W W 1 1 2 1 Tel. / Fax +49 Germany www.viessmann.com [email protected] Direct solar loop / heat exchanger Heat exchanger (0)6452-70-0 Open, vented or closed solar loop Closed Viessmann Werke GmbH & Co. KG Viessmann Postal Code 35107 Allendorf System classification Solar loop, circulation principle Thermosyphon Application(s) Hot water Page 1 Company Brand (optional) Country Website E-mail SOLAR SYSTEM test results 5 Licence Number of 2017-05-17 Annex to Solar KEYMARK Certificate Issued 011-7S2590 A Summary of EN12976-2 Street Viessmannstrasse 1 Store orientation (of main axis) Horizontal Type of auxiliary heating (internal back-up heat) Electric Drain back/down Always filled (no drain) Store location Outdoor Stamp & signature of test lab Comments of test lab Vitosol 100-F SVT 2,51 Solar loop controller Solar loop fluid itocell 100-H CHTB 150 Vitosol 100-F SVT 2,18 Number of collectors in each configuration for each store Solar only / Solar preheat - - 300 602 - - Heat store(s) Collector(s) www.tuv.com/st TÜV Rheinland Energy GmbH Testing Laboratory Date of test report 21228898.001_Report_VITOSOL_111_F_TS1 Solar loop pump - power range 3.0 3.0 °C Freezing point Keymark lic.no. if available - - - Company Name Collector name Company Name Required TYFOROP Chemie GmbH Tyfocor L - If other auxiliary/internal back-up heating, please specifiy: Solar+supplementary OR Solar-only / Solar pre-heat Viessmann Faulquemont S.A.S. - Company Keymark lic.no. if available Viessmann Faulquemont S.A.S. 512 - - 200 512 3.0 011-7S2591 F Company Keymark lic.no. if available Per module Gross Area (AG) Gross length Gross width mm Test report id. number Recommended/required 2015-10-14 Website - to itocell 100-H CHTB 200 Store name itocell 100-H CHTB 300 System family overview -10 Total nominal volume Gross width Gross depth Auxiliary heated volume Electrical aux. heating power litres mm mm litres kW Gross height mm mm Collector name 2.18 2066 1056 2380 1056 2.51 Vitosol 100-F SVT 2,18m² Vitosol 100-F SVT 2,51m² 1322 1685 1644 Store name Vitocell 100-H CHTB Vitocell 100-H CHTB Vitocell 100-H CHTB 150 DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de Stamp & signature of test lab Comments of test lab Comments ... Version 3.6, 2014-06-18
5

Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

Oct 18, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

W W

1 1 2

1

Tel. / Fax +49

Germany

www.viessmann.com

[email protected]

Direct solar loop / heat exchanger Heat exchanger

(0)6452-70-0

Open, vented or closed solar loop Closed

Viessmann Werke GmbH & Co. KG

Viessmann

Postal Code 35107 Allendorf

System classification

Solar loop, circulation principle Thermosyphon

Application(s) Hot water

Page 1

Company

Brand (optional)

Country

Website

E-mail

SOLAR SYSTEM test results

5

Licence Number

of

2017-05-17Annex to Solar KEYMARK Certificate Issued

011-7S2590 ASummary of EN12976-2

Street Viessmannstrasse 1

Store orientation (of main axis) Horizontal

Type of auxiliary heating (internal back-up heat) Electric

Drain back/down Always filled (no drain)

Store location Outdoor

Stamp & signature of test lab

Comments of test lab

Vitosol 100-F SVT 2,51m²

Solar loop controller Solar loop fluid

Vitocell 100-H CHTB 150L

Vitosol 100-F SVT 2,18m²

Number of collectors in each configuration for each store

Solar only / Solar preheat

- -300 602 - -

Heat store(s)Collector(s)

www.tuv.com/st

TÜV Rheinland Energy GmbHTesting Laboratory

Date of test report

21228898.001_Report_VITOSOL_111_F_TS1

Solar loop pump - power range

3.03.0

°CFreezing point

Keymark lic.no. if available -

-

-

CompanyName

Collector name

CompanyName

Required

TYFOROP Chemie GmbH

Tyfocor L

-

If other auxiliary/internal back-up heating, please specifiy:

Solar+supplementary OR Solar-only / Solar pre-heat

Viessmann Faulquemont S.A.S.

-

Company

Keymark lic.no. if available

Viessmann Faulquemont S.A.S.

512 - -200 512

3.0

011-7S2591 F

Company

Keymark lic.no. if availablePer module

Gro

ss

Are

a (A

G)

Gro

ss

len

gth

Gro

ss

wid

th

m² mm

Test report id. number

Recommended/required

2015-10-14

Website

-to

Vitocell 100-H CHTB 200L

Store name

Vitocell 100-H CHTB 300L

System family overview

-10

Tota

l no

min

al

volu

me

Gro

ss

wid

th

Gro

ss

de

pth

Au

xilia

ry

he

ate

d v

olu

me

Ele

ctri

cal a

ux.

he

atin

g p

ow

er

litres mm mm litres kW

Gro

ss

he

igh

t

mmmm

Collector name

2.18 2066 10562380 10562.51

Vitosol 100-F SVT 2,18m²Vitosol 100-F SVT 2,51m²

132216851644

Store name

Vitocell 100-H CHTB Vitocell 100-H CHTB Vitocell 100-H CHTB

150

DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin

Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de

Stamp & signature of test lab

Comments of test lab

Comments ...

Version 3.6, 2014-06-18

Page 2: Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

1 1 2

1

Daily drawoff l Daily drawoff l Daily drawoff l

Viessmann Werke GmbH & Co. KG Country Germany

Brand (optional) Viessmann Website www.viessmann.com

Certification No. 011-7S2590 A

Annex to Solar KEYMARK Certificate Issued 2017-05-17

Vitosol 100-F SVT 2,51m²

System family overview

Collector name

For each storage and collector size, give number of collectors

Vitocell 100-H CHTB 150LVitocell 100-H CHTB 200LVitocell 100-H CHTB 300L

Tc,ave °C Annual average mains cold water temp.

ΔTc K Seasonal variation of Tc

ISO 9459-5 (DST)

Testing Laboratory

Test method

Website

Test report id. number

Date of test report

Comments of test lab

Stamp & signature of test lab

Th 45 °C Desired hot water temperature (mixing valve temperature).

Max. operating press. - collector side 300 kPa Max. operating press. - tank side 1 000

TÜV Rheinland Energy GmbH

www.tuv.com/st

21228898.001_Report_VITOSOL_111_F_TS1

2015-10-14

kPa

G kWh/m² Annual irradiation South, 45°

Ta,ave °C Annual average outdoor air temperature

3.2 18.5

± ΔTc 6.4 3.0 0.8 7.4

Tc,ave 8.5 10.0 5.4 17.8

fsol=QL/Qd - Solar fraction

Ref. conditions

Stockholm SE Würzburg DE Davos CH Athens GR

G 1 157 1 230 1 684 1 736

Ta,ave 7.5 9.0

Qd,sh MJ/y Not relevant for solar domestic hot water system

Qpar MJ/y Annual parasitic energy: (electricity for pumps/controllers)

Qd MJ/y Annual heat demand for domestic hot water

QL MJ/y Annual heat energy delivered by the solar system

Name of system configuration Vitosol 111-F Typ TS1

Collector name No. Collectors Vitosol 100-F SVT 2,18m² Vitocell 100-H CHTB 150LStorage name1

of 5

Summary of EN12976-2

Vitosol 100-F SVT 2,18m²

test results

Street Viessmannstrasse 1

Postal Code 35107 Allendorf

E-mail [email protected]

Tel. / Fax +49 (0)6452-70-0

Page 2

Company

Perf. indicators for the table above

Calculated annual results for "solar-only / preheat system"

LocationQd,sh

110 140 170

Qd,hw QL Qpar fsol Qd,hw QL Qpar fsol Qd,hw QL Qpar fsol

MJ/y MJ/y MJ/y MJ/y % MJ/y MJ/y %

Stockholm SE 6150 3185 - 52 7821 3627 - 47 9492 3942 - 42

-

MJ/y MJ/y % MJ/y MJ/y

50 9114 4163 - 46

Davos CH 6654 4730 - 71 8483 5361 - 63 10281 5771 - 56

WürzburgDE 5897 3248 - 55 7506 3753

Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75

All values are subject to some uncertainty; e.g. the uncertainty on system output is typically in the range of ± 5 % to ± 15 % Version 3.6, 2014-06-18

Comments of test lab

Stamp & signature of test lab

No comments

DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin

Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de

Page 3: Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

1 1 2

1

Daily drawoff l Daily drawoff l Daily drawoff l

Date of test report 2015-10-14

Test method ISO 9459-5 (DST)

Comments of test lab

Stamp & signature of test lab

Testing Laboratory TÜV Rheinland Energy GmbH

Website www.tuv.com/st

Test report id. number 21228898.001_Report_VITOSOL_111_F_TS1

Th 45 °C Desired hot water temperature (mixing valve temperature).

Max. operating press. - collector side 300 kPa Max. operating press. - tank side 1 000 kPa

Tc,ave °C Annual average mains cold water temp.

ΔTc K Seasonal variation of Tc

G kWh/m² Annual irradiation South, 45°

Ta,ave °C Annual average outdoor air temperature

1 736

± ΔTc 6.4 3.0 0.8 7.4

Tc,ave 8.5 10.0 5.4 17.8

Ref. conditions

Stockholm SE Würzburg DE Davos CH Athens GR

Ta,ave 7.5 9.0 3.2 18.5

G 1 157 1 230 1 684

Qpar MJ/y Annual parasitic energy: (electricity for pumps/controllers)fsol=QL/Qd - Solar fraction

Qd MJ/y Annual heat demand for domestic hot water

QL MJ/y Annual heat energy delivered by the solar system

Perf. indicators for the table above

Qd,sh MJ/y Not relevant for solar domestic hot water system

Athens GR 5834 4667 -

Davos CH 8483 5330 - 63

5330 - 75 5866 - 7080 7064

- 46 10691 4510 - 42

- 5110281 5803 - 56 12110 6118

8326

- 38

WürzburgDE 7506 3753 - 50 9114 4194

9492 3974 - 42 11164 4226Stockholm SE 7821 3627 - 46

Qd,hw QL Qpar fsol Qd,hw QL Qpar fsol Qd,hw

Calculated annual results for "solar-only / preheat system"

LocationQd,sh

140 170 200

QL Qpar fsol

MJ/y %MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y

Name of system configuration Vitosol 111-F Typ TS1

Collector name Vitosol 100-F SVT 2,18m² No. Collectors 1 Storage name Vitocell 100-H CHTB 200L

Vitosol 100-F SVT 2,18m²

Vitosol 100-F SVT 2,51m²

System family overview

Collector name

For each storage and collector size, give number of collectors

Vitocell 100-H CHTB 150LVitocell 100-H CHTB 200LVitocell 100-H CHTB 300L

Postal Code 35107 Allendorf Tel. / Fax +49 (0)6452-70-0

Brand (optional) Viessmann Website www.viessmann.com

Street Viessmannstrasse 1 E-mail [email protected]

Company Viessmann Werke GmbH & Co. KG Country Germany

Summary of EN12976-2 test results Certification No. 011-7S2590 A

Page 3 of 5

Annex to Solar KEYMARK Certificate Issued 2017-05-17

All values are subject to some uncertainty; e.g. the uncertainty on system output is typically in the range of ± 5 % to ± 15 % Version 3.6, 2014-06-18

DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin

Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de

Comments of test lab

Stamp & signature of test lab

No comments

Page 4: Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

1 1 2

1

Daily drawoff l Daily drawoff l Daily drawoff l

Date of test report 2015-10-14

Test method ISO 9459-5 (DST)

Comments of test lab

Stamp & signature of test lab

Testing Laboratory TÜV Rheinland Energy GmbH

Website www.tuv.com/st

Test report id. number 21228898.001_Report_VITOSOL_111_F_TS1

Th 45 °C Desired hot water temperature (mixing valve temperature).

Max. operating press. - collector side 300 kPa Max. operating press. - tank side 1 000 kPa

Tc,ave °C Annual average mains cold water temp.

ΔTc K Seasonal variation of Tc

G kWh/m² Annual irradiation South, 45°

Ta,ave °C Annual average outdoor air temperature

1 736

± ΔTc 6.4 3.0 0.8 7.4

Tc,ave 8.5 10.0 5.4 17.8

Ref. conditions

Stockholm SE Würzburg DE Davos CH Athens GR

Ta,ave 7.5 9.0 3.2 18.5

G 1 157 1 230 1 684

Qpar MJ/y Annual parasitic energy: (electricity for pumps/controllers)fsol=QL/Qd - Solar fraction

Qd MJ/y Annual heat demand for domestic hot water

QL MJ/y Annual heat energy delivered by the solar system

Perf. indicators for the table above

Qd,sh MJ/y Not relevant for solar domestic hot water system

Athens GR 5834 4857 -

Davos CH 8483 5771 - 68

5582 - 79 6213 - 7583 7064

- 50 10691 4888 - 46

- 5610281 6370 - 62 12110 6780

8326

- 42

WürzburgDE 7506 4005 - 53 9114 4510

9492 4320 - 46 11164 4636Stockholm SE 7821 3879 - 50

Qd,hw QL Qpar fsol Qd,hw QL Qpar fsol Qd,hw

Calculated annual results for "solar-only / preheat system"

LocationQd,sh

140 170 200

QL Qpar fsol

MJ/y %MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y

Name of system configuration Vitosol 111-F Typ TS1

Collector name Vitosol 100-F SVT 2,51m² No. Collectors 1 Storage name Vitocell 100-H CHTB 200L

Vitosol 100-F SVT 2,18m²

Vitosol 100-F SVT 2,51m²

System family overview

Collector name

For each storage and collector size, give number of collectors

Vitocell 100-H CHTB 150LVitocell 100-H CHTB 200LVitocell 100-H CHTB 300L

Postal Code 35107 Allendorf Tel. / Fax +49 (0)6452-70-0

Brand (optional) Viessmann Website www.viessmann.com

Street Viessmannstrasse 1 E-mail [email protected]

Company Viessmann Werke GmbH & Co. KG Country Germany

Summary of EN12976-2 test results Certification No. 011-7S2590 A

Page 4 of 5

Annex to Solar KEYMARK Certificate Issued 2017-05-17

All values are subject to some uncertainty; e.g. the uncertainty on system output is typically in the range of ± 5 % to ± 15 % Version 3.6, 2014-06-18

DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin

Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de

Comments of test lab

Stamp & signature of test lab

No comments

Page 5: Summary of EN 12976 Test Results - Annex to KEYMARK ... A.pdf · Athens GR 4573 3879 - 85 5834 4667 - 80 7064 5267 - 75 All values are subject to some uncertainty; e.g. the uncertainty

1 1 2

1

Daily drawoff l Daily drawoff l Daily drawoff l

Date of test report 2015-10-14

Test method ISO 9459-5 (DST)

Comments of test lab

Stamp & signature of test lab

Testing Laboratory TÜV Rheinland Energy GmbH

Website www.tuv.com/st

Test report id. number 21228898.001_Report_VITOSOL_111_F_TS1

Th 45 °C Desired hot water temperature (mixing valve temperature).

Max. operating press. - collector side 300 kPa Max. operating press. - tank side 1 000 kPa

Tc,ave °C Annual average mains cold water temp.

ΔTc K Seasonal variation of Tc

G kWh/m² Annual irradiation South, 45°

Ta,ave °C Annual average outdoor air temperature

1 736

± ΔTc 6.4 3.0 0.8 7.4

Tc,ave 8.5 10.0 5.4 17.8

Ref. conditions

Stockholm SE Würzburg DE Davos CH Athens GR

Ta,ave 7.5 9.0 3.2 18.5

G 1 157 1 230 1 684

Qpar MJ/y Annual parasitic energy: (electricity for pumps/controllers)fsol=QL/Qd - Solar fraction

Qd MJ/y Annual heat demand for domestic hot water

QL MJ/y Annual heat energy delivered by the solar system

Perf. indicators for the table above

Qd,sh MJ/y Not relevant for solar domestic hot water system

Athens GR 8326 7379

Davos CH 12110 9303 77

8767 84 9965 8089 10407

55 16052 8105 50

6315137 10596 70 18165 11511

12488

46

WürzburgDE 10691 6307 59 13371 7316

13939 7159 51 16746 7789Stockholm SE 11164 6213 56

Qd,hw QL Qpar fsol Qd,hw QL Qpar fsol Qd,hw

Calculated annual results for "solar-only / preheat system"

LocationQd,sh

200 250 300

QL Qpar fsol

MJ/y %MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y % MJ/y MJ/y MJ/y

Name of system configuration Vitosol 111-F Typ TS1

Collector name Vitosol 100-F SVT 2,18m² No. Collectors 2 Storage name Vitocell 100-H CHTB 300L

Vitosol 100-F SVT 2,18m²

Vitosol 100-F SVT 2,51m²

System family overview

Collector name

For each storage and collector size, give number of collectors

Vitocell 100-H CHTB 150LVitocell 100-H CHTB 200LVitocell 100-H CHTB 300L

Postal Code 35107 Allendorf Tel. / Fax +49 (0)6452-70-0

Brand (optional) Viessmann Website www.viessmann.com

Street Viessmannstrasse 1 E-mail [email protected]

Company Viessmann Werke GmbH & Co. KG Country Germany

Summary of EN12976-2 test results Certification No. 011-7S2590 A

Page 5 of 5

Annex to Solar KEYMARK Certificate Issued 2017-05-17

All values are subject to some uncertainty; e.g. the uncertainty on system output is typically in the range of ± 5 % to ± 15 % Version 3.6, 2014-06-18

DIN CERTCO ● Alboinstraße 56 ● 12103 Berlin

Tel: +49 30 7562-1131 ● Fax: +49 30 7562-1141 ● E-Mail: [email protected] ● www.dincertco.de

Comments of test lab

Stamp & signature of test lab

No comments