7/29/2019 System Air Conditioning 2
1/15
4.0 Air Conditioning System
Air conditioning for people is the control of temperature, humidity, air movement and
air cleanliness, heat radiation sometimes, normally with mechanical means, to achieve
human thermal comfort. Air conditioning systems can be categorized according to the
means by which the controllable cooling is accomplished in the conditioned space. They
are further segregated to accomplish specific purposes by special equipment
arrangement. In selecting a suitable air conditioning system for a particular application,
consideration should also vent to the following:
System constraints : Cooling load, Zoning requirements, Heating and ventilation
Architectural Constraints : Size and appearance of terminal devices, acceptablenoise level, Space available to house equipment and its location relative to the
conditioned space, acceptability of components obtruding into the conditioned space
Financial Constraints : Capital cost, Operating cost, Maintenance cost
There are four basic system categories of air conditioning, first is central chilled
water air conditioning systems used all air systems. Second, central chilled water air
conditioning systems used all air and water systems. Third, central chilled water airconditioning systems used all water systems, including cooling towers. Fourth is,directexpansion systems such as direct expansion of refrigerant, without the chilled water
cooling medium.
4.1 Central Chilled Water Air Conditioning used all Air System
4.1.1 Single zone
The all-air single-zone air conditioning system is the basic central system which can
supply a constant air volume or a variable air volume at low, medium or high pressure.
Normally, the equipment is located outside the conditioned space but can also beinstalled within the conditioned are if conditions permit. Typical applications include:
Space with uniform loads
Small spaces requiring precision control
Multiple systems for large areas
7/29/2019 System Air Conditioning 2
2/15
Figure 1 : Single Zone system
4.1.2 Reheat
The reheat system is a modification of the single-zone system. It provides:-
Zone or space control for areas of unequal loading.
Heating or cooling of perimeter areas with different exposures.
Close control for process or comfort applications. In the reheat system, heat is
added as a secondary process to either preconditioned primary air or recirculated
room air. The heating medium can be hot water, steam or electricity.
The advantage for this type is, it can closely controls space conditions, but this
advantages for this type system, it is very expensive to operate.
Figure 2 : Reheat system
7/29/2019 System Air Conditioning 2
3/15
4.1.3 Variable Air Volume
The variable air volume system compensates for varying cooling loads by regulating the
volume of cooling air supplied through a single duct.
a. Simple Variable Air Volume (VAV)
A simple VAV system typically cools only and has no requirement for simultaneous
heating and cooling in various zones.
Figure 3 : Simple Variable Air Volume (VAV)
b. Variable Air Volume Reheat
It integrates heating at or near the terminal units. It is applied to systems requiring
full heating and cooling flexibility in interior and exterior zones. Heating is turned on
when the air flow reaches a predetermined minimum.
Figure 4 : Variable Air Volume Reheat
7/29/2019 System Air Conditioning 2
4/15
Advantages
When combined with a perimeter heating system, it offers inexpensive temperature
control for multiple zoning and a high degree of simultaneous heating-cooling
flexibility.
Capital cost is lower since diversities of loads from lights, occupancy, solar and
equipment of as much as 30% are permitted.
Virtually self-balancing.
It is easy and inexpensive to subdivide into new zones and to handle increased loads
with new tenancy or usage if load does not exceed the original design simultaneous
peak.
No zoning is required in central equipment.
Lower operating cost because Fans run long hours at reduced volume
Refrigeration, heating and pumping matches diversity of loads
Unoccupied areas may be fully cut-off
Reduced noise level when the system is running at off-peak loads.
Allows simultaneous heating and cooling without seasonal changeover.
4.1.4 Dual Duct
The dual-duct system employs two air ducts to supply cold air and warm air to a mixing
terminal unit which proportions the cold and warm air in response to a thermostat
located in the conditioned space. The system is well suited to provide temperature
control for individual spaces or zones.
Figure 5 : Dual Duct System
7/29/2019 System Air Conditioning 2
5/15
Advantages (in addition to those common to all air systems)
Systems with terminal volume regulation are self-balancing.
Zoning of central equipment is not required.
Instant temperature response is achieved because of simultaneous availability of
cold and warm air at each terminal unit.
No seasonal changeover is necessary.
Disadvantages
Initial cost is usually higher than other VAV systems.
Does not operate as economically as other VAV systems.
4.1.5 Multi-zone
The multi-zone system applies to a relatively small number of zones served by a single,
central air-handling unit. Different zone requirements are met by mixing cold and warm
air through zone dampers at the central air handler in response to zone thermostats.
Figure 6 : Multi-zone System
Advantages
Easy to balance.
Air transmission and distribution is simplified.
7/29/2019 System Air Conditioning 2
6/15
4.2 Central chilled water air conditioning systems used air and water systems
4.2.1 Induction
The inducting system is designed for use in perimeter rooms of multi - storey, multi-room
building that may have reversing sensible heat characteristics. It is especially adapted
to handle the loads of skyscrapers with minimum space requirements for mechanical
equipment. In the induction system, ducted primary air is fed into a small plenum
chamber where its pressure is reduced by means of a suitable damper to the level
required at the nozzles. The plenum is acoustically treated to attenuate part of the noise
generated in the duct system and in the unit. The primary air is then delivered through
nozzles as high velocity jets which induce secondary air from the room and over the
secondary coil. Induction units are usually installed at a perimeter wall under a window.
Some hotel rooms are providing with induction coils.
Figure 7 : Induction System
The induction system employs air ducts to convey treated air with higher pressure levels
and of the right adjustable quantities to various cooling/heating coil units. These coil
units are built in with induction nozzles such that when high pressure air goes through
7/29/2019 System Air Conditioning 2
7/15
them, air room the room is inducted across the fin surface of the water-circulated coils.
This inducted air stream is either cooled or heated after passing through the coil, and
then mixed with the air coming out of the nozzle. The right quantity of high pressure air is
adjusted automatically in response to a thermostat located in the conditioned space. The
system is well suited to provide temperature control for individual spaces or zones.
Advantages
Individual room temperature control.
Separate sources of heating and cooling for each space available as needed to
satisfy a wide range of load variations.
Low distribution system space required as a result of reducing the air supply by
use of secondary water for cooling and high velocity air design.
Reduced size of central air handling equipment.
Dehumidification & filtration performed in a central plant room remote from
conditioned space.
Outdoor air supply is positive. Minimal maintenance required for individual
induction units which have no moving parts.
Air duct dimensions are smaller than VAV systems or CAV systems
Zoning of central equipment is not required.
No fan comes together with the coil, making the conditioned space quiet.
Disadvantages
Limited to perimeter space.
The primary air supply is usually constant with no provision for shutoff.
Not applicable to spaces with high exhaust requirement.
Higher energy consumption due to increased power required by the primary
pressure drop in the terminal units.
Controls tend to be more complex than for all-air systems.
A low chilled water temperature is needed to control space humidity adequately.
Seasonal changeover is necessary.
Initial cost is usually higher than fan coil systems.
7/29/2019 System Air Conditioning 2
8/15
4.2.2 Fan Coil
The fan-coil system is similar to the inducting system, with the induction unit replaced by
the fan-coil unit. The basic elements of the fan-coil units are a finned-tube coil and a fan
section. The fan section recirculates air continuously from within the perimeter space
through the coil which is supplied with either hot or chilled water. Auxiliary air may be
delivered to the conditioned space for dehumidification and ventilation purposes.
Figure 8 : Fan Coil system
Advantages
System can be operated with the primary air turned off.
The air velocity is fairly constant regardless of the primary air quantity.
Primary air can either connect directly to fan-coil unit or supply the room
separately.
4.2.3 Two-pipe
In two-pipe systems for induction coil, fan-coil or radiant panel systems, the water
distribution circuit consists of one supply and one return pipe. The secondary water is
cold in summer and intermediate seasons and warm in winter. The primary air quantity
is fixed and the primary air temperature is varied in reverse proportion to outside
temperature to provide the necessary amount of heating during summer and
intermediate seasons. During winter cycle operation, the primary air is preheated and
supplied at about 10C to provide a source of cooling.
7/29/2019 System Air Conditioning 2
9/15
Figure 9 : Two-pipe system
Advantages Usually less expensive to install than four pipe systems.
Disadvantages
Less capable of handling widely varying loads or providing widely varying choice of
room temperature than four-pipe systems.
Cumbersome to change over.
More costly to operate than four-pipe systems.
4.3 Central chilled water air conditioning systems used to all water systems, including
cooling towers.
4.3.1 Fan-coil units
Use when heating and cooling loads that proves to be too great for induction units can
be dealt with by separate fan and coil units fitted into the false ceiling of each room or
buildings module. Better air filtration can be achieved than with the induction unit. A
removable access hatch below the unit is required to facilitate motor and filter
maintenance.
Care is taken to match the fan-generated noise to the required acoustic environment. As
with the other systems, the extracted air can be taken through ventilated luminaires to
remove the lighting heat output at source and avoid overheating the room. The supply
and extract ducts only carry the fresh air. All recirculation is confined to the room
7/29/2019 System Air Conditioning 2
10/15
Figure 10 : Fan coil unit installation in false ceiling and vertical unit for fan coil unit
system
4.3.2 Water cooling tower
A water cooling tower cools the water entering it from 35 deg. C to 30 deg. C nominally.
The warmer water is sprayed inside the cooling tower amidst the stream of an upward
air flow produced by the fan at the top of the tower. The air stream going out carrieswater particles. These water particles should not be taken into buildings, to avoid
Legionnaire disease to occur. Condenser water pumps move condenser water through
this circuit. Water in this circuit has to be treated. There is water loss to atmosphere in
using cooling towers.
7/29/2019 System Air Conditioning 2
11/15
4.4 Direct expansion Systems
4.4.1 Window air conditioner
A window unit is an encased assembly designed primarily for mounting in a window,
through a wall, or as a console. These units are designed for comfort cooling and to
provide delivery of conditioned air to a room either without ducts or with very short ducts.
They include a prime source of refrigeration, dehumidification, means for circulating and
cleaning air, and may also include means for ventilating, and/or exhausting and heating.
7/29/2019 System Air Conditioning 2
12/15
Figure 11 : Direct Expansion System for window air conditioner
In a window air conditioner, the indoor unit and outdoor unit of the split system is put into
one single unit. The refrigerant compressor now is part of the machine locating at the
window area. Since this compressor gives out most noise, among other components, the
window unit will make the room acoustically inferior to other air conditioning systems.
Fresh air exchange for the room can be provided by:-
a. setting the ventilator switch of the window air conditioner to open position.
b. installing a ventilating extract fan in the room to extract room air to outside
caution- not to oversize the fan.
c. naturally leaking of air in and out of the room.
4.4.2 Unitary and Rooftop Air Conditioners.
These are commonly air-cooled units. The units are the floor are standing type designed
for installation outdoors or on the roof. A supply air duct and a return air duct are to be
connected to the cooling unit.Be used for general air conditioning of stores, residences,schools, offices, etc. Particularly suitable for single flat building with extensive floor
areas. A remote controller should be installed on an easily accessible wall, incorporating
a temperature selection switch & thermostat.
7/29/2019 System Air Conditioning 2
13/15
Figure 12 : Direct Expansion System for Unitary and Rooftop Air Conditioners.
4.4.3 Split type and package air conditioning systems
A package air conditioning systems are used in factory assembled (floor mounting)
package, placed indoor, containing direct expansion coil, controls, fan and compressor,
with the condenser remotely placed outdoor. A package air unit is a self-contained air-
conditioning unit comprising a hermetically sealed refrigeration compressor, a refrigerant
evaporator coil to cool room air, a hot-water or electric resistance heater battery, a filter,
a water or air cooled refrigerant condenser and automatic controls. Packaged units caneither be completely self-contained, needing only a supply of electricity, or piped to
central heating and condenser cooling-water plant. Small units are fitted into an external
wall and have a change-over valve to reverse the refrigerant flow direction. This enables
the unit to cool the internal air in summer and the external air in winter.
Heat rejected from the condenser is used to heat the internal environment in winter. In
this mode of operation it is called a heat pump. A separate ventilation system may be
needed. Compressor and fan noise levels are compared with the acceptable background
acoustic environment. Maintenance requirement are filter cleaning, bearing lubrication
and replacement of the compressor when it becomes too noisy or breaks down.
Split system unit have a separate condenser install outside the building. Two refrigerant
pipes of small diameter connect the internal and external equipment boxes. This allows
greater flexibility in siting noise-producing compressor. Ducted models provide
7/29/2019 System Air Conditioning 2
14/15
conditioning and ventilation and are often sited on flat roofs. Figure 5 shows a typical
through-the-wall installation. Split system used at same place with package air system.
Figure 13 : Packaged air-conditioning unit.
4.4.4 Heat pumps
The term heat pump, as applied to a year-round air conditioning system, commonly
denotes a system in which refrigeration equipment is used in such a manner that heat is
taken from a heat source and given up to the conditioned space when heating service is
wanted, and is removed from the space and discharged to a heat sink when cooling and
dehumidification are desired.
Heat pumps for air conditioning service may be classified according to
a. type of heat source and sink.
b. Heating and cooling distribution fluid.
c. Type of thermodynamic cycle.
d. Type of building structure.
e. Size and configuration.
7/29/2019 System Air Conditioning 2
15/15
4.4.4.1 Air-to-Air Heat Pumps
The air-to-air heat pump is the most common type of heat pumps. It is particularly
suitable for factory-built unitary heat pumps, and has been widely used for residential
and commercial application. Air is used as the heat source and heat sink. Extended
surface, forced convection heat transfer coils are normally employed to transfer the heat
between the air and the refrigerant. When selecting or designing an air-source heat pup,
two factors in particular must be taken into consideration:
a. the variation in temperature experienced in a given locality.
b. the formation of frost.
4.4.4.2 Water-source Heat Pumps
The water-source heat pump uses water and air as the heat source or heat sink
depending on the mode of operation. When cooling, water is used as the heat sink, and
the heat pump operates as a water-cooled air conditioner. When heating, water is used
as the heat source and the equipment operates as a water chiller. The water-source
heat pump is suitable for many types of multi-room buildings, including office buildings,
hotels, schools, apartment buildings, manufacturing facilities and hospitals.
Advantages
Affords opportunity for energy conservation by recovering heat from interior
zones and/or waste heat and by storing excess heat from daytime cooling for
night time heating.
No wall openings required.
Longer expected life than air-cooled heat pumps.
Lower noise level because condenser fans are eliminated.
Energy for the heat pumps can be metered directly to each tenant.
Total life cycle cost frequently compares favorably to central systems when
considering relative installed cost, operating costs, and system life.
Disadvantages
Space required for boiler, heat exchanger, pumps and heat rejecter.
Higher initial cost than for most other multiple-packaged unit systems.
Reduced air flow can cause the heat pump to cycle cutout. Good filter
maintenance is imperative.