A REPORT ON SUMMER TRAINING AT 220 KV GSS SALAWAS ROAD JODHPUR (RAJ.) Submitted in partial fulfillment Of the Requirement of the degree OF BACHELOR OF TECHCONOLOGY IN ELECTRICAL & ELECTRONICS ENGINEERING SUBMITTED BY:- ANUPRIYA PANDEY DEPT. OF ELETRICAL & ELECTRONICS ENGINEERING RAJASTHAN INSTITUTE OF ENGINEERING & TECH. 1 1
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
AREPORT
ON SUMMER TRAINING
AT220 KV GSS SALAWAS ROAD
JODHPUR (RAJ.)
Submitted in partial fulfillment Of the
Requirement of the degree OF
BACHELOR OF TECHCONOLOGYIN
ELECTRICAL & ELECTRONICS ENGINEERING
SUBMITTED BY:- ANUPRIYA PANDEY
DEPT. OF ELETRICAL & ELECTRONICS ENGINEERING
RAJASTHAN INSTITUTE OF ENGINEERING & TECH.
AKNOWLEDGEMENT
I wish to express my sincere thanks to Mr. Sanwal who arranged my vocational training at 220 KV GSS, Jodhpur . I gratefully acknowledge the valuable cooperation rendered by Mr. S.D. Panwar (Executive Engineer) 220 KV. G.S.S. Jodhpur. I am also thankful to Mr. Prashant Lodha (Astt. Engineer.) for being helpful & providing me valuable instructions & study material . And Special thanks to staff & workers of 220 KV G.S.S, Jodhpur.
1
1
PREFACE
I under went summer training at 220KV G.S.S., SALAWAS ROAD, Jodhpur. This is a part of total 30 days training program incorporated in the curriculum of RTU.As I am a student of electrical & electronics engg. So the training at G.S.S. has been particularly beneficial for me. I saw the various procedure process & equipment used in TRANSMISSION & DISTRIBUTION of electricity by equipments which were studied in the books & this has helped me in better understanding of transmission & distribution concepts of electrical power.G.S.S. is a very large concept & it is very difficult to acquire complete knowledge about it in a short span. I have tried to get acquainted with overall plant functioning & main concept involved there in.
2
2
Contents
3
3
INTRODUCTION
Energy is the basic necessity for the economic development of a country.
Energy exists in different forms in nature but the most important form is the electrical
energy.
The conversion of energy available in different forms in nature into electrical
energy is known as generation of electrical energy.
Various sources of energy available are:-
i) The Solar Energy
ii) The wind Energy
iii) Water
iv) Fuels
4
4
v) Nuclear energy
More than 70 % of the Electricity in India is generated through fuels.
Electricity is generated at 6.6 KV & 11 KV levels which are further stepped up by
step up transformer to 220KV and further to 400 KV level. This Electric supply is
transmitted at 400 KV/220 KV/132 KV voltage level to interconnected Grid
Substations. From these Grid Substations Electric supply is further step down and
distributed to 33KV/11KV substations and finally this supply is made available at
consumer end at 415/220 Volt.
The whole electrical system is classified as
(a) Generation
(b) Transmission
(c) Distribution
(d) Utilization
(e) Switch Gear and Protection
Electricity is generated and is then distributed to various sub-stations, where
the voltage is reduced to 220 K.V. with the help of step down transformer. From these
sub-stations the energy is distributed to the consumer after reducing it to 33 K.V.
The 220kv G.S.S in Jodhpur is situated on Basni Phase-II, Salawas Road, and
9-10 KM away from Jodhpur Railway Station. The names of the Feeders connected to
this GSS are as under:-
1. 220 KV Pali
2. 220 KV Surpura Ist
3. 220 KV Surpura IInd
4. 220 KV Balotra
5. 132 KV Baori
6. 132 KV Banar
7. 132 KV Bilara
8. 132 KV Stainless Steel Factory
9. 132 KV Pali
5
5
10. 132 KV CHB
11. 132 KV P.S.8
12.132 Jodhpur I
13. 132 KV Jodhpur II
14. 33 KV No. 1
15. 33 KV No. 2 (I.O.C)
16. 33 KV No. 3
17. 11 KV No. 1( Industrial Area)
18. 11 KV No. 2 (Industrial Area)
19. 11 KV No. 3 (Lift Canal )
20. 11 KV No. 5 (Industrial Area )
21. 11 KV No. 6 (Domestic Load )
22. 11 KV No. 7 (Domestic Area )
23. 11 KV No. 8 (Industrial Area )
24. 11 KV No. 9 (Industrial Area )
The various components of a substation are described below:-
Incoming Lines
Outgoing Lines
Transformers, main power transformers, auxiliary transformers.
HV & LV switch gear, circuit breaker, isolators etc.
Relay and metering panels, CTs, PTs, control panel
Shunt reactors, shunt capacitors.
Drop out fuses
Power Cables, control cables.
6
6
Station service equipment such a lighting, Auxiliary battery supply,
transformer, Oil purification set, compressed air system, battery overhead
earth wires.
Station earthing system.
Mesh earthing system.
Galvanized steel structures
Communication equipment
SCADA system
Interphase metering system
7
7
POWER TRANSFORMER
Transformer is a static electrical machine, which works on the principle of
electromagnetic induction. It transfers electrics power from one electric circuit to
another electric circuit with the help of magnetic path (flux) on constant frequency but
equal or different voltage and current. For this purpose two set of insulated windings
are wounded on a close terminated silicon steel core. Winding which connected to the
supply is called primary winding and that winding which connected to the load is
called secondary winding.
MAIN PARTS OF POWER TRANSFORMER
1. CORE :
It consist of laminated silicon steel in which quantity of silicon is upto 4%
Thickness of lamination is 0.35 to 0.50 mm. Normally the shape of the core is
rectangular and it has three legs.
2. WINDING :
8
8
Winding of power transformer is an important part. It consist of super
enameled copper wires, the size of wire (diameter) depends on the capacity of
transformer.
3. TAP-CHANGER :
Tap changer is a switching device by which transformation ratio can be
changed by changing the position of tap changing switch.
TAP-CHANGING SYSTEM ON G.S.S. POWER TRANSFORMER
On Load Tap Changer (OLTC):
On load tap changer are employed to change turns ratio of transformer to
regulate system voltage while the transformer is delivering normal load. With the
introduction of on load tap changing the operating efficiency of electrical system has
considerably improved.
Now a days, almost all the large power transformer are fitted with no load tap
changer. All forms of no load tap changer ckt. posses an impedance, which is
introduced to prevent short circuiting of tapping section during tap changer operation.
The impedance can be either a resist for a center tapped reactor.
4. TANK :
It is a metallic tank which is filled with insulating oil. The transformer core
and wdg. Assembly is surrounded by the oil in this tank. It protects the wdg. And core
from the external mechanical damages. Rectangular tanks are simpler in fabrication.
However for large rating power transformer, shaping of tanks becomes
necessary to confirm to transportable profile, shaping is provided by rounded corners
at the ends, truncations of low portions by wall from consideration of loading is well
wages girder and on the covers to reduce the height to minimize the tank oil, the tank
profile may closely follow the electrical clearness along the coils. As is evident
shaping gives saving in tank material and oil but increases complexity and fabrication
cost.
9
9
Transformer tanks may be classified as:
Plain tanks
Shaped tanks
Belt shaped tanks
Corrugated tanks
Stub end type tanks
The transformer tanks are used in GSS. Power transformer is rectangular box (plain
tanks) type in shape.
5. TERMINAL BUSHING:
It is used to isolate the leads, which is coming from the transformer.
6. COOLING SYSTEM:
In power transformer, the oil serves a dual purpose, as an insulating medium
as well as a cooling medium. The heat generated in the transformer is removed by the
transformer oil surrounding the source and is transmitted either to atmospheric air or
water.
This transform of heat is essential to control the temperature with in
permissible limits for the class of insulation, there by ensuring longer life due to less
thermal degradation.
THE DETAILS OF THE VARIOUS TRANSFORMERS USED IN THIS G.S.S.
IS LISTED AS UNDER-
1.)
MAKE-Crompton Greaves ltd.
CAPACITY-50MVA/70MVA/100MVA
VOLTAGE RATIO-220/132
% IMPEDENCE-10.11% at tap 9
NO. OF TAPS- 1-21
QTY. OF OIL-30600Ltr/34.65 tonnes
BUSHING TYPE- Hermetically sealed
TYPE OF COOLING- ONAN/ONFF/OFAR
10
10
2.) MAKE-NGEF,Banglore
CAPACITY-50MVA/70MVA/100MVA
VOLTAGE RATIO-220/132
% IMPEDENCE-9.58% at tap 9
NO. OF TAPS- 1-21
QTY. OF OIL-43466Ltr/34.65 tonnes
BUSHING TYPE- Hermetically sealed
TYPE OF COOLING- ONAN/ONAF/OFAF
3.) MAKE-Telk
CAPACITY-50MVA/70MVA/100MVA
VOLTAGE RATIO-220/132
% IMPEDENCE-12.71% at max voltage
NO. OF TAPS- 1-21
QTY. OF OIL-40850Ltr/36.7 tonnes
BUSHING TYPE- Hermetically sealed
TYPE OF COOLING- ONAN/ONAF/OFAF
4.) .) MAKE- EMCO
CAPACITY-20MVA/25MVA
VOLTAGE RATIO-132/33KV
% IMPEDENCE-10.012%
NO. OF TAPS- 1-17
TYPE OF COOLING- ONAF
TYPE OF COOLING USED IN G.S.S POWER TRANSFORMER
11
11
a) ONAN type cooling:
The generated heat can be dissipated in many ways. In case of smaller rating
of transformer, its tank may be able to dissipate the heat directly to the atmospheric
air whilst bigger rating may require additional dissipating surface in the form of
tubes / radiators connected to tank.
In these cases, the heat dissipation is from transformer oil to atmospheric air
by natural means. This form of cooling is known as ONAN (Oil Natural, Air Natural)
type of cooling.
b) ONAF type cooling:
For further augmenting the rate of dissipating of heat, other means such as
fans blowing air as the cooling surface are employed. The forced air tanks blows
away the heat at a faster rate, there by giving better cooling rate than natural air. This
type of cooling is called ONAF (Oil Natural Air Forced) type of cooling.
In this cooling arrangement, additional rating under ONAN condition viz. either after
shutting off fans, is available which is of the order of 70-75%
c) OFAF type cooling
This method is used for transformers above 60 MVA. In this method the oil is
cooled in external heat exchanger using air blast produced by fans.
COOLING ARRANGEMENTS:
Depending upon the type of cooling and rating of the transformer, the cooling
equipments can be arranged in various ways.
ARRANGEMENTS WITH RADIATOR:
Radiator are commonly use for ONAN type of cooling. Radiators consist of
elements joined to top to bottom headers. Elements in this are made by welding two
previously rolled and pressed thin steel sheets to form a number of channels of flutes
through which oil flows. These radiators can be both mounted directly on the
transformer tank or in the form of a bank and connected to the tank through the pipes.
The surface are available for dissipation of heat is multiplied manifolds by using
12
12
various elements in parallel. As oil passes downwards either due to natural circulation
or force of a pump in the cooling circuit, heat is carried away by the surrounding
atmosphere air.
7. TEMPERATURE METERS:There are two temperature indicating meter in
power transformer which indicate the oil temperature and winding
temperature. Temperature measured is in ◦C.
8. CONSERVATOR AND AIR CELL:
As the temperature of oil increases or decreases during operation, there is a
corresponding rise or fall in volume. To account for this an expansion vessel
(conservator) is connected to the transformer tank.
The conservator has got a capacity between the minimum and maximum oil
level equal to 7.5 and of the oil in transformer.
The atmoseal type conservator, it is filled with oil to level appropriate to the
filling temperature and in the remaining portion is air cell, which is connected to
atmosphere through a breather. As the breathing is through air cell, no moisture
comes in contact with oil, this protect the oil from deterioration or contamination.
A. An efficient barrier between oil and air.
B. A protection against water vapour.
C. The suppression of any gas bubbles formation in the Oil.
Air cell is made from coated fabric with external coating resistance to transformer oil
and inner coating to ozone and weather.
9. BUCHHOLZ RELAY :
The transformer is fitted with double float buchholz relay. It is fitted in the
feed pipe from conservator to tank. Any internal fault in transformer is detected by
buchholz relay; the gas liberated in the transformer is diverted by buchholz relay,
without being trapped anywhere.
10. DEHYDRATING BREATHER:
13
13
The conservator is connected to outside through breather filled with
dehydrating material like silica gel crystals impregnated with cobalt chloride to make
sure that the air in conservator is dry. The material is blue when dry and a whitish
pink when damp.
11. PRESSURE RELIEF VALVE:
In case of severe fault in the transformer, the internal pressure may built up to
a very light level which may result in an explosion of tank. To avoid such a
contingency a pressure relief valve is fitted on the transformer. It is spring loaded and
has contacts for tripping the transformer.
12. OIL TEMPERATURE INDICATOR:Oil temperature indicator operates on
the principle of liquid expansion. The OTI provided with a maximum pointer and two
mercury switches are adjustable to make contact between 50◦ and120◦ with the fixed
differential of 10◦.
13. WINDING TEMPERATURE INDICATOR :
The indicator is fitted with four mercury switches 1st is used for alarm, 2nd is
the for trip, 3rd is for fans on and 4th for pumps control. All switches are adjustable.
14. EARTHING:
Connecting leads from core and end frame are being terminated at the top of
the cover by connecting them to tank cover, and end frame being earthed. For tank
earthing two number studs have been providing on tank.
15. TERMINAL BUSHINGS:
It is used to isolate the leads that are coming from transformer. The size of the
bushing is justified according to the operating voltage of particular winding. The
active part of the bushing consists if an Oil Impregnated Paper (O.I.P.) condenser core
manufactured from superior grade craft paper wound on aluminum tube. This bushing
is voltage graded by suitably interposed aluminum foils forming condenser layers.
16. INSULATING OIL: The insulating oil has three functions;
• Provides additional insulation
14
14
• Protects the paper from dirt and moisture
• Carries away the heat generated in the core and coils.
The insulating oil should have the following properties:
(i) High Dielectric Strength.
(ii) Free from inorganic acid, alkali and corrosive sulphur to prevent injury to the
conductor or insulation.
(iii) Low viscosity to provide good heat transfer.
(iv) Free from sludge under normal operating conditions.
(v) Good resistance to emulsion so that the oil may throw away any moisture that
enters the apparatus.
RATING OF 33/0.4 KV STATION TRANSFORMER (UTTAM BHARAT ELECTRICALS PVT. LTD.)
Tap range in % 8x1.25 to 12 x 1.25
N 20 steps
Step voltage/phase 1588
Rated Current 330 Amp.(max)
Diverter Switch 3.3 OHMS. P.a.
KVA 500
Volts at no load HV 33000
LV 400
Ampere HV 8.75
LV 721.6
Phases HV/LV 3/3
Type of cooling ONAN
Frequency 50 Hz
Imp. Voltage 4.5%Core and wdg. 1050 kg.
15
15
Oil’s wt. 400 kgTotal wt. 2040 kg.Qty. of oil 455 Lt.Maxc. Temp. Rise in oil 40 C
11/0.4 KV STATION TRANSFORMERS(TECHNICAL ASSOCIATES (P) LTD)
KVA 500
Volts At no load HV 11000 V
LV 433 VAmpere HV 2624
LV 666.66Phases HV/LV 3/3
Year of Mfg. 1986
Type of cooling ONFrequency 50 Hz A.C.
Vector Symbol DY-11Oil (Ltrs.) 400Weight of oil 340 kg.Wt. of oil & Wdg. 810 kg. Total Wt. 1585 kg.No load losses 840Load losses 5600 W.
16
16
INSTRUMENT TRANSFORMER INSTRUMENT TRANSFORMER
The lines in a station operated at high voltage and carry current of a thousand
of amperes. The measuring instrument and protective device are designed for low
voltage generally 110V and current about 5A. Therefore, they will not work
satisfactorily if mounted directly on the power lines. This difficulty is overcome by
installing transformer on the power lines. The function of these instrument
transformers is to transfer voltage or current in the power lines to values which are
convenient for the operation of measuring instrument and relays.
CURRENT TRANSFORMER (C.T.)
Current transformer is an instrument and is used for protection and metering of
high values of current. Current transformers are used for reducing a.c. current from
higher value to lower value for measurement/protection/control.
There are two classes of instrument transformers:
A. Measuring current transformers
B. Protective transformers
17
17
Measuring current transformers are used with ammeters, wattmeter, KVA
meters and KWH meters for reducing line current to 1 amp or 5 amps.
Protective current transformers are used over current protection, earth fault
protection, differential protection and impedance protection etc.
Definition of the different terms related with current transformer:
1. RATED PRIMARY CURRENT
The values of primary current on which the primary performance of the
current transformer is specified.
2. RATED SHORT TIME CURRENT
It is defined as R.M.S. value of a.c. component which the CT can carry
without damage.
3. RATED SECONDARY CURRENT
The value of secondary current marked on the rating plate.
4. RATED EXCITING CURRENT The R.M.S. value of current taken by the
secondary winding of a CT when sinusoidal voltage of rated frequency is applied to
secondary with primary winding open.
5. RATED BURDEN
The burden assigned by the manufacture at which the CT performs with
specified accuracy.
6. CURRENT ERROR & RATIO ERROR
The percentage error in the magnitude of secondary current is defined in terms
of current error.
BURDEN ON C.T.
18
18
Rated burden of CT’s and VT’s refer to the maximum load in volt amperes
which may be applied across the secondary terminal, without the ratio and phase
angle errors exceeding the permissible limits. The burden depends upon the number
of relays and instruments connected and their individuals burden typical values.
VARIOUS TYPE OF CONSTRUCTION OF CT’S
A CT has following essential parts:
Magnetic core made up of continuous strip of nickel iron alloy of cooled
rolled grain oriented material.
Insulation over the core by tape.
Secondary winding having several turns would on the insulated core.
Bar primary passing through the window of the core and terminals.
Support porcelain or epoxy insulator.
Synthetic resin or oil insulation.
19
19
VOLTAGE TRANSFORMERS (V.T.)
These are also instrument transformers and used for measurement and
protection. According they are either single phase or three phase. Voltage
transformers are necessary for voltage, directional and distance protection. The
primary of VT is connected directly to power circuit between phase and ground. The
volt-ampere rating of voltage transformer is a few VA to several hundred KVA.
TYPE OF CONSTRUCTION OF VT’S
Electromagnetic potential transformer in which primary and secondary are
wound on magnetic core like a usual transformer.
Capacitor potential transformer, in which the primary voltage is applied to a
capacitor group. The voltage across one capacitor is taken to auxiliary voltage
transformer. The secondary of auxiliary transformers is taken for protection or
measurement.
20
20
CAPACITOR VOLTAGE TRANSFORMER (C.V.T.)
CVT are used for line voltmeters, synchroscope, protective relays, tariff meter etc.
The performance of CVT is affected by the supply frequency, switching transients,
magnitude of connected burden etc.
The CVT is more economical then an electromagnetic voltage transformer
when the nominal system voltage increases above 66KV. The carrier current
equipment can be connected via the capacitor voltage transformers. Thereby there is
no need of separate coupling capacitor. The CVT are used for voltage
above 66KV and above. The capacitor connected in series with the CVT acts like a
potential divider.
CIRCUIT BREAKER
A circuit breaker is a piece of equipment which can break a circuit
automatically under fault condition and make a circuit manually or by remote control
under fault condition.
OPERATING PRINCIPLE
A circuit breaker essentially consists of moving contacts, called electrodes.
Under normal operating conditions, these contacts remains closed and will not open
automatically until and unless the system close and will not open automatically until
and unless the system will becomes faulty. The contacts can be opened manually or
by remote control whenever desired. When a fault occurs on any part of the system,
the trip coils the breaker gets energized and the moving contacts are pulled apart by
some mechanism, thus opening the circuit. When the contacts of the circuit breaker
are separated under fault condition, an is struck between them. The current is able to
continue until the discharge ceases. The production of arc not only delays the current
interaction process but it also generates enormous heat, which may cause damage to
the system or breaker itself. Therefore the main problem in a circuit breaker is to
21
21
extinguish the arc with in the shortest time so that the heat generated by it may not
reach a dangerous value.
SF6 (SULPHUR HEXAFLUORIDE) CIRCUIT BREAKER
In such breaker, SF6 gas is used as the arc quenching medium. The SF6 is an
electronegative gas and has a strongly tendency to absorb free electrons. The contacts
of the breaker are opened in a high pressure flow of SF6 gas and an arc struck
between them. The conducting free electrons in the arc are rapidly captured by the gas
to form relatively immobile negative ions. This loss of conducting electrons in the arc
quickly builds up enough insulation strength to extinguish the arc.
1. CONSTRUCTION
It consists of fixed and moving contacts enclosed in a chamber (called arc
interrupted chamber) containing SF6 gas. This chamber is connected to SF6 gas
reservoir. When the contacts of the circuit breaker are opened the valve mechanism
permits a high pressure SF6 gas from the reservoir to flow towards the arc
interruption chamber. The fixed contacts are the hollow cylinder current carrying
contacts fitted with an arc horn. The moving contacts are also a hollow cylinder with
rectangular holes in the sides to permit the SF6 gas to let out. The tip of the fixed
contacts, moving contacts and arcing horn are coated with copper-tungsten arc
resistance material. Since SF6 gas is costly, it is reconditioned and reclaimed by
suitable auxiliary system after each operation of the breaker.
2. WORKING
In the closed position of the breaker, the contacts remain surrounded by SF6 gas at a
pressure of about 2.8 kg/cm2. When the breaker operates, the moving contacts is
pulled apart and an arc is struck between the contacts. The movement of the moving
contact is synchronized with the opening of a valve which permits SF6 gas at 14
kg/cm2 pressure from the reservoir to the arc interruption chamber. The high pressure
flow of SF6 rapidly absorbs the free electrons in the arc path to form immobile
negative ions which are ineffective as charge carries. The result is that the medium
between the contacts quickly builds up high dielectric strength and causes the
extinction of the arc. After the breaker operation the valve is closed by the action of a
set of spring.
22
22
RATINGS AND SPECIFICAT1ONS OF DIFFERENT CIRCUIT BREAKERS
MOUNTED IN GSS ARE GIVEN AS UNDER-
• breaker serial No. : 403784
• year of manufacture : 2002-03
• Type : 3AT-2
• Rated Voltage : 420 KV
• Rated power frequency : 1050/1425 KVP
withstand voltage
• Rated power frequency : 520/610KV
with stand and voltage
• Rated frequency : 50 Hz
• Rated Normal current : 3150 A
• Rated short time current : 40 kA
• Rated short circuit duration : 1 sec
• First pole to clear factor : 1.3
• Symmetrical : 40 kV
• breaking capacity equivalent : 29000 MVA
• Asymmetrical : 52.5 kV
• rated making current : 100 kA
• Rated pressure of SF6 gas at 20° C gauge : 7.5
• weight of compete breaker : 9280
• weight of SF6 Gas : 7.5 kg
• Rated tri coil voltage : 220±l0VDC
TOTAL NO. OF BREAKERS IN-
220KV SIDE- 9 Nos.
132KV SIDE-16 Nos.
33KV SIDE-10 Nos.
11KV SIDE-12Nos.
23
23
PROTECTION SYSTEM
In order to generate electric power and transmit to customers, millions of
rupees must be spent on power system equipment. This equipment is designed to
work under specified normal conditions.
However a fault may occur causing the system to collapse. This fault occurs
because of
Over voltage due to switching.
Over voltage due to direct and indirect lightning strokes.
Bridging of conductors by birds.
Breakdown of insulation due to decrease of its dielectric strength.
Mechanical damage to equipment.
These short circuits may cause heavy damage to equipment and would also
cause intolerable interruption of service to customers.
Relays are the devices that detect abnormal conditions in electrical circuits by
constantly measuring electrical quantities, which are different under normal and fault
conditions. The basic electrical quantities, which may change under fault conditions,
are voltage, current, phase angle and frequency. Having detected the fault the relay
operates to competent the trip circuit which results in opening of the circuits breaker
and therefore in the disconnection of the faulty circuit.
BASIC REQUIREMENTS OF PROTECTIVE RELAYING
A well designed and protective relaying should have:
1) Speed
2) Selectivity
3) Sensitivity
4) Reliability
5) Simplicity
6) Economy
24
24
TYPES OF PROTECTION
There are two types of protection known as primary and back up.
The Primary Protection is the first line of defense and primary relays clear faults in
the protected system as fast as possible. The reliability, not only of the protected
scheme but also of the associated C.T.’s, P.T.’s and the C.B.s cannot be guaranteed.
Therefore some sort of Back Up Protection must be provided. The back up relay
operates if the primary relay fails and covers not only the local section but the next
one also and have a time delay long enough before the primary relays to operate.
PROTECTIVE RELAYS are classified depending upon their construction and
principle of operation such as :
Ordinary electromagnetic relays consisting of moving plunger, moving iron,
attracted armature hinged and balance Static relays employing thermiontic
valves, transistors or magnetic
amplifiers to obtain the operating characteristics.
Electro-dynamic relays operate on the same principle as moving coil instrument.
The various types of Relays installed at 400 KV GSS are: -
(a) Over current relay
(b) Distance relay
(c) Differential relay
(d) Earth fault relay
(a) OVER CURRENT RELAY AND EARTH FAULT RELAY
Directional type over current relay works on the induction
principles and initiates corrective measures when current in the circuit exceeds the
predetermined value. The actuating source is a current in the circuit supplied to the
relay liom a current transformer. These relays are used on a.c. circuits only and can
operate for fault flow in either direction. But these relay are unsuitable for use as a
directional protective relay under short circuit conditions. When a short circuit occurs,
the system value falls to a low value and there may be insufficient torque developed
in the relay to cause its operation, this difficulty is over come in the directional over
25
25
current relay, which is designed to be almost independent of system voltage and
power factor.
Operation:
Under normal operating conditions, powers flows in the normal direction in
the circuit protected by the relay. Therefore, directional power relay (upper element)
does not operate, thereby keeping the over current element (lower clement)
unenergised. However when a short circuit occurs, there is a tendency for the current
or power to flow in the reverse direction. Should this happen, the disc of the upper
element rotates to bridge the fixed contact I and 2. This completes the circuit for over
current element. The disc ol this element rotates and the moving contact attached to it
closes the trip circ u i t
This operates the circuit breaker which isolates final tripping of the current by
them is not made till the following conditions are satisfied:
(a) Current flows in a direction such as to operate the directional element
(b) Current in the reverse direction exceeds the pre-set value.
(c) Excessive current persists for a period corresponding to the time setting over
current element.
(b) DISTANCE RELAY: Distance protection is the name given to the protection,
whose action depends upon the distance of the feeding point to the fault. The time of
operation of such a protection is a function of the ratio of voltage and current, i.e.
impedance. This impedance between the relay and the fault is dependent upon the
electrical distance between them.
An impedance relay has an operating force proportional to the fault current
and restraining force proportional to the line voltage at the relay. As soon as the ratio
of this voltage to the fault current change i.e. falls below a certain value, the relay
operates. This value is dependent upon the distance of the fault, which is
predetermined. Hence for this reason the relay is discriminative and it does not
operate for any fault occurring outside this distance.
As it is very important to localize the fault, a relay of the above type is given a
controlled time lag, so that the relay nearest to the fault operates first. This time lag is
26
26
made proportional to the distance of the fault by so designing the relay that it has time
lag characteristics, which is dependent upon the line voltage at the relay directly.
Again, the time lag characteristic is inversely proportional to the fault current that is
passing through the relay.
In case of a fault, there is a steady fall of voltage along the line from the .feeding point
to the fault. This voltage gradient can be utilized for grading of the time lags of the
relays, which controls a number of switches in a feeder.. These relays automatically
adjust their time of operation depending upon their distance from fault.
(c) DIFFERENTIAL RELAYS: A differential relay is one that operates when
the difference of two or more electrical quantities exceeds a predetermined value.
Almost any type of relay connected, in a cei-tain way, can be made to operate as
differential relay. There are two fundamental system of differential protection viz.
(a) Current Balance Protection (current differential relay)
(b) Voltage Balance Protection (voltage differential relay)
A current Balance Differential Relay is one that compares the current entering
a section of the system with the current leaving the- section. Under normal operating
conditions, the two currents are equal but as soon as a fault occurs, this condition no
longer applies. The difference between the incoming and outgoing currents in
arranged to flow through the operating coil of the relay. If this differential current is
equal to or greater than the pickup value, the relay will operate and open the circuit
breaker to isolate the faulty section. In Voltage Differential Relay, two similar current
transformers are connected at either end of the element to be protected by means of
pilot wires. The secondary of circuit breakers are connected in series with a relay in
such a way that under normal conditions their induced emfs are in opposition. Under
healthy condition, equal current flows in both primary windings Therefore, the
secondary voltages of the two transformers are balanced against each other and no
current will through the relay operating coil. When a fault occurs in the protected
zone the current in the two primaries will differ from one another and the secondary
voltage will no longer be in balance. This voltage difference will cause a current to
flow through the operating coil of the relay, which closes the trip circuit.
27
27
AUXILLARY EQUIPMENT
LIGHTING ARRESTERS
Lighting arrestors is used to protect the sub-station and transmission lines
arrester is earthed. Gap is, adjusted in such a way that 50% over voltage it operators.
We will use valve type lighting arrestor this types of lighting arrestor is also
called non liner diverter. In this spark-gap, stuck and resistance discs are used. These
are isolated by mica foils.
The resistance of resistance discs with the increases of current value in light
arrestor spark gap and resister remains in series and these are protected from moisture
and atmospheric and these are protected from moisture and atmospheric changes by
keeping them in porcelain pot.
When there is less change in line voltage than there is not flashover in gap but
when there is over voltage and rapid changes in voltage then even grounding of
voltage will not possible the value of flash over voltage depends on surge
current.Operation will start when voltage will increase 10% of rated voltage.
28
28
CAPACITOR BANK
The power factor can be improved by connecting capacitors in parallel with
the equipment operating at lagging power factor; the capacitor draws a leading current
and partly or completely neutralized the lagging reactive component of load current.
LOAD INTERRUPTER SWITCHES
The switches are designed and used to close and open high voltage circuits
under normal working conditions. The are extinguishing device of the load interrupter
is made in the form of a split a molded plastic chute fitted with organic glans, inserts
this chute surrounds the moving knife of the arc extinguishing system. The stationery
acting contact is located in the lower part of the chute.
INSULATORS
The insulators serve two purposes. They support the conductors and confine
the current to the conductors. The most commonly used material for the manufacture
of insulator is porcelain. There are several types of insulators and there use in the
substation will depend upon the service requirement. For example, post insulator is
used for the bus bars. A post insulator consists of a porcelain body, cost iron cap and
flanged cost iron base. The hole in the cap is threaded so that bus bars are directly
bolted to the cap.
29
29
SHUNT REACTOR
Shunt reactor are provided at sending end and receiving end of long EHV &
UHV transmission line. They are, switched in when the line is to be charged or when
the line is on low load.When the line is on no-load or low load, shunt capacitance
predominate and received and voltage is higher then the sending end voltage.
The receiving end voltage of 400KV, 100KM long line may be as high as 800KV.
The shunt capacitance of such line neutralized by switching in the shunt reactor,
during high loads, the series inductive reactance of the line produces IX drop and the
receiving end voltage drops, the shunt reactors are switched off.
Shunt reactors may be connected to the low voltage territory winding of transformer
via a suitable circuit breaker, EHV shunt reactor may be connected to transmission
line without any EHV circuit breaker. Usually oil immersed magnetically shielded
reactor with gapped core are used.
30
30
ISOLATORS
While carrying out inspection or repair in a substation installation, it is
essential to disconnect reliably the unit or the section, on which the work is to be
done, from all other live parts of the installation in order to ensure complete safety of
the working staff. To guard against mistakes it is desirable that an apparatus, which
makes a visible break in the circuit, should do this apparatus is the isolating switch. It
may be defined as a device used to pen (or close) a circuit either when negligible
current is interrupted or whn no significant change in the voltage across the terminal
e.g. each pole of the isolator will result from the operation P.A.
31
31
ISOLATORS ARE CLASSIFIED AS-
1. OFF LOAD ISOLATOR
It is an isolator which is operated when the isolator is already disconnected
from all sources of supply or when the isolator is already disconnected from the
supply and current may be due to capacitance current of bushings bus bar connected
and very short length of cable.
2. ON LOAD ISOLATOR
It is isolator, which is operated in a circuit where there is a parallel path of
low impedance so that no significant change in the voltage across the terminals of
each pole occurs when it is operated.
When the switch is opened, the working contacts between which are is drawn
separate. Acted upon by the high temp of arc the wall of the organic material inserts,
generated gases (mainly hydrogen), which create a loadinterputer switches.
CONTROL CABLES
The control cable and conduit system is required for affecting automatic
controls. The control system generally operates at 110V or 220V and the cables
employed for this purpose are multi core cable having 10 or 37 or 61 conductors
according to requirement, for laying these cables generally ducts is run from control
room basement to centrally located juriction box from where the conduits are run the
required points.
METERING AND INDICATING INSTRUMENTS
There are several metering and indicating instruments e.g. ammeters,
voltmeters, energy meter etc. installed in a sub-station to maintain watch over the
circuit satisfactory operation.
BATTERY CHARGER
D.C. supply (110V) is the heart of the GSS. It energises all
protection .Generally for the normally working the float charger unit supplied the
permanent load at 110V (+ - 1%) and also supplies the trickle charging current to the
32
32
battery on float condition. In battery Room 5 battery Set are installed and
interconnected providing D.C. Current for controlling panels.
FLOAT CHARGING
It is intended to supply float charging current of the battery and
simultaneously the permanent load of station.
BOOST CHARGING
Boost charging is used to charge the batteries after power resumption.
POWER LINE CARRIER COMMUNICATION (PLCC)
1. INTRODUCTION
For exchange of dates and transfer of message between grid substation
voices communication is necessary. For this purpose high frequency carrier current
(30 to 50 kcls) is transmitted on same transmission line on high power is also
transmitted, hence such communication is a “power line carrier communication” or
shortly “PLCC. High frequency carrying current audio singles is generated,
transmitted and received with the help of identical carrier current equipment provided
on each end. Carrier current equipment comprises of following:
(1) Coupling capacitor
(2) Wave trap unit
(3) Transmitter/receiver
1. Coupling Capacitor:
It acts like a filter, it blocks power frequency (50 Hz) while offer low
reactance to carrier frequencies (30-500KC! s) as allow them to pats through because:
For examples A 2000 Pf capacitor offers 1.5 mega ohms to 50 Hz while it just
offer 150 ohms to 500 KHZ. Thus coupling capacitor allows carrier frequency signal
33
33
to enter the carrier equipment but does not allow 50 Hz power frequency current to
enter the carrier equipments.
2. Wave trap unit:
It is parallel turned circuit comprising of I & C. It has low impedance (less
then 0.1 ohms) to 50 Hz and high impedance to carrier frequencies. Thus power
frequencies get passed through wave trap & carrier frequencies passes through
coupling capacitor & reaches carrier current. Wave traps are mounted in outdoor
switchyard.
3. Transmitter & Receiver Unit:
Carrier current unit shown in Figure acts like both transmitter receiver carrier
frequencies are generated in master oscillator can be tuned to a particular frequency
selected fro the application output voltage of oscillator is held constant by voltage
stabilizers. Output of oscillator is fed to amplifier, which increases the strength of
signal to be transmitted to over come the transmission losses.
Line losses very with length of line, frequency, weather conditions size & type of
line; losses in overhead line arc affected by weather. In fair weather the attenuation
(weakening of signal) is about 0.1 dB 1 Km at 80 KI IZ rising to 0.02 dB 1 Km. at
380 KHZ.
Receiving unit comprises of an alternator which reduces signal to
safer value. Band pass filter restricts the acceptance of uncounted signal & matching
transformer or matching element matches the impedance of line &
receiving unit.
34
34
EARTHING
Connecting of an electrical equipment or apparatus to the earth with help of
connecting wire of negligible resistance is known as “earting” or “grounding”.
The provision of an earth electrode for an electrical system is necessitated by
following reasons:
1) All the parts of electrical equipment like casing of machine, switches and circuit
breaker, lead sheathing and armoring of cables, tanks of transformers etc., which have
to be at earth potential, must be connected to an earth electrode. The purpose of this is
to protect the various parts of the installation, as well as the person working against
damage in case the insulation of system fails at any point.
By connecting these parts to an earthed electrode, a continuous low resistance path is
available for leakage currents to flow to earth. This current operates the protective
devices and thus the faulty circuit is halted in case a fault occurs.
2) The electrode ensures that in the event of even voltage on the system due to
lighting discharge or other system faults, those parts equipment which are normally
“dead” as for as voltage are concerned do not attain dangerously high potential.
3) In a three phase circuit the neutral of the system is earthed in order to stabilize the
potential of the circuit with respect to earth. In electrical installations the following
component must be earthed:
(i) The frames, tanks and enclosures of electric machines, transformer, and apparatus,
lighting fitting and other items of equipment.
(ii) The operating mechanism of the switchgear.
(iii) The framework of the switchboards control boards individual panel hoards,
cubicles.
(iv) The structural steel work of substations, metal cable jointing boxes, the metal
sheaths of the cables the rigid metal conduit runs and similar metal work.
35
35
There are two methods of earthing:
1 Pipe earthing.
2 Plate earthing
EARTHING ARRANGEMENT AT 220 KV GSS:
In an grid sub-station of any magnitude the various non current carrying
equipment to be earthed namely substation structures, shielding wires or masts,
equipments tanks and treadles etc are spread over large area and therefore it becomes
necessary to lay a grounding bus connect the various items to be earthed to be ground
bus through suitable connection to heave duplicate earthing is broken the sub-station
may remains safe under all condition. It generally, therefore, becomes desirable to
form a ring of the earthing hut, which can then be connected to the earthing
electrodes. In large sub station the earthing bus itself it said to a depth of 600 to 650
mm. saves as a grounding mat and no separate earthing mat or electrodes may be
required although use of some electrodes for making use of good earth conductivity at
depth unaffected by other condition is considered advisable particular))’ near lighting
arresters and transformers neutral earthing points where lighting surges are required to
be discharged in to earth.
Another way of looking into the sub station earthing problem is that a very
low earthing resistance value is required in a large area occupied by the substation and
obviously such can only be obtained by using a number of rod electrodes and joining
them in parallel. Further to be most effective the electrodes must be placed at distance
such that their areas of influence are not over lapped. If this is done the connections
between the various electrodes if laid at suitable depths may between 400 to 600 mm
will also take part in ground current dissipation to earth like horizontal counterpoises
and equipment to he earthed can also connected to them.
In substation the earthing system invariably takes the shape of grounding mat
with necessary or additional rounding rods accepts in the case of’ very small sub
stations.
36
36
Common earth electrodes should he use for both system earths and equipment
earths. Here also it is recommended to have common earth bus for high voltage and
low voltage system. Where there are manual operating handle to the system earth
electrode. To remove any voltage gradient that may exist between the operating levers
and the ground level and shall be connected to the system earth electrodes.
PLATE EARTHING
In plate earthing plate either of copper of dimension 60cm x 6cm x 3.15mm or
of galvanized iron of dimension 60cm x 60cm x 6.30 is burled into the ground with its
face vertical at a depth of not less that 3 meters from wound levels. The earth plate is
embedded in alternate layers of coke and salt for a minimum thickness of 15 cm. The
earth wire GI wire for GI plate earthing and coppers wire for copper plate earthing is
securely bolted to an earth place with the help of a bolt nut and washer made of
material of that earth plate (made of copper in case ot copper plate earthing and of
galvanized iron in case of GI plate earthing).
A small masonry brick wall enclosure with a cast iron cover or top an
RCC pipe round the earth plate is provided to facilitate its identification and for