Top Banner
AS 1684 SECTION 3 - SUBSTRUCTURE 1 SECTION 3 - SUBSTRUCTURE
28
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

1

SECTION 3 -

SUBSTRUCTURE

Page 2: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

2

3.1 SCOPE

This Section sets out requirements for site preparation, subfloor supports and the determination of footing sizes suitable for supporting timber-framed houses. This Section is derived from AS 2870.1 using allowable soil bearing stresses.

Page 3: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

3

3.2 SITE PREPARATION AND DRAINAGE

The clearing and drainage of the site on which the building is to be erected shall be adequate to ensure protection of any timber framing or components from the effects of prolonged dampness or insect attack

Page 4: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

4

3.2.2 Site clearing

The site shall be cleared of any logs, tree roots or stumps and other wood debris, including waste material from the construction, likely to increase the termite risk or cause damage to footings or concrete slabs or subsoil drainage, within and around the building.

Page 5: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

5

3.2.2 Site drainage

Surface and subsurface water occurring on the building site shall be diverted to prevent it from flowing under the structure. Ponding of water under the structure shall be prevented by filling, grading or the provision of drainage or diversion channels.NOTE: The ground surface should be graded to fall away from the building.

Page 6: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

6

3.3 GROUND CLEARANCES AND SUBFLOOR VENTILATION

Ground clearance and subfloor ventilation shall be provided in accordance with the provisions of the Building Code of Australia.

Page 7: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

7

3.4 DURABILITY

Protection against termites shall be provided in accordance with the provisions of the Building Code of Australia.

3.4.1 Termite management

Page 8: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

8

3.4.2 Species selection

Any species and durability classes of timber may be utilized for floor and subfloor framing where adequate ventilation and weather protection is provided (see also Clause 1.10). NOTE: For extremely damp or unventilated situations or timber in contact with the ground (see Appendix C).

Page 9: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

9

3.5 SUBSTRUCTURE BRACING

The substructure shall be adequately braced against all of the applied loads (see Section 8).

Page 10: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

10

3.6.2 Soil classification

Details provided in this Clause are only applicable to A, S, M or H soil classification with a minimum allowable bearing capacity of 100 kPa.

Soil classifications E and P are beyond the scope of this Section and further professional advice is required.

Page 11: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

11

(a) Floor loads (cont)

TABLE 3.1 P33 AS1684.2

MASS OF TYPICAL FLOORS

Floor and/or ceiling type Mass , kN/m2

Timber flooring up to 22 mm thick plus lightweight floor covering i.e. carpet and underlay 0.30

Timber flooring up to 22 mm thick plus lightweight floor covering and ceilings 0.40

Timber flooring up to 22 mm thick plus ceramic or t erracotta floor covering 0.60

Timber flooring up to 22 mm thick plus ceramic or t erracotta floor coverings and ceilings 0.70

Page 12: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

12

EXAMPLE - FLOOR LOADS :

Calculate floor areas supported by each post as per 2.6.5 Area supported.

Area supported by post atA = 1.5m x 1.8m = 2.7m2

B = 1.5m x 3.6m = 5.4m2

D = 3.0m x 1.8m = 5.4m2

E = 3.0m x 3.6m = 10.8m2

½ ½ + ½

A

B

C

D

E

½

+ ½

B earerspan 3000

Flo

or

jois

tsp

an

3600

½

½ + ½ ½

Flo

or jo

ist

span

36

00

B ea rerspan 3000

B earerspan 3000

Page 13: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

13

Note 2 is alerting us to the fact that different roof configurations distribute the roof loads to the foundations differently for example:

A pitched roof with underpurlins will distribute the load between external walls and internal walls and there may also be concentrations of load at the ends of strutting beams etc.

However a standard trussed roof distributes all of the roof load to the external walls however there may be concentrations of load where girder trusses are located.

Page 14: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

14

The Roof Load Widths (RLW) in the following examples have been calculated based on a building width of 7200 mm, a roof pitch of 20O and an overhang of 600 mm.

Page 15: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

15

Pitched Roof - assuming no point loads from strutting beams etc. and that roof loads on wall X will be taken by post at B and roof loads on wall Y will be evenly distributed between posts at B and C ..............

½ ½ + ½

A

B

C

D

E

F

B earerspan 3000

B earerspan 3000

RLW

R

LW

RLW

A B C

RLWRLW

RLWRLW

600 m moverhang

20O

X Y

Page 16: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

16

.....Roof load at

A = 2.55(RLW) x 1.5 = 3.83m2 x 0.9 (tile roof) = 3.44kN

B = 2.88(RLW) x 1.5 = 4.32m2 x 0.9 (tile roof) = 3.89kN

C = 3.51(RLW) x 1.5 = 5.27m2 x 0.9 (tile roof) = 4.74kN

D = 2.55(RLW) x 3.0 = 7.65m2 x 0.9 (tile roof) = 6.89kN

E = 2.88(RLW) x 3.0 = 8.64m2 x 0.9 (tile roof) = 7.78kN

F = 3.51(RLW) x 3.0 = 10.53m2 x 0.9 (tile roof) = 9.47kN

Page 17: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

17

Trussed Roof - assuming no point loads from girder trusses etc., the roof loads will be evenly distributed to external walls and posts –

A B

600 mmoverhang

20O

½ ½ + ½

A

B

C

D

E

F

RLW

R

LW

B earerspan 3000

B earerspan 3000

Page 18: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

18

.....Roof load at

A = 4.47(RLW) x 1.5 = 6.70m2 x 0.9 (tile roof) = 6.03kN

B = No load

C = 4.47(RLW) x 1.5 = 6.70m2 x 0.9 (tile roof) = 6.03kN

D = 4.47(RLW) x 3.0 = 13.41m2 x 0.9 (tile roof) = 12.07kN

E = No load

F = 4.47(RLW) x 3.0 = 13.41m2 x 0.9 (tile roof) = 12.07kN

Page 19: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

19

TABLE 3.

BEARING LOAD AND FOOTING SIZE

Total vertical

bearing load (kN)

Minimum concrete pier or stump or

sole plate diameter (mm)

Minimum concrete pier/stump or

sole plate size (mm mm)

4.9 250 225 225

7.1 300 275 275

9.0 350 300 300

12 400 350 350

16 450 400 400

Page 20: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

20

3.7 FOOTINGS AND SUPPORTS FOR WIND CLASSIFICATIONS N1

AND N2

This Clause deals with the selection of stumps and posts, and pad footings and sole plates, required to transfer roof, wall and floor loads to the soil foundation.

3.7.1 General

Page 21: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

21

The bracing requirements of Section 8 shall be considered to ensure that the use of footing or post or stump details given in this Section are also adequate to resist lateral loads. For wind classifications greater than N2 (see Clause 3.6).

3.7.1 General

Page 22: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

22

For the purposes of this Clause, footings for stumps or posts are classified as types 1 to 5, as shown in Table 3.3. Footing types 1 to 4 are for use in areas where the allowable foundation bearing pressure is at least 100 kPa. Type 5 footings are only suitable where the allowable foundation bearing pressure equals or exceeds 125 kPa.

3.7.2 Simplified footing

classification

Page 23: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

23

Footings shall be proportioned to evenly distribute vertical and lateral loads from the building to the foundation material such that significant settlement or other movement is prevented. Timber soleplates shall not project beyond any face of the stump or post they support by more than their own thickness, taken across the grain, or three times their own thickness measured along the grain.

NOTE: Further information, including minimum depth requirements, is given in AS 2870.1.

3.7.2 Simplified footing

classification

Page 24: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

24

TABLE 3.3

FOOTING CLASSIFICATION

Footing

type

Minimum

bearing area

(m2)

Bearing

capacity

(kN)

Minimum size of

unreinforced concrete

pad footing (mm)

Minimum size

of timber

soleplates (mm)

1 0.045 4.5230 × 230 × 100 deep

or250 dia. x 100 deep

200 × 225 ×38 thick

2 0.090 9.0300 × 300 × 150 deep

or350 dia. × 150 deep

250 × 360 × 75 thick

3 0.120 12350 × 350 × 200 deep

or400 dia. × 200 deep

300 × 400 × 75 thick

4 0.180 18430 × 430 × 250 deep

or500 dia. × 200 deep

300 × 600 × 100 thick

5 0.180 22430 × 430 × 250 deep

or500 dia. × 200 deep

300 × 600 × 100 thick

Page 25: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

25

(b) Height   The height above ground of any stump or post determined using Table 3.4 shall not exceed 15 times the minimum face width or diameter unless designed in accordance with recognized engineering principles.

– NOTE: Where posts or stumps are designed in accordance with engineering principles, the height limitation may not apply.

3.7.3 Stumps and posts

Page 26: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

26

(c) Embedment  P37 AS1684.2 Stumps or post embedment in the foundation material shall be at least 0.3 times the stump height above ground level or 450 mm, whichever is the greater.

3.7.3 Stumps and posts

Page 27: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

27

TABLE 3.5

LOAD WIDTHS AND BEARER SPANS FOR FOOTING TYPES 1 TO 5FOR BEARERS SUPPORTING FLOOR LOADS ONLY

Floor load width (mm)

1200 1500 1800 2100 2400 3000 3600Footing

typeMaximum permissible bearer span (mm)

1 2 400 1 900 1 600 1 400 1 200 1 000 800

2 4 800 3 900 3 200 2 800 2 400 1 900 1 600

3 6 400 5 200 4 300 3 700 3 200 2 600 2 100

4 9 700 7 700 6 400 5 500 4 800 3 900 3 200

5 12 100 9 700 8 100 6 900 6 000 4 800 4 000

NOTES:

1 Maximum permissible bearer span is for each footing type. Bearer size is determined from the relevantSpan Tables in the Supplements (see Section 4).

2 The Table values are based on a distributed load of 1.55 kPa being 0.4 kPa wall load spread over thefloor area, 0.4 kPa floor load and 0.75 kPa permanent live load.

Page 28: Sub floor code

AS 1684 SECTION 3 - SUBSTRUCTURE

28

TABLE 3.6

LOAD WIDTHS AND BEARER SPANS FOR FOOTING TYPES 1 TO 5 FORBEARERS SUPPORTING SINGLE STOREY LOADBEARING WALLS

Roof load width (mm)

1500 3000 4500 6000 7500Footing

typeRoofing type

Maximum permissible bearer span (mm)

Floor load width 900 mm

1

2

3

4

5

Sheet

2 300

4 500

6 000

9 000

11 300

1 700

3 500

4 600

6 900

8 700

1 400

2 800

3 800

5 600

7 000

1 200

2 400

3 200

4 700

5 900

1 000

2 000

2 700

4 100

5 100

1

2

3

4

5

Tile

1 600

3 300

4 400

6 600

8 200

1 000

2 200

2 900

4 400

5 500

800

1 600

2 200

3 300

4 100

NS

1 300

1 800

2 600

3 300

NS

1 100

1 500

2 200

2 800