Page 1: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

SV100SV100 Open-Loop Vector VFD Open-Loop Vector VFD FV100FV100 Closed-Loop Vector VFD Closed-Loop Vector VFD

1

Page 2: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

SV100/FV100SV100/FV100 Selection Guide Selection Guide SVSV//FVFV Series : Series :

Single Phase(220V): Single Phase(220V): 0.4K0.4KW~2.2KW; W~2.2KW; ThreeThree Phase(380V)Phase(380V): 0.4K: 0.4KW~W~40400KW. 0KW. CCV Series: Mini type, V Series: Mini type,

Single Phase(220V):0.4KSingle Phase(220V):0.4KW~W~1.51.5KWKW, Three Phase:1.5~2.2KW, Three Phase:1.5~2.2KW

2

Page 3: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Hardware InstructionHardware Instruction

3

Page 4: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Hardware StructureHardware Structure

4

Page 5: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

All Series supports wall-mountedAll Series supports wall-mounted

5

Page 6: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Hardware Configuration(FV)Hardware Configuration(FV)

77 digital inputs digital inputs (( 11 high speed pulse input high speed pulse input)。)。 33 analog inputs analog inputs (( -10~10V-10~10V ;; 4~20mA4~20mA)。)。 22 digital ouputs digital ouputs。。 11 relay output relay output

6

Page 7: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Extensible Operation PadExtensible Operation Pad

7

RS485RS485 Communication Communication

RJ45 Cable

Page 8: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Control MethodControl Method

SV100SV100 :: V/FV/F,, Open-loopOpen-loop FV100FV100 :: V/FV/F,, Open-loop and closed-loopOpen-loop and closed-loop Support analog control: Support analog control: ±10V±10V//4~20mA4~20mA Communication ControlCommunication Control Digital Input ControlDigital Input Control Pulse ControlPulse Control (( FV100FV100))

8

Page 9: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Software InstructionSoftware Instruction

9

Page 10: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Main FunctionsMain Functions

10

Page 11: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

Power on the Drive for the first time

After checking the wiring and power supply, power on the VFD, the VFD display “8.8..8.8.8”, then the relay is ON, when the LD displays the setting frequency , the VFD is initializes and starts successfully.

Page 12: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

V/FV/F Control Control (( Key Pad ControlKey Pad Control ))

DefinitionDefinition :: V/FV/F is a constant , is a constant ,A0.01=2A0.01=2 Performance Parameters:Performance Parameters: 11:: Basic Operation Frequency Basic Operation Frequency FF :: A0.12A0.12 22:: External Input Voltage:External Input Voltage:VV 33:: Torque BoostTorque Boost :: A0.13A0.13 ,, b1.07b1.07 Operation ParametersOperation Parameters (( Key Pad SettingKey Pad Setting )) 11:: Main FrequencyMain Frequency :: A0.02=0A0.02=0 22:: Method of Operation CommandMethod of Operation Command :: A0.04=0A0.04=0 33:: Running DirectionRunning Direction :: A0.05:0A0.05:0:: ForwardForward ;; 11:: ReverseReverse 44:: Acc/Dec TimeAcc/Dec Time :: A0.06A0.06 ,, A0.07A0.07 55:: Start/Stop MethodStart/Stop Method:: Group A1Group A1

12

Page 13: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

13

V/FV/F Control Control (( Analog ControlAnalog Control )) DefinitionDefinition :: V/FV/F is a constant . is a constant .A0.01=2A0.01=2 Performance Parameters:Performance Parameters: 11:: Basic Operation Frequency Basic Operation Frequency FF :: A0.12A0.12 22:: External Input Voltage:External Input Voltage:VV 33:: Torque BoostTorque Boost :: A0.13A0.13 ,, b1.07b1.07 Operation ParametersOperation Parameters (( Key Pad SettingKey Pad Setting )) 11:: Main FrequencyMain Frequency:::: A0.02=1A0.02=1,, 22:: Method of Operation CommandMethod of Operation Command :: A0.04=0A0.04=0(Key Pad)(Key Pad) ,, A0.04=1A0.04=1(Di(Di

gital Input)gital Input) :: XiXi setting , setting ,A6.00~A6.06A6.00~A6.06 33:: Running DirectionRunning Direction :: A0.05=0A0.05=0:: ForwardForward ;; 11:: ReverseReverse。。 44:: Acc/Dec TimeAcc/Dec Time :: A0.06A0.06 ,, A0.07A0.07 55:: Start/Stop MethodStart/Stop Method:: Group A1Group A1 6: Analog Setting: A3.00~A3.046: Analog Setting: A3.00~A3.04

Page 14: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

14

V/FV/F Control Control (( Multi-SpeedMulti-Speed )) DefinitionDefinition :: V/FV/F is a constant . is a constant .A0.01=2A0.01=2 Performance Parameters:Performance Parameters: 11:: Basic Operation Frequency Basic Operation Frequency FF :: A0.12A0.12 22:: External Input Voltage:External Input Voltage:VV 33:: Torque BoostTorque Boost :: A0.13A0.13 ,, b1.07b1.07 Operation ParametersOperation Parameters (( Key Pad SettingKey Pad Setting )) 11:: Main FrequencyMain Frequency:::: A0.02=A0.02=0.0. 22:: Method of Operation CommandMethod of Operation Command :: A0.04=0A0.04=0(Key Pad)(Key Pad) ,, A0.04=1A0.04=1(Dig(Dig

ital Input)ital Input) :: XiXi setting , setting ,A6.00~A6.06A6.00~A6.06 33:: Running DirectionRunning Direction :: A0.05=0A0.05=0:: ForwardForward ;; 11:: ReverseReverse。。 44:: Acc/Dec TimeAcc/Dec Time :: A0.06A0.06 ,, A0.07A0.07 55:: Start/Stop MethodStart/Stop Method:: Group A1Group A1 66:: Multi-Frequency(Speed)Multi-Frequency(Speed):: Group Group C0C0

Page 15: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

15

V/FV/F Control Control (( MainMain++Auxiliary FrequencyAuxiliary Frequency ))

DefinitionDefinition :: V/FV/F is a constant . is a constant .A0.01=2A0.01=2 Performance Parameters:Performance Parameters: 11:: Basic Operation Frequency Basic Operation Frequency FF :: A0.12A0.12 22:: External Input Voltage:External Input Voltage:VV 33:: Torque BoostTorque Boost :: A0.13A0.13 ,, b1.07b1.07 Operation ParametersOperation Parameters (( Key Pad SettingKey Pad Setting )) 11:: Main FrequencyMain Frequency:::: A0.02=A0.02=0.0. 22:: Method of Operation CommandMethod of Operation Command :: A0.04=0A0.04=0(Key Pad)(Key Pad) ,, A0.04=1A0.04=1(D(D

igital Input)igital Input) :: XiXi setting , setting ,A6.00~A6.06A6.00~A6.06 33:: Running DirectionRunning Direction :: A0.05=0A0.05=0:: ForwardForward ;; 11:: ReverseReverse。。 44:: Acc/Dec TimeAcc/Dec Time :: A0.06A0.06 ,, A0.07A0.07 55:: Start/Stop MethodStart/Stop Method:: Group A1Group A1 66 :: MainMain++Auxiliary Frequency:Auxiliary Frequency:A0.03+A2A0.03+A2

Page 16: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

16

Open-Loop Vector Control IntroduceOpen-Loop Vector Control Introduce

DefinitionDefinition :: VFD caculate the current via PID,VFD caculate the current via PID,A0.01=0A0.01=0 Performance Parameters:Performance Parameters: 11:: Basic Operation Frequency Basic Operation Frequency FF :: A0.12A0.12 22:: External Input Voltage:External Input Voltage:VV 33:: Auto-tuningAuto-tuning:: set set b0.00b0.00 first first,, Then use the Then use the b0.11b0.11。。 44 :: PIDPID Parameters Parameters :: Group Group A5A5(( Speed Control, Analog ControlSpeed Control, Analog Control))

Page 17: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.

17

OutputsOutputs

Output ParametersOutput Parameters(( PulsePulse)) 11 :: A6.25A6.25 :: Y2Y2 Output Functions Output Functions 22 :: A6.26A6.26 ,, A6.27A6.27

Output ParametersOutput Parameters (( AO1 AO1 )) 11 :: A6.28A6.28 :: AO1AO1 Output Functions Output Functions 22 :: A6.30A6.30 ,, A6.31A6.31

Page 18: SV100 Open-Loop Vector VFD FV100 Closed-Loop Vector VFD 1.