DuraFlexHead Details
STANDARD T-11 TRACKCAD FILE: DFHD1
T-09 TRACK W/ PVC SOFFITCAD FILE: DFHD2
T-01 TRACK W/ WOOD TRIMCAD FILE: DFHD3
3
2
1
3
2
1
1 1/8"3 1/4"
3
2
1
4
1 1/4"
6"
6"
6"
1¾"
1¾"
1¾"
1¾" 1¾"
1¾"
STRAIGHT PARTITIONS
CURVED* OR STRAIGHT PARTITIONS
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
;specifier’snote *Minimum radius for curved DuraFlex partition is 4 .'a
DuraFlexPlan Views
SINGLE PARTING W/ FIXED JAMB DFPL1*Stack Depth = (Opening in Feet x 1.5”/ft.) + 2.5"
BI-PARTING W/ FIXED JAMB DFPL2*Stack Depth = (½ Opening in Feet x 1.5”/ft.) + 2.5"
SINGLE PARTING POCKETED DFPL3*Pocket Depth = (Opening in Feet x 1.5”/ft.) + 3.5"
ROLLING POST POCKETED DFPL4*Pocket Depth = (½ Opening in Feet x 1.5”/ft.) + 6" + Pocket Door
thickness
1. Blocking by others.2. Aluminum striker by Won-Door.3. Sliding jamb by Won-Door.4. 1½" x 3" x continuous height wood jamb stop by others.5. Pocket cover door. Add thickness of door to pocket depth
calculations.
21 1
Stack Depth*
Opening
Stack Depth*
Opening
Pocket Depth* Opening
3
1
4 2
Pocket Depth* Opening
1
5 2
CAD FILE SHOWN IN ITALICS5-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
DuraFlexElevations
Side Views
1. Top of finished floor (carpet, tile, etc.)2. Bottom of header3. Soffit4. Sub floor (concrete, etc.)
SINGLE PARTINGCAD FILE: DSELSP
BI-PARTINGCAD FILE: DSELBP
1
2
3
1
3
4
4
2
Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
1. Ceiling by others (not to be supported by pvc soffit).2. Top of finished floor (carpet, tile, etc.).3. Fabrication height / field dimension height taken from
top of track to top of finished floor.4. Sub floor (concrete, etc.).
DuraFlexElevations
Front Views
T-01 TRACK W/ WOOD TRIMCAD FILE: DFELT09W
T-09 TRACK W/ PVC SOFFITCAD FILE: DFELT09
T-11 TRACKCAD FILE: DFELT11
3
1
2 4 2 4 2 4
1 1/4” 3 1/4" 1 1/8"
3
1
3
1
5-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Part 1 - GENERAL
PART 2 - PRODUCTS
A. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all accordion-type folding partitions shown on the drawings and specified herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, pocket doors, blocking and trim shall be
furnished and installed by other sections.[B. All electrical work including but not limited to the following electrical work by Electrical Section:
1. Provide 115/230 volt single phase (or electrical service in conduit to the reversingmagnetic starter.
2. Provide 115/230 volt single phase (or electrical service between the starter andthe gear motor.
3. Provide 4" X 4" electrical box for the key switch located within line-of-sight of the folding partition.4. Provide 3-conductor, 18-gauge stranded wire in conduit between the key switch and starter.5. Provide key switch for door operation (3 position switch, spring return to center from right or left).]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Sound rated partitions shall have the laboratory sound rating indicated, when tested in accordance with the
requirements of ASTM E-90.
1.04 SUBMITTALSA. Refer to Section 01300 - Shop drawings and Submittals.B. Indicate required stacking depth, pocket width (if applicable) and height of header above finished floor. Show
1.05 DELIVERY, STORAGE AND HANDLINGA. Deliver to job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation
of header, jamb and trim. Provide field dimensions for fabrication.
[C. Permanent power shall be in place for final connection when partitions are erected. Assure access to andproper clearance for motor operators.]
1.07 WARRANTYA. Materials shall be warranted against defects and workmanship for a period of one (1) year from the date of
substantial completion.
2.01 MANUFACTURERA. Folding partitions shall be DuraSound as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 MATERIALSA. Operation: Shall be top supported, and manually [electrically] operated.
208 volt, 3-phase A.C.)
208 volt, 3-phase A.C.)
B. Supervise unloading and handling. Store boxes flat (no more than three high) in a dry area and protect fromelements that may damage materials. Replace damaged materials at no additional cost to the owner.
DuraSoundSpecifications
SECTION 10655 - Accordion Folding Partitions
6-1Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
B. Construction: Shall consist of two parallel accordion-type walls of panels independently suspended with nopantographs or interconnections except at the lead-post.
C. Panels shall be formed of cold rolled vinyl-clad 24-gauge V-grooved steel. Vinyl shall be permanentlybonded by heat pressure lamination to the steel panel. Panels shall be connected by full height extrudedvinyl hinges.
D. Insulation: Interior surfaces of both walls shall be completely covered with a continuous blanket of 2 lb.density foil-backed fiberglass fastened in place with steel spring-clips.
E. Lead-posts: Shall be of 16-gauge cold rolled steel and shall be connected to the partition by specially formedsteel panels. Lead-post hardware shall include standard grip-type handles and sliding latch to effect closure.[Key locks shall be provided.]
F. Perimeter Seals: Shall consist of continuous extruded vinyl sweep strips attached to the top and bottom of thepartition. Leading edges of lead-posts and receiver posts shall be acoustically sealed by extruded vinylinterlocking seals.
G. Hanging weight shall be 4.2 pounds per square foot.
2.03 ACOUSTICAL PERFORMANCEA. Sound transmission class (STC) shall be [select one: STC 48, STC 43] when tested in accordance with
requirements of ASTM E-90.
2.04 COLORSA. Vinyl finish color shall be selected by the architect from manufacturer's standard colors.
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor to within +/- 1/4" (.006) tolerance over the entire length of the
opening.
3.02 INSPECTIONA. Contractor shall inspect prepared opening and immediately notify the architect, in writing, of unacceptable
conditions.
3.03 INSTALLATIONA. Install partitions in accordance with manufacturer's printed instructions.B. Upon completion of the installation, the General Contractor shall protect partitions from damage and replace
or repair subsequent damage so that partitions are acceptable to the architect, at no additional cost to theowner.
OPTIONS[H. Stabilizer Bar: Shall consist of a top supported, internally mounted diagonal brace connected to the lead-post
for proper alignment during operation and latching. (Requires 14" wide header.)][I. Motor operator
Operation: Motor-operated folding partitions shall be driven by means of a roller chain attached to thestabilizer bar trolley. An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignmentduring operation and insure a tight fitting closure without the use of mechanical latches. Motor OperatedAssembly: Shall consist of a 208 volt 3-phase A.C. gear motor],reversing electro-magnetic starter, and limit switch. Size of each motor shall be determined by manufacturerto insure proper operation.]
PART 3 - EXECUTION
115/230 volt single-phase A.C. Motor [or
6-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
1. Two layers 3/4" x 12" x continuous plywood, to be parallel with floor withmaximum tolerance of ±1/4" by others.
2. 3/8" all-thread rod with nuts and washers by others (24" O.C. in opening, 12"O.C. in stack area).
3. Ceiling by others (Ceiling not to be supported by Won-Door PVC Soffit).4. 1½ x 2 1/8 wood trim by others.5. Insulate as required for sound attenuation by others.
" "
1. Three layers 3/4" x 14" x continuous plywood, to be parallel with floor withmaximum tolerance of ±1/4" by others.
2. 3/8" all-thread rod with nuts and washers by others (24" O.C. in opening, 12"O.C. in stack area).
3. Ceiling by others (Ceiling not to be supported by Won-Door PVC Soffit).4. 1½ x 2 1/8 wood trim by others.5. Insulate as required for sound attenuation by others.
" "
DuraSoundHead Details
Straight DoorManual Operation
6-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
Standard T-11 TrackCAD FILE: DSHD1
1
T-09 Track w/ PVC SoffitCAD FILE: DSHD2
T-09 Track w/ Wood TrimCAD FILE: DSHD3
UNDER 14 IN HEIGHT' UNDER 14' IN HEIGHT UNDER 14' IN HEIGHT
2 225
3
3
3
4
4
T-09 Track w/ PVC SoffitCAD FILE: DSHD4
1 1
ABOVE 14' IN HEIGHT *
2 2
3
T-09 Track w/ Wood TrimCAD FILE: DSHD5
ABOVE 14' IN HEIGHT *
www.wondoor.com
12" 12" 12"
14"14"5¾"5¾" 5¾" 5¾"
4¾"4¾"4¾" 4¾" 4¾"4¾"
* Folding partitions greater than 14’ in height require an internal stabilizer bar to keepthe lead-post plumb during operation. In order to allow adequate space
for the stabilizer bar, a 14” wide header is required.within the
partition
;specifier’snote
5
5 5
1. Three layers 3/4" x 14" x continuous plywood, to be parallel with floor with maximumtolerance of ±1/4" by others.
2. 3/8" all-thread rod with nuts and washers by others (24" O.C. in opening, 12" O.C. instack area).
3. Ceiling by others (Ceiling not to be supported by Won-Door PVC Soffit).4. AC electric motor assembly (Motor can be mounted above or below header. See
pg. 6-10 for details about location.)5. 1½ x 2 1/8 wood trim by others.6. 24” X 24” access for installation and service of motor by others.7. Insulate as required for sound attenuation by others.
" "
DuraSoundHead Details
Straight DoorMotorized Operation
6-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
T-09 Track w/ pvc soffitCAD FILE: DSHD6
3
3
1
1
2
2
4
7
7
6
5¾"
5¾"
5¾"
5¾"
4
5
T-09 Track w/ wood trimCAD FILE: DSHD7
www.wondoor.com
14"
14"
1. Three layers 3/4" x 14" x continuousplywood, to be parallel with floor withmaximum tolerance of +/- 1/4" by others.
2. 3/8" all-thread rod with nuts and washersby others (24" O.C. in opening, 12" O.C.in stack area).
3. Ceiling by others.4. A.C. electric motor assembly. (Motor can
be mounted above or below head. Seepg. 6-10.)
5. 1¼” x 2 1/8” wood trim by others.6. (2) layers of 5/8 gypsum by others.7. 5/8” layer of gypsum furnished and
finished by others.8. (1) layer of 5/8” plywood by others.9. Insulate as required for sound attenuation
by others.10. 24” x 24” access for motor installation
and service by others.
"
DuraSoundHead Details
Curved DoorManual & Motorized
6-5Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
T-01 Track w/ wood trimManually Operated Under 14'-0" in Height
CAD FILE: DSHD8
1
2 6
4 5
3
1
63
5 7
8
10
2
4
9
4¾" 4¾"
T-01 Track w/ gyp. soffitMotorized
CAD FILE: DSHD9
1. Two layers ¾ x 12" x continuous plywood, to be parallel with floor with maximumtolerance of 1/4" by others.
2. 3/8" all-thread rod with nuts and washers by others (24" O.C. in opening, 12" O.C. instack area).
3. Ceiling by others.4. 1¼ x 2 1/8 wood trim by others.5. (2) layers of 5/8” gypsum furnished and finished by others.6. Insulate as required for sound attenuation by others.
"
" "
+
www.wondoor.com
12"
5¾"5¾"
14"
DuraSoundPlan Views
Doors Under 14'-0" in Height w/o PocketsManual Operation
Fixed Jamb
Rolling Post
SINGLE PARTING DSPL1*Stack Depth = (Opening in Feet x 1.75 /ft.) + 6""
BI-PARTING DSPL2*Stack Depth = (½ Opening in Feet x 1.75 /ft.) + 6""
SINGLE PARTING DSPL3*Stack Depth = (Opening in Feet x 1.75 /ft.) + 12""
BI-PARTING DSPL4*Stack Depth = (½ Opening in Feet x 1.75 /ft.) + 12""
1. Blocking by others.
6-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CAD FILE SHOWN IN ITALICS
1
1 1
1Stack Depth*
Stack Depth* Stack Depth*
Stack Depth*
Opening
Opening Opening
Opening
Opening
Stack Depth*1
Opening
Stack Depth*1
Opening
Stack Depth*
1
Opening
Stack Depth*
1 1
1
SINGLE PARTING DSPL5*Stack depth = (Opening in Feet x 1.75 /ft.) + 6""
BI-PARTING DSPL6*Stack depth = (½ Opening in Feet x 1.75 /ft.) + 6""
SINGLE PARTING DSPL7*Stack depth = (Opening in Feet x 1.75 /ft.) + 12" "
BI-PARTING DSPL8*Stack depth = (½ Opening in Feet x 1.75 /ft.) + 12""
Fixed Jamb
Rolling Post
1. Blocking by others.
DuraSoundPLAN VIEWS
;specifier’snote Doors over 14’ in height require an internal stabilizer bar assembly to keep
the lead post plumb during operation. A 14” wide header is required whichincreases the profile width of the door to 13¾” as shown above.
6-7Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CAD FILE SHOWN IN ITALICS
Doors over 14’ in Height w/o PocketsManual Operation
Opening
1 2
4
Pocket Depth* Pocket Depth*Pocket Depth* Opening
1 2
4
5
3
Opening
6
4Pocket Depth*
5 5
3 4
Pocket Depth* Opening Pocket Depth*
6
SINGLE PARTING DSPL9*Pocket Depth = (Opening in Feet x 1.75 /ft.) + 9""
BI-PARTING DSPL10*Pocket Depth = (½ Opening in Feet x 1.75 /ft.) + 9""
SINGLE PARTING DSPL11*Pocket Depth = (Opening in Feet x 1.75 /ft.) + 12""
BI-PARTING DSPL12*Pocket Depth = (½ Opening in Feet x 1.75 /ft.) + 12""
Sliding Jamb
Rolling Post
1. Sliding jamb by Won-Door. (Sliding jamb is supported by a trolley andslides forward against the jamb stops when the partition is extended.)
2.3. Blocking by others.4. Pocket door by others Add thickness
of pocket door to pocket depth calculation.5. Jamb striker by Won-Door.6. Rolling post.
1½" x 3" x continuous height wood jamb stops by others.
(Optional for doors with sliding jamb).
DuraSoundPlan Views
Manual Operation w/ PocketsAll Heights
6-8 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CAD FILE SHOWN IN ITALICS
OpeningStack Depth*
3
33
3
OpeningPocket Depth*
12
4
Pocket Depth*
SINGLE PARTING DSPL13*Stack Depth = (Opening in Feet x 1.75 /ft.) + 6""
BI-PARTING DSPL14*Stack Depth = (½ Opening in Feet x 1.75 /ft.) + 6""
SINGLE PARTING DSPL15*Pocket Depth = (Opening in Feet x 1.75 /ft.) + 9""
BI-PARTING DSPL16*Pocket Depth = (½ Opening in Feet x 1.75 /ft.) + 9""
Pocketed
1. Sliding jamb by Won-Door. (Sliding jamb is supported by a trolley andslides forward against the jamb stops when the partition is extended.)
2.3. Blocking by others.4. Pocket door by others Add thickness of door to pocket depth
calculation.5. Jamb striker by Won-Door.
1½" x 3" x continuous height wood jamb stops by others.
(Optional).
DuraSoundPLAN VIEWSMotorized Operation
OpeningPocket Depth*
12
4
3
2 7/8"
5
OpeningStack Depth*
3 2 7/8"
5
6-9Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
CAD FILE SHOWN IN ITALICS
1. Top of finished floor (carpet, tile, etc.).2. Ceiling line.3.4. Sub floor (concrete, etc.).5. A. C. motor operator by Won-Door.
(Motor may be located above or belowheader.)
6. 3'x2' access by others.7. Key switch by others (must be located
within line-of-sight of door operation).
Bottom of header.
DuraSoundElevations
Side Views
SINGLE PARTING
CAD FILE: DSELSP
BI-PARTING
CAD FILE: DSELBP
SINGLE PARTINGMotor Operated - Fixed Jamb Motor Operated - Pocketed
CAD FILE: DSELSPAC
SINGLE PARTING
CAD FILE: DSELSPAC2
2
33
7 7
4
1
2
4
1
1
1
22
33
44
5 5
6 6
;specifier’snote For motorized bi-parting doors, a motor operator is located at one end
only (typically above the stack end or pocketed end of the door). For motorizedbi-parting doors, motor operators are required at both ends.un-equal
6-10 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Pocket
ManualManual
DuraSoundElevations
Front Views
Std. T-11 TrackCAD FILE: DSELT11
1T-09 Track W/ Soffit
CAD FILE: DSELT09T-01 Track W/ Wood Trim
CAD FILE: DSELT01
2
3
4
1
2
3
4
1
2
3
4
1. Sub-floor (concrete, etc.)2. Top of finished floor. (carpet, tile, etc.)3. Ceiling by others.4. Header by others.5. Wood trim and drywall by others.
All motorized doors and manual doors above 14'-0" inheight (see on pg. 6-7):
Stacked Width: 13¾"Extended Width: 11½"
specifier’s noteStacked Extended
5
6-11Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
;specifier’snote
* Fabrication height is from top oftracks to top of finished floor.
DuraSoundCurved Door Guidelines
6-12 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2
3
1
12"
6"6" 6"
6"
1. Center line of header. (Radius of curved track is determined bymeasuring the center line of the header).
2. Center line of inside track.3. Center line of outside track.
1. Minimum standard radius is 4’ (measured from the center line of the header).Any custom radius greater than 4’ may be specified.
2. Templates of header radii are supplied to the field upon request.3. Refer to head detail for manually operated door on pg. 6-5.
;specifier’snote
Manually Operated Under 14'
DuraSoundCurved Door Guidelines
2
1
14"
7"7" 7" 7"
1. Center line of header. (Radius of curved track is determined bymeasuring the center line of the header).
2. Center line of inside track.3. Center line of outside track.
1. Minimum standard radius is 4’ (measured from the center line of the header).Any custom radius greater than 4 may be specified.
2. Templates of header radii are supplied to the field upon request.3. Maximum height for curved DuraSound partition is 23 .4. Refer to head detail for motor operated door on pg. 6-5.
'
'
;specifier’snote
Motorized & Manually Operated Over 14'
6-13Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
DuraSoundConfiguration Options
2-Way Meeting
6-14 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2-WAY, 90° MEETING
2-WAY, INTERMEDIATE
4½"
STACK*
;specifier’snote *Meeting post stacks in the direction indicated by the arrow. Allow for an additional
amount of stack depth for the meeting post (4” for 90 Meeting and 4½” for Intermediate).°
4-WAY MEETING
3-WAY MEETING
DuraSoundConfiguration Options
3-Way and 4-Way Meeting
6-15Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
2½"
;specifier’snote *Meeting post may stack in either direction shown. Allow for an additional 2½”
of stack depth for the meeting post.
DuraSoundMotor Operator Wiring Diagram
6-16 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
A.C. MOTOR DRIVE UNIT
REVERSING
MAGNETIC
STARTER
TYPICAL CONTROL SCHEMATIC
1 2 3 4 5 6 987 10
11
12
13
FWD REV OL
WIRE DUCT
T1
COVER PLATE & KEY SWITCH ASSEMBLY BYOTHERS (LOCATED WITHIN LINE OF SIGHT OFPARTITION)
SIGHT OF PARTITION.
115 VOLT, SINGLE PHASE W/ GROUND
CONTRACTOR
4" x 4" "J" BOX WITH PLASTER RING BYELECTRICAL CONTRACTOR
NOTE: ALL WIRING, CONDUIT, FITTINGS, ETC. MUSTCONFORM TO NEC, JIC INDUSTRIAL CODE &APPLICABLE LOCAL CODES. ALL CONDUITS &CONDUCTORS BY ELECTRICAL CONTRACTOR
3 CONDUCTOR, 14 GA. MAXIMUM & 18 GA. MINIMUM24 VOLT A.C., CONDUIT & WIRE BY ELECTRICAL CONTRACTOR
PART 1- GENERAL
PART 2- PRODUCTS
1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all accordion-type folding partitions shown on the drawing and specified herein.
1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, pocket doors, field painting, blocking and
wood trim as required shall be furnished and installed by other sections.[B. All electrical work including but not limited to the following electrical work by Electrical Section:
1. Provide 115 / 230 volt single phase (or A.C.) electrical service in conduit to thereversing magnetic starter.
2. Provide 115 / 230 volt single phase (or A.C.) electrical service in conduit between thestarter and the gear motor.
3. Provide 4"x4" electrical box for the key switch located within line-of-sight of the folding partition.4. Provide 3-conductor, 18 gauge stranded wire in conduit between the key switch and starter.5. Provide key switch for door operation (3 position switch, spring return to center from right or left).]
1.03 QUALITY ASSURANCEA. Installation shall be accomplished by factory trained personnel.B. Sound rated partitions shall have the laboratory sound rating indicated, when tested in accordance with the
requirements of ASTM E-90.
1.04 SUBMITTALSA. Refer to Section 01300-Shop drawings and SubmittalsB. Indicate required stacking depth, pocket width, if applicable, and height of header above finished floor.
Show installation details and layout [and electrical requirements].
1.05 DELIVERY, STORAGE AND HANDLINGA. Deliver to the job site in manufacturer's original, unopened package.
1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of the section. Assure accurate installation
of header, jamb and trim. Provide field dimensions for fabrication.
[C. Permanent power shall be in place for final connection when partitions are erected. Assure access to andproper clearance for motor operations.]
1.07 WARRANTYA. Materials shall be warranted against defects and workmanship for a period of one (1) year from date of
substantial completion.
2.01 MANUFACTURERA. Folding partitions shall be DuraSound XL as manufactured by Won-Door Corporation, Salt Lake City, Utah.
2.02 MATERIALSA. Operation: Shall be top supported and manually [electrically] operated.B. Construction: Shall consist of two parallel, accordion-type walls of panels independently suspended with no
pantographs or interconnections except at the lead-post.
208 volt, 3-phase
208 volt, 3-phase
B. Supervise unloading and handling. Store boxes flat (not more than three high) in a dry area and protect fromelements that may damage materials. Replace damaged materials at no additional cost to the owner.
DuraSound XLSpecifications
SECTION 10655 - Accordion Folding Partitions
7-1Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
C. Panels shall be formed of cold rolled vinyl-clad 24 gauge V-grooved steel. Vinyl shall be permanently bondedby heat pressure lamination to the steel panels. Panels shall be connected by full height extruded vinylhinges.
D. Insulation: interior surfaces of both walls shall be completely covered with a continuous blanket of two (2)pounds density foil-backed fiberglass fastened in place with steel spring-clips.
E. Suspension systems: Shall consist of two extruded aluminum tracks spaced 12" (.305) on center attached tothe overhead structural support. Each panel shall be suspended by a steel hanger pin and a pair of 1½”(.038) diameter nylon-tired ball bearing rollers. Each lead-post shall be suspended by a 8-wheel ball bearingtrolley.
F. Leadpost: Shall be of 16 gauge cold rolled steel and shall be connected to the partition by specially formedsteel panels. Lead-post hardware shall include standard grip-type handles and a sliding latch to effectclosure. [Key locks shall be provided.]
G. Perimeter Seals: Shall consist of continuous extruded vinyl sweep strips attached to the top and bottom ofthe partition. Leading edges of the lead-posts and receiver posts shall be acoustically sealed by extrudedvinyl interlocking seals.
H. Hanging weight shall be 4.5 pounds per square foot.I. Stabilizer Bar: Shall consist of a internal diagonal bracing member that insures proper
alignment and latching of the leadpost during operation.
2.03 ACOUSTICAL PERFORMANCEA. Sound transmission class (STC) shall be 48 when tested in accordance with requirements of ASTM E-90.
2.04 COLORSA. Vinyl finish color shall be selected by the architect from manufacturer's standard colors (M-885 White or
[2.05 MOTOR OPERATORA. Operation: Motor-operated folding partition shall be driven by means of a roller chain attached to the
stabilizer bar trolley. An internally mounted stabilizer shall keep lead-posts plumb and in proper alignmentduring operation and insure a tight fitting closure without the use of mechanical latches.
B. Motor Operator Assembly: Shall consist of a 208 volt 3 phase A.C. gear motor, [115 / 230 volt single-phaseA.C. motor,] reversing electro-magnetic starter, limit switch and key switch. Size of each motor shall bedetermined by manufacturer to insure proper operation.]
3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be leveled with the finished floor to within +/- 1/4" (.006) tolerance over the entire length of the
openings.
3.02 INSPECTIONA. Contractor shall inspect prepared opening and immediately notify the architect, in writing, of any unacceptable
conditions.
3.03 INSTALLATIONA. Install partitions in accordance with manufacturer's printed instruction.B. Upon completion of the installation, the General Contractor shall protect partitions from damage and replace
or repair subsequent damage so that partitions are acceptable to the architect, at no additional charge to theowner.
ML-745 Teak).
PART 3-EXECUTION
top supported
DuraSound XLSpecifications
SECTION 10655 - Accordion Folding Partitions
7-2 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
1. 3/8" All-thread rod with nuts and washers by others (24" O.C. in opening, 12" O.C.in stack area).
2. Two (2) layers 3/4" x 24" x continuous plywood, to be parallel with floor withmaximum tolerance of ±1/4" by others. (Three (3) layers required if over 14'-0" inheight)
3. Insulate as required for sound attenuation by others.4. Ceiling by others (ceiling not to be attached to Won-Door PVC Soffit).5. PVC Soffit by Won-Door.6. 4 3/8 x continuous wood trim by others.7. Motor operator assembly (Can be mounted above or below header).8. Wood blocking by others.9. 5/8" x 24" x continuous gypsum board attached to plywood with screws - furnished,
finished and installed by others.10. 24” X 24” access for motor installation and service by others.
"
DuraSound XLHead Details
STRAIGHT - MANUAL w/ pvc soffitCAD FILE:XLHD1
4
STRAIGHT - MANUAL w/ wood trimCAD FILE:XLHD2
5
3
4
3
8
46
6
10
CURVED - MOTORIZEDCAD FILE:XLHD4
STRAIGHT - MOTORIZEDCAD FILE:XLHD3
4
10
24"
24" 24"
24"
9 7/16" 9 7/16"9 7/16"9 7/16"
9 7/16" 9 7/16" 9 7/16" 9 7/16"
7-3Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
DuraSound XLPlan Views
SINGLE PARTING XLPL1*Stack Depth = (Opening in Feet x .875 /ft.) + 8”"
BI-PARTING XLPL2*Stack Depth = (½ Opening in Feet x .875 /ft.) + 8""
SINGLE PARTING XLPL3*Pocket Depth = (Opening in Feet x .875 /ft.) + 11""
Sliding Jamb
1. Blocking by others.
Fixed Jamb
1. Blocking by others.2. Optional pocket cover door. Add thickness of door to pocket
depth.3. Sliding jamb (Sliding jamb is supported by a trolley and slides
forward against the jamb stops when the partition is extended.)4. 1½" x 3" wood jamb stops by others.
Opening
Stack Depth*
2 7/8"
1
1
1
1
1
Opening
Stack Depth* Stack Depth*
1
OpeningPocket Depth*
4
22 7/8"
3
CAD FILE SHOWN IN ITALICS
7-4 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
1. Top of finished floor (carpet,tile, etc.)
2. Bottom of header3. Soffit4. Subfloor (concrete, etc.)
1. Top of finished floor (carpet, tile, etc.)2. Bottom of header3. Soffit4. Subfloor (concrete, etc.)
1. Top of finished floor (carpet, tile, etc.).2. Bottom of header.3. Soffit.4. Sub floor (concrete, etc.)5. A.C. motor operator assembly.6. 3'x2' removable access panel by others.7. Key switch by others.
mFor bi-parting doors, a otor operator istypically located at one end only. Forbi-parting doors, motor operators are requiredat both ends.
un-equal
DuraSound XLElevations
Side Views
SINGLE PARTINGCAD FILE: DSELSP
4
1
2
3
BI-PARTINGCAD FILE: DSELBP
4
1
2
3
SINGLE PARTING W/ MOTORCAD FILE: DSELSPAC
4
1
7
2
3
5
6
;specifier’snote
7-5Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
1. Sub-floor (concrete, etc.).2. Top of finished floor (carpet, tile, etc.).3. Ceiling by others (not to be supported by Won-Door
PVC soffit).4. Fabrication height / field dimension height taken from
top of track to top of finished floor.5. Wood header by others (see pg. 7-3 for details).
DuraSound XLElevations
Front Views
T-08 TRACK w/ pvc soffitCAD FILE: XLELT08
3
2
11
3
T-08 TRACK w/ wood trimCAD FILE: XLELT08W
Door Profile Widths:
Stacked Width: 23 ¾”Extended Width: 14”
Stacked Extended
5½" 4¼"
2
4
5 5
4
7-6 Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
Motor Operator Wiring Diagram
DuraSound XL
7-7Won-Door Corpora t ion 1865 S . 3 4 8 0 W . Sal t Lake C i t y , U T 84104 (800) 453-8494, January 1999
www.wondoor.com
A.C. MOTOR DRIVE UNIT
REVERSING
MAGNETIC
STARTER
TYPICAL CONTROL SCHEMATIC
1 2 3 4 5 6 987 10
11
12
13
FWD REV OL
WIRE DUCT
T1
COVER PLATE & KEY SWITCH ASSEMBLY BYOTHERS (LOCATED WITHIN LINE OF SIGHT OFPARTITION)
SIGHT OF PARTITION.
115 VOLT, SINGLE PHASE W/ GROUND
CONTRACTOR
4" x 4" "J" BOX WITH PLASTER RING BYELECTRICAL CONTRACTOR
NOTE: ALL WIRING, CONDUIT, FITTINGS, ETC. MUSTCONFORM TO NEC, JIC INDUSTRIAL CODE &APPLICABLE LOCAL CODES. ALL CONDUITS &CONDUCTORS BY ELECTRICAL CONTRACTOR