SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

Dec 17, 2015

Download

Documents

Clyde Skinner
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 1

SYMAP-BC

Page 2: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 2

Symap-BC features

• 17 analogue inputs for current and voltage transformers are used for protection functions

• Free programmable relay outputs and inputs

• 4 analogue outputs / 4 analogue inputs

• 4 communication ports

• Protection functions in accordance to ANSI

• Self control functions, Watchdog and redundant backup

• Key functions via transponder technology

Page 3: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 3

Optional

• Alarm Recorder• GPS-Module for real time recording• Profibus-DP, IEC60870-5-103 Protocol• Fiberoptic module• Combined sensor - input• Extendable

– External modules for additional digitale und analogue I/O

Page 4: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 4

Measuring system

17 Measuring inputs

• 3x Feeder current• 6x Differential current• 9x Voltage inputs • 2x Ground current• 2x Grund voltage

Alternative: Combined sensors

DISPLAY

CPU

17

19

1516

CT

CB GPT

PT

1

2

3

4

5

6

13

R S T

26

21

14

Page 5: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 5

Communication

• 2x CAN Buses • 1x RS422/485 - fiberoptic or electrical

CAN 2

CAN 1Field level

Process level

RS 422/485

PC – TOOL

• 1x RS232C

Page 6: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 6

Protections functions in accordance to ANSI

• CURRENT

50, 51, 67, 46, 87

• Voltage

27, 59, 47

• Earth fault

50N, 51N, 67G(S),64/59N

• Other

25(A), 79, 81, 86, 94, 95i

Page 7: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 7

ANSI Protection functions #2

• 25/A Automatic synchronizing

• 27 Under voltage, Inst.

• 46 Negative phase sequence   

• 47 Phase sequence voltage      

• 50 Over current Inst.       

• 50N Current earth fault, Inst.

• 50BF Circuit-breaker failure

• 51 Over current

• 51N Current earth fault• 51V Voltage restrained overcur. 

• 59 Over voltage, Inst

• 64 /59N Ground over voltage      

• 67 Directional overcurrent       

• 67N/S Directional earth fault 

• 79 Auto reclosing      

• 81 Frequency      

• 86 Electrical lock out      

• 94 Trip circuit supervision

• 95i Inrush blocking 

       

Page 8: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 8

Additional ANSI-Functions

• 2 Time relay starting/closing        

• 12 Over speed device      

• 14 Under speed device      

• 24 Over excitation             

• 32 Reverse power      

• 37 Undercurrent      

• 40 Loss of field      

• 49T Thermal supervision    

• 49C Thermal overload    

• 51 Motor starting      

• 51LR Locked rotor   

• 66 Number of start      

• 87MTG– Motor

– Generator

– Transformer Diff.Protection

• 90 Voltage regulating

• XX Insulation measuring– (Rotor earth fault monitoring)

Page 9: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 9

Symap-BC Configuration

• 5 breaker controls• Libary of graphics• Transponder control of

several level– Event History

• Interlocking with other switching elements – Free progammable

G M T

Bus 1

Bus 2

23.4 KV

23.4 KV

0

ACK.EM. STOP

Page 10: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 10

Parameter inputs

Manual PC-Tool

The user can access the following:

- Systems parameters - Protection parameters - Alarm parameters - Relay- und trip-Parameter

Page 11: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 11

Event-ProcessMeasuring Input Measuring Analysis Process - control

MU

CU

RU

Measuring Event

LCD& LED

Alarmctrl.

Eventctrl.

EventHistory

Relayctrl.

ProcessProcess

Page 12: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 12

Symap-BC Recording Unit

• Recording of

– Total of 42 Inputs• 72 Samples : 5 sec

• 6 Samples : 60 sec

• Several recordings possible

• Pre-trigger setting adjustable

• Trigger event free programmable

• Data storage protected by battery back-up

Recorder : OFFSamples : 24Rec.Period: 3,00 secTrigger by: all-date : 00y00m00d-time : 00h00m00s-event : 0 / 0

Keyboard control:START RECORDERSTOP RECORDER

- Recorder Setting -

Page 13: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 13

Connection

Page 14: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 14

Symap-BC technical data

• Measuring inputs for wires up to 4mm²

• CT inputs automatically short circuited if terminal plugs are disconnected

• All connections are terminal plug types

• Connection plugs can not be interchanged due to mechanicl coding

• Basic unit:– 12 Relay outputs

– 14 Digital inputs• self supplyed

– Power supply• 12-36V -DC

• 36-72V -DC

• 80-300V-DC / 60-230V-AC

Page 15: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 15

Symap-BC dimensions

• Protection class of front panel NEMA4 (IP65)– Gasket for panel cut out

• Compact device for flush mounting– Only 130mm mounting depth

required

Page 16: SYMAP-BC1. 2 Symap-BC features 17 analogue inputs for current and voltage transformers are used for protection functions Free programmable relay outputs.

SYMAP-BC 16

Symap-BC certifcates

• EMC according to IEC / KERI

• Approval applieded & pending:– Electrical Utility Companies - HEW / etc.– Germanischer Lloyd (GL)– Lloyds register of shipping (LR)– and other classifications