All external anchors, dowels and fixings should be of stainless steel or other
corrosion resistant materials. Any metal dowels and fixings securing the
cladding panels should be suitable, permanent and adequately protected
from corrosion.
Height of the façade must be less than 28 m if the joints are filled with mortar
and less than 18 m if the joints are not filled
TIES
Corrosion resistant wire (copper,
brass ,stainless steel or zintane)brass ,stainless steel or zintane)
DIAMETERS
-5mm for slabs 30 to 40mm thick
-6mm for slabs graeter than 40 mm
thick
AIR SPACE
The distance between the back of the stone and the
reference plane of the support or the insulation must be
greater than equal to 2cm
FIXING THE ANCHOR IN THE SUPPORT
-either by embedding the anchor with cement mortar
-or by mechanical means using stainless steel wedge –type compatible
with the metal of the tie
cladding
ties
Wall cladding consisting of stone slabs attached to a stable
support by ties, these ties are coated in a plug of mortar ,in a
ventilated air space created between the cladding and the support