Top Banner
MASON INDUSTRIES, Inc. Manufacturers of Vibration Control Products NY Reply to: PO Box 410, Smithtown, NY 11787 350 Rabro Drive 2101 W. Crescent Ave., Suite D Hauppauge, NY 11788 Anaheim, CA 92801 631/348-0282 714/535-2727 FAX 631/348-0279 FAX 714/535-5738 [email protected] [email protected] SVCSA SVCSA-110-1 BULLETIN SVCS-100 SEISMIC SPECIFICATION APPLICATION DRAWINGS JANUARY 2004 Centrifugal Chiller Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints Centrifugal Chiller Seismically Rated Twin Sphere Air Spring Mounts Reciprocating Direct Height Saving Brackets, High Deflection Springs and Seismic Restraints Drive Compressor Steam Generator Directly mounted on Restrained Spring Mounts Double Concrete Filled Base with Height Saving Brackets, High Deflection Springs Suction Pump and Seismic Restraints End Suction Pump Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints End Suction Pump Steel Base with Height Saving Brackets, Air Springs and Seismic Restraints HVAC Unit Suspended from Hangers and restrained by Cable Assemblies in four corners HVAC Unit Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints HVAC Unit Directly mounted on 1” Deflection Springs Vertical Tank Type Concrete Filled Base, 1” Deflection Springs and Seismic Restraints Compressor Horizontal Tank Type Directly mounted on Restrained Spring Mounts Compressor Direct Drive Blower Bolted to Steel Base supported by Restrained Spring Mounts Utility Blower Directly mounted on Seismically Restrained Mounts Centrifugal Blower Concrete Filled Base with Height Saving Brackets, High Deflection Springs and Seismic Snubbers Centrifugal Blower Concrete Filled Base with 1” Deflection Springs, Built In Corners and Seismic Snubbers Axial Blower Steel Base with Height Saving Brackets, High Deflection Springs and Thrust Restraints. Axial Blower Suspended by Hangers, restrained by Cable Assemblies and Thrust Restraints Large Multi-sectioned Steel Base and Beam Supports using Restrained Air Spring Mounts Cooling Tower Large Multi-sectioned Steel Base and Beam Supports using High Deflection Steel Spring Cooling Tower Restrained Mounts Packaged HVAC Steel Base with Restrained Twin Sphere Air Spring Mounts Cooling Tower Rooftop Packaged Steel Base and Restrained Spring Mounts HVAC Cooling Tower Large Transformer Steel Base supported by Air Spring Mounts and Seismic Restraints 2S 3S 4S 5S 6S 7S 8S 9S 10S 11S 12S 13S 14S 15S 16S 17S 18S 19S 20S 21S 22S 23S 24S Page Equipment Isolation Description hangers are the same as in static locations but designated by numbers in the Selection Guide rather than letters to distinguish the two applications. We hope these illustrations will help. Seismic Applications are basically the same as Non Seismic but complicated by the need to keep equipment in place. Whenever we show our Z-1011 heavily cushioned snubbers, the input to the equipment will not exceed 4 G. All mountings, hanger-cables or snubbers are designed to resist the seismic force in any zone or specification. Many of the mountings and NOTE: All floor mounted systems are on seismically attached Housekeeping Pads. All pipelines include Safeflex expansion joints to allow seismic movement.
24

svcsa1

Mar 07, 2015

Download

Documents

Imran Saif
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: svcsa1

MASON INDUSTRIES, Inc.Manufacturers of Vibration Control Products

NY Reply to: PO Box 410, Smithtown, NY 11787350 Rabro Drive 2101 W. Crescent Ave., Suite D

Hauppauge, NY 11788 Anaheim, CA 92801631/348-0282 714/535-2727

FAX 631/348-0279 FAX 714/[email protected] [email protected]

SVCSASVCSA-110-1 BULLETIN

SVCS-100SEISMICSPECIFICATIONAPPLICATIONDRAWINGS

JANUARY 2004

Centrifugal Chiller Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints

Centrifugal Chiller Seismically Rated Twin Sphere Air Spring Mounts

Reciprocating Direct Height Saving Brackets, High Deflection Springs and Seismic RestraintsDrive CompressorSteam Generator Directly mounted on Restrained Spring Mounts

Double Concrete Filled Base with Height Saving Brackets, High Deflection Springs Suction Pump and Seismic Restraints

End Suction Pump Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints

End Suction Pump Steel Base with Height Saving Brackets, Air Springs and Seismic Restraints

HVAC Unit Suspended from Hangers and restrained by Cable Assemblies in four corners

HVAC Unit Steel Base with Height Saving Brackets, High Deflection Springs and Seismic Restraints

HVAC Unit Directly mounted on 1” Deflection Springs

Vertical Tank Type Concrete Filled Base, 1” Deflection Springs and Seismic RestraintsCompressorHorizontal Tank Type Directly mounted on Restrained Spring MountsCompressorDirect Drive Blower Bolted to Steel Base supported by Restrained Spring Mounts

Utility Blower Directly mounted on Seismically Restrained Mounts

Centrifugal Blower Concrete Filled Base with Height Saving Brackets, High Deflection Springsand Seismic Snubbers

Centrifugal Blower Concrete Filled Base with 1” Deflection Springs, Built In Corners and Seismic Snubbers

Axial Blower Steel Base with Height Saving Brackets, High Deflection Springs and Thrust Restraints.

Axial Blower Suspended by Hangers, restrained by Cable Assemblies and Thrust Restraints

Large Multi-sectioned Steel Base and Beam Supports using Restrained Air Spring MountsCooling Tower Large Multi-sectioned Steel Base and Beam Supports using High Deflection Steel Spring Cooling Tower Restrained Mounts

Packaged HVAC Steel Base with Restrained Twin Sphere Air Spring MountsCooling Tower Rooftop Packaged Steel Base and Restrained Spring MountsHVAC Cooling TowerLarge Transformer Steel Base supported by Air Spring Mounts and Seismic Restraints

2S

3S4S

5S6S

7S

8S9S

10S

11S12S

13S

14S15S16S

17S

18S

19S

20S

21S

22S

23S

24S

Page Equipment Isolation Description

hangers are the same as in static locations butdesignated by numbers in the Selection Guiderather than letters to distinguish the twoapplications. We hope these illustrations will help.

Seismic Applications are basically the same asNon Seismic but complicated by the need tokeep equipment in place. Whenever we showour Z-1011 heavily cushioned snubbers, theinput to the equipment will not exceed 4 G. Allmountings, hanger-cables or snubbers aredesigned to resist the seismic force in any zoneor specification. Many of the mountings and

NOTE: All floor mounted systems are on seismically attached Housekeeping Pads.All pipelines include Safeflex expansion joints to allow seismic movement.

Page 2: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

2S

CENTRIFUGAL CHILLER on WFSL Base with height saving brackets and high deflection SLF Mounts and Z-1011 Seismic

Restraints. Reinforced housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

SLF MOUNTSWITH SPECIFIEDDEFLECTIONSPECIFICATION 5

RESILIENT Z-1011 SEISMIC SNUBBERSMUST BE SECURED WITH SAB ANCHORSSPECIFICATION 17

WFSL BASE - WIDE FLANGE STEELBASE MINIMUM 6" (152mm) OR 1/10LONGEST BASE DIMENSIONSPECIFICATION 20

SAFEFLEX SFDEJEXPANSION JOINTINSTALLED ONEQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

HEIGHTSAVINGBRACKETS

FRICTION PADBOLTING NOTREQUIRED

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 3: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

3S

SLR-MT RESTRAINED TWIN SPHERE AIRSPRING MOUNT WITH SPECIFIEDFREQUENCY. MUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 9

3 AIR SPRING LEVELING VALVES(PIPING NOT SHOWN)

CONTROLS 2 ENDAIR SPRINGS

CORNER VALVEEACH SIDECONTROLS CORNERAIR SPRINGS

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

CENTRIFUGAL CHILLER directly mounted onseismically rated SLR-MT Restrained Twin Sphere Air Spring Mounts. Reinforced

housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration

and noise and to allow for seismic displacement.

Page 4: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

4S

SLF SPRING MOUNTS WITH SPECIFIED DEFLECTION SPECIFICATION 5

HEIGHT SAVINGBRACKET

COMPRESSOR MANUFACTURERSBASE MUST HAVE SUFFICIENT INTEGRITY TO ACCEPT MOUNTINGAND SNUBBER LOADING

RECIPROCATING DIRECT DRIVE COMPRESSOR with height saving brackets on high deflection SLF Mounts and Z-1011 Seismic

Restraints. Reinforced housekeeping pad secured by HPA Anchors.

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

FRICTION PADBOLTING NOTREQUIRED

Page 5: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

5S

STEAM GENERATOR directly mounted on SLR Restrained Spring Mounts. Reinforced housekeeping pad secured by HPA Anchors.

IN SEISMIC ZONES EXTENDEDBASE PLATES MAYBE REQUIREDTO MEET BOLTING CODES ANDMUST BE ANCHORED WITHSAB ANCHORS.SPECIFICATION 19

SLR RESTRAINEDSPRING MOUNT WITHSPECIFIED DEFLECTION.MUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 9

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

Page 6: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

6S

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OF THE SHUTOFF VALVES SPECIFICATION 23

DOUBLE SUCTION PUMP on concrete filled BMK Base with height saving brackets, high deflection SLF Spring Mounts and Z-1011 Seismic

Restraints. Reinforced housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

FILL PUMP BASEWITH GROUT IFCALLED FOR BYPUMP MANUFACTURER

BMK FLOATING CONCRETE BASE MINIMUM 6" (150mm) OR 1/12 LONGEST BASE DIMENSIONSPECIFICATION 21

SLF SPRING MOUNTSWITH SPECIFIED DEFLECTIONSPECIFICATION 5

HEIGHT SAVINGBRACKETS

BMK BASE IS LARGE ENOUGHTO SUPPORT SUCTION ANDDISCHARGE ELBOWS

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS. SPECIFICATION 29

FRICTION PADBOLTING NOTREQUIRED

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 7: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

7S

END SUCTION PUMP on WFSL Base with height saving brackets, high deflection SLF Mounts and Z-1011 Seismic Restraints. Reinforced

housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and

noise and to allow for seismic displacement.

SLF SPRING MOUNTS WITH SPECIFIED DEFLECTIONSPECIFICATION 5

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

WFSL BASE - WIDE FLANGE STEELBASE MINIMUM 6" (152mm) OR 1/10LONGEST BASE DIMENSIONSPECIFICATION 20

SAFEFLEX SFDEJEXPANSION JOINTINSTALLED ONEQUIPMENT SIDE OF THE SHUTOFF VALVESSPECIFICATION 23

WFSL BASE ISLARGE ENOUGHTO SUPPORTSUCTION ELBOW

HEIGHTSAVINGBRACKETS

FRICTION PADBOLTING NOTREQUIRED

REINFORCED HOUSEKEEPING PAD ISATTACHED TO THE STRUCTURE TO MEETTHE SEISMIC CODE BY HPA ANCHORS LOCKEDTO THE PAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 8: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

8S

WFSL BASE - WIDE FLANGE STEEL BASE MINIMUM 6" (152mm) OR 1/10 LONGEST BASE DIMENSION SPECIFICATION 20

WFSL BASE IS LARGE ENOUGH TO SUPPORT SUCTION ELBOW.

MT TWIN SPHERE AIR SPRINGS MUST BE INSTALLED WITH AIRSPRING LEVELING VALVES SPECIFICATION 8

CORNER VALVEEACH SIDECONTROLS CORNERAIR SPRINGS

CONTROLS 2 ENDAIR SPRINGS

3 AIR SPRING LEVELING VALVES (PIPING NOT SHOWN)

END SUCTION PUMP on WFSL Base with height saving brackets, MT Air Springs and Z-1011 Seismic Restraints. Reinforced housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for

seismic displacement.

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OF THE SHUTOFF VALVESSPECIFICATION 23

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

REINFORCED HOUSEKEEPINGPAD IS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

FRICTION PADBOLTING NOTREQUIRED

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 9: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

9S

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OF THE SHUTOFF VALVESSPECIFICATION 23

RW30N SPRING HANGERSWITH SPECIFIED DEFLECTIONSPECIFICATION 10

HVAC UNIT suspended from RW30N Hangers and restrained by SCB Cable Assemblies in four corners. SAFEFLEX Expansion

Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

SCBH - SEISMICCABLE BRACING HOOKSPECIFICATION 12

SRC - SEISMICROD CLAMP ANDANGLE BRACES FORTHREADED RODSSPECIFICATION 14

SCB - SEISMIC CABLE BRACINGBOTH SIDES (ONE SIDE SHOWN)SPECIFICATION 12

SWAY BRACINGNOT SHOWNTHIS SIDE

45°

3/8"

RESTRAINT ANGLE30° TO 60° TO STRUCTURE.ANGLE OF ATTACHMENT 45°

DOUBLE DEFLECTIONNEOPRENE ELEMENTWITH PROJECTINGBUSHING TO PREVENTSTEEL TO STEEL CONTACT.

NEOPRENE SPRING CUPWITH A PROJECTINGBUSHING TO PREVENTSTEEL TO STEEL CONTACT.

ROD CAN SWING 30°BEFORE CONTACTINGRESILIENT BUSHING.

30°

REBOUND WASHER TO PREVENT UP LIFT.

Page 10: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

10S

WFSL BASE - WIDE FLANGE BASE BASEMINIMUM 6" (152mm) OR 1/10 LONGEST BASEDIMENSION. SUPPLEMENTARY BASE IS USEDTO PROVIDE SNUBBER ATTACHMENT STRENGTHOR SUPPORT MULTIPLE SECTIONS.SPECIFICATION 20

SLF SPRING MOUNTSWITH SPECIFIEDDEFLECTIONSPECIFICATION 5

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

HVAC UNIT on steel base with height saving brackets, high deflection SLF Spring Mounts and Z-1011 Seismic Restraints. Reinforced

housekeeping pad secured by HPA Anchors. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and

noise and to allow for seismic displacement.

HEIGHT SAVINGBRACKETS

REINFORCED HOUSEKEEPINGPAD IS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17 FRICTION PAD

BOLTING NOTREQUIRED

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 11: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

11S

HVAC UNIT directly mounted on 1" deflection SSLFH Spring Mounts. Reinforced housekeeping pad secured by HPA Anchors.

SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

SSLFH SPRING MOUNTSWITH SPECIFIED DEFLECTION.MUST BE SECURED WITHSAB ANCHORS SPECIFICATION 7

SAFEFLEX SFDEJ EXPANSION JOINT INSTALLED ON EQUIPMENT SIDE OF THE SHUTOFF VALVESSPECIFICATION 23

MANUFACTURERS BASE MUSTHAVE ADEQUATE STRUCTURALINTEGRITY OR A SUPPLEMENTARYBASE IS REQUIRED

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 12: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

12S

SLF SPRING MOUNTSWITH SPECIFIEDDEFLECTIONSPECIFICATION 5

STABILITY FURTHERIMPROVED BYSPREADING OF MOUNTS

VERTICAL TANK TYPE COMPRESSOR directly mounted on BMK Concrete Filled Base, 1" deflection SLF Mounts and Z-1011 Seismic Restraints. Reinforced housekeeping pad secured by HPA Anchors.

CENTER OF GRAVITYIS LOWERED BY MASSOF BMK FLOATINGCONCRETE BASE

HIGH CENTER OF GRAVITYWITHOUT CONCRETEBASE (POOR STABILITY)

LOWERED CENTER OFGRAVITY ON CONCRETEBASE (IMPROVED STABILITY)

BMK FLOATINGCONCRETE BASEMINIMUM 6" (150mm) OR 1/12 LONGESTBASE DIMENSIONSPECIFICATION 21

TEMPLATES

REINFORCED HOUSEKEEPINGPAD IS ATTACHED TO THESTRUCTURE TO MEET THESEISMIC CODE BY HPAANCHORS LOCKED TO THEPAD REINFORCING STEELAND SCREWED TO SASFLOOR STUDS.SPECIFICATION 29

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

Page 13: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

HORIZONTAL TANK TYPE COMPRESSOR directly mounted on SLR Restrained Spring Mounts.

Reinforced housekeeping pad secured by HPA Anchors.

SLR RESTRAINED SPRING MOUNTWITH SPECIFIED FREQUENCY.MUST BE SECURED WITHSAB ANCHORSSPECIFICATION 9

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

IN SEISMIC ZONES EXTENDEDBASE PLATES MAYBE REQUIREDTO MEET BOLTING CODES ANDMUST BE ANCHORED WITHSAB ANCHORS.SPECIFICATION 19

13S

Page 14: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

MS-SLR - STEEL ANGLE BASECOMPENSATES FOR BLOWER OVERHANG AND PREVENTS TIPPING

DIRECT DRIVE BLOWER bolted to MS-SLR Steel Angle Base supported by SLR-A Restrained Spring Mounts.

Reinforced housekeeping pad secured by HPA Anchors.

SLR-A RESTRAINED SPRING MOUNTWITH SPECIFIED DEFLECTION,WIND RESISTANT OR SEISMICCAPACITY WHICH EVER IS HIGHER.MUST BE SECURED WITH SAB ANCHORSSPECIFICATION 6

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL ANDSCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

NOTE: NO OUTBOARD SUPPORT LOCATION BY MANUFACTURER

14S

Page 15: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

UTILITY BLOWER directly mounted on seismically restrained SLR-A Mounts. Reinforced housekeeping pad secured by HPA Anchors.

Also useful for non seismic outdoor windy locations.

SLR-A SPRING MOUNTWITH SPECIFIED DEFLECTION,WIND RESISTANT OR SEISMICCAPACITY WHICH EVER IS HIGHER.MUST BE SECURED WITH SAB ANCHORSSPECIFICATION 6

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL ANDSCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

NOTE: MOUNT LOCATION OMITTED BECAUSE OF SECTIONTOTAL 6 MOUNTS

15S

Page 16: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

BMK FLOATING CONCRETE BASE MINIMUM 6" (150mm) OR 1/12 LONGEST BASE DIMENSIONSPECIFICATION 21

SLF SPRING MOUNTSWITH SPECIFIEDDEFLECTIONSPECIFICATION 5

MOTOR SLIDE RAILSTO MATCH MOTORFRAME

RESILIENT Z-1011SEISMIC SNUBBERSSPECIFICATION 17

HEIGHT SAVINGBRACKETS

CENTRIFUGAL BLOWER on concrete filled BMK Base with height saving brackets, high deflection SLF Spring Mounts and Z-1011 Seismic

Snubbers. Reinforced housekeeping pad secured by HPA Anchors.

TEMPLATES

ANCHOR BOLTSAND ANCHORSLEEVES

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

FRICTION PADBOLTING NOTREQUIRED

16S

Page 17: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

BMK FLOATING CONCRETE BASE MINIMUM 6" (150mm) OR 1/12 LONGEST BASE DIMENSIONSPECIFICATION 21

SLF SPRING MOUNTS WITH SPECIFIED DEFLECTIONSPECIFICATION 5

MOTOR SLIDE RAILS TO MATCH MOTOR FRAME

RESILIENT Z-1011SEISMIC SNUBBERSSPECIFICATION 17

CENTRIFUGAL BLOWER on concrete filled BMK Base with built in corners, 1" deflection SLF Spring Mounts and Z-1011 Seismic

Restraints. Reinforced housekeeping pad secured by HPA Anchors.

TEMPLATES

ANCHOR BOLTSAND ANCHORBOLT SLEEVES

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

FRICTION CUPBOLTING NOTREQUIRED

17S

Page 18: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

18S

AXIAL BLOWER with WBI/WBD Thrust Restraints mounted on WFSL Base with height saving brackets, high deflection SLF Mounts and Z-1011 Seismic

Restraints. Reinforced housekeeping pad secured by HPA Anchors.

WFSL - WIDE FLANGE STEEL BASE MINIMUM 6" OR 1/10 LONGEST BASE DIMENSION SPECIFICATION 20

SLF SPRING MOUNTS WITH SPECIFIED DEFLECTION SPECIFICATION 5

HEIGHT SAVING BRACKETS

AIR FLOW

STEEL CROSSBRACING

WBI\WBD THRUST RESTRAINTS ACROSS FLEXIBLECONNECTION WITH DEFLECTION EQUAL TOHANGER DEFLECTIONSPECIFICATION 28

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17 REINFORCED HOUSEKEEPING PAD

IS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

FRICTION PADBOLTING NOTREQUIRED

Page 19: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

THREADEDROD

RW30N SPRINGHANGERSWITH SPECIFIEDDEFLECTIONSPECIFICATION 10

WBI\WBD THRUST RESTRAINTSACROSS FLEXIBLE CONNECTIONWITH DEFLECTION EQUAL TOHANGER DEFLECTIONSPECIFICATION 28

AIR FLOW

AXIAL BLOWER with WBI/WBD Thrust Restraints suspended by RW30N Hangers and restrained by SCB Cable Assemblies

SCBH - SEISMIC CABLEBRACING HOOKSPECIFICATION 12

SCB - SEISMIC CABLE BRACINGBOTH SIDES (ONE SIDE SHOWN)

SPECIFICATION 12

RESTRAINT ANGLE30° TO 60° TO STRUCTURE

SWAY BRACINGNOT SHOWNTHIS SIDE

ANGLE OF ATTACHMENT 45°

19S

SRC - SEISMICROD CLAMP ANDANGLE BRACES FORTHREADED RODSSPECIFICATION 14

3/8"

30°

DOUBLE DEFLECTIONNEOPRENE ELEMENTWITH PROJECTINGBUSHING TO PREVENTSTEEL TO STEEL CONTACT.

NEOPRENE SPRING CUPWITH A PROJECTINGBUSHING TO PREVENTSTEEL TO STEEL CONTACT.

ROD CAN SWING 30°BEFORE CONTACTINGRESILIENT BUSHING.

REBOUND WASHER TO PREVENT UP LIFT.

Page 20: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

20S

LARGE MULTI-SECTIONED COOLING TOWER secured to steel base and beam supports using SLR-MT Restrained Air Spring Mounts. SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

STRUCTURAL SUB BASENORMALLY BY OTHERS

3 AIR SPRING LEVELING VALVES(PIPING NOT SHOWN)

COLUMNS EXTENSIONS OR PEDESTALS PROPERLY REINFORCED

CORNER VALVE EACH SIDE.CONTROLS 3 SIDE AIR SPRINGS

CONTROLS2 CORNERAIR SPRING

STEEL BASE BY MASON

ALL INTERFACESSECURED

SLR-MT RESTRAINED AIRSPRING MOUNTS WITH SPECIFIED FREQUENCY.WIND RESISTANT OR SEISMICCAPACITY IN SEISMIC ZONES,WHICHEVER IS HIGHER.SPECIFICATION 9

SAFEFLEX SFDEJEXPANSION JOINT

INSTALLED ONEQUIPMENT SIDE OF

THE SHUTOFF VALVESSPECIFICATION 23

Page 21: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

STRUCTURAL SUB BASENORMALLY BY OTHERS

STEEL BASEBY MASON

PROPERLY REINFORCED COLUMNS, EXTENSIONS OR PEDESTALS

LARGE MULTI-SECTIONED COOLING TOWER secured to steel base and beam supports using high deflection SLR Restrained Spring Mounts.

SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

HIGH DEFLECTION SLR RESTRAINEDSPRING MOUNTSWITH SPECIFIEDDEFLECTION.WIND RESISTANTOR SEISMIC CAPACITYIN SEISMIC ZONES,WHICHEVER IS HIGHER.SPECIFICATION 6

SAFEFLEX SFDEJEXPANSION JOINTINSTALLED ONEQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

ALL INTERFACESSECURED

SPRING DEFLECTION BASED ONFAN RPM WHEN LESS THAN 600 RPM

21S

Page 22: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

ADDITIONAL STEEL TO HOLD AIR SPRING LEVELING VALVES

PROPERLY REINFORCED COLUMNS, EXTENSIONS OR PEDESTALS

STEEL BASE BY MASON

PACKAGED HVAC COOLING TOWER on steel base withSLR-MT Restrained Twin Sphere Air Spring Mounts.

SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

SLR-MT RESTRAINED TWIN SPHEREAIR SPRING MOUNTS WITH SPECIFIEDFREQUENCY. WIND RESISTANT ORSEISMIC CAPACITY IN SEISMIC ZONES,WHICHEVER IS HIGHER.SPECIFICATION 9

SAFEFLEX SFDEJEXPANSION JOINTINSTALLED ONEQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

3 AIR SPRING LEVELING VALVES(PIPING NOT SHOWN)

CONTROLS 2 ENDAIR SPRINGS

CORNER VALVEEACH SIDECONTROLSCORNERAIR SPRINGS

22S

Page 23: svcsa1

MASON INDUSTRIES SEISMIC APPLICATIONS

23S

HIGH DEFLECTION SLRRESTRAINED SPRING MOUNTSWITH SPECIFIED DEFLECTION.WIND RESISTANT OR SEISMICCAPACITY IN SEISMIC ZONES,WHICHEVER IS HIGHER.SPECIFICATION 6

STEEL BASEBY MASON

ROOFTOP PACKAGED HVAC COOLING TOWER on steel base and SLR Restrained Spring Mounts.

SAFEFLEX Expansion Joints are installed in pipelines to reduce blade frequency vibration and noise and to allow for seismic displacement.

SAFEFLEX SFDEJ EXPANSION JOINTINSTALLED ON EQUIPMENT SIDE OFTHE SHUTOFF VALVESSPECIFICATION 23

EXTENDED BASEPLATE TO MEETBOLTING CODE

SPRING DEFLECTION BASED ON FAN RPM WHEN LESS THAN 600 RPM

PROPERLY REINFORCED COLUMNS, EXTENSIONS OR PEDESTALS

CR - CONTROL RODSUSED ONLY WHEN SAFEFLEX CANNOT BE PREEXTENDED TO PRESSURIZED LENGTH DURING INSTALLATION

Page 24: svcsa1

MASON INDUSTRIESSEISMIC APPLICATIONS

LARGE TRANSFORMER mounted on a WFSL or KSL Base supported by MT Air Spring Mounts and Z-1011 Seismic Restraints. Reinforced

housekeeping pad secured by HPA Anchors. Schematic Only– Final installation to meet all safety regulations as well as electrical and other codes.

WFSL BASE - WIDE FLANGE STEEL BASE MINIMUM 6" (152mm) OR 1/10 LONGEST BASE DIMENSIONSPECIFICATION 20

CORNER VALVEEACH SIDECONTROLS CORNERAIR SPRINGS

CONTROLS 2 ENDAIR SPRINGS

MT TWIN SPHERE AIR SPRINGSMUST BE INSTALLED WITH AIRSPRING LEVELING VALVESSPECIFICATION 8

RESILIENT Z-1011SEISMIC SNUBBERSMUST BE SECUREDWITH SAB ANCHORSSPECIFICATION 17

REINFORCED HOUSEKEEPING PADIS ATTACHED TO THE STRUCTURETO MEET THE SEISMIC CODE BYHPA ANCHORS LOCKED TO THEPAD REINFORCING STEEL AND SCREWED TO SAS FLOOR STUDS.SPECIFICATION 29

3 AIR SPRING LEVELING VALVES (PIPING NOT SHOWN)FRICTION PAD

BOLTING NOTREQUIRED

24S

KSL BASE - STEEL CHANNEL REINFORCED AND FILLED WITH CONCRETE. BASE MINIMUM 6" (152mm) OR 1/12 LONGEST BASE DIMENSIONSPECIFICATION 21 ALL OTHER CALLOUTS ABOVE APPLY HERE

1/04Tm401

Printedin U.S.A.