CO2
CO
H
HS
NO2
S
TH
TS
T
MS
T LV
CHWS
CWV
CA
CD
CDR
CWR
CWS
CW
F-CW
H-CW
S-CW
HW
HW 140°
HW-R
HW-R 140°
GV
GW
HWR
HWS
G
OV
OW
PD
V
SS
SHWR
SHWS
STM
SD
OSD
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRCULATION
HOT WATER RECIRCULATION 140°
GREASE VENT
GREASE WASTE
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
STEAM
STORM DRAINAGE
OVERFLOW STORM DRAINAGE
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION2"
CAP
PLUG
2"
4"
4" 4"
REF-HG REFRIGERANT-HOT GAS
MECHANICAL PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF DETAIL SHEET OR EQUIPMENT NUMBERNUMBER OF DETAIL OR EQUIPMENT TYPE
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISEPIPE DROP
PIPE TEE REDUCING 45 DEGREE TEE45 DEGREE TEE
?
----
* NOTE *ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
TYPE (SEE SCHEDULE) NUMBER OF SLOTS /ACTIVE SLOT LENGTH (PLENUM LENGTH) / NECK SIZE
DUCT BEING DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GE/A GREASE EXHAUST AIR16"Ø GE/A
SE/A SMOKE EXHAUST AIR16"Ø SE/A
FLUE EXHAUST GAS FLUE16"Ø FLUE
C/A COMBUSTION AIR16"Ø C/A
S-O/A CONDITIONED OUTSIDE AIR16"Ø S-O/A
Ø ROUNDABV ABOVEAD AREA DRAINADD ADDENDUMAFF ABOVE FINISHED FLOORAFUE ANNUAL FUEL UTILIZATION EFFICIENCYALT ALTERNATEAP ACCESS PANELARCH ARCHITECT/ARCHITECTURALBFF BELOW FINISHED FLOORBLW BELOWBTU BRITISH THERMAL UNITSBTUH BRITISH THERMAL UNITS PER HOURCA COMBUSTION AIRCAP CAPACITYCB CATCH BASINCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCO CLEAN OUTCW COLD WATERDB DRY BULBDIA DIAMETERDN DOWNEA EACHEA EXHAUST AIRE/A EXHAUST AIREAT ENTERING AIR TEMPERATUREEG EXHAUST GRILLEELEC ELECTRICALEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXIST EXISTINGF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFD FIRE DAMPERFG FLUE GASFL FLOORFO FUEL OILFOV FUEL OIL VENTFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFPM FEET PER MINUTEFS FLOOR SINKFT FOOT/FEETFTR FIN TUBE RADIATIONGAL GALLONGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGW GREASE WASTEHB HOSE BIBHP HORSE POWERHTG HEATINGHTR HEATERHW HOT WATERIN INCHINV INVERTLB POUNDLB/HR POUNDS PER HOURLAT LEAVING AIR TEMPERATURELD LINEAR DIFFUSERLP LOW PRESSURELPG LIQUEFIED PETROLEUM GAS
LV LOUVERLWT LEAVING WATER TEMPERATUREM/A MIXED AIRMAX MAXIMUMMBH ONE THOUSAND BTU PER HOURMOD MOTORIZED OPERATED DAMPERMECH MECHANICALMFR MANUFACTURERMIN MINIMUMMISC MISCELLANEOUSMTR MOTORMU/A MAKE-UP/AIRNC NOISE CRITERIANC NORMALLY CLOSEDNIC NOT IN CONTRACTNK NECKNO NUMBERNO NORMALLY OPENNTS NOT TO SCALEOA OUTSIDE AIRO/A OUTSIDE AIRPD PRESSURE DROPPLBG PLUMBINGPRESS PRESSUREPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIG POUNDS PER SQUARE INCH GAUGEPWR POWERR/A RETURN AIRRCP RADIANT CEILING PANELRD ROOF DRAINREC RECESSEDRED REDUCERRG RETURN GRILLERH RELATIVE HUMIDITYRL/A RELIEF AIRRM ROOMRPM REVOLUTIONS PER MINUTERW RAIN WATERSF SQUARE FOOTSA SUPPLY AIRS/A SUPPLY AIRSAN SANITARYSF SQUARE FOOTSD SUPPLY DIFFUSERSDA SMOKE DAMPERSM SURFACE MOUNTSP STANDPIPESP STATIC PRESSURESTM STEAMT THERMOSTATTD TRANSFER DUCTTDR TRENCH DRAINTEMP TEMPERATURETYP TYPICALUG UNDERGROUNDVAC VACUUMV VENTVAV VARIABLE AIR VOLUMEVD VOLUME DAMPERVENT VENTILATIONVTR VENT THROUGH ROOFW WASTEWB WET BULBWCO WALL CLEAN OUTWH WALL HYDRANTWMS WIRE MESH SCREEN
ABBREVIATIONS
AC AIR CONDITIONING UNITAS AIR SEPARATORAHU AIR HANDLING UNITAS AIR SEPARATORB BOILERBP BOILER PUMPCH CHILLERCT COOLING TOWERCU CONDENSING UNITCUH CABINET UNIT HEATERCWP CONDENSER WATER PUMPCHWP CHILLED WATER PUMPDBP DOMESTIC WATER BOOSTER PUMPDC DUCT MOUNTED COILDCP DOMESTIC WATER CIRCULATING PUMPEF EXHAUST FANEDC ELECTRIC DUCT COILET EXPANSION TANK
EUH ELECTRIC UNIT HEATERFCU FAN COIL UNITFP FIRE PUMPGI GREASE INTERCEPTORGRV GRAVITY ROOF VENTILATORHWP HEATING WATER PUMPHX HEAT EXCHANGERHRU HEAT RECOVERY UNITPRV POWER ROOF VENTILATORRE RETURN/EXHAUST FANRTU ROOFTOP UNITSEP SEWAGE EJECTOR PUMPSF SUPPLY FANSP SUMP PUMPUH UNIT HEATERWH WATER HEATER
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
JOHN R. FARINA P.E.DELAWARE PE# 13559
ISSUEFOR BID
09/22/2020
As indicated
9/21
/202
0 1:
56:0
8PM
\\ded
csrv
06\ u
sers
\rmal
in\M
y D
ocum
e nts
\R19
DSW
A A d
min
19 P
022_
rmal
in6C
3 LD
.rvt
M101
1ST FLR HVAC DUCTPLAN
JRFRWM
07-01-20202018230.00
DOVER, DELAWARE
DSWAADMINISTRATIONBUILDING
SCALE: 1/8" = 1'-0"1FIRST FLOOR HVAC PLAN -WEST
SCALE: 1/8" = 1'-0"2FIRST FLOOR HVAC PLAN -EAST
DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK AND VAV BOXES WHERE
REQUIRED IN HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.
4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.
5. ALL DUCT BRANCHES SHALL HAVE A VOLUME DAMPER IN THE BRANCH DUCTWORK LOCATED WITHIN ONE FOOT AFTER THE BRANCH OFF.
6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT PER ITS MANUFACTURER'S WRITTEN INSTRUCTIONS AND ADHERE TO ALL REQUIRED CLEARANCES.
0 4' 8'2'1/4" = 1'-0"M101
3 FIRST FLOOR HVAC PLAN - MECHANICAL ROOM PARTIAL PLAN
Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID
REF
.N
.I.C
.
1
2
3
4
5
6
B
bb
dd
A
cc
d
C
D
E
F
7
9
22
ee
aa
8
23
EF1
REFER TO PLAN1/M101 FOR DUCTWORK
CONTINUATION FROMAHU-1
AHU1
B
A
C
D
E
F
9 10 12 13 14 15 16 17 18 19 2120
22
AHU2
EF2 RG W/ PLENUM RETURN
(TYP.-ALL)
RG W/PLENUM RETURN(TYP.-ALL)
CD-110" NK375 CFM
CD-18" NK175 CFM (TYP.-5)
12x10 EA UPTO EF-3
12x10 EA UPTO EF-6
SA UPTO AHU-5
RA UPTO AHU-4
RA UPTO AHU-5
SA UPTO AHU-4
VAV5-4
VAV5-2
VAV5-3
VAV5-1
VAV5-7
VAV5-8
VAV5-6
VAV5-9
VAV5-11
VAV5-10
VAV5-12
VAV5-5
10x12 EA DN
14"Ø S/A
EG-16x6100 CFM(TYP.-2)
VAV5-13
AHU3
STAIR-2111A-2
OFFICE205
OFFICE206
ELEV.-2119-2
OFFICE204
20x18 SA DN30x18 RA DN
LD-110" NK250 CFM(TYP.-2)
CD-18" NK200 CFM
8"
10"10"
16x14
18x1
6 14x1210x10
LD-110" NK275 CFM(TYP.-2)
8"
8" 8"
8" 8"
8"
10"10"
CD-18" NK200 CFM(TYP.-6)
CD-18" NK150 CFM
CD-18" NK125 CFM
CD-18" NK200 CFM
CD-110" NK300 CFM(TYP.-2)
CD-18" NK200 CFM
CD-18" NK125 CFM
CD-110" NK300 CFM(TYP.-2)
CD-110" NK300 CFM
CD-18" NK150 CFM
CD-110" NK225 CFM
CD-18" NK125 CFM
CD-110" NK200 CFM
CD-16" NK50 CFM
CD-16" NK75 CFM
CD-18" NK225 CFM
LD-3, 250 CFM.REFER TO SCHEDULES SHEET M600 FOR MORE INFORMATION(TYP.-5)
EG-16x6 NK100 CFM
EG-16x675 CFM
EG-16x6
75 CFM
8x8
12x10
12x1214x1414x16
16x16
10"8"
10x14
10x1
2
10"
10"
6x1210x12
10"10"
6x108x10
8"8"
10"
12x1
2
8"
10"
8"
10x1
210
x14
10"
10"10" 10x1
2
10"
12x1
2 8"8"6" 10x10
10"
10x14
10x1
2
10"
10"
10"10"
10"
8"
8"
10x1214x12
12"
12x1
414
x14
30x2
0
10"6x128" 20x16
8"14"
8"
8"
8"
8"
8x1012x12
8"
8"
14x1
2
12"
20x1
824
x20
26x208x1210"
6x12
10"
6x8
6"
6"
6"
6"
8"
10x12
6x6
6x6
6x10
6x6
6x6
8x10
12x1
06x
6
AC4
10"
10x1
2
LD-110" NK250 CFM(TYP.-2)
LD-110" NK250 CFM(TYP.-2)
FD
FD
FD
VD(TYP.)
VD (TYP.)VD(TYP.)
VD(TYP.)
ALL CEILNG DIFFUSERS ANDRETURN GRILLES IN THIS ROOM
ARE TO BE HUNG FROM DECK BECAUSE DROP
CEILING WILL NOT BE INSTALLED(TYP.-6)
(MOUNTEDABOVEDOORWAY)
LINEAR DIFFUSERS SHALL HAVE TWO SLOTS WITH ONE SLOT'S AIRFLOW ANGLED AT WINDOW ABOVE AND OTHER SLOT'S AIRFLOW ANGLED AT WINDOW BELOW(TYP.-5)
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
JOHN R. FARINA P.E.DELAWARE PE# 13559
ISSUEFOR BID
09/22/2020
1/8" = 1'-0"
9/21
/202
0 1:
56:2
0PM
\\ded
csrv
06\ u
sers
\rmal
in\M
y D
ocum
e nts
\R19
DSW
A A d
min
19 P
022_
rmal
in6C
3 LD
.rvt
M102
2ND FLR HVAC DUCTPLAN
JRFRWM
07-01-20202018230.00
DOVER, DELAWARE
DSWAADMINISTRATIONBUILDING
SCALE: 1/8" = 1'-0"1SECOND FLOOR HVAC PLAN -WEST
SCALE: 1/8" = 1'-0"2SECOND FLOOR HVAC PLAN -EAST
DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK AND VAV BOXES WHERE
REQUIRED IN HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.
4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.
5. ALL DUCT BRANCHES SHALL HAVE A VOLUME DAMPER IN THE BRANCH DUCTWORK LOCATED WITHIN ONE FOOT AFTER THE BRANCH OFF.
6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT PER ITS MANUFACTURER'S WRITTEN INSTRUCTIONS AND ADHERE TO ALL REQUIRED CLEARANCES.
Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
JOHN R. FARINA P.E.DELAWARE PE# 13559
ISSUEFOR BID
09/22/2020
1/8" = 1'-0"
9/21
/202
0 1:
56:3
2PM
\\ded
csrv
06\ u
sers
\rmal
in\M
y D
ocum
e nts
\R19
DSW
A A d
min
19 P
022_
rmal
in6C
3 LD
.rvt
M103
TOP ROOF HVACDUCT PLAN
JRFRWM
07-01-20202018230.00
DOVER, DELAWARE
DSWAADMINISTRATIONBUILDING
SCALE: 1/8" = 1'-0"1 ROOF HVAC PLAN - EAST
DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK WHERE REQUIRED IN
HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.
4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.
Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID
REF
.N
.I.C
.
REF.
N.I.C.
UP
T LV
T LV
B
A
C
D
E
F
9 10 12 13 14 15 16 17 18 19 2120
22
ee
1 1/4" HWS1 1/4" HWR
1 1/2" HWR1 1/2" HWS
VAV3-3
VAV4-1
VAV4-3
VAV4-6
VAV4-7 VAV
4-13 VAV4-11
VAV4-12
VAV4-10
VAV3-12
VAV3-11
VAV3-10
VAV3-9
VAV3-8
VAV3-7
VAV3-6VAV
3-5
VAV3-4
VAV4-2
VAV4-4
VAV4-5
VAV4-8
1/2" HWR1/2" HWS
1/2" HWR1/2" HWS3/4" HWS
1/2" HWS1/2" HWR1/2" HWS
1/2" HWR1/2" HWR1/2" HWS
3-WAY
1/2" HWS1/2" HWR1/2" HWR
1/2" HWS1/2" HWR1/2" HWS
3-WAY
1/2" HWS1/2" HWR
1/2" HWS1/2" HWR3/4" HWR1" HWR
1" HWS
1/2" HWR1/2" HWS
1" HWS
1" HWR
3/4" HWR3/4" HWS
1/2" HWS1/2" HWR
3/4" HWR3/4" HWS
1/2" HWR1/2" HWS
1/2" HWR1/2" HWS
VAV4-9
1/2" HWR1/2" HWS
1/2" HWR1/2" HWS
1/2" HWR1/2" HWS
1/2" HWS1/2" HWR
1" HWR
1" HWS
1/2" HWS1/2" HWR
1/2" HWS1/2" HWR
1/2" HWS1/2" HWR
1/2" HWS1/2" HWR
1/2" HWS1/2" HWR
PLOTTER ROOM147
ACCOUNTING FILES152COPY / PRINT
ROOM146
FLEXWORKSTATIONS
118
STAFF TOILET151
KITCHENETTE117
SERVER ROOM148
OPEN SPACE116B
STAFF TOILET150
ADMINISTRATIONFILES
149 OPEN SPACE116C
OPEN SPACE116A
STAFF TOILET154
SAFETY STORAGE153
STAFF TOILET114
AV CLOSET108A
STAFF TOILET113
LOADING BAY134
OFFICE129
OFFICE126
OFFICE120
OFFICE140
OFFICE142
OFFICE139
OFFICE124
OFFICE125
OFFICE123
OFFICE121
OFFICE122
OFFICE127
OFFICE128
OFFICE131
OFFICE136
OFFICE135OFFICE
137
OFFICE143
OFFICE144
OFFICE130
CORRIDOR116
CORRIDOR111
ELEV.-1119-1
MECH145
STAIR-1111A-1
OFFICE138
CONFERENCEROOM
141
STAIR-1132-1
OFFICE133
3/4" HWR
1" HWS1" HWR
AC2
AC3
FIELD-ROUTE 1/2" CONDENSATE.
REFER TO DRAWING NOTES FOR
MORE INFORMATION
CU2
CU3
CUH3
REFER TO PARTIAL PLAN3/M111 ON THIS SHEET FOR DETAILS IN THIS AREA OF WORK
1 1/4" HWR1 1/4" HWS
1 1/4" HWS1 1/4" HWR
T VAV4-4
T VAV4-3
T VAV4-6
T VAV4-7
T VAV4-13
T VAV4-11
T VAV4-12T VAV
4-10
T VAV3-12
T VAV3-11
T VAV3-10
T VAV3-9
T VAV3-8
T VAV3-7
T VAV3-6
T VAV3-5
T VAV3-4
T VAV4-1
T VAV3-3
T VAV4-2
T VAV4-5
T VAV4-8
T VAV4-9
BAS PANEL
REMOTE DIFFERENTIALPRESSURE
TRANSMITTERDPT
ROUTE HWS&R DN IN WALL TOCUH AND/OR PROVIDE COSMETICPIPING ENCLOSURE TOCONCEAL PIPING. COORDINATEW/ ARCHITECT FOR ENCLOSUREMATERIAL, COLOR, ETC.(TYP.)
?
AC-1 &AC-2T-STATS
3/4" HWS&R UP TO CUH-2 IN STAIRWELL
ON 2ND FLOOR
3/4" HWR3/4" HWS
MOUNTED ONFLOORUNDERNEATHSTAIRS
MULTIMEDIACONFERENCEROOM-112CO2 SENSOR
CONFERENCE ROOM-141CO2 SENSOR
1
2
3
4
5
6
B
bb
dd
A
cc
d
C
D
E
F
7
9
22
ee
aa
8
23
VAV3-1
OFFICE103
STORAGE104
KITCHENETTE102
WOMEN107
JAN.106
MEN105
VESTIBULE109
VESTIBULE100
AV CLOSET108A
OFFICE115
EDUCATIONCENTER
101
3/4" HWR3/4" HWS
AC1
CU1
EUH2
1/2" HWS1/2" HWR
3/4" HWR3/4" HWS
FIELD-ROUTE 1/2" CONDENSATE.REFER TO DRAWING NOTES
FOR MORE INFORMATION
3-WAY
VAV3-2
AC-1T-STAT
AHU-1T-STAT
T VAV3-1
T VAV3-2
ROUTE CONDENSATE AND REFRIGERANTPIPING FROM AC-1 DOWN IN EXTERIOR
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
JOHN R. FARINA P.E.DELAWARE PE# 13559
ISSUEFOR BID
09/22/2020
As indicated
9/21
/202
0 1:
56:4
5PM
\\ded
csrv
06\ u
sers
\rmal
in\M
y D
ocum
e nts
\R19
DSW
A A d
min
19 P
022_
rmal
in6C
3 LD
.rvt
M111
1ST FLR HYDRONICPIPING PLAN
JRFRWM
07-01-20202018230.00
DOVER, DELAWARE
DSWAADMINISTRATIONBUILDING
0 4' 8'2'1/8" = 1'-0"M111
2 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - EAST
0 4' 8'2'1/8" = 1'-0"M111
1 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - WEST
DRAWING NOTES:1. SEE DRAWING M000 FOR LEGEND & ABBREVIATIONS.2. CONTRACTOR SHALL FIELD -ROUTE REFRIGERANT PIPING FROM DUCTLESS SPLIT SYSTEM INDOOR UNIT TO OUTDOOR
CONDENSING UNIT. SIZE AND INSULATE PIPING PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. COORDINATE WITH EQUIPMENT VENDOR TO ROUTE ALL REFRIGERANT PIPING WITHIN MAXIMUM EQUIVALENT LENGTH OF PIPING ALLOWED. CONTRACTOR SHALL PROVIDE EQUIPMENT VENDOR WITH FINAL LINE LENGTHS FOR FINAL PIPE SIZING, REFRIGERANT CHARGE, ETC.
3. FIELD ROUTE NEW CONDENSATE PIPING TO APPROVED DISCHARGE LOCATION. PROVIDE PLUGS ON ALL ELBOWS AND TEES.
4. ALL CONDENSATE IN SERVER ROOM SHALL NOT BE ROUTED OVER ANY ELECTRICAL EQUIPMENT AND ROUTED HIGH NEAR CEILNG.
5. CONTRACTOR SHALL PROVIDE WALL MOUNTED CONDENSATE PUMP FOR EACH WALL MOUNTED DUCTLESS SPLIT INDOOR UNIT ON THIS SHEET (AC-3 & AC-4). CONDENSATE PUMP TO BE ASPEN PUMPS MODEL ASP-MW-UNI, 1.2 GPH FLOW @ 33' TDH, 1/4" PUMP DISCHARGE, 115V/1∅/60Hz, 39" CABLE. PROVIDE WITH RESERVOIR OVERFLOW PROTECTION SWITCH AND FLOAT ACTIVATED SWITCH FOR ON/OFF OPERATION. PROVIDE 1/4" VINYL TUBE AND CHECK VALVE ON DISCHARGE. INSTALL PER MANUFACTURER'S INSTRUCTIONS.
6. INTENT IS TO PROVIDE A 3-WAY VALVE CONFIGURATION FOR ALL VAV BOXES AND/OR CABINET UNIT HEATERS AT THE END OF ALL PIPE RUNS.
7. FINAL ROUTING OF PIPING MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. PIPING SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.
8. PROVIDE SHUT-OFF VALVE AND COMBINATION SHUT-OFF/BALANCING VALVE ON ALL BRANCH PIPING TAKE-OFFS FOR BRANCHES TO MORE THAN ONE VAV BOX AND/OR UNIT HEATER. REFER TO DETAIL 7/M-202 FOR MORE INFORMATION.
9. PROVIDE BOILER MANUFACTURER RECOMMENDED CONDENSATE NEUTRALIZATION KIT PER BOILER AND ROUTE CONDENSATE DISCHARGE TO FLOOR DRAIN IN MECHANICAL ROOM.
10. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO VALVES IN PIPING AND VAV BOXES WHERE REQUIRED IN HARD CEILINGS. VALVES SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.
11. REFER TO CONTROL DRAWINGS FOR LOCATION OF CO2 SENSORS. CO2 SENSORS SHALL BE PLACED IN ALL DENSELY OCCUPIED SPACES (40 PEOPLE/SF OR MORE).
0 4' 8'2'1/4" = 1'-0"M111
3 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - MECHANICAL ROOM PARTIAL PLAN
Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
JOHN R. FARINA P.E.DELAWARE PE# 13559
ISSUEFOR BID
09/22/2020
1/8" = 1'-0"
9/21
/202
0 1:
57:0
2PM
\\ded
csrv
06\ u
sers
\rmal
in\M
y D
ocum
e nts
\R19
DSW
A A d
min
19 P
022_
rmal
in6C
3 LD
.rvt
M112
2ND FLR HYDRONICPIPING PLAN
JRFRWM
07-01-20202018230.00
DOVER, DELAWARE
DSWAADMINISTRATIONBUILDING
0 4' 8'2'1/8" = 1'-0"M112
1 SECOND FLOOR HVAC HYDRONIC PIPING PLAN - EAST
DRAWING NOTES:1. SEE DRAWING M000 FOR LEGEND & ABBREVIATIONS.2. CONTRACTOR SHALL FIELD -ROUTE REFRIGERANT PIPING FROM DUCTLESS SPLIT SYSTEM INDOOR UNIT TO OUTDOOR
CONDENSING UNIT. SIZE AND INSULATE PIPING PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. COORDINATE WITH EQUIPMENT VENDOR TO ROUTE ALL REFRIGERANT PIPING WITHIN MAXIMUM EQUIVALENT LENGTH OF PIPING ALLOWED. CONTRACTOR SHALL PROVIDE EQUIPMENT VENDOR WITH FINAL LINE LENGTHS FOR FINAL PIPE SIZING, REFRIGERANT CHARGE, ETC.
3. FIELD ROUTE NEW CONDENSATE PIPING TO APPROVED DISCHARGE LOCATION. PROVIDE PLUGS ON ALL ELBOWS AND TEES.
4. ALL CONDENSATE IN ELEVATOR MACHINE CLOSET SHALL NOT BE ROUTED OVER ANY ELECTRICAL EQUIPMENT AND ROUTED HIGH NEAR CEILNG.
5. CONTRACTOR SHALL PROVIDE WALL MOUNTED CONDENSATE PUMP FOR THE WALL MOUNTED DUCTLESS SPLIT INDOOR UNIT ON THIS SHEET (AC-5). CONDENSATE PUMP TO BE ASPEN PUMPS MODEL ASP-MW-UNI, 1.2 GPH FLOW @ 33' TDH, 1/4" PUMP DISCHARGE, 115V/1∅/60Hz, 39" CABLE. PROVIDE WITH RESERVOIR OVERFLOW PROTECTION SWITCH AND FLOAT ACTIVATED SWITCH FOR ON/OFF OPERATION. PROVIDE 1/4" VINYL TUBE AND CHECK VALVE ON DISCHARGE. INSTALL PER MANUFACTURER'S INSTRUCTIONS.
6. INTENT IS TO PROVIDE A 3-WAY VALVE CONFIGURATION FOR ALL VAV BOXES AND/OR CABINET UNIT HEATERS AT THE END OF ALL PIPE RUNS.
7. FINAL ROUTING OF PIPING MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. PIPING SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.
8. PROVIDE SHUT-OFF VALVE AND COMBINATION SHUT-OFF/BALANCING VALVE ON ALL BRANCH PIPING TAKE-OFFS FOR BRANCHES TO MORE THAN ONE VAV BOX AND/OR UNIT HEATER. REFER TO DETAIL 7/M-202 FOR MORE INFORMATION.
9. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO VALVES IN PIPING AND VAV BOXES WHERE REQUIRED IN HARD CEILINGS. VALVES SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.
10. REFER TO CONTROL DRAWINGS FOR LOCATION OF CO2 SENSORS. CO2 SENSORS SHALL BE PLACED IN ALL DENSELY OCCUPIED SPACES (40 PEOPLE/SF OR MORE).
Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID