SVG SUPER VERSATILE GAS BURNER SVG SERIES BURNERS In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. CAPACITIES (Btu/hr) SVG-2 (See Reverse Side for Metric Capacities) TILE DESIGNATION HR HS HC HA MR MS MA High Velocity Round High Velocity Square High Velocity Ceramic High Velocity Alloy Medium Velocity Round Medium Velocity Square Medium Velocity Alloy CAPACITY (10 3 Btu/hr) BURNER MODEL BURNER STATIC INLET AIR PRESSURE: 100 SERIES (16 OSIG) / 200 SERIES (8 OSIG) SVG 110 / 210 110 110 110 Not Available 120 120 120 SVG 112 / 212 250 250 250 Not Available 275 275 260 SVG 115 / 215 410 410 410 Not Available 415 415 410 SVG 120 / 220 700 700 700 Not Available 750 750 735 SVG 125 / 225 1,000 1,000 1,000 1,000 1,200 1,200 1,240 SVG 130 / 230 1,300 1,300 1,300 1,250 1,500 1,500 1,510 SVG 140 / 240 2,200 2,200 2,200 2,070 2,500 2,500 2,400 5,000 5,000 5,300 5,300 SVG 160 / 260 4,350 Not Available 4,350 4,150 4,600 Not Available 4,600 9,000 9,000 9,150 SVG 180 / 280 Pending Not Available Not Available Not Available Pending Not Available Pending NOTES: 1. Capacities based on natural gas with HHV of 1034 Btu/ft 3 , 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air. 2. Air and gas flows based on 60°F @ sea level. 3. Static air pressure measured at the burner air inlet pressure tap. 4. Flame lengths measured from the end of the burner tile. 5. All data based on industry standard air and gas piping practices. 6. Flame detection available via UV scanner or flame rod. 7. Burners can be operated above the rated static inlet air pressure; consult Hauck. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 2/07 www.hauckburner.com Fax: 717-273-9882
36
Embed
SVG SUPER VERSATILE GAS BURNER - promgas.com.uapromgas.com.ua/hauck/svg/svg.pdf · SVG SUPER VERSATILE GAS BURNER SVG-E SERIES BURNERS In accordance with Hauck’s commitment to Total
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
SVG SUPER VERSATILE GAS BURNER SVG SERIES BURNERS
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
CAPACITIES (Btu/hr)
SVG-2
(See Reverse Side for Metric Capacities)
TILE DESIGNATION
HR HS HC HA MR MS MA High Velocity
Round High Velocity
Square High Velocity
Ceramic High Velocity
Alloy Medium Velocity
Round Medium Velocity
Square Medium Velocity
Alloy
CAPACITY (103 Btu/hr)
BURNER MODEL BURNER STATIC INLET AIR PRESSURE: 100 SERIES (16 OSIG) / 200 SERIES (8 OSIG)
SVG 110 / 210 110 110 110 Not Available 120 120 120
SVG 112 / 212 250 250 250 Not Available 275 275 260
SVG 115 / 215 410 410 410 Not Available 415 415 410
SVG 120 / 220 700 700 700 Not Available 750 750 735
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER SVG-E SERIES BURNERS
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
2/07 Fax: 717-273-9882
CAPACITIES (kW)
SVG-E-2
TILE DESIGNATION
HR HS HC HA MR MS MA High Velocity
Round High Velocity
Square High Velocity
Ceramic High Velocity
Alloy Medium Velocity
Round Medium Velocity
Square Medium Velocity
Alloy
CAPACITY (kW)
BURNER MODEL BURNER STATIC INLET AIR PRESSURE: E SERIES (3,450 Pa)
SVG 25-E 29.1 29.1 29.1 Not Available 31.7 31.7 31.7
SVG 32-E 66.1 66.1 66.1 Not Available 72.7 72.7 69.2
SVG 40-E 108 108 108 Not Available 110 110 108
SVG 50-E 185 185 185 Not Available 198 198 194
SVG 65-E 265 265 265 265 317 317 328
SVG 80-E 343 343 343 330 395 395 400
SVG 100-E 582 582 582 548 660 660 635
SVG 150-E 1,150 Not Available 1,150 1,100 1,220 Not Available 1,220
SVG 200-E Pending Not Available Not Available Not Available Pending Not Available Pending
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER ����������������������������������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� �����������������
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
5/06 Fax: 717-273-9882
METRIC DIMENSIONS
SVG-E-3.1
Y72
88 M
ET
RIC
(N
OT
TO
SC
ALE
)
HIG
H V
EL
OC
ITY
SQ
UA
RE
TIL
E
SV
G 2
5B-E
-HS
– S
VG
100
-E-H
S
SVG SUPER VERSATILE GAS BURNER ��������������������������
SVG SUPER VERSATILE GAS BURNER ����������������������������������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� �����������������
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
11/07 Fax: 717-273-9882
METRIC DIMENSIONS
SVG-E-3.2
Y711
9 M
ETR
IC
(NO
T TO
SC
ALE)
HIG
H V
ELO
CIT
Y C
ERA
MIC
TU
BE
SVG
25B
-E-H
C –
SVG
150
-E-H
C
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SVG SUPER VERSATILE GAS BURNER In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
BURNER MODEL SVG 110 / 210 In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SUPPLEMENTAL DATA
SVG-4
(See Reverse Side for Metric Data)
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 16 OSIG (110) / 8 OSIG (210)
Air Flow for 110 / 210 (scfh) 110 110 110 130 130 125
Min. Input @ Air Flow (103 Btu/hr) 3.3 3.3 3.3 3.5 3.5 3.8
Max. Excess Air (%) 250 250 250
Not Available
300 300 250
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 25-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Min. Input @ Air Flow (kW) 0.9 0.9 0.9 0.9 0.9 1.0
Max. Excess Air (%) 250 250 250
Not Available
300 300 250
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER
BURNER MODEL SVG 112 / 212 In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SUPPLEMENTAL DATA
SVG-4.1
(See Reverse Side for Metric Data)
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 16 OSIG (112) / 8 OSIG (212)
Air Flow for 112 / 212 (scfh) 390 390 390 320 320 340
Min. Input @ Air Flow (103 Btu/hr) 8.3 8.3 8.3 3.4 3.4 6.0
Max. Excess Air (%) 400 400 400
Not Available
900 900 500
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 32-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Air Flow @ 45 Pa (nm3/hr) 10.5 10.5 10.5 8.6 8.6 9.2
Min. Input @ Air Flow (kW) 2.2 2.2 2.2 0.9 0.9 1.6
Max. Excess Air (%) 400 400 400
Not Available
900 900 500
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 115 / 215
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Air Flow for 115 / 215 (scfh) 350 350 350 415 415 450
Min. Input @ Air Flow (103 Btu/hr) 3.9 3.9 3.9 4.4 4.4 8.0
Max. Excess Air (%) 850 850 850
Not Available
900 900 500
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 40-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Air Flow @ 45 Pa (nm3/hr) 9.5 9.5 9.5 11.1 11.1 12.1
Min. Input @ Air Flow (kW) 1.0 1.0 1.0 1.2 1.2 2.1
Max. Excess Air (%) 850 850 850
Not Available
900 900 500
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 120 / 220
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Air Flow for 120 / 220 (scfh) 700 700 700 830 830 900
Min. Input @ Air Flow (103 Btu/hr) 6.8 6.8 6.8 8.0 8.0 8.7
Max. Excess Air (%) 1,000 1,000 1,000
Not Available
1,000 1,000 1,000
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER
BURNER MODEL SVG 50-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
Air Flow @ 45 Pa (nm3/hr) 18.9 18.9 18.9 22.2 22.2 24.3
Min. Input @ Air Flow (kW) 1.8 1.8 1.8 2.1 2.1 2.3
Max. Excess Air (%) 1,000 1,000 1,000
Not Available
1,000 1,000 1,000
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 125 / 225
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 65-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
2/07 Fax: 717-273-9882 SVG-E-4.4
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 3,450 Pa
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
METRIC DATA
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 130 / 230
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 80-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
2/07 Fax: 717-273-9882
METRIC DATA
SVG-E-4.5
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 3,450 Pa
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 140 / 240
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SUPPLEMENTAL DATA
(See Reverse Side for Metric Data)
SVG-4.6
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 16 OSIG (140) / 8 OSIG (240)
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 100-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 160 / 260
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. SVG-4.7
Air Flow for 160 / 260 (scfh) 5,810 5,810 9,600 5,450 5,960
Min. Input @ Air Flow (103 Btu/hr) 24.7 24.7 47 27.6 13.2
Max. Excess Air (%) 2,400
Not Available
2,400 2,000 2,000
Not Available
4,700
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SUPPLEMENTAL DATA
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 150-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051
2/07 Fax: 717-273-9882
METRIC DATA
SVG-E-4.7
TILE DESIGNATION
HR HS HC HA MR MS MA
High
Velocity Round
High Velocity Square
High Velocity Ceramic
High Velocity
Alloy
Medium Velocity Round
Medium Velocity Square
Medium Velocity
Alloy
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 3,450 Pa
BURNER SPECIFICATIONS - LOW FIRE BURNER STATIC INLET AIR PRESSURE OF 45 Pa
Input @ 10% Excess Air (kW) 150 150 210 139 154
Air Flow @ 45 Pa (nm3/hr) 157 157 260 146 161
Min. Input @ Air Flow (kW) 6.6 6.6 12.4 7.3 3.5
Max. Excess Air (%) 2,400
Not Available
2,400 2,000 2,000
Not Available
4,700
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 180 / 280
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
BURNER SPEIFICATION - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 16 OSIG (180) / 8 OSIG (280)
9,000 9,000 9,150 Max. Input @ 10% Excess Air for 180 / 280 (103 Btu/hr)
Pending Pending Pending
92,200 91,100 94,800 Max. Air Flow for 180 / 280 (scfh)
Pending Pending Pending
Min. Input @ Max. Air Flow (103 Btu/hr) 391 345 419
Max. Excess Air (%) 2,400 2,700 2,300
9.0 13.5 10.9 Air Orifice ΔP for 180 / 280 ("wc)
Pending Pending Pending
5.8 2.5 4.1 Gas Inlet Pressure for 180 / 280 ("wc)
Pending Pending Pending
Flame Length @ Max. Input (in) 120 132 96
Flame Diameter @ Max. Input (in) 17
Not Available
36
Not Available
20
BURNER SPECIFICATIONS - LOW FIRE BURNER STATIC INLET AIR PRESSURE OF 0.17 OSIG (180) / 0.10 OSIG (280)
Input @ 10% Excess Air (103 Btu/hr) 1,000 984 1,090
Air Flow for 180 / 280 (scfh) 10,400 10,200 11,300
Min. Input @ Air Flow (103 Btu/hr) 58.1 33.8 57.1
Max. Excess Air (%) 1,800
Not Available
3,100
Not Available
2,000
NOTES:
1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 60°F @ sea level.
3. Static air pressure measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static inlet air pressure; consult Hauck.
SVG SUPER VERSATILE GAS BURNER BURNER MODEL SVG 200-E
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
BURNER SPECIFICATIONS - HIGH FIRE BURNER STATIC INLET AIR PRESSURE OF 3,450 Pa
Max. Input @ 10% Excess Air (kW)
Max. Air Flow @ 3,450 Pa (nm3/hr)
Min. Input @ Max. Air Flow (kW)
Max. Excess Air (%)
Air Orifice ΔP (Pa)
Gas Inlet Pressure (Pa)
Flame Length @ Max. Input (mm)
Flame Diameter @ Max. Input (mm)
Pending Not Available
Pending Not Available
Pending
BURNER SPECIFICATIONS - LOW FIRE BURNER STATIC INLET AIR PRESSURE OF 45 Pa
Input @ 10% Excess Air (kW)
Air Flow @ 45 Pa (nm3/hr)
Min. Input @ Air Flow (kW)
Max. Excess Air (%)
Pending Not Available Pending Not
Available Pending
NOTES:
1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G., and an stoichiometric air:gas ratio of 9.74:1 with burner firing into chamber under no pressure @ 10% excess air.
2. Air and gas flows based on 0°C @ sea level.
3. Static air pressures measured at the burner air inlet pressure tap.
4. Flame lengths measured from the end of the burner tile.
5. All data based on industry standard air and gas piping practices.
6. Flame detection available via UV scanner or flame rod.
7. Burners can be operated above the rated static air inlet pressure; consult Hauck.