8/16/2019 Symmetrical Componet Fauly calculation
1/521
1
Hands-On Relay School
Jon F. Daume
Bonneville Power Administration
March 14-15, 2011
Theory TrackTransmission Protection Theory
Symmetrical Components &Fault Calculations
8/16/2019 Symmetrical Componet Fauly calculation
2/521
2
Class Outline
Power system troublesSymmetrical components
Per unit system
Electrical equipment impedances
Sequence networks
Fault calculations
8/16/2019 Symmetrical Componet Fauly calculation
3/521
3
Power System ProblemsFaults
Equipment troubleSystem disturbances
8/16/2019 Symmetrical Componet Fauly calculation
4/521
4
Fault CausesLightning
Wind and ice
VandalismContamination
External forces
Cars, tractors, balloons, airplanes, trees, critters,flying saucers, etc.
Equipment failures
System disturbances
Overloads, system swings
8/16/2019 Symmetrical Componet Fauly calculation
5/521
5
8/16/2019 Symmetrical Componet Fauly calculation
6/521
6
Fault TypesOne line to ground (most common)
Three phase (rare but most severe)
Phase to phase
Phase to phase to ground
8/16/2019 Symmetrical Componet Fauly calculation
7/521
7
Symmetrical
Components
8/16/2019 Symmetrical Componet Fauly calculation
8/521
8
Balanced & Unbalanced SystemsBalanced System:
3 Phase load3 Phase fault
Unbalanced System:
Phase to phase faultOne line to ground
fault
Phase to phase toground fault
Open pole orconductor
Unbalanced load
8/16/2019 Symmetrical Componet Fauly calculation
9/521
9
Balanced & Unbalanced Systems
A
C
B
Balanced
System
A
C
BUnbalanced System
8/16/2019 Symmetrical Componet Fauly calculation
10/521
10
Sequence Currents for
Unbalanced Network
Ia2
Ic2Ib2
Negative Sequence
Ic0Ib0
Ia0
Zero Sequence
Ia1
Ic1
Ib1
Positive Sequence
8/16/2019 Symmetrical Componet Fauly calculation
11/521
11
Sequence QuantitiesCondition + - 0
3 Phase load - -3 Phase fault - -
Phase to phase fault
-One line to ground fault
Two phase to ground fault
Open pole or conductor
Unbalanced load
8/16/2019 Symmetrical Componet Fauly calculation
12/521
12
Phase Values From Sequence
ValuesCurrents:
I A = Ia0 + Ia1 + Ia2IB = Ib0 + Ib1 + Ib2
IC = Ic0 + Ic1 + Ic2
Voltages:
V A = Va0 + Va1 + Va2
VB = Vb0 + Vb1 + Vb2
VC = Vc0 + Vc1 + Vc2
8/16/2019 Symmetrical Componet Fauly calculation
13/521
13
a Operator a = -0.5 + j √3= 1 ∠ 120°
2a2 = -0.5 – j √3= 1 ∠ 240°
2
1 + a + a2 = 0
1
a
a 2
8/16/2019 Symmetrical Componet Fauly calculation
14/521
14
Phase Values From Sequence
ValuesCurrents:
I A = Ia0 + Ia1 + Ia2IB = Ia0 + a
2Ia1 + aIa2
IC = Ia0 + aIa1 + a2Ia2
Voltages:
V A = Va0 + Va1 + Va2
VB = Va0 + a2Va1 + aVa2
VC = Va0 + aVa1 + a2Va2
8/16/2019 Symmetrical Componet Fauly calculation
15/521
15
Sequence Values From Phase
ValuesCurrents:
Ia0 = (I A + IB + IC)/3Ia1 = (I A + aIB + a
2IC)/3
Ia2 = (I A + a2IB + aIC)/3
Voltages:
Va0 = (V A + VB + VC)/3
Va1 = (V A + aVB + a2VC)/3
Va2 = (V A + a2VB + aVC)/3
8/16/2019 Symmetrical Componet Fauly calculation
16/521
16
Zero Sequence Filter 3Ia0 = Ig = Ir = I A + IB + IC
and: 1 + a + a2
= 0
I A = Ia0 + Ia1 + Ia2
+IB = Ia0 + a2Ia1 + aIa2
+IC = Ia0 + aIa1 + a2Ia2
= Ig = 3Iao + 0 + 0
8/16/2019 Symmetrical Componet Fauly calculation
17/521
17
Ia
Ic
Ib
3I0 = Ia + Ib + Ic
Zero Sequence Current Filter
8/16/2019 Symmetrical Componet Fauly calculation
18/521
18
Zero Sequence Voltage Filter
3V0
3 VO Polarizing Potential
Ea Eb Ec
8/16/2019 Symmetrical Componet Fauly calculation
19/521
19
Negative Sequence Filter Some protective relays are designed to
sense negative sequence currents and/or
voltages
Much more complicated than detecting zero
sequence valuesMost modern numerical relays have negative
sequence elements for fault detection
and/or directional control
8/16/2019 Symmetrical Componet Fauly calculation
20/521
20
ExampleI A = 3 + j 4
IB = -7 - j 2IC = -2 + j 7
+ j
- j
IA = 3+ j 4
IB = -7- j 2
IC = -2+ j 7
8/16/2019 Symmetrical Componet Fauly calculation
21/521
21
Zero SequenceIa0 = (I A + IB + IC)/3
= [(3+ j 4)+(-7- j 2)+(-2+ j 7)]/3= -2 + j 3 = 3.61 ∠ 124°
Ia0 = Ib0 = Ic0
Ic0Ib0
Ia0
Zero Sequence
8/16/2019 Symmetrical Componet Fauly calculation
22/521
22
Positive SequenceIa1 = (I A + aIB + a
2IC)/3
= [(3+ j 4)+(-0.5+ j √3/2)(-7- j 2)+(-0.5- j √3/2)(-2+ j 7)]/3
= [(3+ j 4)+(5.23- j5 .06)+(7.06- j 1.77)]/3
= 5.10 - j 0.94 = 5.19 ∠ -10.5°
Ib1 is rotated -120º Ic1 is rotated +120º
8/16/2019 Symmetrical Componet Fauly calculation
23/521
23
Positive Sequence
Ia1
Ic1
Ib1
8/16/2019 Symmetrical Componet Fauly calculation
24/521
24
Negative SequenceIa2 = (I A + a
2IB + aIC)/3
= [(3+ j 4)+(-0.5- j √3/2)(-7- j 2)+(-0.5+ j √3/2)(-2+ j 7)]/3
= [(3+ j 4)+(1.77+ j 7.06)+(-5.06- j 5.23)]/3
= -0.1 + j 1.94 = 1.95 ∠ 92.9°
Ib2 is rotated +120º Ic2 is rotated -120º
8/16/2019 Symmetrical Componet Fauly calculation
25/521
25
Negative Sequence
Ia2
Ic2Ib2
8/16/2019 Symmetrical Componet Fauly calculation
26/521
26
Reconstruct Phase Currents
Ia
Ic
Ib
Ic1
Ib1
Ia1
Ib0
Ia0
Ic0
Ia2
Ib2
Ic2
8/16/2019 Symmetrical Componet Fauly calculation
27/521
27
Positive, Negative, and ZeroSequence Impedance
Network Calculations for aFault Study
8/16/2019 Symmetrical Componet Fauly calculation
28/521
28
+, -, 0 Sequence Networks
Simple 2 Source Power System Example
Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
8/16/2019 Symmetrical Componet Fauly calculation
29/521
29
Impedance Networks & Fault TypeFault Type + - 0
3 Phase fault
- -Phase to phase fault -
One line to ground fault
Two phase to ground fault
8/16/2019 Symmetrical Componet Fauly calculation
30/521
30
Per Unit
8/16/2019 Symmetrical Componet Fauly calculation
31/521
31
Per UnitPer unit values are commonly used for fault
calculations and fault study programs
Per unit values convert real quantities to
values based upon number 1
Per unit values include voltages, currents andimpedances
Calculations are easier
Ignore voltage changes due to transformers
Ohms law still works
8/16/2019 Symmetrical Componet Fauly calculation
32/521
32
Per Unit
Convert equipment impedances into per unit
values
Transformer and generator impedances are
given in per cent (%)
Line impedances are calculated in ohmsThese impedances are converted to per unit
ohms impedance
8/16/2019 Symmetrical Componet Fauly calculation
33/521
33
Base kVA or MVA
Arbitrarily selected
All values converted to common KVA or MVABase
100 MVA base is most often used
Generator or transformer MVA rating may beused for the base
8/16/2019 Symmetrical Componet Fauly calculation
34/521
34
Base kV
Use nominal equipment or line voltages
765 kV 525 kV345 kV 230 kV
169 kV 138 kV
115 kV 69 kV
34.5 kV 13.8 kV
12.5 kV etc.
8/16/2019 Symmetrical Componet Fauly calculation
35/521
35
Base Ohms, Amps
Base ohms:
kV
2
1000 = kV
2
base kVA base MVA
Base amps:
base kVA = 1000 base MVA
√3 kV √3 kV
8/16/2019 Symmetrical Componet Fauly calculation
36/521
36
Base Ohms, Amps (100 MVA Base)
kV Base Ohms Base Amps
525 2756.3 110.0
345 1190.3 167.3
230 529.0 251.0
115 132.3 502.0
69 47.6 836.7
34.5 11.9 1673.513.8 1.9 4183.7
12.5 1.6 4618.8
8/16/2019 Symmetrical Componet Fauly calculation
37/521
37
Conversions
Percent to Per Unit:
base MVA x % Z of equipment3φ MVA rating 100
= Z pu Ω @ base MVA
If 100 MVA base is used:
% Z of equipment = Z pu Ω3φ MVA rating
8/16/2019 Symmetrical Componet Fauly calculation
38/521
38
Ohms to Per Unit
pu Ohms = ohms / base ohms
base MVA x ohms = puΩ
@ base MVAkV2LL
8/16/2019 Symmetrical Componet Fauly calculation
39/521
39
Per Unit to Real Stuff
Amps = pu amps x base amps
kV = pu kV x base kVOhms = pu ohms x base ohms
8/16/2019 Symmetrical Componet Fauly calculation
40/521
40
Converting Between Bases
Znew = Zold x base MVAnew x kV2old
base MVAold kV2new
Evaluation of System
8/16/2019 Symmetrical Componet Fauly calculation
41/521
41
Evaluation of System
ComponentsDetermine positive, negative, and zero
sequence impedances of various devices
(Z1, Z2, Z0)
Only machines will act as a voltage source in
the positive sequence networkConnect the various impedances into networks
according to topography of the system
Connect impedance networks for various fault
types or other system conditions
8/16/2019 Symmetrical Componet Fauly calculation
42/521
42
Synchronous Machines
~
Machine values:Machine reactances given in % of the
machine KVA or MVA rating
Ground impedances given in ohms
8/16/2019 Symmetrical Componet Fauly calculation
43/521
43
Synchronous Machines
Machine values:
Subtransient reactance (X"d)
Transient reactance (X'd)
Synchronous reactance (Xd)
Negative sequence reactance (X2)
Zero sequence reactance (X0)
8/16/2019 Symmetrical Componet Fauly calculation
44/521
44
Synchronous Machines
Machine neutral ground impedance: Usually
expressed in ohms
Use 3R or 3X for fault calculations
Calculations generally ignores resistance
values for generatorsCalculations generally uses X”d for all
impedance values
8/16/2019 Symmetrical Componet Fauly calculation
45/521
45
Generator Example
Machine nameplate values:
250 MVA, 13.8 kV
X"d = 25% @ 250 MVA
X'd = 30% @ 250 MVA
Xd = 185% @ 250 MVA
X2 = 25% @ 250 MVA
X0 = 10% @ 250 MVA
8/16/2019 Symmetrical Componet Fauly calculation
46/521
46
Generator Example
Convert machine reactances to per unit @common MVA base, (100):
X"d = 25% / 250 = 0.1 pu
X'd = 30% / 250 = 0.12 pu
Xd = 185% / 250 = 0.74 puX2 = 25% / 250 = 0.1 pu
X0 = 10% / 250 = 0.04 pu
base MVA x % Z of equipment = Z pu Ω @ base MVA
3φ MVA rating 100
8/16/2019 Symmetrical Componet Fauly calculation
47/521
47
Generator Example
~R1 jX1” = 0.1
R0 jX0 = 0.04
R2 jX2 = 0.1
8/16/2019 Symmetrical Componet Fauly calculation
48/521
48
Transformers
Zx X
Ze
ZhH 1:N
Vh
Ih
ZhxH
X
Equivalent Transformer - Impedance in %
ZhxΩ = Vh /Ih = Zh + Zx /N2
Zhx % = Vh /Ih x MVA/kV2 x 100
8/16/2019 Symmetrical Componet Fauly calculation
49/521
49
Transformers
Impedances in % of the transformer MVA
rating
Convert from circuit voltage to tap voltage:
%Xtap = %Xcircuit kV2circuit
kV2tap
f
8/16/2019 Symmetrical Componet Fauly calculation
50/521
50
Transformers
Convert to common base MVA:
%X @ base MVA =
base MVA x %X of Transformer
MVA of Measurement
%X of Transformer = pu X @ 100 MVA
MVA of MeasurementX1 = X2 = X0 unless a special value is given for
X0
T f E l
8/16/2019 Symmetrical Componet Fauly calculation
51/521
51
Transformer Example
250 MVA Transformer
13.8 kV Δ- 230 kV Yg
10% Impedance @ 250 MVA
X = 10% = 0.04 pu @ 100 MVA
250
X1 = X2 = X0 = X
Assume R1, R2, R0 = 0
T f E l
8/16/2019 Symmetrical Componet Fauly calculation
52/521
52
Transformer ExampleR1 jX1 = 0.04
R0 jX0 = 0.04
R2 jX2 = 0.04
Zero sequence connection depends upon
winding configuration.
8/16/2019 Symmetrical Componet Fauly calculation
53/521
T f C ti
8/16/2019 Symmetrical Componet Fauly calculation
54/521
54
Transformer ConnectionsWinding Connection Sequence Network Connections
Z1, Z2 Z0
Z1, Z2 Z0
Z1, Z2 Z0
Z1, Z2 Z0
D lt W T f
8/16/2019 Symmetrical Componet Fauly calculation
55/521
55
Delta Wye Transformer
A
B
C
Ia
Ic
Ib
IA
IB
IC
nIA
nIC
3I0 = IA+IB+IC
nIB
8/16/2019 Symmetrical Componet Fauly calculation
56/521
Transformer Connections
8/16/2019 Symmetrical Componet Fauly calculation
57/521
57
Transformer Connections
A YG / YG connection provides a series
connection for zero sequence current
A Δ / YG connection provides a zero sequence(I0) current source for the YG winding
Auto transformer provides same connection asYG / YG connection
Use 3R or 3X if a Y is connected to ground
with a resistor or reactor
Three Winding Transformer
8/16/2019 Symmetrical Componet Fauly calculation
58/521
58
Three Winding Transformer
Impedances ZHL, ZHM, & ZML given in % at
corresponding winding rating
Convert impedances to common base MVA
Calculate corresponding “T” network
impedances:ZH = (ZHL+ ZHM - ZML)/2
ZM
= (- ZHL
+ ZHM
+ ZML
)/2
ZL = (ZHL- ZHM + ZML)/2
“T” Network
8/16/2019 Symmetrical Componet Fauly calculation
59/521
59
T Network
Calculate corresponding “T” network
impedances:
ZH = (ZHL+ ZHM - ZML)/2
ZM = (- ZHL+ ZHM + ZML)/2
ZL = (ZHL- ZHM + ZML)/2ZHL= ZH + ZL
ZHM = ZH + ZMZML= ZM+ ZL
ZH ZM
ZL
Transformer Example
8/16/2019 Symmetrical Componet Fauly calculation
60/521
60
Transformer Example
230 kV YG/115 kV YG/13.2 kV Δ
Nameplate Impedances
ZHL= 5.0% @ 50 MVA
ZHM = 5.75% @ 250 MVA
ZML = 3.15% @ 50 MVA
Transformer Example
8/16/2019 Symmetrical Componet Fauly calculation
61/521
61
Transformer Example
Convert impedances to per unit @ common
MVA Base (100)
ZHL= 5.0% @ 50 MVA = 5.0 / 50
= 0.10 pu
ZHM = 5.75% @ 250 MVA = 5.75 / 250= 0.023 pu
ZML = 3.15% @ 50 MVA = 3.15 / 50= 0.063 pu
8/16/2019 Symmetrical Componet Fauly calculation
62/521
Transformer Example
8/16/2019 Symmetrical Componet Fauly calculation
63/521
63
Transformer Example
0.03 -0.007
0.07
H M 0.03 -0.007
0.07
H M
LL
H, 230 kV L, 13.8 kV M, 115 kV
+, - Sequence 0 Sequence
8/16/2019 Symmetrical Componet Fauly calculation
64/521
Problem
Calculate pu impedances for generators and
transformers
Use 100 MVA baseIgnore all resistances
Problem
8/16/2019 Symmetrical Componet Fauly calculation
65/521
65
Problem
Fault
13.8 kV 13.8 kV230 kV230 kV
115 kV
Problem - Generator Data
8/16/2019 Symmetrical Componet Fauly calculation
66/521
66
Problem Generator Data
Machine nameplate values:
300 MVA Nameplate rating
X"d = 25% @ 300 MVA
X'd = 30% @ 300 MVA
Xd = 200% @ 300 MVAX2 = 25% @ 300 MVA
X0 = 10% @ 300 MVA
Left generator: 13.8 kVRight generator: 115 kV
Problem - Transformer Data
8/16/2019 Symmetrical Componet Fauly calculation
67/521
67
Problem Transformer Data
Two winding transformer nameplate values
300 MVA Transformer
13.8 kV Δ- 230 kV Yg10% Impedance @ 300 MVA
Three winding transformer nameplate values
230 kV Yg/115 kV Yg/13.8 kV ΔZ
HL
= 5.0% @ 50 MVA (230 kV – 13.8 kV)
ZHM = 6.0% @ 300 MVA (230 kV –115 kV)
ZML = 3.2% @ 50 MVA (115 kV – 13.8 kV)
Transmission Lines
8/16/2019 Symmetrical Componet Fauly calculation
68/521
68
Transmission Lines
R jX
Positive & Negative Sequence
8/16/2019 Symmetrical Componet Fauly calculation
69/521
69
Line Impedance
Z1 = Z2 = Ra + j 0.2794 f log GMDsep60 GMRcond
or
Z1 = Ra + j (Xa + Xd) Ω/mile
Ra and Xa from conductor tables
Xd = 0.2794 f log GMD
60
8/16/2019 Symmetrical Componet Fauly calculation
70/521
70
Positive & Negative SequenceLine Impedancef = system frequency
GMDsep = Geometric mean distance
between conductors = 3√(dabdbcdac) where
dab, dac, dbc = spacing between conductorsin feet
GMRcond = Geometric mean radius of
conductor in feetRa = conductor resistance, Ω/mile
Zero Sequence Line Impedance
8/16/2019 Symmetrical Componet Fauly calculation
71/521
71
q p
Z0 = Ra + Re +
j 0.01397 f log De _______ 3√(GMRcond GMDsep2)
or
Z0 = Ra + Re + j (Xa + Xe - 2Xd) Ω/mile
Zero Sequence Line Impedance
8/16/2019 Symmetrical Componet Fauly calculation
72/521
72
q p
Re = 0.2862 for a 60 Hz. system. Re does
not vary with ρ.
De = 2160 √(ρ /f) = 2788 @ 60 Hz.
ρ = Ground resistivity, generally assumed to
be 100 meter ohms.Xe = 2.89 for 100 meter ohms average
ground resistivity.
Transmission Lines
8/16/2019 Symmetrical Componet Fauly calculation
73/521
73
Ra j(Xa+Xd)
Ra+Re j(Xa+Xe-2Xd)
Ra j(Xa+Xd)
Z1
Z2
Z0
Transmission Line Example
8/16/2019 Symmetrical Componet Fauly calculation
74/521
74
p
230 kV Line
50 Miles long
1272 kcmil ACSR Pheasant Conductor
Ra = 0.0903 Ω /mile @ 80° C
Xa = 0.37201 Ω /mileGMR = 0.0466 feet
Structure: horizontal “H” frame
Transmission Line Example
8/16/2019 Symmetrical Componet Fauly calculation
75/521
75
pStructure “H” frame:
GMD = 3√(dabdbcdac) =3√(23x23x46)
= 28.978 feet
Xd = 0.2794 f log GMD60
= 0.2794 log 28.978 = 0.4085Ω
/mile
A CB
23 Feet 23 FeetJ6 Configuration
Transmission Line Example
8/16/2019 Symmetrical Componet Fauly calculation
76/521
76
p
Z1 = Z2 = Ra + j (Xa + Xd)
= 0.0903 + j (0.372 + 0.4085)
= 0.0903 + j 0.781 Ω /mileZ1 Line = 50(0.0903 + j 0.781)
= 4.52 + j 39.03 Ω = 39.29 Ω ∠ 83.4 °
Per unit @ 230 kV, 100 MVA Basebase MVA x ohms = pu Ω @ base MVA
kV2LL
Z1 Line = (4.52 + j 39.03)100/2302
= 0.0085 + j 0.0743 pu
Transmission Line Example
8/16/2019 Symmetrical Componet Fauly calculation
77/521
77
Z0 = Ra + Re + j (Xa + Xe – 2Xd) = 0.0903
+ 0.286+ j (0.372 + 2.89 - 2 x0.4085)
= 0.377 + j 2.445 Ω /mileZ0 Line = 50(0.377 + j 2.445)
= 18.83 + j 122.25Ω
= 123.69Ω
∠ 81.2 °
Per unit @ 230 kV, 100 MVA Base
Z0 Line = (18.83 + j 122.25)100/2302
= 0.0356 + j 0.2311 pu
Transmission Line Example
8/16/2019 Symmetrical Componet Fauly calculation
78/521
78
Z1
Z2
Z0
0.0085 j0.0743
0.0356 j0.2311
0.0085 j0.0743
Long Parallel Lines
8/16/2019 Symmetrical Componet Fauly calculation
79/521
79
Mutual impedance between lines
Mutual Impedance
8/16/2019 Symmetrical Componet Fauly calculation
80/521
80
Result of coupling between parallel lines
Only affects Zero sequence network
Will affect ground fault magnitudes
Will affect ground current flow in lines
Line #1
Line #2
3I0, Line #1
3I0, Line #2
Mutual Impedance
8/16/2019 Symmetrical Componet Fauly calculation
81/521
81
ZM = Re + j 0.838 log De Ω/mile
GMDcircuits
or
ZM = Re + j (Xe − 3Xd circuits) Ω/mile
Re = 0.2862 @ 60 Hz
De = 2160 √(ρ /f) = 2788 @ 60 Hz
Xe = 2.89 for 100 meter ohms averageground resistivity
Mutual Impedance
8/16/2019 Symmetrical Componet Fauly calculation
82/521
82
GMDcircuits is the ninth root of all possible
distances between the six conductors,
approximately equal to center to centerspacing
GMDcircuits =
9√(da1a2da1b2da1c2db1a2db1b2db1c2dc1a1dc1b2dc1c2)
Xd circuits = 0.2794 log GMDcircuits
Mutual Impedance Example
8/16/2019 Symmetrical Componet Fauly calculation
83/521
83
A CB
23 Feet 23 Feet
A CB
23 Feet 23 Feet
Circuit #1 Circuit #2
46 Feet
46 Feet
92 Feet
69 Feet
69 Feet
92 Feet
115 Feet
138 Feet
115 Feet
92 Feet
Mutual Impedance Example
8/16/2019 Symmetrical Componet Fauly calculation
84/521
84
GMDcircuits =9√(da1a2da1b2da1c2db1a2db1b2db1c2dc1a1dc1b2dc1c2) =
9√(92x115x138x69x92x115x46x69x92)= 87.84 feet
Xd circuits = 0.2794 log GMDcircuits
= 0.2794 log 87.84 = 0.5431 Ω/mileZM = Re + j (Xe − 3Xd circuits)
= 0.2862 + j (2.89 - 3x0.5431)
= 0.2862 + j 1.261 Ω/mile(Z 0 = 0.377 + j 2.445 Ω /mile)
Mutual Impedance Model
8/16/2019 Symmetrical Componet Fauly calculation
85/521
85
Bus 1 Bus 2
Z0 Line 1
Z0 Line 2
ZM
Bus 1 Bus 2Z02 - ZM
Z01- ZM
ZM
Mutual Impedance Model
8/16/2019 Symmetrical Componet Fauly calculation
86/521
86
Model works with at least 1 common bus
ZM Affects zero sequence network only
ZM For different line voltages:
pu Ohms = ohms x base MVAkV1 x kV2
Mutual impedance calculations and modelingbecome much more complicated with larger
systems
8/16/2019 Symmetrical Componet Fauly calculation
87/521
Problem
8/16/2019 Symmetrical Componet Fauly calculation
88/521
88
Calculate Z1 and Z0 pu impedances for a
transmission line
Calculate R1, Z1, R0 and Z0
Calculate Z1 and Z0 and the angles for Z1and Z0
Calculate Z0 mutual impedance between
transmission linesUse 100 MVA base and 230 kV base
Problem
8/16/2019 Symmetrical Componet Fauly calculation
89/521
89
Fault
13.8 kV 13.8 kV230 kV230 kV
115 kV
Transmission Line Data
8/16/2019 Symmetrical Componet Fauly calculation
90/521
90
2 Parallel 230 kV Lines
60 Miles long
1272 kcmil ACSR Pheasant conductor Ra = 0.0903 Ω /mile @ 80° C
Xa = 0.37201 Ω /mile
GMR = 0.0466 feetH frame structure - flat, 23 feet between
conductors
Spacing between circuits = 92 feet centerline tocenterline
8/16/2019 Symmetrical Componet Fauly calculation
91/521
91
Fault Calculations andImpedance Network
Connections
Why We Need Fault Studies
8/16/2019 Symmetrical Componet Fauly calculation
92/521
92
Relay coordination and settings
Determine equipment ratings
Determine effective grounding of system
Substation ground mat design
Substation telephone protectionrequirements
Locating faults
Fault Studies
8/16/2019 Symmetrical Componet Fauly calculation
93/521
93
Fault Types:
3 Phase
One line to ground
Phase to phase
Phase to phase to ground
Fault Locations:
Bus fault
Line endLine out fault (bus fault with line open)
Intermediate faults on transmission line
Fault Study Assumptions
8/16/2019 Symmetrical Componet Fauly calculation
94/521
94
Ignore loads
Use generator X”d
Generator X2 equal X”d
Ignore generator resistance
Ignore transformer resistance0 Ω Fault resistance assumed
Negative sequence impedance = positivesequence impedance
Positive Sequence Network
8/16/2019 Symmetrical Componet Fauly calculation
95/521
95
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1l
V1=1-I1Z1+
Vl = 1 Vr = 1
I1
Fault
Negative Sequence Network
8/16/2019 Symmetrical Componet Fauly calculation
96/521
96
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2lV2= -I2Z2
+
I2
Fault
Zero Sequence Network
8/16/2019 Symmetrical Componet Fauly calculation
97/521
97
Z0sl Z0tl Z0Ll Z0Lr Z0sr
Z0h Z0m
Z0l
V0= -I0Z0+
I0
Fault
Network Reduction
8/16/2019 Symmetrical Componet Fauly calculation
98/521
98
Simple 2 Source Power System Example
Fault
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
Three Phase Fault
8/16/2019 Symmetrical Componet Fauly calculation
99/521
99
Only positive sequence impedance network
usedNo negative or zero sequence currents or
voltages
Simple 2 Source Power System Example
Fault
Three Phase Fault
+++
8/16/2019 Symmetrical Componet Fauly calculation
100/521
100
1PU
Z1
0.084
I1=11.9 I2=0 I0=0
V0
-
+
V2
-
+
V1
-
+
Z0
0.081
Z2
0.084
Three Phase Fault
8/16/2019 Symmetrical Componet Fauly calculation
101/521
101
Simple 2 Source Power System Example
Fault
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1lV1=1-I1Z1
+
Vl = 1 Vr = 1
Sequence Network Connection for 3 Phase Fault
I1
0.1 0.0370.04 0.037 0.1
0.03
0.07
-0.007
Three Phase Fault
8/16/2019 Symmetrical Componet Fauly calculation
102/521
102
Positive Sequence Network Reduced
Simple 2 Source Power System Example
Fault
V1=1-I1Z1+
Vl = 1 Vr = 1
I1
0.177 0.160
Three Phase Fault VectorsIc
8/16/2019 Symmetrical Componet Fauly calculation
103/521
103
Va
Vc
Vb
Ia
Ib
Three Phase Fault
MVA = MVA
8/16/2019 Symmetrical Componet Fauly calculation
104/521
104
MVAFault = MVABase
ZFault pu
or
I pu Fault current = 1 pu ESource
ZFault pu
Three Phase Fault
I = E / Z = 1 / Z
8/16/2019 Symmetrical Componet Fauly calculation
105/521
105
I1 = E / Z1 = 1 / Z1
I2 = I0 = 0
I A = I1 + I2 + I0 = I1
IB = a2I1
IC = aI1V1 = 1 – I1Z1 = 0
V2
= 0, V0
= 0
V A = VB = VC = 0
Phase to Phase Fault
8/16/2019 Symmetrical Componet Fauly calculation
106/521
106
Positive and negative sequence impedance
networks connected in parallelNo zero sequence currents or voltages
Simple 2 Source Power System Example
Fault
Phase to Phase Fault
8/16/2019 Symmetrical Componet Fauly calculation
107/521
107
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
+
V2
-
+
V1
-
+
Phase to Phase Fault
Fault
8/16/2019 Symmetrical Componet Fauly calculation
108/521
108
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2l
V2= -I2Z2+
I2 = -I1
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1m
Z1l
V1=1-I1Z1
I1
+
Vl = 1 Vr = 1
Sequence Network Connection for Phase to Phase Fault
Fault
Phase to Phase Fault Vectors
8/16/2019 Symmetrical Componet Fauly calculation
109/521
109
Va
Vc
Vb
Ic
Ib
Phase to Phase FaultI1 = - I2 = E = 1 I0 = 0
8/16/2019 Symmetrical Componet Fauly calculation
110/521
110
I1 I2 E ___1___ I0 0
(Z1 + Z2) (Z1 + Z2)
I A = I0 + I1 + I2 = 0
IB = I0 + a2I1 + aI2 = a
2I1 - aI1
IB = (a2 - a) E = _- j √3 E_ = - j 0.866 E(Z1 + Z2) (Z1 + Z2) Z1
IC
= - IB
(assume Z 1 = Z 2 )
Phase to Phase FaultV1 = E - I1Z1 = 1 - I1Z1
8/16/2019 Symmetrical Componet Fauly calculation
111/521
111
V1 E I1Z1 1 I1Z1
V2 = - I2Z2 = V1
V0 = 0
V A = V1 + V2 + V0 = 2 V1
VB = V0 + a2
V1 + aV2 = a2
V1 + aV1 = -V1VC = -V1
Phase to phase fault = 86.6%3 phase fault
Single Line to Ground Fault
8/16/2019 Symmetrical Componet Fauly calculation
112/521
112
Positive, negative and zero sequence
impedance networks connected in series
Simple 2 Source Power System Example
Fault
Single Line to Ground Fault
+++
8/16/2019 Symmetrical Componet Fauly calculation
113/521
113
1PU
Z1
.084
I0=4.02
V0
-
+
V2
-
+
V1
-
+
Z2
.084
Z0
.081
I2=4.02I1=4.02
Single Line to Ground Fault
Z l Z tl Z Ll Z L ZZ1l
V1=1-I1Z1+
Vl = 1 Vr = 10.07
8/16/2019 Symmetrical Componet Fauly calculation
114/521
114
Z2sl Z2tl Z2Ll Z2Lr Z2sr
Z2h Z2m
Z2l
V2= -I2Z2+
Z0sl Z0tl Z0Ll Z0Lr Z0sr
Z0h Z0m
Z0l
V0= -I0Z0+
Z1sl Z1tl Z1Ll Z1Lr Z1sr
Z1h Z1mI1
I2
I0
Sequence Network Connection for One Line to Ground Fault
I1 = I2 = I0
0.1 0.0370.04 0.037 0.1
0.03 -0.007
0.04 0.1160.04 0.116 0.04
0.03
0.07
-0.007
0.1 0.0370.04 0.037 0.10.03
0.07
-0.007
Single Line to Ground Fault VectorsVc
8/16/2019 Symmetrical Componet Fauly calculation
115/521
115
Va
Vb Ia
Single Line to Ground Fault
I1 = I2 = I0 = E = 1
8/16/2019 Symmetrical Componet Fauly calculation
116/521
116
1 2 0 ____ _____ ____ _____
(Z1 + Z2 + Z0) (Z1 + Z2 + Z0)
I A = I1 + I2 + I0 = 3 I0
IB = I0 + a2I1 + aI2 = I0 + a
2I0 + aI0 = 0
IC = 0
I Ground = I Residual = 3I0
Single Line to Ground Fault
V1 = E - I1Z1 = 1 - I1Z1
8/16/2019 Symmetrical Componet Fauly calculation
117/521
117
1 1 1 1 1
V2 = - I2Z2
V0 = - I0Z0
V A = V1 + V2 + V0 = 0
VB = V0 + a2
V1 + aV2 = (Z1 - Z0 ) + a2
(Z0+Z1+Z1)
VC
= V0
+ aV1
+ a2V2
= (Z1
- Z0
) + a
(assumes Z 1 = Z 2 ) (Z0+Z1+Z1)
Two Phase to Ground Fault
8/16/2019 Symmetrical Componet Fauly calculation
118/521
118
Positive, negative and zero sequence
impedance networks connected in parallel
Simple 2 Source Power System Example
Fault
Two Phase to Ground Fault
+++
8/16/2019 Symmetrical Componet Fauly calculation
119/521
119
1PU
Z1
I1
Z2
I2
Z0
I0
V0
-
V2
-
V1
-
8/16/2019 Symmetrical Componet Fauly calculation
120/521
Two Phase to Ground Fault Vectors
Ic
8/16/2019 Symmetrical Componet Fauly calculation
121/521
121
Va
Vc
Vb
Ib
Other Conditions
Fault calculations and symmetrical
8/16/2019 Symmetrical Componet Fauly calculation
122/521
122
components can also be used to evaluate:
Open pole or broken conductor Unbalanced loads
Load included in fault analysis
Transmission line fault location
For these other network conditions, refer to
references.
References
Circuit Analysis of AC Power Systems, Vol. 1 &2, Edith Clarke
8/16/2019 Symmetrical Componet Fauly calculation
123/521
123
, d C a e
Electrical Transmission and Distribution
Reference Book, Westinghouse Electric Co.,
East Pittsburgh, Pa.
Symmetrical Components, Wagner and Evans,McGraw-Hill Publishing Co.
Symmetrical Components for Power Systems
Engineering, J. Lewis Blackburn, MarcelDekker, Inc.
8/16/2019 Symmetrical Componet Fauly calculation
124/521
124
The end
Jon F. DaumeBonneville Power Administration
Retired!
Theory Track
Transmission Protection TheoryTransmission System
8/16/2019 Symmetrical Componet Fauly calculation
125/521
1
Hands-On Relay School
Jon F. DaumeBonneville Power Administration
March 14-15, 2011
Transmission System
Protection
Discussion Topics• Protection overview
• Transmission line protectionPh d d f lt t ti
8/16/2019 Symmetrical Componet Fauly calculation
126/521
2
– Phase and ground fault protection
– Line differentials
– Pilot schemes
– Relay communications
– Automatic reclosing
• Breaker failure relays• Special protection or remedial action schemes
Power Transfer
Vs VrX
8/16/2019 Symmetrical Componet Fauly calculation
127/521
3
Power Transfer
0
0.5
1
0 30 60 90 120 150 180
Angle Delta
T r a n s m i t t e d P o w
e r
P = Vs Vr sin / X
Increase Power Transfer
• Increase transmission system operating
voltage
8/16/2019 Symmetrical Componet Fauly calculation
128/521
4
voltage
• Increase angle δ• Decrease X
– Add additional transmission lines
– Add series capacitors to existing lines
8/16/2019 Symmetrical Componet Fauly calculation
129/521
5
Power Transfer During Faults
Power Transfer
1.2
8/16/2019 Symmetrical Componet Fauly calculation
130/521
6
0
0.2
0.4
0.6
0.8
1
1.2
0 30 60 90 120 150 180
Angle Del ta
T r a n s
m i t t e d P o w e
r
Normal
1LG
LL
LLG
3 Phase
Vs Vr
8/16/2019 Symmetrical Componet Fauly calculation
131/521
7
Power Transfer
0
0.2
0.4
0.6
0.8
1
1.2
0 30 60 90 120 150 180
Angle Delta
P o w e
r
BP1
3
21
P2
6
4
5
A
System Stability
• Relay operating speed
• Circuit breaker opening speed
8/16/2019 Symmetrical Componet Fauly calculation
132/521
8
• Circuit breaker opening speed
• Pilot tripping• High speed, automatic reclosing
• Single pole switching
• Special protection or remedial action
schemes
IEEE Device Numbers
Numbers 1 - 97 used
21 Distance relay
8/16/2019 Symmetrical Componet Fauly calculation
133/521
9
21 Distance relay
25 Synchronizing or synchronism checkdevice
27 Undervoltage relay
32 Directional power relay43 Manual transfer or selector device
46 Reverse or phase balance current relay
50 Instantaneous overcurrent or rate of riserelay (fixed time overcurrent)
(IEEE C37.2)
51 AC time overcurrent relay52 AC circuit breaker
59 O lt l
IEEE Device Numbers
8/16/2019 Symmetrical Componet Fauly calculation
134/521
10
59 Overvoltage relay
62 Time delay stopping or opening relay63 Pressure switch
67 AC directional overcurrent relay
79 AC reclosing relay
81 Frequency relay
86 Lock out relay87 Differential relay
(IEEE C37.2)
Relay Reliability
• Overlapping protection
– Relay systems are designed with a high level
8/16/2019 Symmetrical Componet Fauly calculation
135/521
11
Relay systems are designed with a high level
of dependability
– This includes redundant relays
– Overlapping protection zones
• We will trip no line before its time – Relay system security is also very important
– Every effort is made to avoid false trips
Relay Reliability
• Relay dependability (trip when required)
– Redundant relays
8/16/2019 Symmetrical Componet Fauly calculation
136/521
12
Redundant relays
– Remote backup – Dual trip coils in circuit breaker
– Dual batteries
– Digital relay self testing – Thorough installation testing
– Routine testing and maintenance
– Review of relay operations
Relay Reliability
• Relay security (no false trip)
– Careful evaluation before purchase
8/16/2019 Symmetrical Componet Fauly calculation
137/521
13
p
– Right relay for right application – Voting
• 2 of 3 relays must agree before a trip
– Thorough installation testing – Routine testing and maintenance
– Review of relay operations
8/16/2019 Symmetrical Componet Fauly calculation
138/521
14
Transmission
Line Protection
Western Transmission System
Voltage, kV Northwest WECC
115 - 161 27400 miles 48030 miles
8/16/2019 Symmetrical Componet Fauly calculation
139/521
15
Northwest includes Oregon, Washington, Idaho,
Montana, northern Nevada, Utah, British Columbia
and Alberta.WECC is Western Electricity Coordinating Council
which includes states and provinces west of Rocky
Mountains.
230 20850 miles 41950 miles
287 - 345 4360 miles 9800 miles
500 9750 miles 16290 miles
260 - 500 DC 300 miles 1370 miles
Transmission Line Impedance
• Z ohms/mile = Ra + j (Xa + Xd)
• R X function of conductor type length
8/16/2019 Symmetrical Componet Fauly calculation
140/521
16
Ra, Xa function of conductor type, length
• Xd function of conductor spacing, length
Ra j(Xa+Xd)
Line Angles vs. Voltage
Z = √[Ra2 + j(Xa+Xd)2]
∠θ ° = tan-1 (X/R)
8/16/2019 Symmetrical Componet Fauly calculation
141/521
17
( )
Voltage Level Line Angle (∠θ °)7.2 - 23 kV 20 - 45 deg.
23 - 69 kV 45 - 75 deg.
69 - 230 kV 60 - 80 deg.
230 - 765 kV 75 - 89 deg.
Typical Line Protection
8/16/2019 Symmetrical Componet Fauly calculation
142/521
18
8/16/2019 Symmetrical Componet Fauly calculation
143/521
19
Distance Relays
(21, 21G)
8/16/2019 Symmetrical Componet Fauly calculation
144/521
CT & PT Connections
V Phase
8/16/2019 Symmetrical Componet Fauly calculation
145/521
21
21
67N
I Phase
3I0 = Ia + Ib + Ic 3V0
I Polarizing
Instrument Transformers
• Zsecondary = Zprimary x CTR / VTR• The PT location determines the point from
which impedance is measured
8/16/2019 Symmetrical Componet Fauly calculation
146/521
22
which impedance is measured
• The CT location determines the faultdirection
– Very important consideration for • Transformer terminated lines
• Series capacitors
• Use highest CT ratio that will work tominimize CT saturation problems
Saturated CT Current
100
150
8/16/2019 Symmetrical Componet Fauly calculation
147/521
23
-100
-50
0
50
-0.017 0.000 0.017 0.033 0.050 0.0
Original Distance Relay
• True impedance characteristic – Circular characteristic concentric to RX axis
8/16/2019 Symmetrical Componet Fauly calculation
148/521
24
• Required separate directional element• Balance beam construction
– Similar to teeter totter
– Voltage coil offered restraint
– Current coil offered operation
• Westinghouse HZ – Later variation allowed for an offset circle
Impedance Characteristic
X
8/16/2019 Symmetrical Componet Fauly calculation
149/521
25
R
Directional
mho Characteristic
• Most common distance element in use• Circular characteristic
Passes through RX origin
8/16/2019 Symmetrical Componet Fauly calculation
150/521
26
– Passes through RX origin
– No extra directional element required
• Maximum torque angle, MTA, usually setat line angle, ∠θ ° – MTA is diameter of circle
• Different techniques used to provide full
fault detection depending on relay type – Relay may also provide some or full
protection for ground faults
3 Zone mho Characteristic
X
Zone 3
8/16/2019 Symmetrical Componet Fauly calculation
151/521
27
R
Zone 1
Zone 2
3 Zone Distance Elements Mho Characteristic
Typical Reaches
%
8/16/2019 Symmetrical Componet Fauly calculation
152/521
28
21 Zone 1 85-90%
21 Zone 2 125-180%, Time Delay Trip
21 Zone 3 150-200%, Time Delay Trip
Typical Relay Protection Zones
67 Ground Instantaneous Overcurrent
67 Ground Time Overcurrent
67 Ground Time Permissive Transfer Trip Overcurrent
Coordination Considerations,
Zone 1• Zone 1
– 80 to 90% of Line impedance
Account for possible errors
8/16/2019 Symmetrical Componet Fauly calculation
153/521
29
– Account for possible errors
• Line impedance calculations
• CT and PT Errors
• Relay inaccuracy
– Instantaneous trip
Coordination Considerations
• Zone 2 – 125% or more of line impedance
• Consider strong line out of service
8/16/2019 Symmetrical Componet Fauly calculation
154/521
30
g
• Consider lengths of lines at next substation – Time Delay Trip
• > 0.25 seconds (15 cycles)
• Greater than BFR clearing time at remote bus• Must be slower if relay overreaches remote zone
2’s.
– Also consider load encroachment
– Zone 2 may be used with permissiveoverreach transfer trip w/o time delay
Coordination Considerations
• Zone 3 – Greater than zone 2
• Consider strong line out of service
8/16/2019 Symmetrical Componet Fauly calculation
155/521
31
• Consider strong line out of service
• Consider lengths of lines at next substation
– Time Delay Trip
• > 1 second
• Greater than BFR clearing time at remote bus
• Must be longer if relay overreaches remote zone
3’s.
– Must consider load encroachment
Coordination Considerations
• Zone 3 Special Applications – Starter element for zones 1 and 2
Provides current reversal logic for permissive
8/16/2019 Symmetrical Componet Fauly calculation
156/521
32
– Provides current reversal logic for permissive
transfer trip (reversed)
– May be reversed to provide breaker failure
protection
– Characteristic may include origin for current
only tripping
– May not be used
Problems for Distance Relays
• Fault in front of relay
• Apparent Impedance
8/16/2019 Symmetrical Componet Fauly calculation
157/521
33
• Load encroachment• Fault resistance
• Series compensated lines
• Power swings
3 Phase Fault in Front of Relay
• No voltage to make impedancemeasurement-use a potential memory
circuit in distance relay
8/16/2019 Symmetrical Componet Fauly calculation
158/521
34
circuit in distance relay
• Use a non-directional, instantaneous
overcurrent relay (50-Dead line fault relay)
• Utilize switch into fault logic – Allow zone 2 instantaneous trip
Apparent Impedance• 3 Terminal lines with apparent
impedance
• Fault resistance also looks like anapparent impedance
8/16/2019 Symmetrical Componet Fauly calculation
159/521
35
apparent impedance
• Most critical with very short orunbalanced legs
• Results in – Short zone 1 reaches
– Long zone 2 reaches and time delays
• Pilot protection may be required
Apparent Impedance
Bus A Bus BZa = 1 ohm
Ia = 1
Zb = 1
Ib = 1
8/16/2019 Symmetrical Componet Fauly calculation
160/521
36
Z apparent @
Bus A = Za +ZcIc/Ia
= 3 Ohms
Apparent Impedance
Ic = Ia + Ib = 2 Zc = 1
Bus C
Coordination Considerations
• Zone 1 – Set to 85 % of actual impedance to nearest
terminal
8/16/2019 Symmetrical Componet Fauly calculation
161/521
37
• Zone 2
– Set to 125 + % of apparent impedance to
most distant terminal – Zone 2 time delay must coordinate with all
downstream relays
• Zone 3 – Back up for zone 2
Load Encroachment
• Z Load = kV2
/ MVA – Long lines present biggest challenge
– Heavy load may enter relay characteristic
8/16/2019 Symmetrical Componet Fauly calculation
162/521
38
• Serious problem in August, 2003 East
Coast Disturbance
• NERC Loading Criteria – 150 % of emergency line load rating
– Use reduced voltage (85 %)
– 30° Line Angle• Z @ 30° = Z @ MTA cos (∠MTA° -∠30° ) for mho
characteristic
8/16/2019 Symmetrical Componet Fauly calculation
163/521
Load Encroachment
X
Zone 3
8/16/2019 Symmetrical Componet Fauly calculation
164/521
40
R
Zone 1
Zone 2
Load Consideration with Distance Relays
Load
Area
Lens Characteristic
• Ideal for longer transmission lines• More immunity to load encroachment
8/16/2019 Symmetrical Componet Fauly calculation
165/521
41
• Less fault resistance coverage• Generated by merging the common area
between two mho elements
Lens Characteristic
8/16/2019 Symmetrical Componet Fauly calculation
166/521
42
Tomato Characteristic
• May be used as an external out of stepblocking characteristic
• Reaches set greater than the tripping
8/16/2019 Symmetrical Componet Fauly calculation
167/521
43
g pp g
elements
• Generated by combining the total area of
two mho elements
Quadrilateral Characteristic
• High level of freedom in settings• Blinders on left and right can be moved in
or out
8/16/2019 Symmetrical Componet Fauly calculation
168/521
44
– More immunity to load encroachment (in)
– More fault resistance coverage (out)
• Generated by the common area between – Left and right blinders
– Below reactance element
– Above directional element
Quadrilateral Characteristic
X
8/16/2019 Symmetrical Componet Fauly calculation
169/521
45
R
Quadrilateral Characteristic
Special Load Encroachment
X
Zone 4
8/16/2019 Symmetrical Componet Fauly calculation
170/521
46
R
Zone 1
Zone 2
8/16/2019 Symmetrical Componet Fauly calculation
171/521
Fault ResistanceX
Zone 3
8/16/2019 Symmetrical Componet Fauly calculation
172/521
48
R
Zone 1
Zone 2
Fault Resistance Effect on a Mho Characteristic
Rf
Series Compensated Lines
• Series caps added to increase loadtransfers
– Electrically shorten line
8/16/2019 Symmetrical Componet Fauly calculation
173/521
49
• Negative inductance
• Difficult problem for distance relays
• Application depends upon location ofcapacitors
Series Caps
Zl Zc
Zl > Zc
8/16/2019 Symmetrical Componet Fauly calculation
174/521
50
21
21 Zl > Zc
8/16/2019 Symmetrical Componet Fauly calculation
175/521
Coordination Considerations
• Zone 1 – 80 to 90% of compensated line impedance
– Must not overreach remote bus with caps in
service
8/16/2019 Symmetrical Componet Fauly calculation
176/521
52
service
• Zone 2
– 125% + of uncompensated apparent lineimpedance
– Must provide direct tripping for any line fault
with caps bypassed – May require longer time delays
Power Swing
• Power swings can cause false trip of 3phase distance elements
• Option to
8/16/2019 Symmetrical Componet Fauly calculation
177/521
53
– Block on swing (Out of step block)
– Trip on swing (Out of step trip)
• Out of step tripping may require special breaker • Allows for controlled separation
• Some WECC criteria to follow if OOSB
implemented
Out Of Step Blocking
X
OOSB Outer Zone
OOS
B Inner Zone
8/16/2019 Symmetrical Componet Fauly calculation
178/521
54
R
Zone 1
Zone 2
Typical Out Of Step Block Characteristic
t = 30 ms?
Ground Distance
P t ti
8/16/2019 Symmetrical Componet Fauly calculation
179/521
55
Protection
and Kn(21G)
Fault Types
• 3 Phase fault – Positive sequence impedance network only
• Phase to phase fault
– Positive and negative sequence
8/16/2019 Symmetrical Componet Fauly calculation
180/521
56
– Positive and negative sequenceimpedance networks in parallel
• One line to ground fault
– Positive, negative, and zero sequenceimpedance networks in series
• Phase to phase to ground fault
– Positive, negative, and zero sequenceimpedance networks in parallel
Sequence Networks
8/16/2019 Symmetrical Componet Fauly calculation
181/521
57
8/16/2019 Symmetrical Componet Fauly calculation
182/521
Kn - Why?• Using phase/phase or phase/ground
quantities does not give proper reachmeasurement for 1LG fault
• Using zero sequence quantities gives thezero sequence source impedance not the
8/16/2019 Symmetrical Componet Fauly calculation
183/521
59
zero sequence source impedance, not theline impedance
• Current compensation (Kn) does work forground faults
• Voltage compensation could also be used
but is less common
Current Compensation, KnK
n= (Z
0L- Z
1L)/3Z
1LZ0L = Zero sequence transmission line impedance
Z1L = Positive sequence transmission line
impedance
8/16/2019 Symmetrical Componet Fauly calculation
184/521
60
impedanceIRelay = I A + 3I0(Z0L- Z1L)/3Z1L = I A + 3KnI0
ZRelay = V A Relay/IRelay = V A/(I A + 3KnI0) = Z1L
Reach of ground distance relay with current
compensation is based on positive sequence line
impedance, Z1L
Current Compensation, Kn• Current compensation (Kn) does work for
ground faults.
• Kn = (Z0L – Z1L)/3Z1
– Kn may be a scalar quantity or a vector quantitywith both magnitude and angle
8/16/2019 Symmetrical Componet Fauly calculation
185/521
61
K may be a scalar quantity or a vector quantitywith both magnitude and angle
• Mutual impedance coupling from parallel
lines can cause a ground distance relay tooverreach or underreach, depending uponground fault location
• Mutual impedance coupling can provideincorrect fault location values for groundfaults
Ground Fault
Protection
8/16/2019 Symmetrical Componet Fauly calculation
186/521
62
Protection
(67N)
Ground Faults
• Directional ground overcurrent relays(67N)
• Ground overcurrent relays
– Time overcurrent ground (51)
8/16/2019 Symmetrical Componet Fauly calculation
187/521
63
Time overcurrent ground (51)
– Instantaneous overcurrent (50)
• Measure zero sequence currents• Use zero sequence or negative sequence
for directionality
Typical Ground OvercurrentSettings
• 51 Time overcurrentSelect TOC curve, usually very inverse
Pickup, usually minimum
Time delay >0.25 sec. for remote bus fault
8/16/2019 Symmetrical Componet Fauly calculation
188/521
64
Time delay 0.25 sec. for remote bus fault
• 50 Instantaneous overcurrent
>125% Remote bus fault• Must consider affects of mutual coupling
from parallel transmission lines.
Polarizing for DirectionalGround Overcurrent Relays
• I Residual and I polarizing – I Polarizing: An autotransformer neutral CT
may not provide reliable current polarizing
• I Residual and V polarizing
8/16/2019 Symmetrical Componet Fauly calculation
189/521
65
p g
– I Residual 3I0 = Ia + Ib + Ic
– V Polarizing 3V0 = Va + Vb + Vc• Negative sequence
– Requires 3 phase voltages and currents
– More immune to mutual coupling problems
Current Polarizing
CT
H1
X1
H2
Y1
8/16/2019 Symmetrical Componet Fauly calculation
190/521
66
I Polarizing
Auto Transformer Polarizing Current Source
H3
X3
X2 Y2
Y3
H0X0
Voltage PolarizingEa Eb Ec
8/16/2019 Symmetrical Componet Fauly calculation
191/521
67
3 VO Polarizing Potential
Mutual Coupling
• Transformer affect between parallel lines – Inversely proportional to distance between
lines
• Only affects zero sequence current
8/16/2019 Symmetrical Componet Fauly calculation
192/521
68
y q
• Will affect magnitude of ground currents
• Will affect reach of ground distance relays
Mutual Coupling
Line #13I0, Line #1
8/16/2019 Symmetrical Componet Fauly calculation
193/521
69
Line #2
3I0, Line #2
Mutual Coupling vs. GroundRelays
Taft
645 Amps
1315 Amps645 Amps
1980 Amps
GarrisonTaft Garrison
8/16/2019 Symmetrical Componet Fauly calculation
194/521
70
Taft
920 Amps
260 Amps920 Amps
1370 Amps
1LG Faults With Mutual Impedances
1LG Faults Without Mutual Impedances
GarrisonTaft Garrison
Other Line
8/16/2019 Symmetrical Componet Fauly calculation
195/521
71
Other Line
Protection Relays
Line Differential
8/16/2019 Symmetrical Componet Fauly calculation
196/521
72
87 87
Line Differential Relays
• Compare current magnitudes, phase, etc.at each line terminal
• Communicate information between relays
• Internal/external fault? Trip/no trip?
8/16/2019 Symmetrical Componet Fauly calculation
197/521
73
p p
• Communications dependant!
• Changes in communications paths orchannel delays can cause potential
problems
Phase Comparison
• Compares phase relationship at terminals• 100% Channel dependant
– Looped channels can cause false trips
• Nondirectional overcurrent on channel
8/16/2019 Symmetrical Componet Fauly calculation
198/521
74
Nondirectional overcurrent on channel
failure
• Immune to swings, load, series caps• Single pole capability
Pilot Wire
• Common on power house lines• Uses metallic twisted pair
– Problems if commercial line used
– Requires isolation transformers and protection
8/16/2019 Symmetrical Componet Fauly calculation
199/521
75
on pilot wire
• Nondirectional overcurrent on pilot failure• Newer versions use fiber or radio
• Generally limited to short lines if metallic
twisted pair is used
8/16/2019 Symmetrical Componet Fauly calculation
200/521
8/16/2019 Symmetrical Componet Fauly calculation
201/521
Current Differential
• Single pole capability• 3 Terminal line capability
• May include an external, direct transfer trip
feature
8/16/2019 Symmetrical Componet Fauly calculation
202/521
78
• Immune to swings, load, series caps
Transfer Trip
8/16/2019 Symmetrical Componet Fauly calculation
203/521
79
Transfer Trip
8/16/2019 Symmetrical Componet Fauly calculation
204/521
Tone 1 Xmit
Tone 2 Xmit
Tone 1 Rcvd
Tone 2 Rcvd
Protective Relay
Protective Relay
Direct Transfer Trip
8/16/2019 Symmetrical Componet Fauly calculation
205/521
81
PCB Trip Coil PCB Trip Coil
Direct Transfer Trip
Direct Transfer Trip Initiation
• Zone 1 distance• Zone 2 distance time delay trip
• Zone 3 distance time delay trip
• Instantaneous ground trip
Time overcurrent ground trip
8/16/2019 Symmetrical Componet Fauly calculation
206/521
82
• Time overcurrent ground trip
• BFR-Ring bus, breaker & half scheme• Transformer relays on transformer
terminated lines
• Line reactor relays
Tone 2 Xmit
Tone 2 Rcvd
Permissive Relay
Tone 2 Xmit
Tone 2 Rcvd
Permissive Relay
Permissive Transfer Trip
8/16/2019 Symmetrical Componet Fauly calculation
207/521
83
PCB Trip Coil PCB Trip Coil
Permissive Transfer Trip
Permissive Keying
• Zone 2 instantaneous• Permissive overcurrent ground (very
sensitive setting)
• PCB 52/b switch
8/16/2019 Symmetrical Componet Fauly calculation
208/521
84
• Current reversal can cause problems
8/16/2019 Symmetrical Componet Fauly calculation
209/521
PRT Current Reversal
A B
Id
Ia
Ic
I Fault, Line AB
I Fault, Line CD
8/16/2019 Symmetrical Componet Fauly calculation
210/521
86
C D
Breaker B opens instantaneously. Relays at B drop out.
Fault current on line CD changes direction.
Relays at A remain picked up and trip by permissive signal from B.
Relays at C drop out and stop keying permissive signal to C.
Relays at D pick up and key permissive signal to D.
Directional ComparisonBlocking
• Overreaching relays• Delay for channel time
• Channel failure can allow overtrip
• Often used with “On/Off” carrier
8/16/2019 Symmetrical Componet Fauly calculation
211/521
87
Block Xmit
Block Rcvd
Block Xmit
Block Rcvd
Forward
Relay
Reverse
Relay
Reverse
Relay
Forward
Relay
Directional Comparison
8/16/2019 Symmetrical Componet Fauly calculation
212/521
88
PCB Trip Coil PCB Trip Coil
Directional Comparison Blocking Scheme
Time DelayTime Delay TDTD
Directional Comparison Relays
• Forward relays must overreach remotebus
• Forward relays must not overreach remote
reverse relays
• Time delay (TD) set for channel delay
8/16/2019 Symmetrical Componet Fauly calculation
213/521
89
• Time delay (TD) set for channel delay
• Scheme will trip for fault if channel lost – Scheme may overtrip for external fault on
channel loss
Tone Equipment
• Interface between relays andcommunications channel
• Analog tone equipment
• Digital tone equipment
8/16/2019 Symmetrical Componet Fauly calculation
214/521
90
• Security features
– Guard before trip
– Alternate shifting of tones
– Parity checks on digital
Tone Equipment
• Newer equipment has 4 or morechannels
– 2 for direct transfer trip
– 1 for permissive transfer trip
1 for drive to lock out (block reclose)
8/16/2019 Symmetrical Componet Fauly calculation
215/521
91
– 1 for drive to lock out (block reclose)
Relay to Relay Communications
• Available on many new digital relays• Eliminates need for separate tone gear
• 8 or more unique bits of data sent from
one relay to other
• Programmable functions
8/16/2019 Symmetrical Componet Fauly calculation
216/521
92
• Programmable functions
– Each transmitted bit programmed for specificrelay function
– Each received bit programmed for specific
purpose
TelecommunicationsChannels
• Microwave radio – Analog (no longer available)
– Digital
• Other radio systems• Dedicated fiber between relays
8/16/2019 Symmetrical Componet Fauly calculation
217/521
93
Dedicated fiber between relays
– Short runs
• Multiplexed fiber
– Long runs
• SONET Rings
TelecommunicationsChannels
• Power line carrier current – On/Off Carrier often used with directional
comparison
• Hard wire
– Concern with ground mat interconnections
8/16/2019 Symmetrical Componet Fauly calculation
218/521
94
Concern with ground mat interconnections
– Limited to short runs• Leased line
– Rent from phone company
– Considered less reliable
Automatic Reclosing (79)
• First reclose ~ 80% success rate• Second reclose ~ 5% success rate
• Must delay long enough for arc to
deionizet = 10.5 + kV/34.5 cycles
8/16/2019 Symmetrical Componet Fauly calculation
219/521
95
y
14 cycles for 115 kV; 25 cycles for 500 kV
• Must delay long enough for remoteterminal to clear
• 1LG Faults have a higher success ratethan 3 phase faults
Automatic Reclosing (79)
• Most often single shot• Delay of 30 to 60 cycles following line trip
is common
• Checking:
– Hot bus & dead line
8/16/2019 Symmetrical Componet Fauly calculation
220/521
96
Hot bus & dead line
– Hot line & dead bus – Sync check
• Utilities have many different criteria for
transmission line reclosing
More on Reclosing
• Only reclose for one line to ground faults• Block reclose for time delay trip (pilot
schemes)
• Never reclose on power house lines
• Block reclosing for transformer fault on
8/16/2019 Symmetrical Componet Fauly calculation
221/521
97
Block reclosing for transformer fault on
transformer terminated lines• Block reclosing for bus faults
• Block reclosing for BFR
• Do not use them
Breaker Failure
Relay
8/16/2019 Symmetrical Componet Fauly calculation
222/521
98
y
(50BF)
Breaker Failure
• Stuck breaker is a severe impact tosystem stability on transmission systems
• Breaker failure relays are recommended
by NERC for transmission systemsoperated above 100 kV
8/16/2019 Symmetrical Componet Fauly calculation
223/521
99
• BFRs are not required to be redundant by
NERC
Breaker Failure Relays
1. Fault on line2. Normal protective relays detect fault and
send trip to breaker.
3. Breaker does not trip.
4. BFR Fault detectors picked up.
8/16/2019 Symmetrical Componet Fauly calculation
224/521
100
p p
5. BFR Time delay times out (8 cycles)6. Clear house (open everything to isolate
failed breaker)
Breaker Failure Relay
BFR Fault
Detector PCB TripCoil #1
TD
Protective Relay
TripTD
BFR Retrip
BFR Time
Delay, 8~
8/16/2019 Symmetrical Componet Fauly calculation
225/521
101
Typical Breaker Failure Scheme with Retrip
86
Block Close
PCB Trip
Coil #2
Delay, 8
Typical BFR Clearing Times
Proper Clearing:
0 Fault occurs
+1~ Relays PU, Key TT
+2~ PCB trips
+1~ Remote terminal clears
Failed Breaker:
0 Fault occurs
+1~ BFR FD PU
+8~ BFR Time Delay
+1~ BFR Trips 86 LOR+2~ BU PCBs trip
+1~ Remote terminal clears
8/16/2019 Symmetrical Componet Fauly calculation
226/521
102
3-4 Cycles local clearingtime
4-5 Cycles remote clearing
time
12-13 Cycles local back upclearing time
13-14 Cycles remote
backup clearing
Remedial Action
Schemes (RAS)
8/16/2019 Symmetrical Componet Fauly calculation
227/521
103
aka: SpecialProtection Schemes
Remedial Action Schemes
• Balance generation and loads• Maintain system stability
• Prevent major problems (blackouts)
• Prevent equipment damage• Allow system to be operated at higher
levels
8/16/2019 Symmetrical Componet Fauly calculation
228/521
104
levels
• Provide controlled islanding
• Protect equipment and lines from thermal
overloads• Many WECC & NERC Requirements
Remedial Action Schemes
• WECC Compliant RAS – Fully redundant
– Annual functional test
– Changes, modifications and additions must beapproved by WECC
Non WECC RAS
8/16/2019 Symmetrical Componet Fauly calculation
229/521
105
• Non WECC RAS
– Does not need full redundancy
– Local impacts only
– Primarily to solve thermal overload problems
Underfrequency Load Shedding
• Reduce load to match available generation
• Undervoltage (27) supervised (V > 0.8 pu)
• 14 Cycle total clearing time required
• Must conform to WECC guidelines
• 4 Steps starting at 59.4 Hz.
8/16/2019 Symmetrical Componet Fauly calculation
230/521
106
• Restoration must be controlled• Must coordinate with generator 81 relays
• Responsibility of control areas
Undervoltage Load Shedding
• Detect 3 Phase undervoltage• Prevent voltage collapse
• Sufficient time delay before tripping to ride
through minor disturbances
• Must Conform to WECC Guidelines
8/16/2019 Symmetrical Componet Fauly calculation
231/521
107
• Primarily installed West of Cascades
Generator Dropping
• Trip generators for loss of load• Trip generators for loss of transmission
lines or paths
– Prevent overloading
8/16/2019 Symmetrical Componet Fauly calculation
232/521
108
Reactive Switching
• On loss of transmission lines – Trip shunt reactors to increase voltage
– Close shunt capacitors to compensate for loss
of reactive supplied by transmission lines – Close series capacitors to increase load
transfers
8/16/2019 Symmetrical Componet Fauly calculation
233/521
109
– Utilize generator var output if possible – Static Var Compensators (SVC) provide high
speed adjustments
Direct Load Tripping
• Provide high speed trip to shed load – May use transfer trip
– May use sensitive, fast underfrequency (81)
relay• Trip large industrial loads
8/16/2019 Symmetrical Componet Fauly calculation
234/521
110
Other RAS Schemes
• Controlled islanding – Force separation at know locations
• Load brake resistor insertion
– Provide a resistive load to slow downacceleration of generators
• Out of step tripping
8/16/2019 Symmetrical Componet Fauly calculation
235/521
111
• Out of step tripping
– Force separation on swing
• Phase shifting transformers
– Control load flows
Typical RAS Controller
8/16/2019 Symmetrical Componet Fauly calculation
236/521
112
Typical RAS Controller Outputs
• Generator tripping
• Load tripping
• Controlled islanding and separation (Four
Corners)• Insert series caps on AC Intertie
• Shunt capacitor insertion
8/16/2019 Symmetrical Componet Fauly calculation
237/521
113
Shunt capacitor insertion
• Shunt reactor tripping
• Chief Jo Load Brake Resister insertion
• Interutility signaling• AGC Off
Chief Jo Brake
8/16/2019 Symmetrical Componet Fauly calculation
238/521
1141400 Megawatts @ 230 kV
RAS Enabling Criteria
• Power transfer levels• Direction of power flow
• System configuration
• Some utilities are considering automatic
enabling/disabling based on SCADA data
8/16/2019 Symmetrical Componet Fauly calculation
239/521
115
• Phasor measurement capability in relayscan be used to enable RAS actions
RAS Design Criteria
• Generally fully redundant• Generally use alternate route on
telecommunications
• Extensive use of transfer trip for signalingbetween substations, power plants, control
centers and RAS controllers
8/16/2019 Symmetrical Componet Fauly calculation
240/521
116
centers, and RAS controllers
UFOs vs. Power Outages
8/16/2019 Symmetrical Componet Fauly calculation
241/521
117
the end
8/16/2019 Symmetrical Componet Fauly calculation
242/521
118
Jon F. Daume
Bonneville Power Administration
retired
March 15, 2011
8/16/2019 Symmetrical Componet Fauly calculation
243/521
8/16/2019 Symmetrical Componet Fauly calculation
244/521
8/16/2019 Symmetrical Componet Fauly calculation
245/521
8/16/2019 Symmetrical Componet Fauly calculation
246/521
8/16/2019 Symmetrical Componet Fauly calculation
247/521
8/16/2019 Symmetrical Componet Fauly calculation
248/521
8/16/2019 Symmetrical Componet Fauly calculation
249/521
8/16/2019 Symmetrical Componet Fauly calculation
250/521
8/16/2019 Symmetrical Componet Fauly calculation
251/521
8/16/2019 Symmetrical Componet Fauly calculation
252/521
8/16/2019 Symmetrical Componet Fauly calculation
253/521
8/16/2019 Symmetrical Componet Fauly calculation
254/521
8/16/2019 Symmetrical Componet Fauly calculation
255/521
8/16/2019 Symmetrical Componet Fauly calculation
256/521
8/16/2019 Symmetrical Componet Fauly calculation
257/521
8/16/2019 Symmetrical Componet Fauly calculation
258/521
8/16/2019 Symmetrical Componet Fauly calculation
259/521
8/16/2019 Symmetrical Componet Fauly calculation
260/521
8/16/2019 Symmetrical Componet Fauly calculation
261/521
8/16/2019 Symmetrical Componet Fauly calculation
262/521
8/16/2019 Symmetrical Componet Fauly calculation
263/521
8/16/2019 Symmetrical Componet Fauly calculation
264/521
8/16/2019 Symmetrical Componet Fauly calculation
265/521
8/16/2019 Symmetrical Componet Fauly calculation
266/521
8/16/2019 Symmetrical Componet Fauly calculation
267/521
8/16/2019 Symmetrical Componet Fauly calculation
268/521
8/16/2019 Symmetrical Componet Fauly calculation
269/521
8/16/2019 Symmetrical Componet Fauly calculation
270/521
8/16/2019 Symmetrical Componet Fauly calculation
271/521
8/16/2019 Symmetrical Componet Fauly calculation
272/521
8/16/2019 Symmetrical Componet Fauly calculation
273/521
8/16/2019 Symmetrical Componet Fauly calculation
274/521
8/16/2019 Symmetrical Componet Fauly calculation
275/521
8/16/2019 Symmetrical Componet Fauly calculation
276/521
8/16/2019 Symmetrical Componet Fauly calculation
277/521
8/16/2019 Symmetrical Componet Fauly calculation
278/521
8/16/2019 Symmetrical Componet Fauly calculation
279/521
8/16/2019 Symmetrical Componet Fauly calculation
280/521
8/16/2019 Symmetrical Componet Fauly calculation
281/521
8/16/2019 Symmetrical Componet Fauly calculation
282/521
8/16/2019 Symmetrical Componet Fauly calculation
283/521
8/16/2019 Symmetrical Componet Fauly calculation
284/521
8/16/2019 Symmetrical Componet Fauly calculation
285/521
8/16/2019 Symmetrical Componet Fauly calculation
286/521
8/16/2019 Symmetrical Componet Fauly calculation
287/521
8/16/2019 Symmetrical Componet Fauly calculation
288/521
8/16/2019 Symmetrical Componet Fauly calculation
289/521
8/16/2019 Symmetrical Componet Fauly calculation
290/521
8/16/2019 Symmetrical Componet Fauly calculation
291/521
8/16/2019 Symmetrical Componet Fauly calculation
292/521
8/16/2019 Symmetrical Componet Fauly calculation
293/521
8/16/2019 Symmetrical Componet Fauly calculation
294/521
8/16/2019 Symmetrical Componet Fauly calculation
295/521
8/16/2019 Symmetrical Componet Fauly calculation
296/521
8/16/2019 Symmetrical Componet Fauly calculation
297/521
8/16/2019 Symmetrical Componet Fauly calculation
298/521
8/16/2019 Symmetrical Componet Fauly calculation
299/521
8/16/2019 Symmetrical Componet Fauly calculation
300/521
8/16/2019 Symmetrical Componet Fauly calculation
301/521
8/16/2019 Symmetrical Componet Fauly calculation
302/521
8/16/2019 Symmetrical Componet Fauly calculation
303/521
8/16/2019 Symmetrical Componet Fauly calculation
304/521
8/16/2019 Symmetrical Componet Fauly calculation
305/521
8/16/2019 Symmetrical Componet Fauly calculation
306/521
8/16/2019 Symmetrical Componet Fauly calculation
307/521
8/16/2019 Symmetrical Componet Fauly calculation
308/521
8/16/2019 Symmetrical Componet Fauly calculation
309/521
8/16/2019 Symmetrical Componet Fauly calculation
310/521
8/16/2019 Symmetrical Componet Fauly calculation
311/521
8/16/2019 Symmetrical Componet Fauly calculation
312/521
8/16/2019 Symmetrical Componet Fauly calculation
313/521
8/16/2019 Symmetrical Componet Fauly calculation
314/521
8/16/2019 Symmetrical Componet Fauly calculation
315/521
8/16/2019 Symmetrical Componet Fauly calculation
316/521
8/16/2019 Symmetrical Componet Fauly calculation
317/521
8/16/2019 Symmetrical Componet Fauly calculation
318/521
8/16/2019 Symmetrical Componet Fauly calculation
319/521
8/16/2019 Symmetrical Componet Fauly calculation
320/521
8/16/2019 Symmetrical Componet Fauly calculation
321/521
8/16/2019 Symmetrical Componet Fauly calculation
322/521
8/16/2019 Symmetrical Componet Fauly calculation
323/521
8/16/2019 Symmetrical Componet Fauly calculation
324/521
8/16/2019 Symmetrical Componet Fauly calculation
325/521
8/16/2019 Symmetrical Componet Fauly calculation
326/521
8/16/2019 Symmetrical Componet Fauly calculation
327/521
8/16/2019 Symmetrical Componet Fauly calculation
328/521
8/16/2019 Symmetrical Componet Fauly calculation
329/521
8/16/2019 Symmetrical Componet Fauly calculation
330/521
8/16/2019 Symmetrical Componet Fauly calculation
331/521
8/16/2019 Symmetrical Componet Fauly calculation
332/521
8/16/2019 Symmetrical Componet Fauly calculation
333/521
8/16/2019 Symmetrical Componet Fauly calculation
334/521
8/16/2019 Symmetrical Componet Fauly calculation
335/521
8/16/2019 Symmetrical Componet Fauly calculation
336/521
8/16/2019 Symmetrical Componet Fauly calculation
337/521
8/16/2019 Symmetrical Componet Fauly calculation
338/521
8/16/2019 Symmetrical Componet Fauly calculation
339/521
8/16/2019 Symmetrical Componet Fauly calculation
340/521
8/16/2019 Symmetrical Componet Fauly calculation
341/521
8/16/2019 Symmetrical Componet Fauly calculation
342/521
8/16/2019 Symmetrical Componet Fauly calculation
343/521
8/16/2019 Symmetrical Componet Fauly calculation
344/521
8/16/2019 Symmetrical Componet Fauly calculation
345/521
8/16/2019 Symmetrical Componet Fauly calculation
346/521
8/16/2019 Symmetrical Componet Fauly calculation
347/521
8/16/2019 Symmetrical Componet Fauly calculation
348/521
8/16/2019 Symmetrical Componet Fauly calculation
349/521
8/16/2019 Symmetrical Componet Fauly calculation
350/521
8/16/2019 Symmetrical Componet Fauly calculation
351/521
8/16/2019 Symmetrical Componet Fauly calculation
352/521
8/16/2019 Symmetrical Componet Fauly calculation
353/521
8/16/2019 Symmetrical Componet Fauly calculation
354/521
8/16/2019 Symmetrical Componet Fauly calculation
355/521
8/16/2019 Symmetrical Componet Fauly calculation
356/521
8/16/2019 Symmetrical Componet Fauly calculation
357/521
8/16/2019 Symmetrical Componet Fauly calculation
358/521
8/16/2019 Symmetrical Componet Fauly calculation
359/521
8/16/2019 Symmetrical Componet Fauly calculation
360/521
8/16/2019 Symmetrical Componet Fauly calculation
361/521
8/16/2019 Symmetrical Componet Fauly calculation
362/521
8/16/2019 Symmetrical Componet Fauly calculation
363/521
8/16/2019 Symmetrical Componet Fauly calculation
364/521
8/16/2019 Symmetrical Componet Fauly calculation
365/521
8/16/2019 Symmetrical Componet Fauly calculation
366/521
8/16/2019 Symmetrical Componet Fauly calculation
367/521
8/16/2019 Symmetrical Componet Fauly calculation
368/521
8/16/2019 Symmetrical Componet Fauly calculation
369/521
8/16/2019 Symmetrical Componet Fauly calculation
370/521
8/16/2019 Symmetrical Componet Fauly calculation
371/521
Transmission System Faults and
Event AnalysisFault Analysis Theory
andModern Fault Analysis Methods
Presented by:
Matthew Rhodes
Electrical Engineer, SRP
1
8/16/2019 Symmetrical Componet Fauly calculation
372/521
Transmission System FaultTheory
• Symmetrical Fault Analysis• Symmetrical Components
• Unsymmetrical Fault Analysis usingsequence networks
• Lecture material originally developed byDr. Richard Farmer, ASU Research
Professor 2
8/16/2019 Symmetrical Componet Fauly calculation
373/521
3
Symmetrical Faults
8/16/2019 Symmetrical Componet Fauly calculation
374/521
4
Faults
Shunt faults:
Three phase a bc
Line to line
Line to ground
2 Line to ground
b
a
c
a
bc
a b
c
8/16/2019 Symmetrical Componet Fauly calculation
375/521
5
Faults
Series faults
One open phase: a bc
2 open phasesa bc
Increased phaseimpedance
Za bc
8/16/2019 Symmetrical Componet Fauly calculation
376/521
6
Why Study Faults?• Determine currents and voltages in the
system under fault conditions• Use information to set protective devices
• Determine withstand capability thatsystem equipment must have:
– Insulating level
– Fault current capability of circuit breakers:• Maximum momentary current
• Interrupting current
8/16/2019 Symmetrical Componet Fauly calculation
377/521
7
Symmetrical Faults
α
t=0
2 V