Top Banner
Std, KO & KOL Seat Comparisons November 2012
7

Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

Apr 28, 2018

Download

Documents

buidien
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

Std, KO & KOL Seat Comparisons  

November  2012  

Page 2: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

Maximum  Flow  Overview  

Size  Standard  Seat  Max  

Flow  (GPM)  KO  Seat  Max  Flow  

(GPM)  KOL  Seat  Max  Flow  

(GPM)  NFPA  20  Flow  

Requirement  (GPM)  

2”   500   250   400   250  

3”   850   520   650   500  

4”   2000   900   1200   1000  

6”   4400   2500   2750   2500  

8”   7700   4000   5000   4000  

10”   12450   6600   7500   N/A  

Note:  Flows  based  on  100  PSID  across  valve.  

Page 3: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

Cv  Overview  

Size  Standard  Seat  Cv  

(GPM)  KO  Seat  Cv  (GPM)  

KOL  Seat  Cv  (GPM)  

NFPA  20  Cv  Requirement  (GPM)  

2”   50   25   40   25  

3”   85   52   65   50  

4”   200   90   120   100  

6”   440   250   275   250  

8”   770   400   500   400  

10”   1245   660   750   N/A  

Page 4: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

6”  Std,  KO,  &  KOL  Seat  Comparison  

Page 5: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

8”  Std,  KO,  &  KOL  Seat  Comparison  

Page 6: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

10”  Std,  KO,  &  KOL  Seat  Comparison  

Page 7: Std, KO & KOL Seat Comparisons - Cla-Val vs. KOL.pdf · 100-01 Std, KO, KOL Seat Comparison (Normal Flow) 350 (GPM) CIA-VAI Standard Seat KO seat KOC seat FM Minimum Flow Requirement:

10”  Standard  Seat  vs.  KOL