CO2 CO H HS NO2 S TH TS T MS T LV CHWS CWV CA CD CDR CWR CWS CW F - CW H - CW S - CW HW HW 140° HW - R HW - R 140° GV GW HWR HWS G OV OW PD V SS SHWR SHWS STM SD OSD CHWR CHILLED WATER RETURN CHILLED WATER SUPPLY COMBINATION WASTE & VENT COMPRESSED AIR CONDENSATE DRAINAGE CONDENSATE RETURN CONDENSER WATER RETURN CONDENSER WATER SUPPLY DOMESTIC COLD WATER FILTERED COLD WATER HARD COLD WATER SOFT COLD WATER HOT WATER HOT WATER 140° HOT WATER RECIRCULATION HOT WATER RECIRCULATION 140° GREASE VENT GREASE WASTE HEATING WATER RETURN HEATING WATER SUPPLY NATURAL GAS OIL VENT OIL WASTE PUMP DISCHARGE SANITARY VENT SANITARY SEWER SOLAR HOT WATER RETURN SOLAR HOT WATER SUPPLY STEAM STORM DRAINAGE OVERFLOW STORM DRAINAGE REF - L REF - S REFRIGERANT - LIQUID REFRIGERANT - SUCTION 2" CAP PLUG 2" 4" 4" 4" REF - HG REFRIGERANT - HOT GAS MECHANICAL PIPING SYMBOLS KEYNOTE CONTINUATION SYMBOL NUMBER OF DETAIL SHEET OR EQUIPMENT NUMBER NUMBER OF DETAIL OR EQUIPMENT TYPE REVISION NUMBER - SHOWN ON PLANS GENERAL MECHANICAL SYMBOLS ROOM NAME AND NUMBER ABOVE GROUND PIPING PIPE SIZE TAG (DIAMETER) PIPE RISE PIPE DROP PIPE TEE REDUCING 45 DEGREE TEE 45 DEGREE TEE ? - --- * NOTE * ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS. PG PROPANE GAS Room 1 RO REVERSE OSMOSIS WATER IW INDIRECT WASTE 16"x8" 16"/8" (E) FD S M B D C 16"Ø E/A O/A T/A L/A R/A S/A EXHAUST AIR 16"Ø E/A OUTSIDE AIR 16"Ø O/A RELIEF AIR 16"Ø L/A RETURN AIR 16"Ø R/A SUPPLY AIR 16"Ø S/A TRANSFER AIR 16"Ø T/A GRILLES, REGISTERS & DIFFUSERS TAG CFM THROW-150FPM/ 100FPM/ 50FPM NECK SIZE / MODULE SIZE EXISTING DUCT TAG OVAL DUCT SIZE TAG (WIDTH / HEIGHT) SQUARE DUCT SIZE TAG (WIDTH x HEIGHT) HVAC SYMBOLS RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE RECTANGULAR RETURN/TRANSFER AIR DUCT RISE ROUND DUCT SIZE TAG (DIAMETER) LINEAR DIFFUSER TAG CFM TYPE (SEE SCHEDULE) NUMBER OF SLOTS / ACTIVE SLOT LENGTH (PLENUM LENGTH) / NECK SIZE DUCT BEING DEMOLISHED ELEVATION (CENTER OF FACE) ROUND SUPPLY/OUTSIDE AIR DUCT RISE ROUND RETURN/TRANSFER AIR DUCT RISE RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE ROUND EXHAUST/RELIEF AIR DUCT RISE DROP DROP DROP DROP DROP DROP GE/A GREASE EXHAUST AIR 16"Ø GE/A SE/A SMOKE EXHAUST AIR 16"Ø SE/A FLUE EXHAUST GAS FLUE 16"Ø FLUE C/A COMBUSTION AIR 16"Ø C/A S - O/A CONDITIONED OUTSIDE AIR 16"Ø S - O/A Ø ROUND ABV ABOVE AD AREA DRAIN ADD ADDENDUM AFF ABOVE FINISHED FLOOR AFUE ANNUAL FUEL UTILIZATION EFFICIENCY ALT ALTERNATE AP ACCESS PANEL ARCH ARCHITECT/ARCHITECTURAL BFF BELOW FINISHED FLOOR BLW BELOW BTU BRITISH THERMAL UNITS BTUH BRITISH THERMAL UNITS PER HOUR CA COMBUSTION AIR CAP CAPACITY CB CATCH BASIN CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CLG CEILING CO CLEAN OUT CW COLD WATER DB DRY BULB DIA DIAMETER DN DOWN EA EACH EA EXHAUST AIR E/A EXHAUST AIR EAT ENTERING AIR TEMPERATURE EG EXHAUST GRILLE ELEC ELECTRICAL EQUIP EQUIPMENT EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EXIST EXISTING F DEGREES FAHRENHEIT FCO FLOOR CLEAN OUT FD FLOOR DRAIN FD FIRE DAMPER FG FLUE GAS FL FLOOR FO FUEL OIL FOV FUEL OIL VENT FOR FUEL OIL RETURN FOS FUEL OIL SUPPLY FPM FEET PER MINUTE FS FLOOR SINK FT FOOT/FEET FTR FIN TUBE RADIATION GAL GALLON GC GENERAL CONTRACTOR GPM GALLONS PER MINUTE GW GREASE WASTE HB HOSE BIB HP HORSE POWER HTG HEATING HTR HEATER HW HOT WATER IN INCH INV INVERT LB POUND LB/HR POUNDS PER HOUR LAT LEAVING AIR TEMPERATURE LD LINEAR DIFFUSER LP LOW PRESSURE LPG LIQUEFIED PETROLEUM GAS LV LOUVER LWT LEAVING WATER TEMPERATURE M/A MIXED AIR MAX MAXIMUM MBH ONE THOUSAND BTU PER HOUR MOD MOTORIZED OPERATED DAMPER MECH MECHANICAL MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MTR MOTOR MU/A MAKE-UP/AIR NC NOISE CRITERIA NC NORMALLY CLOSED NIC NOT IN CONTRACT NK NECK NO NUMBER NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR O/A OUTSIDE AIR PD PRESSURE DROP PLBG PLUMBING PRESS PRESSURE PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE PWR POWER R/A RETURN AIR RCP RADIANT CEILING PANEL RD ROOF DRAIN REC RECESSED RED REDUCER RG RETURN GRILLE RH RELATIVE HUMIDITY RL/A RELIEF AIR RM ROOM RPM REVOLUTIONS PER MINUTE RW RAIN WATER SF SQUARE FOOT SA SUPPLY AIR S/A SUPPLY AIR SAN SANITARY SF SQUARE FOOT SD SUPPLY DIFFUSER SDA SMOKE DAMPER SM SURFACE MOUNT SP STANDPIPE SP STATIC PRESSURE STM STEAM T THERMOSTAT TD TRANSFER DUCT TDR TRENCH DRAIN TEMP TEMPERATURE TYP TYPICAL UG UNDERGROUND VAC VACUUM V VENT VAV VARIABLE AIR VOLUME VD VOLUME DAMPER VENT VENTILATION VTR VENT THROUGH ROOF W WASTE WB WET BULB WCO WALL CLEAN OUT WH WALL HYDRANT WMS WIRE MESH SCREEN ABBREVIATIONS AC AIR CONDITIONING UNIT AS AIR SEPARATOR AHU AIR HANDLING UNIT AS AIR SEPARATOR B BOILER BP BOILER PUMP CH CHILLER CT COOLING TOWER CU CONDENSING UNIT CUH CABINET UNIT HEATER CWP CONDENSER WATER PUMP CHWP CHILLED WATER PUMP DBP DOMESTIC WATER BOOSTER PUMP DC DUCT MOUNTED COIL DCP DOMESTIC WATER CIRCULATING PUMP EF EXHAUST FAN EDC ELECTRIC DUCT COIL ET EXPANSION TANK EUH ELECTRIC UNIT HEATER FCU FAN COIL UNIT FP FIRE PUMP GI GREASE INTERCEPTOR GRV GRAVITY ROOF VENTILATOR HWP HEATING WATER PUMP HX HEAT EXCHANGER HRU HEAT RECOVERY UNIT PRV POWER ROOF VENTILATOR RE RETURN/EXHAUST FAN RTU ROOFTOP UNIT SEP SEWAGE EJECTOR PUMP SF SUPPLY FAN SP SUMP PUMP UH UNIT HEATER WH WATER HEATER EQUIPMENT ABBREVIATIONS 48"x2 1/2" 400 SLB3 8" / 24x24 300 SD3 400 12" / --- SD9 LINEAR BAR GRILLE LINEAR SLOT DIFFUSER PERFORATED DIFFUSER WITH DEFLECTORS ROUND DIFFUSER WITH ADJUSTABLE PATTERNS LOUVERED DOUBLE DEFLECTION GRILLE 12"x10" / --- 500 SG7 TYPE (SEE SCHEDULE) 10" / 24x24 H-5/7/14 22 400 SD1 3-CONE DIFFUSER THROW PATTERN MAX NC RATING 1 / 4' - 0" / 8" 200 LSD1 8' - 0" AFF 1 / 4' - 0" / 8" 200 LSD1 18' - 0" 1 / 4' - 0" / 8" 200 LSD1 SECTION TOTAL TRACK LENGTH 12"x10" / 24x12 500 RG9 LOUVERED GRILLE 12"x10" / 24x24 18 500 RG2 EGGCRATE RETURN GRILLE 2" DOM. WM PIPE ACCESSORY TAGS DOMESTIC WATER METER BALANCING VALVE 1/4 TURN BALL VALVE CHECK VALVE 3-WAY MIXING VALVE MOTORIZED CONTROL VALVE 3 WAY MOTORIZED CONTROL VALVE PRESSURE REDUCING VALVE REFRIGERANT SOLENOID VALVE BUTTERFLY VALVE 2" BALANCING 2" SHUTOFF 2" CHECK 2" TMV 2" M-CNTRL 2" 3-WAY CNTRL 2" PRV 3/8" SOLENOID 2" BUTTERFLY DATA DEVICE TAGS DAMPER TAGS VAV-XX RTU-XX EQUIPMENT ID SYMBOL B B B INLET COLLAR DAMPER MANUAL BALANCING DAMPER BACKDRAFT DAMPER COMBINATION FIRE/SMOKE DAMPER FIRE DAMPER SMOKE DAMPER MOTORIZED DAMPER SENSOR MANUAL SWITCH THERMOSTAT TEMPERATURE SENSOR TEMPERATURE & HUMIDITY SENSOR HUMIDITY SENSOR NITROGEN DIOXIDE SENSOR CARBON MONOXIDE SENSOR CARBON DIOXIDE SENSOR HUMIDISTAT ISSUED: SUSTAINABLE DESIGN CONSULTING SUSTAINABILITY CONSULTANT 1432 K STREET NW, 3RD FLOOR WASHINGTON, DC 20005 202-667-1620 fax 202-667-1622 DEDC, LLC FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER 315 SOUTH CHAPEL STREET NEWARK, DELAWARE 19711 302-738-7172 fax: 302-738-7175 SCALE: DATE: DRAWN BY: PROJ MGR: PROJECT NO: PROJECT TITLE SHEET TITLE ISSUE BLOCK COPYRIGHT © 2019 Delaware 309 S Governors Ave Dover, DE 19904 302.734.7950 Maryland 312 West Main St, Suite 300 Salisbury, MD 21801 410.546.9100 North Carolina 3333 Jaeckle Drive, Suite 102 Wilmington, NC 28403 910.341.7600 www.beckermorgan.com Rittenhouse Station 250 South Main Street, Suite 109 Newark, DE 19711 302.369.3700 JOHN R. FARINA P.E. DELAWARE PE# 13559 ISSUE FOR BID 09/22/2020 No Scale 9/21/2020 1:55:50 PM \\dedcsrv06\users\rmalin\My Documents\R19 DSWA Admin 19P022_rmalin6C3LD.rvt M000 MECHANICAL TITLE SHEET JRF RWM 07-01-2020 2018230.00 DOVER, DELAWARE DSWA ADMINISTRATION BUILDING Mark Date Description 1 02/28/2020 ISSUE FOR PERMIT 2 09/22/2020 ISSUE FOR BID
16

T LV - carrowconstruction.com

Feb 08, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: T LV - carrowconstruction.com

CO2

CO

H

HS

NO2

S

TH

TS

T

MS

T LV

CHWS

CWV

CA

CD

CDR

CWR

CWS

CW

F-CW

H-CW

S-CW

HW

HW 140°

HW-R

HW-R 140°

GV

GW

HWR

HWS

G

OV

OW

PD

V

SS

SHWR

SHWS

STM

SD

OSD

CHWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

COMBINATION WASTE & VENT

COMPRESSED AIR

CONDENSATE DRAINAGE

CONDENSATE RETURN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

DOMESTIC COLD WATER

FILTERED COLD WATER

HARD COLD WATER

SOFT COLD WATER

HOT WATER

HOT WATER 140°

HOT WATER RECIRCULATION

HOT WATER RECIRCULATION 140°

GREASE VENT

GREASE WASTE

HEATING WATER RETURN

HEATING WATER SUPPLY

NATURAL GAS

OIL VENT

OIL WASTE

PUMP DISCHARGE

SANITARY VENT

SANITARY SEWER

SOLAR HOT WATER RETURN

SOLAR HOT WATER SUPPLY

STEAM

STORM DRAINAGE

OVERFLOW STORM DRAINAGE

REF-L

REF-S

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION2"

CAP

PLUG

2"

4"

4" 4"

REF-HG REFRIGERANT-HOT GAS

MECHANICAL PIPING SYMBOLS

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF DETAIL SHEET OR EQUIPMENT NUMBERNUMBER OF DETAIL OR EQUIPMENT TYPE

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

PIPE RISEPIPE DROP

PIPE TEE REDUCING 45 DEGREE TEE45 DEGREE TEE

?

----

* NOTE *ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE

USED IN THIS SET OF DRAWINGS.

PG PROPANE GAS

Room1

RO REVERSE OSMOSIS WATER

IW INDIRECT WASTE

16"x8"

16"/8"

(E)

FD

S

M

B

D

C

16"Ø

E/A

O/A

T/A

L/A

R/A

S/A

EXHAUST AIR16"Ø E/A

OUTSIDE AIR16"Ø O/A

RELIEF AIR16"Ø L/A

RETURN AIR16"Ø R/A

SUPPLY AIR16"Ø S/A

TRANSFER AIR16"Ø T/A

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

THROW-150FPM/ 100FPM/ 50FPMNECK SIZE / MODULE SIZE

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

ROUND DUCT SIZE TAG (DIAMETER)

LINEAR DIFFUSER TAGCFM

TYPE (SEE SCHEDULE) NUMBER OF SLOTS /ACTIVE SLOT LENGTH (PLENUM LENGTH) / NECK SIZE

DUCT BEING DEMOLISHED

ELEVATION (CENTER OF FACE)

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

GE/A GREASE EXHAUST AIR16"Ø GE/A

SE/A SMOKE EXHAUST AIR16"Ø SE/A

FLUE EXHAUST GAS FLUE16"Ø FLUE

C/A COMBUSTION AIR16"Ø C/A

S-O/A CONDITIONED OUTSIDE AIR16"Ø S-O/A

Ø ROUNDABV ABOVEAD AREA DRAINADD ADDENDUMAFF ABOVE FINISHED FLOORAFUE ANNUAL FUEL UTILIZATION EFFICIENCYALT ALTERNATEAP ACCESS PANELARCH ARCHITECT/ARCHITECTURALBFF BELOW FINISHED FLOORBLW BELOWBTU BRITISH THERMAL UNITSBTUH BRITISH THERMAL UNITS PER HOURCA COMBUSTION AIRCAP CAPACITYCB CATCH BASINCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCO CLEAN OUTCW COLD WATERDB DRY BULBDIA DIAMETERDN DOWNEA EACHEA EXHAUST AIRE/A EXHAUST AIREAT ENTERING AIR TEMPERATUREEG EXHAUST GRILLEELEC ELECTRICALEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXIST EXISTINGF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFD FIRE DAMPERFG FLUE GASFL FLOORFO FUEL OILFOV FUEL OIL VENTFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFPM FEET PER MINUTEFS FLOOR SINKFT FOOT/FEETFTR FIN TUBE RADIATIONGAL GALLONGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGW GREASE WASTEHB HOSE BIBHP HORSE POWERHTG HEATINGHTR HEATERHW HOT WATERIN INCHINV INVERTLB POUNDLB/HR POUNDS PER HOURLAT LEAVING AIR TEMPERATURELD LINEAR DIFFUSERLP LOW PRESSURELPG LIQUEFIED PETROLEUM GAS

LV LOUVERLWT LEAVING WATER TEMPERATUREM/A MIXED AIRMAX MAXIMUMMBH ONE THOUSAND BTU PER HOURMOD MOTORIZED OPERATED DAMPERMECH MECHANICALMFR MANUFACTURERMIN MINIMUMMISC MISCELLANEOUSMTR MOTORMU/A MAKE-UP/AIRNC NOISE CRITERIANC NORMALLY CLOSEDNIC NOT IN CONTRACTNK NECKNO NUMBERNO NORMALLY OPENNTS NOT TO SCALEOA OUTSIDE AIRO/A OUTSIDE AIRPD PRESSURE DROPPLBG PLUMBINGPRESS PRESSUREPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIG POUNDS PER SQUARE INCH GAUGEPWR POWERR/A RETURN AIRRCP RADIANT CEILING PANELRD ROOF DRAINREC RECESSEDRED REDUCERRG RETURN GRILLERH RELATIVE HUMIDITYRL/A RELIEF AIRRM ROOMRPM REVOLUTIONS PER MINUTERW RAIN WATERSF SQUARE FOOTSA SUPPLY AIRS/A SUPPLY AIRSAN SANITARYSF SQUARE FOOTSD SUPPLY DIFFUSERSDA SMOKE DAMPERSM SURFACE MOUNTSP STANDPIPESP STATIC PRESSURESTM STEAMT THERMOSTATTD TRANSFER DUCTTDR TRENCH DRAINTEMP TEMPERATURETYP TYPICALUG UNDERGROUNDVAC VACUUMV VENTVAV VARIABLE AIR VOLUMEVD VOLUME DAMPERVENT VENTILATIONVTR VENT THROUGH ROOFW WASTEWB WET BULBWCO WALL CLEAN OUTWH WALL HYDRANTWMS WIRE MESH SCREEN

ABBREVIATIONS

AC AIR CONDITIONING UNITAS AIR SEPARATORAHU AIR HANDLING UNITAS AIR SEPARATORB BOILERBP BOILER PUMPCH CHILLERCT COOLING TOWERCU CONDENSING UNITCUH CABINET UNIT HEATERCWP CONDENSER WATER PUMPCHWP CHILLED WATER PUMPDBP DOMESTIC WATER BOOSTER PUMPDC DUCT MOUNTED COILDCP DOMESTIC WATER CIRCULATING PUMPEF EXHAUST FANEDC ELECTRIC DUCT COILET EXPANSION TANK

EUH ELECTRIC UNIT HEATERFCU FAN COIL UNITFP FIRE PUMPGI GREASE INTERCEPTORGRV GRAVITY ROOF VENTILATORHWP HEATING WATER PUMPHX HEAT EXCHANGERHRU HEAT RECOVERY UNITPRV POWER ROOF VENTILATORRE RETURN/EXHAUST FANRTU ROOFTOP UNITSEP SEWAGE EJECTOR PUMPSF SUPPLY FANSP SUMP PUMPUH UNIT HEATERWH WATER HEATER

EQUIPMENT ABBREVIATIONS

48"x2 1/2"400SLB3

8" / 24x24300SD3

40012" / ---

SD9

LINEAR BAR GRILLE

LINEAR SLOT DIFFUSER

PERFORATED DIFFUSERWITH DEFLECTORS

ROUND DIFFUSER WITHADJUSTABLE PATTERNS

LOUVERED DOUBLEDEFLECTION GRILLE

12"x10" / ---500SG7

TYPE (SEE SCHEDULE)

10" / 24x24H-5/7/1422

400SD13-CONE DIFFUSER

THROW PATTERNMAX NC RATING

1 / 4' - 0" / 8"200LSD1

8' - 0" AFF

1 / 4' - 0" / 8"200LSD1

18' - 0"1 / 4' - 0" / 8"

200LSD1

SECTION TOTAL TRACK LENGTH

12"x10" / 24x12500RG9

LOUVERED GRILLE

12"x10" / 24x2418

500RG2

EGGCRATE RETURNGRILLE

2" DOM. WMPIPE ACCESSORY TAGS

DOMESTIC WATER METER

BALANCING VALVE

1/4 TURN BALL VALVE

CHECK VALVE

3-WAY MIXING VALVE

MOTORIZED CONTROL VALVE

3 WAY MOTORIZED CONTROLVALVE

PRESSURE REDUCING VALVE

REFRIGERANT SOLENOID VALVE

BUTTERFLY VALVE

2" BALANCING

2" SHUTOFF

2" CHECK

2" TMV

2" M-CNTRL

2" 3-WAY CNTRL

2" PRV

3/8" SOLENOID

2" BUTTERFLY

DATA DEVICE TAGS

DAMPER TAGS

VAV-XX

RTU-XX

EQUIPMENT IDSYMBOL

BBB INLET COLLAR DAMPER

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKEDAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

SENSOR

MANUAL SWITCH

THERMOSTAT

TEMPERATURE SENSOR

TEMPERATURE & HUMIDITY SENSOR

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

HUMIDISTAT

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

No Scale

9/21

/202

0 1:

55:5

0PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M000

MECHANICAL TITLESHEET

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 2: T LV - carrowconstruction.com

REF.

N.I.C.

UP

REF

.N

.I.C

.

1

2

3

4

5

6

B

bb

dd

A

cc

d

C

D

E

F

7

9

22

ee

aa

8

23

VAV3-1

50"x18" RA UPTO AHU-1

30"x28" SA UPTO AHU-1

12x10 EA UPTO EF-1

RG-2, 36x206350 CFMAPPROX.10'-10" AFF

RG-222x10

1225 CFM.MOUNT BELOW SOFFIT

30"Ø

16"Ø S/A

AC1

30"x28" S/A

CU1

EG-150 CFM

EG-150 CFM

EG-150 CFM

EG-1100 CFM

EG-1100 CFM

EG-150 CFM

16"x16" SA

OFFICE103

STORAGE104

KITCHENETTE102

VESTIBULE109

VESTIBULE100

OFFICE115

EDUCATIONCENTER

101

EUH1

EUH2SG-1

10"x12" FACE650 CFMAPPROX. 10'-6" AFF.ANGLE AIRFLOW DOWNWARD AT 45 DEGREE ANGLE20x8 SD-1

425 CFM(TYP.-8)

SD-114x6 FACE150 CFM(TYP.-10)

CD-110" NK250 CFM

36"x20" R/A

16x16

14x12

14x12

14x1

2

10x12

10x1

2

14x1810"

10x1

0

6x8

6x12

10"

SD-114x6 FACE

300 CFM

6" 6"

LD-210" NK275 CFM

10"10"

10"10"

10"

10"

MOUNT LD IN SLOPED SOFFIT CHANNEL.CONCEAL DUCTS TO GREATEST

EXTENT POSSIBLE(TYP.-4)

VD(TYP.)

VD(TYP.)

LD-210" NK

300 CFM(TYP.-2)

10" SA DN TOLOWER CEILING

HEIGHT

6"

8"

8" DUCT

6"

6"6"

8x10

12x10

CD-18" NK

100 CFM(TYP.-2)

ALL DUCTWORK IN BOARD ROOMSHALL BE INTERNALLY LINED

WITH INSULATION PER SPECIFICATIONSAND PAINTED DARK. COORDINATE EXACT

COLOR WITH ARCHITECT

ALL DUCTWORK IN EDUCATION CENTER SHALL BE INTERNALLY

LINED WITH INSULATION PERSPECIFICATIONS AND PAINTED DARK.

COORDINATE WITH ARCHITECTFOR EXACT PAINT COLOR

ROUTEDUCT

UNDER BEAMVD IN

VERTICAL BRANCH(TYP.-2)

STORAGE104

MEN105

JAN.106

WOMEN107

KITCHENETTE102

OFFICE103

20x8 SD-1400 CFM(TYP.-4)

28"Ø

24"Ø

20"Ø

18"Ø

12"Ø

12"Ø

10"Ø (TYP.-4)

14"Ø

10"Ø 10"Ø

10"Ø

8"Ø (TYP.-8)

10"Ø

30"x28"

16"Ø18" ROUND DUCTDN OFF BOTTOM

OF 20x14 DUCT

10x10

10x1

0

12"Ø

14"Ø

10"Ø

RG-1

DUCT BRANCH SHALL BE ROUTEDUP HIGH INTO BAY BETWEEN

THE STRUCTURAL BEAMS. DUCTBRANCH SHALL SLOPE ALONG

SLANTED CEILING(TYP.)

ROUTE MAIN DUCTALONG BOTTOMOF STRUCTURE

16" ROUNDDUCT UPTO BOTTOMOF BEAM

VD(TYP.)

BRANCH OFF TOPOF DUCT. VD IN

VERTICAL

LINEAR DIFFUSER SHALL HAVE AIRFLOW DIRECTED HORIZONTALLY AS REQUIRED TO

REDUCE DRAFTS ON OCCUPANTS.(TYP.-6)

SD-114x6 FACE

300 CFM

SD-114x6 FACE

275 CFM(TYP.-3)

6"

CD-18" NK150 CFM

8"

14"

RG-1

COORDINATE ALL ROUTINGOF DUCTWORK IN EDUCATION

CENTER WITH ARCHITECTURALCLOUDS, SUPPORTS, TRUSSES,

GLULAM, I-BEAMS, ETC.

LINEAR DIFFUSER SHALL HAVE AIRFLOW DIRECTED

HORIZONTALLY AS REQUIRED TO REDUCE

DRAFTS ON OCCUPANTS.(TYP.-6)

20x14 DUCT UPAND OVER BEAM

SD-114x6 FACE

300 CFM

18"Ø

16"Ø12"Ø

10"Ø

ANGLE BRANCHDUCT UPINTO BAYBETWEEN

BEAMS(TYP.)

16" SA UP INTO BAY BETWEEN

BEAMS

6"Ø

6"Ø

CD-1, 6" NK12x12 FACE75 CFM(TYP.-2)

6"Ø

8"Ø

RG-1

24x18 TD

8"

LD-210" NK

275 CFM(TYP.-4)

16"Ø

6x6(TYP.-2)RG-1

6x6 NK50 CFM(TYP.-2)

VD

VD

ANGLE SUPPLY AIR DIFFUSER

DOWN AT GLASS(TYP.-6)

SPIRAL DUCT MOUNTED SUPPLY AIR DIFFUSER SD-1SHALL BE ANGLED DOWNWARDS TOWARDS GLASS WINDOWS.

(TYPICAL OF ALL SD'S IN EDUCATION CENTER)

CD-18" NK

12x12 FACE100 CFM

AV CLOSET108A

B

A

C

D

E

F

9 10 12 13 14 15 16 17 18 19 2120

22

ee

VAV3-3

VAV4-1

VAV4-3

VAV4-6

VAV4-7

VAV4-13 VAV

4-11

VAV4-12

VAV4-10

VAV3-12

VAV3-11

VAV3-10

VAV3-9

VAV3-8

VAV3-7

VAV3-6

VAV3-5

VAV3-4

SA UPTO AHU-2

RA UPTO AHU-2

VAV4-2

VAV4-4

VAV4-5

VAV4-8

RA UPTO AHU-2

SA UPTO AHU-3

RG-222x10

1225 CFM.MOUNT BELOW SOFFIT

RG-1 W/PLENUM RETURN

(TYP.-ALL)CD-1

10" NK300 CFM(TYP.-2)

RG W/PLENUM RETURN

(TYP.-ALL)

CD-18" NK200 CFM(TYP.-2)

RG W/PLENUM RETURN

(TYP.-ALL)

VAV4-9

16"x16" SA 8"x6"6"x6"

8"x8"

8"x6" EA UPTO EF-2

FLEXWORKSTATIONS

118

KITCHENETTE117

OPEN SPACE116B

ADMINISTRATIONFILES

149

OPEN SPACE116C

OPEN SPACE116A

SAFETY STORAGE153

LOADING BAY134

OFFICE129

OFFICE142

OFFICE139

OFFICE125

OFFICE122

OFFICE128

OFFICE131

OFFICE136

OFFICE137

OFFICE143

OFFICE144

OFFICE130

CORRIDOR116

ELEV.-1119-1

MECH145

STAIR-1111A-1

CONFERENCEROOM

141

STAIR-1132-1

OFFICE133

LOUVER, LV-1

EF4

8"CD-18" NK225 CFM

LD-110" NK250 CFM(TYP.-2)

10" 10"

8"CD-18" NK225 CFM

8"CD-18" NK225 CFM

8"CD-18" NK225 CFM

12x14

10x1

2

12x14

10x1

2

12x14

10x1

2

12x14

10x1

2

14x18

12"

14x12 10x12 6x12CD-18" NK175 CFM(TYP.-3)

CD-16" NK100 CFM

42x1

4

22x20

20x20 20x18 18x1810"

12x128x12

10"

10"

10"

10"

10"

10"

10"10"

10"

10"

10"10" 10"

10"

10"

10"

10" 10"

10"

12x12 12x12 12x128x12 8x12 10x1210" 10" 10" 10"

18x14 16x14 14x12 10x1222x20

8"

8"

CD-18" NK

100 CFM6"

CD-18" NK175 CFM

6x10

8"8"CD-18" NK175 CFM

8"CD-18" NK150 CFM

CD-18" NK125 CFM(TYP.-2)

8"

8"

8x12

10"

10" 10"

8x12

CD-18" NK175 CFM

8"

8"

8"

8"12x126x10

10x1

06x

10

10"

CD-16" NK100 CFM(TYP.-2)

6"

10x10 8x10 6x10

8"

8"

8"

8" 8"

8"

CD-18" NK125 CFM(TYP.-2)

CD-18" NK150 CFM

8"

CD-18" NK150 CFM

CD-112" NK500 CFM

8"

12"

10"

6x8

8x14

8x106x10

8"

8"

8"

8"

8"

CD-18" NK125 CFM(TYP.-2)

8x10

6x10

6"

6"

8"

CD-16" NK75 CFM(TYP.-2)

CD-16" NK

100 CFM

CD-16" NK75 CFM

6"

6"

6"

6"

6x8

8x8

6"

8"

8"8"

8"

6x1010x10

8"

8"

8"8"

8"8"

8"

CD-18" NK150 CFM(TYP.-2)

8x12 8x106x10

10"12x12

14x1416"

12x1814x18

6"

6x10

6x10

8"

6"

CD-16" NK50 CFM

CD-18" NK150 CFM

16x1820x18 18x18

CD-18" NK150 CFM(TYP.-2)

CD-16" NK100 CFM(TYP.-2)

10"

EG-1100 CFM

EG-150 CFM

EG-1125 CFM

EG-1150

CFM

EG-150 CFM

EG-1100 CFM EG-1

50 CFM

6"6"6"8"

8"

10x10 10x8 6x8

16x18

CD-16" NK100 CFM

CD-16" NK125 CFM6" 6" 6"

8" 8" 8"

CD-110" NK

300 CFM(TYP.-2)

CD-110" NK

300 CFM(TYP.-2)

CD-110" NK

300 CFM(TYP.-2)

LD-110" NK250 CFM(TYP.-2)

3x36"

AC2

AC3

CU2

CU3

6"Ø

6"Ø

6"Ø

10"x

10"

6"Ø

6"Ø

6"Ø

6"x1

0"

10"x

10"

6"x1

0"

6"Ø

6"Ø

8"Ø

8"Ø

6"Ø

6"Ø

ROUTEDUCT

UNDER BEAM

OFFICE121

OFFICE120

MULTIMEDIACONFERENCE ROOM

112

STAIR111A

MEN114

WOMEN113

COPY / PRINT ROOM146

PLOTTER ROOM147

SERVER ROOM148

WOMEN150

MEN151

ACCOUNTING FILES152

STAFF TOILET154

OFFICE123

OFFICE124

OFFICE126

OFFICE127

OFFICE129

OFFICE130

OFFICE135

OFFICE138

OFFICE140

10" 10" 10" 10" 10" 10"

LD-110" NK250 CFM(TYP.-2)

LD-110" NK250 CFM(TYP.-2)

FD

FD

FD

FD

FD

FD

16x14

CUH1

CUH4

8"x6"

FD FD

FD

VD(TYP.)

VD(TYP.)

VD(TYP.)

VD(TYP.)

VD (TYP.)

VD(TYP.)

VD (TYP.)

REFER TO PARTIAL PLAN3/M101 ON THIS SHEETFOR DETAILS IN THISAREA OF WORK

SD-114x6 FACE

300 CFM

CD-16" NK100 CFM

RG-1RG-1

RG-1RG-1

RG-1

RG-1

RG-1

RG-1

RG-1RG-1

RG-1

RG-1RG-1

RG-1

RG-1

RG-1RG-1

RG-1RG-1RG-1

RG-1

RG-1

RG-1RG-1

RG-1

RG-1RG-1

RG-1

RG-1 RG-1

RG-1

RG-1RG-1

CD-1, 6" NK75 CFM

CD-18" NK150 CFM(TYP.-2)

CD-18" NK125 CFM

6x6

26x20 TD W/ FD

RG-156x16

IN PLENUMW/ WMS

RG-1

FD

8x6 TDW/ FD

16x12 TD W/ FD

30x20 TDW/ FD

30x20 TDW/ FD

8x6 TD

8x6 TD

8x6 TD

8x6 TD

8x6 TD

8x6 TD18x12 TD(TYP.-4)10x8 TD

(TYP.-8)

8x6 TD(TYP.-9)

12x10 TD

12x10 TDW/ FD

8x6 TD42x14

16X16

RG-1

52x24 TDW/ FD

8"

CD-18" NK

12x12 FACE100 CFM

AV CLOSET108A

OFFICE115

l

DUCT MOUNTEDCO2 SENSOR

E

F

12

22

B1

B2

24x20 RA UPTO AHU-4

20x18SA UP

TO AHU-4OFFICE

144

ELEV.-1119-1

MECH145STAIR-1

111A-1

10x10 EA UPTO EF-3

LV-1300 CFM

20x1

8

20x1

824

x20

24x20 RG-1 IN PLENUM

W/ WMS

EF5

4"Ø

FG

4"Ø

FG

4"Ø

CA 4"Ø

CA

CEILING HUNGUH SHOWN FOR

REFERENCE. COORDINATEROUTING OF

BOILER BREECHPIPING WITH UHAND ITS PIPING

10'-0" MINIMUM (TYP.-2)

FDFD FD

10x1

0

WEATHERHOOD

CUH1

SEE 2/M-101 FORDUCTWORK CONTINUATIONS

INSTALL EF-5 BELOW UNIT HEATER AND ABOVE BACKFLOW PREVENTER AND GAS METER IN AREA WHILE ADHERING TO ALL

REQUIRED CLEARANCES. COORDINATE LOCATION WITH PLUMBING DRAWINGS

l

DUCT MOUNTEDCO2 SENSOR

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

As indicated

9/21

/202

0 1:

56:0

8PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M101

1ST FLR HVAC DUCTPLAN

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

SCALE: 1/8" = 1'-0"1FIRST FLOOR HVAC PLAN -WEST

SCALE: 1/8" = 1'-0"2FIRST FLOOR HVAC PLAN -EAST

DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK AND VAV BOXES WHERE

REQUIRED IN HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.

4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.

5. ALL DUCT BRANCHES SHALL HAVE A VOLUME DAMPER IN THE BRANCH DUCTWORK LOCATED WITHIN ONE FOOT AFTER THE BRANCH OFF.

6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT PER ITS MANUFACTURER'S WRITTEN INSTRUCTIONS AND ADHERE TO ALL REQUIRED CLEARANCES.

0 4' 8'2'1/4" = 1'-0"M101

3 FIRST FLOOR HVAC PLAN - MECHANICAL ROOM PARTIAL PLAN

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 3: T LV - carrowconstruction.com

REF

.N

.I.C

.

1

2

3

4

5

6

B

bb

dd

A

cc

d

C

D

E

F

7

9

22

ee

aa

8

23

EF1

REFER TO PLAN1/M101 FOR DUCTWORK

CONTINUATION FROMAHU-1

AHU1

B

A

C

D

E

F

9 10 12 13 14 15 16 17 18 19 2120

22

AHU2

EF2 RG W/ PLENUM RETURN

(TYP.-ALL)

RG W/PLENUM RETURN(TYP.-ALL)

CD-110" NK375 CFM

CD-18" NK175 CFM (TYP.-5)

12x10 EA UPTO EF-3

12x10 EA UPTO EF-6

SA UPTO AHU-5

RA UPTO AHU-4

RA UPTO AHU-5

SA UPTO AHU-4

VAV5-4

VAV5-2

VAV5-3

VAV5-1

VAV5-7

VAV5-8

VAV5-6

VAV5-9

VAV5-11

VAV5-10

VAV5-12

VAV5-5

10x12 EA DN

14"Ø S/A

EG-16x6100 CFM(TYP.-2)

VAV5-13

AHU3

STAIR-2111A-2

OFFICE205

OFFICE206

ELEV.-2119-2

OFFICE204

20x18 SA DN30x18 RA DN

LD-110" NK250 CFM(TYP.-2)

CD-18" NK200 CFM

8"

10"10"

16x14

18x1

6 14x1210x10

LD-110" NK275 CFM(TYP.-2)

8"

8" 8"

8" 8"

8"

10"10"

CD-18" NK200 CFM(TYP.-6)

CD-18" NK150 CFM

CD-18" NK125 CFM

CD-18" NK200 CFM

CD-110" NK300 CFM(TYP.-2)

CD-18" NK200 CFM

CD-18" NK125 CFM

CD-110" NK300 CFM(TYP.-2)

CD-110" NK300 CFM

CD-18" NK150 CFM

CD-110" NK225 CFM

CD-18" NK125 CFM

CD-110" NK200 CFM

CD-16" NK50 CFM

CD-16" NK75 CFM

CD-18" NK225 CFM

LD-3, 250 CFM.REFER TO SCHEDULES SHEET M600 FOR MORE INFORMATION(TYP.-5)

EG-16x6 NK100 CFM

EG-16x675 CFM

EG-16x6

75 CFM

8x8

12x10

12x1214x1414x16

16x16

10"8"

10x14

10x1

2

10"

10"

6x1210x12

10"10"

6x108x10

8"8"

10"

12x1

2

8"

10"

8"

10x1

210

x14

10"

10"10" 10x1

2

10"

12x1

2 8"8"6" 10x10

10"

10x14

10x1

2

10"

10"

10"10"

10"

8"

8"

10x1214x12

12"

12x1

414

x14

30x2

0

10"6x128" 20x16

8"14"

8"

8"

8"

8"

8x1012x12

8"

8"

14x1

2

12"

20x1

824

x20

26x208x1210"

6x12

10"

6x8

6"

6"

6"

6"

8"

10x12

6x6

6x6

6x10

6x6

6x6

8x10

12x1

06x

6

AC4

10"

10x1

2

LD-110" NK250 CFM(TYP.-2)

LD-110" NK250 CFM(TYP.-2)

FD

FD

FD

VD(TYP.)

VD (TYP.)VD(TYP.)

VD(TYP.)

ALL CEILNG DIFFUSERS ANDRETURN GRILLES IN THIS ROOM

ARE TO BE HUNG FROM DECK BECAUSE DROP

CEILING WILL NOT BE INSTALLED(TYP.-6)

(MOUNTEDABOVEDOORWAY)

LINEAR DIFFUSERS SHALL HAVE TWO SLOTS WITH ONE SLOT'S AIRFLOW ANGLED AT WINDOW ABOVE AND OTHER SLOT'S AIRFLOW ANGLED AT WINDOW BELOW(TYP.-5)

6x8

46x2

0

RG-1

RG-1

RG-1

RG-1RG-1

RG-1

RG-1

RG-1

RG-1

RG-1RG-1

RG-1

RG-1

RG-1

RG-1

RG-1RG-1

6x10

46x20 IN PLENUM W/ WMS

RG-2, 18x12 FACESURFACE MOUNT ON SOFFIT RG-1

lDUCT MOUNTEDCO2 SENSOR

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

1/8" = 1'-0"

9/21

/202

0 1:

56:2

0PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M102

2ND FLR HVAC DUCTPLAN

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

SCALE: 1/8" = 1'-0"1SECOND FLOOR HVAC PLAN -WEST

SCALE: 1/8" = 1'-0"2SECOND FLOOR HVAC PLAN -EAST

DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK AND VAV BOXES WHERE

REQUIRED IN HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.

4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.

5. ALL DUCT BRANCHES SHALL HAVE A VOLUME DAMPER IN THE BRANCH DUCTWORK LOCATED WITHIN ONE FOOT AFTER THE BRANCH OFF.

6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT PER ITS MANUFACTURER'S WRITTEN INSTRUCTIONS AND ADHERE TO ALL REQUIRED CLEARANCES.

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 4: T LV - carrowconstruction.com

B

A

C

D

E

F

9 10 12 13 14 15 16 17 18 19 2120

22

AHU4

AHU5

EF3

EF6

CU4

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

1/8" = 1'-0"

9/21

/202

0 1:

56:3

2PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M103

TOP ROOF HVACDUCT PLAN

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

SCALE: 1/8" = 1'-0"1 ROOF HVAC PLAN - EAST

DRAWING NOTES:1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS.2. PROVIDE DUCTWORK TRANSITIONS TO ALL AIR HANDLER OPENINGS AND/OR CURB OPENINGS AS REQUIRED.3. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO MANUAL VOLUME DAMPERS IN DUCTWORK WHERE REQUIRED IN

HARD CEILINGS. VOLUME DAMPERS SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.

4. FINAL ROUTING OF DUCTWORK MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. DUCTWORK SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 5: T LV - carrowconstruction.com

REF

.N

.I.C

.

REF.

N.I.C.

UP

T LV

T LV

B

A

C

D

E

F

9 10 12 13 14 15 16 17 18 19 2120

22

ee

1 1/4" HWS1 1/4" HWR

1 1/2" HWR1 1/2" HWS

VAV3-3

VAV4-1

VAV4-3

VAV4-6

VAV4-7 VAV

4-13 VAV4-11

VAV4-12

VAV4-10

VAV3-12

VAV3-11

VAV3-10

VAV3-9

VAV3-8

VAV3-7

VAV3-6VAV

3-5

VAV3-4

VAV4-2

VAV4-4

VAV4-5

VAV4-8

1/2" HWR1/2" HWS

1/2" HWR1/2" HWS3/4" HWS

1/2" HWS1/2" HWR1/2" HWS

1/2" HWR1/2" HWR1/2" HWS

3-WAY

1/2" HWS1/2" HWR1/2" HWR

1/2" HWS1/2" HWR1/2" HWS

3-WAY

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR3/4" HWR1" HWR

1" HWS

1/2" HWR1/2" HWS

1" HWS

1" HWR

3/4" HWR3/4" HWS

1/2" HWS1/2" HWR

3/4" HWR3/4" HWS

1/2" HWR1/2" HWS

1/2" HWR1/2" HWS

VAV4-9

1/2" HWR1/2" HWS

1/2" HWR1/2" HWS

1/2" HWR1/2" HWS

1/2" HWS1/2" HWR

1" HWR

1" HWS

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

PLOTTER ROOM147

ACCOUNTING FILES152COPY / PRINT

ROOM146

FLEXWORKSTATIONS

118

STAFF TOILET151

KITCHENETTE117

SERVER ROOM148

OPEN SPACE116B

STAFF TOILET150

ADMINISTRATIONFILES

149 OPEN SPACE116C

OPEN SPACE116A

STAFF TOILET154

SAFETY STORAGE153

STAFF TOILET114

AV CLOSET108A

STAFF TOILET113

LOADING BAY134

OFFICE129

OFFICE126

OFFICE120

OFFICE140

OFFICE142

OFFICE139

OFFICE124

OFFICE125

OFFICE123

OFFICE121

OFFICE122

OFFICE127

OFFICE128

OFFICE131

OFFICE136

OFFICE135OFFICE

137

OFFICE143

OFFICE144

OFFICE130

CORRIDOR116

CORRIDOR111

ELEV.-1119-1

MECH145

STAIR-1111A-1

OFFICE138

CONFERENCEROOM

141

STAIR-1132-1

OFFICE133

3/4" HWR

1" HWS1" HWR

AC2

AC3

FIELD-ROUTE 1/2" CONDENSATE.

REFER TO DRAWING NOTES FOR

MORE INFORMATION

CU2

CU3

CUH3

REFER TO PARTIAL PLAN3/M111 ON THIS SHEET FOR DETAILS IN THIS AREA OF WORK

1 1/4" HWR1 1/4" HWS

1 1/4" HWS1 1/4" HWR

T VAV4-4

T VAV4-3

T VAV4-6

T VAV4-7

T VAV4-13

T VAV4-11

T VAV4-12T VAV

4-10

T VAV3-12

T VAV3-11

T VAV3-10

T VAV3-9

T VAV3-8

T VAV3-7

T VAV3-6

T VAV3-5

T VAV3-4

T VAV4-1

T VAV3-3

T VAV4-2

T VAV4-5

T VAV4-8

T VAV4-9

BAS PANEL

REMOTE DIFFERENTIALPRESSURE

TRANSMITTERDPT

ROUTE HWS&R DN IN WALL TOCUH AND/OR PROVIDE COSMETICPIPING ENCLOSURE TOCONCEAL PIPING. COORDINATEW/ ARCHITECT FOR ENCLOSUREMATERIAL, COLOR, ETC.(TYP.)

?

AC-1 &AC-2T-STATS

3/4" HWS&R UP TO CUH-2 IN STAIRWELL

ON 2ND FLOOR

3/4" HWR3/4" HWS

MOUNTED ONFLOORUNDERNEATHSTAIRS

MULTIMEDIACONFERENCEROOM-112CO2 SENSOR

CONFERENCE ROOM-141CO2 SENSOR

1

2

3

4

5

6

B

bb

dd

A

cc

d

C

D

E

F

7

9

22

ee

aa

8

23

VAV3-1

OFFICE103

STORAGE104

KITCHENETTE102

WOMEN107

JAN.106

MEN105

VESTIBULE109

VESTIBULE100

AV CLOSET108A

OFFICE115

EDUCATIONCENTER

101

3/4" HWR3/4" HWS

AC1

CU1

EUH2

1/2" HWS1/2" HWR

3/4" HWR3/4" HWS

FIELD-ROUTE 1/2" CONDENSATE.REFER TO DRAWING NOTES

FOR MORE INFORMATION

3-WAY

VAV3-2

AC-1T-STAT

AHU-1T-STAT

T VAV3-1

T VAV3-2

ROUTE CONDENSATE AND REFRIGERANTPIPING FROM AC-1 DOWN IN EXTERIOR

WALL AND PENETRATE EXTERIORWALL LOW NEAR GRADE

AHU-2 T-STAT

AHU-2 CO2 SENSOR

AHU-1 CO2 SENSOR

LOBBY-110CO2 SENSOR

E

F

12

22

1 1/4" HWS

1 1/4" HWR

1 1/2" HWR

1 1/2" HWS

B1

B2

2" HWR

2" HWS

HWP1

HWP2

AS-1

ET1

2" HWR UP

2" HWS UP OFFICE144

ELEV.-1119-1

MECH145

STAIR-1111A-1

UH1

1/2" HWR

1/2" HWS

BP1

BP2

1/2" HWR1/2" HWS

2 1/2" HWR

2 1/2" HWS

PF1

2 1/2" HWR

2 1/2" HWS

CUH1

2" HWS

2" HWS

2" HWR 2" HWR

2 1/2" HWR

2 1/2" HWS

BAS PANEL

SEE 2/M-111 FORPIPING CONTINUATIONS

MOUNTED ONFLOOR UNDERNEATHSTAIRS

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

As indicated

9/21

/202

0 1:

56:4

5PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M111

1ST FLR HYDRONICPIPING PLAN

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

0 4' 8'2'1/8" = 1'-0"M111

2 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - EAST

0 4' 8'2'1/8" = 1'-0"M111

1 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - WEST

DRAWING NOTES:1. SEE DRAWING M000 FOR LEGEND & ABBREVIATIONS.2. CONTRACTOR SHALL FIELD -ROUTE REFRIGERANT PIPING FROM DUCTLESS SPLIT SYSTEM INDOOR UNIT TO OUTDOOR

CONDENSING UNIT. SIZE AND INSULATE PIPING PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. COORDINATE WITH EQUIPMENT VENDOR TO ROUTE ALL REFRIGERANT PIPING WITHIN MAXIMUM EQUIVALENT LENGTH OF PIPING ALLOWED. CONTRACTOR SHALL PROVIDE EQUIPMENT VENDOR WITH FINAL LINE LENGTHS FOR FINAL PIPE SIZING, REFRIGERANT CHARGE, ETC.

3. FIELD ROUTE NEW CONDENSATE PIPING TO APPROVED DISCHARGE LOCATION. PROVIDE PLUGS ON ALL ELBOWS AND TEES.

4. ALL CONDENSATE IN SERVER ROOM SHALL NOT BE ROUTED OVER ANY ELECTRICAL EQUIPMENT AND ROUTED HIGH NEAR CEILNG.

5. CONTRACTOR SHALL PROVIDE WALL MOUNTED CONDENSATE PUMP FOR EACH WALL MOUNTED DUCTLESS SPLIT INDOOR UNIT ON THIS SHEET (AC-3 & AC-4). CONDENSATE PUMP TO BE ASPEN PUMPS MODEL ASP-MW-UNI, 1.2 GPH FLOW @ 33' TDH, 1/4" PUMP DISCHARGE, 115V/1∅/60Hz, 39" CABLE. PROVIDE WITH RESERVOIR OVERFLOW PROTECTION SWITCH AND FLOAT ACTIVATED SWITCH FOR ON/OFF OPERATION. PROVIDE 1/4" VINYL TUBE AND CHECK VALVE ON DISCHARGE. INSTALL PER MANUFACTURER'S INSTRUCTIONS.

6. INTENT IS TO PROVIDE A 3-WAY VALVE CONFIGURATION FOR ALL VAV BOXES AND/OR CABINET UNIT HEATERS AT THE END OF ALL PIPE RUNS.

7. FINAL ROUTING OF PIPING MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. PIPING SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.

8. PROVIDE SHUT-OFF VALVE AND COMBINATION SHUT-OFF/BALANCING VALVE ON ALL BRANCH PIPING TAKE-OFFS FOR BRANCHES TO MORE THAN ONE VAV BOX AND/OR UNIT HEATER. REFER TO DETAIL 7/M-202 FOR MORE INFORMATION.

9. PROVIDE BOILER MANUFACTURER RECOMMENDED CONDENSATE NEUTRALIZATION KIT PER BOILER AND ROUTE CONDENSATE DISCHARGE TO FLOOR DRAIN IN MECHANICAL ROOM.

10. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO VALVES IN PIPING AND VAV BOXES WHERE REQUIRED IN HARD CEILINGS. VALVES SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.

11. REFER TO CONTROL DRAWINGS FOR LOCATION OF CO2 SENSORS. CO2 SENSORS SHALL BE PLACED IN ALL DENSELY OCCUPIED SPACES (40 PEOPLE/SF OR MORE).

0 4' 8'2'1/4" = 1'-0"M111

3 FIRST FLOOR HVAC HYDRONIC PIPING PLAN - MECHANICAL ROOM PARTIAL PLAN

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 6: T LV - carrowconstruction.com

REF

.N

.I.C

.

B

A

C

D

E

F

9 10 12 13 14 15 16 17 18 19 2120

22

AHU2

VAV5-4

VAV5-2

VAV5-3

VAV5-1

VAV5-7

VAV5-8

VAV5-6

VAV5-9

VAV5-11

VAV5-10

VAV5-12

VAV5-5

VAV5-13

1/2" HWS

1/2" HWR1/2" HWR

1/2" HWS

1/2" HWR

1/2" HWS

3/4" HWS3/4" HWR

1" HWR1" HWS

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

1/2" HWS1/2" HWR

3/4" HWS3/4" HWR

1" HWS1" HWR

3/4" HWS3/4" HWR

1 1/4" HWS

1 1/4" HWR1 1/4" HWS

1 1/4" HWR

1/2" HWR 1/2" HWS1/2" HWR1/2" HWS

1/2" HWS

1/2" HWR

3/4" HWS3/4" HWR1/2" HWS

1/2" HWR

3-WAY

3-WAY

AHU3

CUH2

CUH4

2" HWR DN

2" HWS DN

2" HWR2" HWS

3/4" HWS 3/4" HWR1/2" HWR

1/2" HWS

3/4" HWS

3/4" HWR

CU4

(ON ROOF ABOVE)

AC4

(ON WALL ABOVECLOSET DOOR)

OFFICE204

HR FILES202

CONFERENCE ROOM203

OFFICE208

OFFICE207

OFFICE209

OFFICE212

OFFICE213

WORK ROOM /STORAGE / FLEX

211

OFFICE214

FUTURE OVERFLOW215

COPY210

CORRIDOR201

WOMEN218

MEN217

CORRIDOR201

ELEV.119

STORAGE219

JANITOR219A

STAIR111A

1 1/2" HWR1 1/2" HWS

FIELD-ROUTE 1/2"CONDENSATE.

REFER TODRAWING NOTES

FOR MOREINFORMATION

T VAV5-4

T VAV5-2

T VAV5-3

T VAV5-7

T VAV5-6

T VAV5-8

T VAV5-9 T VAV

5-11

T VAV5-12

T VAV5-10

T VAV5-13

T VAV5-5

T VAV5-1

3-WAY

3-WAY

BAS PANELIN CEILING

3/4" HWS&R FROM FLOORBELOW UP INTO CUH-2

PROVIDEWALL-MOUNTED

THERMOSTATFOR AC-4 IN

CLOSET

ROUTE HWS&R DN WALL TOCUH AND/OR PROVIDE COSMETIC

PIPING ENCLOSURE TOCONCEAL PIPING. COORDINATE

W/ ARCHITECT FOR ENCLOSUREMATERIAL, COLOR, ETC.

(TYP.)

BREAK ROOM-216CO2 SENSOR

CONFERENCEROOM-203CO2 SENSOR

ISSUED:

SUSTAINABLE DESIGN CONSULTINGSUSTAINABILITY CONSULTANT

1432 K STREET NW, 3RD FLOORWASHINGTON, DC 20005

202-667-1620 fax 202-667-1622

DEDC, LLCFIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175

SCALE:DATE:

DRAWN BY: PROJ MGR:

PROJECT NO:

PROJECT TITLE

SHEET TITLE

ISSUE BLOCK

COPYRIGHT © 2019

Delaware309 S Governors Ave

Dover, DE 19904302.734.7950

Maryland312 West Main St, Suite 300

Salisbury, MD 21801410.546.9100

North Carolina3333 Jaeckle Drive, Suite 102

Wilmington, NC 28403910.341.7600

www.beckermorgan.com

Rittenhouse Station250 South Main Street, Suite 109

Newark, DE 19711302.369.3700

JOHN R. FARINA P.E.DELAWARE PE# 13559

ISSUEFOR BID

09/22/2020

1/8" = 1'-0"

9/21

/202

0 1:

57:0

2PM

\\ded

csrv

06\ u

sers

\rmal

in\M

y D

ocum

e nts

\R19

DSW

A A d

min

19 P

022_

rmal

in6C

3 LD

.rvt

M112

2ND FLR HYDRONICPIPING PLAN

JRFRWM

07-01-20202018230.00

DOVER, DELAWARE

DSWAADMINISTRATIONBUILDING

0 4' 8'2'1/8" = 1'-0"M112

1 SECOND FLOOR HVAC HYDRONIC PIPING PLAN - EAST

DRAWING NOTES:1. SEE DRAWING M000 FOR LEGEND & ABBREVIATIONS.2. CONTRACTOR SHALL FIELD -ROUTE REFRIGERANT PIPING FROM DUCTLESS SPLIT SYSTEM INDOOR UNIT TO OUTDOOR

CONDENSING UNIT. SIZE AND INSULATE PIPING PER MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. COORDINATE WITH EQUIPMENT VENDOR TO ROUTE ALL REFRIGERANT PIPING WITHIN MAXIMUM EQUIVALENT LENGTH OF PIPING ALLOWED. CONTRACTOR SHALL PROVIDE EQUIPMENT VENDOR WITH FINAL LINE LENGTHS FOR FINAL PIPE SIZING, REFRIGERANT CHARGE, ETC.

3. FIELD ROUTE NEW CONDENSATE PIPING TO APPROVED DISCHARGE LOCATION. PROVIDE PLUGS ON ALL ELBOWS AND TEES.

4. ALL CONDENSATE IN ELEVATOR MACHINE CLOSET SHALL NOT BE ROUTED OVER ANY ELECTRICAL EQUIPMENT AND ROUTED HIGH NEAR CEILNG.

5. CONTRACTOR SHALL PROVIDE WALL MOUNTED CONDENSATE PUMP FOR THE WALL MOUNTED DUCTLESS SPLIT INDOOR UNIT ON THIS SHEET (AC-5). CONDENSATE PUMP TO BE ASPEN PUMPS MODEL ASP-MW-UNI, 1.2 GPH FLOW @ 33' TDH, 1/4" PUMP DISCHARGE, 115V/1∅/60Hz, 39" CABLE. PROVIDE WITH RESERVOIR OVERFLOW PROTECTION SWITCH AND FLOAT ACTIVATED SWITCH FOR ON/OFF OPERATION. PROVIDE 1/4" VINYL TUBE AND CHECK VALVE ON DISCHARGE. INSTALL PER MANUFACTURER'S INSTRUCTIONS.

6. INTENT IS TO PROVIDE A 3-WAY VALVE CONFIGURATION FOR ALL VAV BOXES AND/OR CABINET UNIT HEATERS AT THE END OF ALL PIPE RUNS.

7. FINAL ROUTING OF PIPING MAY DIFFER IN FIELD THAN SHOWN ON PLANS AFTER COMPLETION OF BUILDING CONSTRUCTION. PIPING SHALL BE ROUTED TO AVOID STRUCTURAL BEAMS, TRUSSES, SOFFITS, ETC.

8. PROVIDE SHUT-OFF VALVE AND COMBINATION SHUT-OFF/BALANCING VALVE ON ALL BRANCH PIPING TAKE-OFFS FOR BRANCHES TO MORE THAN ONE VAV BOX AND/OR UNIT HEATER. REFER TO DETAIL 7/M-202 FOR MORE INFORMATION.

9. PROVIDE LOCKABLE ACCESS DOORS FOR ACCESS TO VALVES IN PIPING AND VAV BOXES WHERE REQUIRED IN HARD CEILINGS. VALVES SHALL BE GROUPED TOGETHER WHERE FEASIBLE TO MINIMIZE THE AMOUNT OF ACCESS DOORS REQUIRED.

10. REFER TO CONTROL DRAWINGS FOR LOCATION OF CO2 SENSORS. CO2 SENSORS SHALL BE PLACED IN ALL DENSELY OCCUPIED SPACES (40 PEOPLE/SF OR MORE).

Mark Date Description1 02/28/2020 ISSUE FOR PERMIT2 09/22/2020 ISSUE FOR BID

Page 7: T LV - carrowconstruction.com
Page 8: T LV - carrowconstruction.com
Page 9: T LV - carrowconstruction.com
Page 10: T LV - carrowconstruction.com
Page 11: T LV - carrowconstruction.com
Page 12: T LV - carrowconstruction.com
Page 13: T LV - carrowconstruction.com
Page 14: T LV - carrowconstruction.com
Page 15: T LV - carrowconstruction.com
Page 16: T LV - carrowconstruction.com