Top Banner

of 15

System Air Conditioning 2

Apr 03, 2018

Download

Documents

Azmi Suhardi
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/29/2019 System Air Conditioning 2

    1/15

    4.0 Air Conditioning System

    Air conditioning for people is the control of temperature, humidity, air movement and

    air cleanliness, heat radiation sometimes, normally with mechanical means, to achieve

    human thermal comfort. Air conditioning systems can be categorized according to the

    means by which the controllable cooling is accomplished in the conditioned space. They

    are further segregated to accomplish specific purposes by special equipment

    arrangement. In selecting a suitable air conditioning system for a particular application,

    consideration should also vent to the following:

    System constraints : Cooling load, Zoning requirements, Heating and ventilation

    Architectural Constraints : Size and appearance of terminal devices, acceptablenoise level, Space available to house equipment and its location relative to the

    conditioned space, acceptability of components obtruding into the conditioned space

    Financial Constraints : Capital cost, Operating cost, Maintenance cost

    There are four basic system categories of air conditioning, first is central chilled

    water air conditioning systems used all air systems. Second, central chilled water air

    conditioning systems used all air and water systems. Third, central chilled water airconditioning systems used all water systems, including cooling towers. Fourth is,directexpansion systems such as direct expansion of refrigerant, without the chilled water

    cooling medium.

    4.1 Central Chilled Water Air Conditioning used all Air System

    4.1.1 Single zone

    The all-air single-zone air conditioning system is the basic central system which can

    supply a constant air volume or a variable air volume at low, medium or high pressure.

    Normally, the equipment is located outside the conditioned space but can also beinstalled within the conditioned are if conditions permit. Typical applications include:

    Space with uniform loads

    Small spaces requiring precision control

    Multiple systems for large areas

  • 7/29/2019 System Air Conditioning 2

    2/15

    Figure 1 : Single Zone system

    4.1.2 Reheat

    The reheat system is a modification of the single-zone system. It provides:-

    Zone or space control for areas of unequal loading.

    Heating or cooling of perimeter areas with different exposures.

    Close control for process or comfort applications. In the reheat system, heat is

    added as a secondary process to either preconditioned primary air or recirculated

    room air. The heating medium can be hot water, steam or electricity.

    The advantage for this type is, it can closely controls space conditions, but this

    advantages for this type system, it is very expensive to operate.

    Figure 2 : Reheat system

  • 7/29/2019 System Air Conditioning 2

    3/15

    4.1.3 Variable Air Volume

    The variable air volume system compensates for varying cooling loads by regulating the

    volume of cooling air supplied through a single duct.

    a. Simple Variable Air Volume (VAV)

    A simple VAV system typically cools only and has no requirement for simultaneous

    heating and cooling in various zones.

    Figure 3 : Simple Variable Air Volume (VAV)

    b. Variable Air Volume Reheat

    It integrates heating at or near the terminal units. It is applied to systems requiring

    full heating and cooling flexibility in interior and exterior zones. Heating is turned on

    when the air flow reaches a predetermined minimum.

    Figure 4 : Variable Air Volume Reheat

  • 7/29/2019 System Air Conditioning 2

    4/15

    Advantages

    When combined with a perimeter heating system, it offers inexpensive temperature

    control for multiple zoning and a high degree of simultaneous heating-cooling

    flexibility.

    Capital cost is lower since diversities of loads from lights, occupancy, solar and

    equipment of as much as 30% are permitted.

    Virtually self-balancing.

    It is easy and inexpensive to subdivide into new zones and to handle increased loads

    with new tenancy or usage if load does not exceed the original design simultaneous

    peak.

    No zoning is required in central equipment.

    Lower operating cost because Fans run long hours at reduced volume

    Refrigeration, heating and pumping matches diversity of loads

    Unoccupied areas may be fully cut-off

    Reduced noise level when the system is running at off-peak loads.

    Allows simultaneous heating and cooling without seasonal changeover.

    4.1.4 Dual Duct

    The dual-duct system employs two air ducts to supply cold air and warm air to a mixing

    terminal unit which proportions the cold and warm air in response to a thermostat

    located in the conditioned space. The system is well suited to provide temperature

    control for individual spaces or zones.

    Figure 5 : Dual Duct System

  • 7/29/2019 System Air Conditioning 2

    5/15

    Advantages (in addition to those common to all air systems)

    Systems with terminal volume regulation are self-balancing.

    Zoning of central equipment is not required.

    Instant temperature response is achieved because of simultaneous availability of

    cold and warm air at each terminal unit.

    No seasonal changeover is necessary.

    Disadvantages

    Initial cost is usually higher than other VAV systems.

    Does not operate as economically as other VAV systems.

    4.1.5 Multi-zone

    The multi-zone system applies to a relatively small number of zones served by a single,

    central air-handling unit. Different zone requirements are met by mixing cold and warm

    air through zone dampers at the central air handler in response to zone thermostats.

    Figure 6 : Multi-zone System

    Advantages

    Easy to balance.

    Air transmission and distribution is simplified.

  • 7/29/2019 System Air Conditioning 2

    6/15

    4.2 Central chilled water air conditioning systems used air and water systems

    4.2.1 Induction

    The inducting system is designed for use in perimeter rooms of multi - storey, multi-room

    building that may have reversing sensible heat characteristics. It is especially adapted

    to handle the loads of skyscrapers with minimum space requirements for mechanical

    equipment. In the induction system, ducted primary air is fed into a small plenum

    chamber where its pressure is reduced by means of a suitable damper to the level

    required at the nozzles. The plenum is acoustically treated to attenuate part of the noise

    generated in the duct system and in the unit. The primary air is then delivered through

    nozzles as high velocity jets which induce secondary air from the room and over the

    secondary coil. Induction units are usually installed at a perimeter wall under a window.

    Some hotel rooms are providing with induction coils.

    Figure 7 : Induction System

    The induction system employs air ducts to convey treated air with higher pressure levels

    and of the right adjustable quantities to various cooling/heating coil units. These coil

    units are built in with induction nozzles such that when high pressure air goes through

  • 7/29/2019 System Air Conditioning 2

    7/15

    them, air room the room is inducted across the fin surface of the water-circulated coils.

    This inducted air stream is either cooled or heated after passing through the coil, and

    then mixed with the air coming out of the nozzle. The right quantity of high pressure air is

    adjusted automatically in response to a thermostat located in the conditioned space. The

    system is well suited to provide temperature control for individual spaces or zones.

    Advantages

    Individual room temperature control.

    Separate sources of heating and cooling for each space available as needed to

    satisfy a wide range of load variations.

    Low distribution system space required as a result of reducing the air supply by

    use of secondary water for cooling and high velocity air design.

    Reduced size of central air handling equipment.

    Dehumidification & filtration performed in a central plant room remote from

    conditioned space.

    Outdoor air supply is positive. Minimal maintenance required for individual

    induction units which have no moving parts.

    Air duct dimensions are smaller than VAV systems or CAV systems

    Zoning of central equipment is not required.

    No fan comes together with the coil, making the conditioned space quiet.

    Disadvantages

    Limited to perimeter space.

    The primary air supply is usually constant with no provision for shutoff.

    Not applicable to spaces with high exhaust requirement.

    Higher energy consumption due to increased power required by the primary

    pressure drop in the terminal units.

    Controls tend to be more complex than for all-air systems.

    A low chilled water temperature is needed to control space humidity adequately.

    Seasonal changeover is necessary.

    Initial cost is usually higher than fan coil systems.

  • 7/29/2019 System Air Conditioning 2

    8/15

    4.2.2 Fan Coil

    The fan-coil system is similar to the inducting system, with the induction unit replaced by

    the fan-coil unit. The basic elements of the fan-coil units are a finned-tube coil and a fan

    section. The fan section recirculates air continuously from within the perimeter space

    through the coil which is supplied with either hot or chilled water. Auxiliary air may be

    delivered to the conditioned space for dehumidification and ventilation purposes.

    Figure 8 : Fan Coil system

    Advantages

    System can be operated with the primary air turned off.

    The air velocity is fairly constant regardless of the primary air quantity.

    Primary air can either connect directly to fan-coil unit or supply the room

    separately.

    4.2.3 Two-pipe

    In two-pipe systems for induction coil, fan-coil or radiant panel systems, the water

    distribution circuit consists of one supply and one return pipe. The secondary water is

    cold in summer and intermediate seasons and warm in winter. The primary air quantity

    is fixed and the primary air temperature is varied in reverse proportion to outside

    temperature to provide the necessary amount of heating during summer and

    intermediate seasons. During winter cycle operation, the primary air is preheated and

    supplied at about 10C to provide a source of cooling.

  • 7/29/2019 System Air Conditioning 2

    9/15

    Figure 9 : Two-pipe system

    Advantages Usually less expensive to install than four pipe systems.

    Disadvantages

    Less capable of handling widely varying loads or providing widely varying choice of

    room temperature than four-pipe systems.

    Cumbersome to change over.

    More costly to operate than four-pipe systems.

    4.3 Central chilled water air conditioning systems used to all water systems, including

    cooling towers.

    4.3.1 Fan-coil units

    Use when heating and cooling loads that proves to be too great for induction units can

    be dealt with by separate fan and coil units fitted into the false ceiling of each room or

    buildings module. Better air filtration can be achieved than with the induction unit. A

    removable access hatch below the unit is required to facilitate motor and filter

    maintenance.

    Care is taken to match the fan-generated noise to the required acoustic environment. As

    with the other systems, the extracted air can be taken through ventilated luminaires to

    remove the lighting heat output at source and avoid overheating the room. The supply

    and extract ducts only carry the fresh air. All recirculation is confined to the room

  • 7/29/2019 System Air Conditioning 2

    10/15

    Figure 10 : Fan coil unit installation in false ceiling and vertical unit for fan coil unit

    system

    4.3.2 Water cooling tower

    A water cooling tower cools the water entering it from 35 deg. C to 30 deg. C nominally.

    The warmer water is sprayed inside the cooling tower amidst the stream of an upward

    air flow produced by the fan at the top of the tower. The air stream going out carrieswater particles. These water particles should not be taken into buildings, to avoid

    Legionnaire disease to occur. Condenser water pumps move condenser water through

    this circuit. Water in this circuit has to be treated. There is water loss to atmosphere in

    using cooling towers.

  • 7/29/2019 System Air Conditioning 2

    11/15

    4.4 Direct expansion Systems

    4.4.1 Window air conditioner

    A window unit is an encased assembly designed primarily for mounting in a window,

    through a wall, or as a console. These units are designed for comfort cooling and to

    provide delivery of conditioned air to a room either without ducts or with very short ducts.

    They include a prime source of refrigeration, dehumidification, means for circulating and

    cleaning air, and may also include means for ventilating, and/or exhausting and heating.

  • 7/29/2019 System Air Conditioning 2

    12/15

    Figure 11 : Direct Expansion System for window air conditioner

    In a window air conditioner, the indoor unit and outdoor unit of the split system is put into

    one single unit. The refrigerant compressor now is part of the machine locating at the

    window area. Since this compressor gives out most noise, among other components, the

    window unit will make the room acoustically inferior to other air conditioning systems.

    Fresh air exchange for the room can be provided by:-

    a. setting the ventilator switch of the window air conditioner to open position.

    b. installing a ventilating extract fan in the room to extract room air to outside

    caution- not to oversize the fan.

    c. naturally leaking of air in and out of the room.

    4.4.2 Unitary and Rooftop Air Conditioners.

    These are commonly air-cooled units. The units are the floor are standing type designed

    for installation outdoors or on the roof. A supply air duct and a return air duct are to be

    connected to the cooling unit.Be used for general air conditioning of stores, residences,schools, offices, etc. Particularly suitable for single flat building with extensive floor

    areas. A remote controller should be installed on an easily accessible wall, incorporating

    a temperature selection switch & thermostat.

  • 7/29/2019 System Air Conditioning 2

    13/15

    Figure 12 : Direct Expansion System for Unitary and Rooftop Air Conditioners.

    4.4.3 Split type and package air conditioning systems

    A package air conditioning systems are used in factory assembled (floor mounting)

    package, placed indoor, containing direct expansion coil, controls, fan and compressor,

    with the condenser remotely placed outdoor. A package air unit is a self-contained air-

    conditioning unit comprising a hermetically sealed refrigeration compressor, a refrigerant

    evaporator coil to cool room air, a hot-water or electric resistance heater battery, a filter,

    a water or air cooled refrigerant condenser and automatic controls. Packaged units caneither be completely self-contained, needing only a supply of electricity, or piped to

    central heating and condenser cooling-water plant. Small units are fitted into an external

    wall and have a change-over valve to reverse the refrigerant flow direction. This enables

    the unit to cool the internal air in summer and the external air in winter.

    Heat rejected from the condenser is used to heat the internal environment in winter. In

    this mode of operation it is called a heat pump. A separate ventilation system may be

    needed. Compressor and fan noise levels are compared with the acceptable background

    acoustic environment. Maintenance requirement are filter cleaning, bearing lubrication

    and replacement of the compressor when it becomes too noisy or breaks down.

    Split system unit have a separate condenser install outside the building. Two refrigerant

    pipes of small diameter connect the internal and external equipment boxes. This allows

    greater flexibility in siting noise-producing compressor. Ducted models provide

  • 7/29/2019 System Air Conditioning 2

    14/15

    conditioning and ventilation and are often sited on flat roofs. Figure 5 shows a typical

    through-the-wall installation. Split system used at same place with package air system.

    Figure 13 : Packaged air-conditioning unit.

    4.4.4 Heat pumps

    The term heat pump, as applied to a year-round air conditioning system, commonly

    denotes a system in which refrigeration equipment is used in such a manner that heat is

    taken from a heat source and given up to the conditioned space when heating service is

    wanted, and is removed from the space and discharged to a heat sink when cooling and

    dehumidification are desired.

    Heat pumps for air conditioning service may be classified according to

    a. type of heat source and sink.

    b. Heating and cooling distribution fluid.

    c. Type of thermodynamic cycle.

    d. Type of building structure.

    e. Size and configuration.

  • 7/29/2019 System Air Conditioning 2

    15/15

    4.4.4.1 Air-to-Air Heat Pumps

    The air-to-air heat pump is the most common type of heat pumps. It is particularly

    suitable for factory-built unitary heat pumps, and has been widely used for residential

    and commercial application. Air is used as the heat source and heat sink. Extended

    surface, forced convection heat transfer coils are normally employed to transfer the heat

    between the air and the refrigerant. When selecting or designing an air-source heat pup,

    two factors in particular must be taken into consideration:

    a. the variation in temperature experienced in a given locality.

    b. the formation of frost.

    4.4.4.2 Water-source Heat Pumps

    The water-source heat pump uses water and air as the heat source or heat sink

    depending on the mode of operation. When cooling, water is used as the heat sink, and

    the heat pump operates as a water-cooled air conditioner. When heating, water is used

    as the heat source and the equipment operates as a water chiller. The water-source

    heat pump is suitable for many types of multi-room buildings, including office buildings,

    hotels, schools, apartment buildings, manufacturing facilities and hospitals.

    Advantages

    Affords opportunity for energy conservation by recovering heat from interior

    zones and/or waste heat and by storing excess heat from daytime cooling for

    night time heating.

    No wall openings required.

    Longer expected life than air-cooled heat pumps.

    Lower noise level because condenser fans are eliminated.

    Energy for the heat pumps can be metered directly to each tenant.

    Total life cycle cost frequently compares favorably to central systems when

    considering relative installed cost, operating costs, and system life.

    Disadvantages

    Space required for boiler, heat exchanger, pumps and heat rejecter.

    Higher initial cost than for most other multiple-packaged unit systems.

    Reduced air flow can cause the heat pump to cycle cutout. Good filter

    maintenance is imperative.