Submittal Ref. #: 514501.2 rev3 Design envelope split coupled vertical in line pump Model: Series Design Envelope Sensorless 4300 0308-005.0 Project name: CC-15409 Parc Elise - 4400 Cambie Street Location: Vancouver, BC Representative: Date submitted: 1/7/2016 Phone number: Engineer: Cada & Associates e-mail: Contractor: Submitted by: Con-Cur West Marketing Inc. 604-540-5088 dhaskell@concurwest.com Dave Haskell Application design data Tag number: P-1/2 Pipe orientation: Single Suction pressure: 0 ft Service: Heating Loop Location: Fluid: Water: Quantity: 2 Operating temperature: 60 F Viscosity: 31 SSU Duty flow per pump: 190 USgpm Specific gravity: 1.0000 Duty head: 48 ft Safety factor % head: 0 % Environment: Indoors Total dissolved solids: 0 ppm Materials of construction Construction: BF Impeller: Bronze (B584-844) Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416 Connections: Inlet: 3 in, Outlet: 3 in Flush line: Braided Stainless Steel Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber Mechanical seal data Seal type: Outside Balanced Rotating face: Resin Bonded Carbon Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide Springs: Stainless Steel Secondary seal: Viton Rotating hardware: Stainless Steel Motor electrical data Supplier: Factory Choice Insulation class: Class F Insulation Size: 5 hp Inverter motor type: Inverter Duty Frame number: 184TC Efficiency: NEMA Prem (12.12) Enclosure: ODP Operating speed @ 100% flow: 1714 rpm Motor Electrics: 575/3/60 Operating speed @ 50% flow: 1242 rpm IVS102 controller data Sensorless control: Yes-Quadratic press control Communication port: RS 485 BMS protocol: BACnet Native Analog inputs: 2 (current or voltage) Enclosure: UL Type 12 Analog outputs: 1 (current) Fused disconnect switch: No 4 (programmable) Control orientation: L1 Digital outputs: 2 (programmable) Expansion card: None Cooling: Fan cooled through back channel BHP at 50% load/flow and 55% of design head: 0.76 hp IVSAmbTemp1txt Meets ASHRAE 90.1: No EMI/RFI control: Integrated fliter to meet EN61800-3 Min. maintained sys. pressure: 19.2 ft Harmonic suppression: Integrated DC link reactor** *If minimum maintained system pressure is not known, default is 40% of design head. ** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation. www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 1 of 42 Ambient Temp Digital Inputs:
42

Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Aug 02, 2018

Download

Documents

phunglien
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Design envelope split coupled vertical in line pump

Model: Series Design Envelope Sensorless 4300 0308-005.0

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: P-1/2 Pipe orientation: Single

Suction pressure: 0 ftService: Heating Loop

Location: Fluid: Water:

Quantity: 2 Operating temperature: 60 F

Viscosity: 31 SSUDuty flow per pump: 190 USgpm

Specific gravity: 1.0000Duty head: 48 ft

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 3 in, Outlet: 3 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Supplier: Factory Choice Insulation class: Class F Insulation

Size: 5 hp Inverter motor type: Inverter Duty

Frame number: 184TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Operating speed @ 100% flow: 1714 rpm

Motor Electrics: 575/3/60 Operating speed @ 50% flow: 1242 rpm

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

Enclosure: UL Type 12 Analog outputs: 1 (current)

Fused disconnect switch: No 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channel

BHP at 50% load/flow and 55% of design head:

0.76 hp IVSAmbTemp1txt

Meets ASHRAE 90.1: No EMI/RFI control: Integrated fliter to meet EN61800-3

Min. maintained sys. pressure: 19.2 ft Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.

** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does notguarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the systemelectrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrongcan also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 1 of 42

Ambient Temp Digital Inputs:

Page 2: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-1/2 Service: Heating Loop Location:

--- Motor Data --- Motor Size: 5 hp

--- Design Duty Point --- Flow: 190 usgpm Head: 48 ft Impeller: 7.38 in

--- Performance Data ---• NPSHR: 6.2162 ft• Eff. @ Design: 75.87 % • BHP @ Design: 3.04 hp• Mtr Capability @ Rated Spd: 4.46 hp• %Mtr Safety: 46.99%• BEP @ Design Imp.:

79.91 % @ 265.8 usgpm• %max imp. range: 63.16 %• Outlet Velocity: 8.25 ft/s• VFD Op.Speed: 1714 rpm• VFD Setting: 58.3 Hz

Series 4300Design Envelope: 0308-005.0 @ 58.3 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 80 160 240 320 400 4800

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

8.19 in

6.00 in

System

7.38 in

3 hp

5 hp

7.5 hp

80

80

78

78

73

73

65

65%

5440

Water:, spgr= 1.0000

PT72-2-0 (3.20.1.2)ANSI/HI 14.6.3.4.1

81

--- Admin Data --- Tag Num: P-1/2 Service: Heating Loop Location:

--- Motor Data --- Motor Size: 5 hp

--- Design Duty Point --- Flow: 190 usgpm Head: 48 ft Impeller: 7.38 in

--- Control Data ---1. Hmax @ 58.3 Hz:• 190 @ 48, 3.04 hp2. Control (QPC) @ 54.1 Hz:• 168 @ 41.7, 2.37 hp3. Control (QPC) @ 50.0 Hz:• 145.3 @ 36, 1.82 hp4. Control (QPC) @ 45.9 Hz:• 120.6 @ 30.8, 1.35 hp5. Control (QPC) @ 41.5 Hz:• 89.4 @ 25.6, 0.92 hp6. Index @ 37.3 Hz:• 47.5 @ 21, 0.57 hp7. Hmin: 19.2 ft 35.7 Hz:• Setting= 40.00% Hmax

Series 4300Design Envelope: 0308-005.0

Integrated Intelligent Variable Speed with Sensorless Control

0 80 160 240 320 400 4800

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

63.0 Hz

37.3 Hz

35.7 Hz

18.0 Hz

System

Avg.Load (QPC)

58.3 Hz

5 hp

8080

80

77

77

73

73

6555

Index Flow (25.0% Duty Flow)

Water:, spgr= 1.0000

PT72-2-0 (3.20.1.2)ANSI/HI 14.6.3.4.1

1

2

3

4

5

6

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 2 of 42

Page 3: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

22500

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 190 USgpm 56.9 ft 73.85 %

Design point 190 USgpm 48 ft 75.87 %

50% average flow (with default load profile) 95 usgpm 26.4 ft 64.26 %

Dimensional data (not for construction)

Top viewSide view

Weight: 349 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

.

Selected options Environmental Application: Indoors

Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-43 (516860-020)

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 3 of 42

Page 4: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Design envelope split coupled vertical in line pump

Model: Series Design Envelope Sensorless 4300 0408-010.0

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: P-3/4 Pipe orientation: Single

Suction pressure: 0 ftService: Chilled Water Loop

Location: Fluid: Water:

Quantity: 2 Operating temperature: 60 F

Viscosity: 31 SSUDuty flow per pump: 485 USgpm

Specific gravity: 1.0000Duty head: 52 ft

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416

Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data

Seal type: Outside Balanced Rotating face: Resin Bonded Carbon

Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data

Supplier: Factory Choice Insulation class: Class F Insulation

Size: 10 hp Inverter motor type: Inverter Duty

Frame number: 215TC Efficiency: NEMA Prem (12.12)

Enclosure: ODP Operating speed @ 100% flow: 1681 rpm

Motor Electrics: 575/3/60 Operating speed @ 50% flow: 1180 rpm

IVS102 controller data

Sensorless control: Yes-Quadratic press control Communication port: RS 485

BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)

Enclosure: UL Type 12 Analog outputs: 1 (current)

Ambient temperature:Fused disconnect switch: No Digital inputs: 4 (programmable)

Control orientation: L1 Digital outputs: 2 (programmable)

Expansion card: None Cooling: Fan cooled through back channel

BHP at 50% load/flow and 55% of design head:

2.01 hp IVSAmbTemp1txt

Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated fliter to meet EN61800-3

Min. maintained sys. pressure: 20.8 ft Harmonic suppression: Integrated DC link reactor**

*If minimum maintained system pressure is not known, default is 40% of design head.

** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does notguarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the systemelectrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrongcan also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 4 of 42

Page 5: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: P-3/4 Service: Chilled Water Loop Location:

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 485 usgpm Head: 52 ft Impeller: 8.19 in

--- Performance Data ---• NPSHR: 11.1 ft• Eff. @ Design: 79.38 % • BHP @ Design: 8.02 hp• Mtr Capability @ Rated Spd: 8.74 hp• %Mtr Safety: 8.97%• BEP @ Design Imp.:

79.51 % @ 510.5 usgpm• %max imp. range: 100.00 %• Outlet Velocity: 12.22 ft/s• VFD Op.Speed: 1681 rpm• VFD Setting: 57.0 Hz

Series 4300Design Envelope: 0408-010.0 @ 57.0 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 0.2 0.4 0.6 0.8 10

10

20

30

40

50

60

70

80

Flow ( 1,000 usgpm)

Head

(ft)

8.19 in

6.00 in

System

8.19 in

5 hp

7.5 hp

10 hp

79

79

76

76

72

72

64

64%

53

53%

39

Water:, spgr= 1.0000

PT87-3-0 (3.20.1.2)ANSI/HI 14.6.3.4.1

80

--- Admin Data --- Tag Num: P-3/4 Service: Chilled Water Loop Location:

--- Motor Data --- Motor Size: 10 hp

--- Design Duty Point --- Flow: 485 usgpm Head: 52 ft Impeller: 8.19 in

--- Control Data ---1. Hmax @ 57.0 Hz:• 485 @ 52, 8.02 hp2. Control (QPC) @ 52.5 Hz:• 428.3 @ 45.1, 6.17 hp3. Control (QPC) @ 48.1 Hz:• 368.7 @ 38.8, 4.61 hp4. Control (QPC) @ 43.4 Hz:• 298.8 @ 32.6, 3.22 hp5. Control (QPC) @ 39.0 Hz:• 224.3 @ 27.5, 2.16 hp6. Index @ 34.5 Hz:• 121.3 @ 22.8, 1.28 hp7. Hmin: 20.8 ft 32.3 Hz:• Setting= 40.00% Hmax

Series 4300Design Envelope: 0408-010.0

Integrated Intelligent Variable Speed with Sensorless Control

0 0.2 0.4 0.6 0.8 10

10

20

30

40

50

60

70

80

Flow ( 1,000 usgpm)

Head

(ft)

60.0 Hz

34.5 Hz

32.3 Hz

18.0 Hz

System

Avg.Load (QPC)

57.0 Hz

10 hp

8079

79

76

76

72

72

6453

Index Flow (25.0% Duty Flow)

Water:, spgr= 1.0000

PT87-3-0 (3.20.1.2)ANSI/HI 14.6.3.4.1

1

2

3

4

5

6

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 5 of 42

Page 6: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

22500

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 485 USgpm 59.1 ft 79.01 %

Design point 485 USgpm 52 ft 79.38 %

50% average flow (with default load profile) 242.5 usgpm 28.6 ft 73.39 %

Dimensional data (not for construction)

Top viewSide view

Weight: 484 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 4 9ANSI-125 8 0.6257.5

Outlet 4 9ANSI-125 8 0.6257.5

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

.

Selected options Environmental Application: Indoors

Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-64 (516860-023)

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 6 of 42

Page 7: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

Submittal

Product: User Defined Products

Model: DE START-UP

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2

Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor: Order No:

Submitted by: Dave Haskell Approved by: Date:

This page is intentionally left blank. A submittal is unavailable for this product.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 7 of 42

Page 8: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Close coupled vertical in-line pump

Model: Series 4380-3x3x6-1.5 hp Pump (Motor supplier: Armstrong choice)

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: P-5/6 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: Water:

Quantity: 2 Operating temperature: 60 F

Viscosity: 31 SSUDuty flow per pump: 140 USgpm

Specific gravity: 1.0000Duty head: 21 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: BF Impeller: Bronze (B584-844)

Rating: ANSI-125 Shaft sleeve: 316 SS

Connections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber

Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon

Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: EPDM

Rotating hardware: Stainless Steel

Motor electrical data

Supplier: Factory Choice Insulation class: Class F Insulation

Size: 1.5 hp Inverter motor type: Not applicable

Frame number: 145JM Efficiency: NEMA Prem (12.12)

Enclosure: ODP Speed: 1760 rpm

Motor Electrics: 208/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 8 of 42

Page 9: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

--- Admin Data --- Tag Num: P-5/6 Service: Location:

--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 140 usgpm Head: 21 ft Impeller: 5.37 in

--- Performance Data --- • NPSHR: 10.5 ft • Eff. @ Design: 72.87 % • BHP @ Design: 1.02 hp • Mtr Capability @ Rated Spd: 1.50 hp • %Mtr Safety: 47.23% • BEP @ Design Imp.: 73.56 % @ 161.5 usgpm • Impeller Max BHP @ Flow: 1.21 hp @ 234.2 usgpm • %max imp. range: 51.54 % • Outlet Velocity: 6.08 ft/s

Series 4380

3x3x6 @ 1760 rpm

0 50 100 150 200 250 3000

8

16

24

32

40

Flow (usgpm)

Head

(ft)

6.19 in

4.50 in

System

5.37 in

0.75 hp1 hp

1.5 hp

2 hp

3 hp

0.5 hp

77

77

74

74

70

70

62

62

52

52%

39

Water:, spgr= 1.0000

PT70-1-0 (3.20.1.2)ANSI/HI 14.6.3.4.1

77

Dimensional data (not for construction)

Top viewSide view

Weight: 209 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 9 of 42

Page 10: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 3 7.5ANSI-125 4 0.6256

Outlet 3 7.5ANSI-125 4 0.6256

*Equally spaced straddling centreline

Special instructions

.

Additional equipment Flotrex: FTV-3FA (570200-477) Suction Guide: SG-33 (516860-019)

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 10 of 42

Page 11: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Wet rotor circulator

Model: Part number: 110223-307Series ASTRO 250CI FLG

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: P-7/8 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: PropyleneGlycol:30

Quantity: 2 Operating temperature: 60 F

Viscosity: 37.213 SSUDuty flow per pump: 10 USgpm

Specific gravity: 1.0248Duty head: 10 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: STD125 Impeller: Polyether Imide (PEI)

Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada

Motor electrical data

Supplier: Factory Choice Insulation class: Not applicable

Size: 0.157 hp Inverter motor type: Not applicable

Frame number: Not applicable Efficiency: Std

Enclosure: ODP Speed: 3600 rpm

Motor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 11 of 42

Page 12: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

--- Admin Data --- Tag Num: P-7/8 Service: Location:

--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm

--- Design Duty Point --- Flow: 10 usgpm Head: 10 ft

--- Pump Data --- Pump Size: Astro 250CI Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 10.5 usgpm Projected Head: 10.9 ft

Series Astro MultiSpeed

Astro 250CI @ Discrete Speeds

0 4 8 12 16 200

5

10

15

20

25

30

Flow (usgpm)

Head

(ft)

System

Projected

[1] 2300

[2] 2900

[3] 3600

PropyleneGlycol:30, spgr= 1.0248

PT620-0-228 (3.20.1.2)

Dimensional data (not for construction)

Side viewFront view

Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 12 of 42

Page 13: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Special instructions

.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 13 of 42

Page 14: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Wet rotor circulator

Model: Part number: 110223-305Series ASTRO 230CI FLG

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: P-9 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: PropyleneGlycol:30

Quantity: 1 Operating temperature: 60 F

Viscosity: 37.213 SSUDuty flow per pump: 8 USgpm

Specific gravity: 1.0248Duty head: 7 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: STD125 Impeller: Polyether Imide (PEI)

Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada

Motor electrical data

Supplier: Factory Choice Insulation class: Not applicable

Size: 0.13 hp Inverter motor type: Not applicable

Frame number: Not applicable Efficiency: Std

Enclosure: ODP Speed: 3600 rpm

Motor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 14 of 42

Page 15: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

--- Admin Data --- Tag Num: P-9 Service: Location:

--- Motor Data --- Motor Size: 0.13 hp Motor Speed: [3] 3600 rpm

--- Design Duty Point --- Flow: 8 usgpm Head: 7 ft

--- Pump Data --- Pump Size: Astro 230CI Impeller: 2.36 in Suction Head Req: 0 ft Projected Flow: 9.125 usgpm Projected Head: 9.1073 ft

Series Astro MultiSpeed

Astro 230CI @ Discrete Speeds

0 4 8 12 16 200

4

8

12

16

20

Flow (usgpm)

Head

(ft)

System

Projected

[1] 2300

[2] 2900 [3] 3600

PropyleneGlycol:30, spgr= 1.0248

PT617-0-225 (3.20.1.2)

Dimensional data (not for construction)

Side viewFront view

Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 15 of 42

Page 16: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Special instructions

.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 16 of 42

Page 17: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

E.2 series dry motor circulator

Model: Part number: 182202-658Series E8.2B brz 120V

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: PDR-1/2 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: Potable/Drinking Water

Quantity: 2 Operating temperature: 60 F

Viscosity: 31 SSUDuty flow per pump: 15 USgpm

Specific gravity: 1.0000Duty head: 20 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: AB Impeller: 30% Glass-filled Noryl

Rating: Not applicable Bearings: Permanently lubricated SS

Connections: Inlet: 1.25 in, Outlet: 1.25 in

Mechanical seal data

Manufacturer: Armstrong Seal: Silicon Carbide

Seal type: Bellows-style Silicon Carbide

Motor electrical data

Supplier: Factory Choice Insulation class: Not applicable

Size: 0.167 hp Inverter motor type: Not applicable

Frame number: Not applicable Efficiency: Std

Enclosure: ODP Speed: 3380 rpm

Motor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 17 of 42

Page 18: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

--- Admin Data --- Tag Num: PDR-1/2 Service: Location:

--- Motor Data --- Motor Size: 0.167 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 15 usgpm Head: 20 ft

--- Pump Data --- Pump Size: E8.2B Impeller: 2.9 in Projected Flow: 16.4 usgpm Projected Head: 23.9 ft

Series E.2

Selected Size: E8.2B @ 3380 rpm

0 20 40 60 80 100 120 140 1600

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

System

Projected

E8.2B

Water, spgr= 1.0000

PT204-0-68 (3.20.1.2)

Dimensional data (not for construction)

Back viewSide view

Weight: 15 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 18 of 42

Page 19: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.25 5N/A 4 0.53.88

Outlet 1.25 5N/A 4 0.53.88

*Equally spaced straddling centreline

Special instructions

.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 19 of 42

Page 20: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Wet rotor circulator

Model: Part number: 110223-308Series ASTRO 250SS FLG

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: PDR-3 Pipe orientation: Single

Suction pressure: 0 ftService:

Location: Fluid: Potable/Drinking Water

Quantity: 1 Operating temperature: 60 F*

Viscosity: 31 SSUDuty flow per pump: 8 USgpm

Specific gravity: 1.0000Duty head: 12 ft

Total dissolved solids: 0 ppm

* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.

Materials of construction

Construction: SS150 Impeller: Polyether Imide (PEI)

Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada

**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)

Motor electrical data

Supplier: Factory Choice Insulation class: Not applicable

Size: 0.157 hp Inverter motor type: Not applicable

Frame number: Not applicable Efficiency: Std

Enclosure: ODP Speed: 3600 rpm

Motor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 20 of 42

Page 21: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

--- Admin Data --- Tag Num: PDR-3 Service: Location:

--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm

--- Design Duty Point --- Flow: 8 usgpm Head: 12 ft

--- Pump Data --- Pump Size: Astro 250SS Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 8.4619 usgpm Projected Head: 13.4 ft

Series Astro MultiSpeed

Astro 250SS @ Discrete Speeds

0 4 8 12 16 200

5

10

15

20

25

30

Flow (usgpm)

Head

(ft)

System

Projected

[1] 2300

[2] 2900

[3] 3600

Water, spgr= 1.0000

PT620-0-228 (3.20.1.2)

Dimensional data (not for construction)

Side viewFront view

Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 21 of 42

Page 22: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Special instructions

.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 22 of 42

Page 23: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Design Envelope Booster System

Series : 6800 G/E Design Envelope Model: N250222-7.5 hp

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Tag number: DBP-1 Water Supply: Tank

Suction (supply) pressure: 46.2 ftService:

Location: Total flow capacity: 330.0 USgpm

Quantity: 1 System boost pressure rating: 93.0 ft

Power Supply: Discharge pressure: 139.2 ft575/3/60

System construction data

System description: Duplex Piping material: Stainless Steel 304

Header size: 4 in Valve type Check valve only

Header connections: Grooved Maximum working pressure: 536.0 ft

Suction orientation: Right* Discharge orientation: Right*

*when facing booster controller Low lead certification: NSF 372

Pump data N250222Number of pumps: 2 Duty flow per pump: 165 USgpm

Operation: 2 Duty Duty head: 93 ft

Series: 4700 Motor size: 7.5 hp

Size: VMS-32:02-2 Motor speed: 3600 rpm

Motor efficiency: NEMA Premium (12.12)Construction: Stainless Steel 304

Motor enclosure: ODP

Booster control panel data

Enclosure: NEMA 12 Painted steel Human Machine Interface: Alpha-Numeric

Selected features: BMS Port (serial communication port for connection to BMS - BacNet (MS/TP))HMI: Alpha-Numeric

IVS-102 variable frequency control data

Quantity: 2 (integrated with motors) EMI/RFI control: Integrated filter to meet EN61800-3

Enclosure: UL Type 12 Cooling: Fan cooled through back channel

Harmonic suppression: Integrated DC link reactor Ambient temperature: -10C to +45C(upto 1000m elevation)

Drawdown tank data

Size and rating: 132 US Gallon Non-ASME Mounting: Remote Mounted

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 23 of 42

Page 24: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Performance curve

Dimensional data (not for construction)

WEIGHTS (lb) NOT for CONSTRUCTION

Weights

976

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 24 of 42

Page 25: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Booster controller wiring diagram

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 25 of 42

Page 26: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 26 of 42

Page 27: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

Submittal

Product: User Defined Products

Model: BOOSTER START-UP

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2

Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor: Order No:

Submitted by: Dave Haskell Approved by: Date:

This page is intentionally left blank. A submittal is unavailable for this product.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 27 of 42

Page 28: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

SubmittalProduct : Vortex Air Separators

Model: VA-4-U

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2

Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Order No: Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Submitted by: Dave Haskell Approved by: Date:

Technical Data

Max.Working Temperature 375° F (190° C)

Connection Type 150# Flanged ANSI (RFSO)

Max.working Pressure4"-6" Models:160 psi(1103 kPa), 8"-12" Models:165 psi(1140 kPa)

Materials Of Construction

Gasket Non-Asbestos

Shell4"-6" Models:Cast Iron, 8"-12" Models:Fabricated Steel

DIMENSIONAL DATA (in, lb ) NOT for CONSTRUCTION

A B C D E F H J K N WeightVelocity

(ft/s)Max.Flow

RateStrainer.

sq. in

4 1.5 9.5 18 2.25 6.8 22.25 10.75 16 9 170 4 160.0 USgpm N/A

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 28 of 42

Page 29: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

SubmittalProduct : Vortex Air Separators

Model: VA-6-U

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2

Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Order No: Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Submitted by: Dave Haskell Approved by: Date:

Technical Data

Max.Working Temperature 375° F (190° C)

Connection Type 150# Flanged ANSI (RFSO)

Max.working Pressure4"-6" Models:160 psi(1103 kPa), 8"-12" Models:165 psi(1140 kPa)

Materials Of Construction

Gasket Non-Asbestos

Shell4"-6" Models:Cast Iron, 8"-12" Models:Fabricated Steel

DIMENSIONAL DATA (in, lb ) NOT for CONSTRUCTION

A B C D E F H J K N WeightVelocity

(ft/s)Max.Flow

RateStrainer.

sq. in

6 1.5 12.5 24 4 9.85 32.24 16 22 12 331 4 360.0 USgpm N/A

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 29 of 42

Page 30: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

Submittal

Product: User Defined Products

Model: ABX050-40

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BC V3K 6X2Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor: Order No:

Submitted by: Dave Haskell Approved by: Date:

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 30 of 42

ABX - BRAZED PLATE HEAT EXCHANGERS

Armstrong’s ABX brazed plate heat exchangers are designed to facilitate heat transfer between two media of different temperatures. ABX produces high heat transfer rates that allow for a compact, corrosion resistant and robust design.

TYPICAL SPECIFICATION

Furnish and install on the plans and described herein, an Armstrong ABX050-_40_____ brazed plate heat exchanger. Each heat exchanger must be designed to have the capacity and pressure/temperature rating as detailed in the schedule. The heat exchanger must utilize 316L stainless steel plates and copper braze to separate the two fluids while transferring heat and preventing corrosion.

Each heat exchanger shall be Armstrong ABX050-_40_________ or approved equal.

C

E

L

D

A B

A1 B1

B2A2

QUANTITY TAG No. MODEL No. COMMENTS 2 HX-1, HX-2 ABX050-40

Page 31: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3Submittal

Product: User Defined ProductsModel: ABX030-30

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BC V3K 6X2Reference: 514501.2.3Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Order No:Submitted by: Dave Haskell Approved by: Date:

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 31 of 42

ABX - BRAZED PLATE HEAT EXCHANGERS

Armstrong’s ABX brazed plate heat exchangers are designed to facilitate heat transfer between two media of different temperatures. ABX produces high heat transfer rates that allow for a compact, corrosion resistant and robust design.

TYPICAL SPECIFICATION

Furnish and install on the plans and described herein, an Armstrong ABX030-_30_____ brazed plate heat exchanger. Each heat exchanger must be designed to have the capacity and pressure/temperature rating as detailed in the schedule. The heat exchanger must utilize 316L stainless steel plates and copper braze to separate the two fluids while transferring heat and preventing corrosion.

Each heat exchanger shall be Armstrong ABX030-_30_________ or approved equal.

C

E

L

D

A B

A1 B1

B2A2

QUANTITY TAG No. MODEL No. COMMENTS 1 HX-3 ABX030-30

Page 32: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project # : 514501.2 rev3Submittal

Product: Expansion

Model: Expansion Equipment

Project Number: 514501.2.3

Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3

Date:

Location: Vancouver, BC

1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Representative: Con-Cur West Marketing Inc. 71A Clipper Street

Coquitlam, BC

V3K 6X2

Phone: 604-540-5088, Fax: 604-540-5084 Order No:

Submitted by: Dave HaskellApproved by: Date:

SYSTEM DATATag Num : EXT-1 Service : Location : Qty : 1Selection Method : Manual

Application: Heating

This has been a Manual Selection, so no data is available.

Expansion Tank:AX-40VTank Model : 1Tank Qty

Tank Volume :25.0 us gal Max. Working Pres. : 346.6 ft

Charge Pressure: 26.8 ft • Not for Domestic Potable Water Systems

• California Code Sight-Glass available upon request.Standard factory charge is 12 psi (83 kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII, Division 1.

• This submittal supercedes 37.51 and 37.50

Shell : Steel WORKING TEMPERATURE : 240°F (115°C)

Diaphragm : Heavy Duty Butyl WORKING PRESSURE : 150 psi (1034 kPa)

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 32 of 42

Page 33: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project # : 514501.2 rev3Submittal

Product: Expansion

Model: Expansion Equipment

Project Number: 514501.2.3

Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3

Date:

Location: Vancouver, BC

1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Representative: Con-Cur West Marketing Inc. 71A Clipper Street

Coquitlam, BC

V3K 6X2

Phone: 604-540-5088, Fax: 604-540-5084 Order No:

Submitted by: Dave HaskellApproved by: Date:

SYSTEM DATATag Num : EXT-2 Service : Location : Qty : 1Selection Method : Manual

Application: Heating

This has been a Manual Selection, so no data is available.

Expansion Tank:AX-20VTank Model : 1Tank Qty

Tank Volume :11.0 us gal Max. Working Pres. : 346.6 ft

Charge Pressure: 26.8 ft • Not for Domestic Potable Water Systems

• California Code Sight-Glass available upon request.Standard factory charge is 12 psi (83 kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII, Division 1.

• This submittal supercedes 37.51 and 37.50

Shell : Steel WORKING TEMPERATURE : 240°F (115°C)

Diaphragm : Heavy Duty Butyl WORKING PRESSURE : 150 psi (1034 kPa)

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 33 of 42

Page 34: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project # : 514501.2 rev3Submittal

Product: Expansion

Model: Expansion Equipment

Project Number: 514501.2.3

Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3

Date:

Location: Vancouver, BC

1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor:

Representative: Con-Cur West Marketing Inc. 71A Clipper Street

Coquitlam, BC

V3K 6X2

Phone: 604-540-5088, Fax: 604-540-5084 Order No:

Submitted by: Dave HaskellApproved by: Date:

SYSTEM DATATag Num : EXT-3 Service : Location : Qty : 1Selection Method : Manual

Application: Heating

This has been a Manual Selection, so no data is available.

Expansion Tank:AST-80Tank Model : 1Tank Qty

Tank Volume :35.0 us gal Max. Working Pres. : 346.6 ft

Charge Pressure: 40 psi • For Domestic Potable Water Systems & Draw down tanks for Pressure Booster Systems.Standard factory charge is 40 psi (276

kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII,Division 1.

Shell : Carbon SteelWORKING TEMP. : 240°F (115°C)

WORKING PRESSURE Liner : Polypropylene: 150 psi (1034 kPa)

System Conn. : Stainless Steel Fixed Diaphragm : Butyl-FDA approved

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 34 of 42

Page 35: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Project #: 514501.2 rev3

Submittal

Product: User Defined Products

Model: SEISMIC CLIPS

Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.

Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2

Reference: 514501.2.3

Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:

Date: 1/7/2016Engineer: Cada & Associates

Date: 1/7/2016 Contractor: Order No:

Submitted by: Dave Haskell Approved by: Date:

This page is intentionally left blank. A submittal is unavailable for this product.

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 35 of 42

Page 36: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Flo-trex valve

Model: FTV-F (2.5 to 12 inch)

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Designflowrate

Tag Qty Model Size Config Flange ratingPressure

Drop*Associated pump

P-1/2 2 FTV-4FA 4 in Angle ANSI-125 190.0 USgpm 2.8 ft P-1/2 Design Envelope Sensorless 4300 0308-005.0

P-3/4 2 FTV-6FA 6 in Angle ANSI-125 485.0 USgpm 2.8 ft P-3/4 Design Envelope Sensorless 4300 0408-010.0

P-5/6 2 FTV-3FA 3 in Angle ANSI-125 140.0 USgpm 3.4 ft P-5/6 4380-3x3x6-1.5 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM

Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

Operating limits (temperature - pressure)

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 36 of 42

Page 37: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 37 of 42

Page 38: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Dimensional data (not for construction)

Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb

Side view Front view

Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb

Side view Front view

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 38 of 42

Page 39: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Model: FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 39 lb

Side view Front view

Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 39 of 42

Page 40: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Submittal Ref. #: 514501.2 rev3

Suction guide

Model: SG (2 to 12 inches)

Project name: CC-15409 Parc Elise - 4400 Cambie Street

Location: Vancouver, BC Representative:

Date submitted: 1/7/2016 Phone number:

Engineer: Cada & Associates e-mail:

Contractor: Submitted by:

Con-Cur West Marketing Inc.

604-540-5088

[email protected]

Dave Haskell

Application design data

Design flowrate

Tag Qty Model System PumpPressure

Drop*Associated pump

P-1/2 2 SG-43 4 in 3 in 190.0 USgpm 1.5 ft P-1/2 Design Envelope Sensorless 4300 0308-005.0

P-3/4 2 SG-64 6 in 4 in 485.0 USgpm 2.9 ft P-3/4 Design Envelope Sensorless 4300 0408-010.0

P-5/6 2 SG-33 3 in 3 in 140.0 USgpm 0.8 ft P-5/6 4380-3x3x6-1.5 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

SG-43

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-64

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

SG-33

Body: Cast Iron Cover gasket: Synthetic fiber

Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-43-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 40 of 42

Page 41: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

Dimensional data (not for construction)

SG-43 Weight: 52 lb

Side view Top view

SG-64 Weight: 85 lb

Side view Top view

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 41 of 42

Page 42: Submittal - Pro Wrestling Reviews Drawings/49 - North... · 22500 Desi gn envelope pumping unit capability Operating poin t Flow Head Eff iciency Full capab ility at 100 % design

SG-33 Weight: 45 lb

Side view Top view

Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 42 of 42