FAN DUTY : 1.269 m³/s Item Description Size / Quantity Unit App. Pressure Drop (Pascal) Total App. Pressure Drop (Pascal) 1 Fume Hood Total Pressure Drop 1 No. 500 500 2 Phoenix Flow Control Valve 1 No: 250 250 3 Manual/ Motorised Volume Control Dampers 1 No. 30 30 4 Back draft damper 1 No. 35 35 5 Sound Attenuator 1 No. 80 80 6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3 7 Approximate Ducting Length, 1.93 Pascal per Metre 14.2 m 1.93 Pascal per Metre 27.5 8 Approximate Ducting Length, 2.51 Pascal per Metre ( horizontal 87+35+31.5 ) 153.5 m 2.51 Pascal per Metre 385.3 9 Approximate Ducting Length, 2.51 Pascal per Metre ( vertical riser ) 48 m 2.51 Pascal per Metre 120 10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8 11 Duct & Fittings safety factor 10 % safety factor 153.60 1689.50 Static Pressure Calculations H-M2-45-24-HDE-20 Exhaust of Contaminated Lab fume air to outside. Total ESP For the fan
27

Static Pressure

May 01, 2017

Download

Documents

SuchitK
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Static Pressure

FAN DUTY : 1.269 m³/s

Item Description Size / QuantityUnit App. Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1 Fume Hood Total Pressure Drop 1 No. 500 500

2 Phoenix Flow Control Valve 1 No: 250 250

3 Manual/ Motorised Volume Control Dampers 1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3

7Approximate Ducting Length, 1.93 Pascal per

Metre14.2 m 1.93 Pascal per Metre 27.5

8Approximate Ducting Length, 2.51 Pascal per

Metre ( horizontal 87+35+31.5 )153.5 m 2.51 Pascal per Metre 385.3

9Approximate Ducting Length, 2.51 Pascal per

Metre ( vertical riser )48 m 2.51 Pascal per Metre 120

10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8

11 Duct & Fittings safety factor 10 % safety factor 153.60

1689.50

Static Pressure Calculations

H-M2-45-24-HDE-20

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 2: Static Pressure

FAN DUTY : 0.741 m³/s

Item Description Size / QuantityUnit App. Pressure Drop

(Pascal)

Total App. Pressure Drop

(Pascal)

1 Fume Hood Total Pressure Drop 1 No. 500 500

3 Phoenix Flow Control Valve 1 No: 250 250

3Manual/ Motorised Volume Control

Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6Approximate Ducting Length,0.54

Pascal per Metre (horizontal)25.2 m. 0.54 Pascal per Metre 13.6

7Approximate Ducting Length, 0.19

Pascal per Metre (horizontal )8.5 m 0.19 Pascal per Metre 1.6

8Approximate Ducting Length, 0.49

Pascal per Metre ( horizontal )4.5 m 0.49 Pascal per Metre 2.2

9Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )60 m 0.91 Pascal per Metre 54.6

10Approximate Ducting Length, 0.91

Pascal per Metre ( vertical )25 m 0.91 Pascal per Metre 22.8

11Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )67 m 0.91 Pascal per Metre 61

Approximate Ducting Length, 0.91

Pascal per Metre ( horizontal )13 m 0.91 Pascal per Metre 11.8

12 Approximate Duct Fittings 20 % of Duct pressure drop 36.2

13 Duct & Fittings safety factor 10 % safety factor 109.80

1208.6

H-M2-45-24-HDE-15

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 3: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

58 m.2.69 Pascal per

Metre156

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

20 m2.69 Pascal per

Metre53.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.4

11Duct & Fittings safety

factor10 % safety factor 122.70

1350.2

H-M2-45-24-HDE-01

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 4: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

62 m.2.69 Pascal per

Metre166.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

22 m2.69 Pascal per

Metre59.2

9 Approximate Duct Fittings20 % of Duct

pressure drop58.7

10Duct & Fittings safety

factor10 % safety factor 124.70

1371.7

H-M2-45-24-HDE-02

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 5: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

20 m.2.69 Pascal per

Metre53.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

38 m2.69 Pascal per

Metre102.2

9 Approximate Duct Fittings20 % of Duct

pressure drop44.7

10Duct & Fittings safety

factor10 % safety factor 116.30

1279.3

H-M2-45-24-HDE-04

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 6: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1353.1

H-M2-45-24-HDE-05

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 7: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 123.10

1353.8

H-M2-45-24-HDE-06

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 8: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre67.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop55.9

10Duct & Fittings safety

factor10 % safety factor 123.10

1353.8

H-M2-45-24-HDE-07

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 9: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop54.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1347.1

H-M2-45-24-HDE-08

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 10: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

49 m2.69 Pascal per

Metre131.8

9 Approximate Duct Fittings20 % of Duct

pressure drop54.9

10Duct & Fittings safety

factor10 % safety factor 122.40

1347.1

H-M2-45-24-HDE-09

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 11: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

34 m.2.69 Pascal per

Metre91.5

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

36 m2.69 Pascal per

Metre96.8

9 Approximate Duct Fittings20 % of Duct

pressure drop50.1

10Duct & Fittings safety

factor10 % safety factor 119.60

1315.3

H-M2-45-24-HDE-10

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 12: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

30 m.2.69 Pascal per

Metre80.7

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

25 m2.69 Pascal per

Metre62.3

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

36 m2.69 Pascal per

Metre96.8

9 Approximate Duct Fittings20 % of Duct

pressure drop48

10Duct & Fittings safety

factor10 % safety factor 118.30

1301.1

H-M2-45-24-HDE-11

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 13: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

18 m.2.69 Pascal per

Metre48.4

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

53 m2.69 Pascal per

Metre142.6

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

32 m2.69 Pascal per

Metre86.1

9

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

75 m2.69 Pascal per

Metre201.8

10 Approximate Duct Fittings20 % of Duct

pressure drop95.7

11Duct & Fittings safety

factor10 % safety factor 146.90

1616.5

H-M2-45-24-HDE-14

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 14: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

50 m.2.69 Pascal per

Metre134.5

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

6.5 m2.69 Pascal per

Metre17.5

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

75 m2.69 Pascal per

Metre201.8

9 Approximate Duct Fittings20 % of Duct

pressure drop70.8

10Duct & Fittings safety

factor10 % safety factor 132.00

1451.6

H-M2-45-24-HDE-13

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 15: Static Pressure

FAN DUTY : 0.382 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised

Volume Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.69 Pascal per

Metre (horizontal)

20 m.2.69 Pascal per

Metre53.8

7

Approximate Ducting

Length, 2.69 Pascal per

Metre (vertical )

4.5 m2.69 Pascal per

Metre12.1

8

Approximate Ducting

Length, 2.69 Pascal per

Metre ( horizontal )

12 m2.69 Pascal per

Metre32.3

9 Approximate Duct Fittings20 % of Duct

pressure drop19.6

10Duct & Fittings safety

factor10 % safety factor 101.30

1114.1

H-M2-45-24-HDE-03

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 16: Static Pressure

FAN DUTY : 0.575 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 2.37 Pascal per

Metre (horizontal)

90 m.2.37 Pascal per

Metre213.3

7

Approximate Ducting

Length, 2.37 Pascal per

Metre (vertical )

50 m2.37 Pascal per

Metre118.5

8

Approximate Ducting

Length, 2.37 Pascal per

Metre ( horizontal )

42 m2.37 Pascal per

Metre99.5

9

Approximate Ducting

Length, 2.37 Pascal per

Metre ( horizontal )

35 m2.37 Pascal per

Metre82.9

10 Approximate Duct Fittings20 % of Duct

pressure drop102.8

11Duct & Fittings safety

factor10 % safety factor 151.20

1663.2

H-M2-45-24-HDE-12

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 17: Static Pressure

FAN DUTY : 0.844 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

28 m.0.91 Pascal per

Metre25.5

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

23 m0.91 Pascal per

Metre20.9

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

25 m0.91 Pascal per

Metre22.8

9

Approximate Ducting

Length, 1.17 Pascal per

Metre ( horizontal )

15 m1.17 Pascal per

Metre17.6

10 Approximate Duct Fittings20 % of Duct

pressure drop17.4

11Duct & Fittings safety

factor10 % safety factor 99.90

1099.1

H-M2-45-24-HDE-21

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 18: Static Pressure

FAN DUTY : 0.634 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

25 m.0.91 Pascal per

Metre22.8

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

64 m0.91 Pascal per

Metre58.2

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

14 m0.91 Pascal per

Metre12.7

9

Approximate Ducting

Length, 1.31 Pascal per

Metre ( horizontal )

13 m1.31 Pascal per

Metre17

10 Approximate Duct Fittings20 % of Duct

pressure drop22.14

11Duct & Fittings safety

factor10 % safety factor 102.78

1130.6

H-M2-45-24-HDE-23

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 19: Static Pressure

FAN DUTY : 0.634 m³/s

Item Description Size / QuantityUnit App. Pressure

Drop (Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

17.5 m.0.91 Pascal per

Metre15.9

7

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

65 m0.91 Pascal per

Metre59.2

8

Approximate Ducting

Length, 0.91 Pascal per

Metre ( vertical )

14 m0.91 Pascal per

Metre12.7

9

Approximate Ducting

Length, 1.31 Pascal per

Metre ( horizontal )

13 m1.31 Pascal per

Metre17

10 Approximate Duct Fittings20 % of Duct

pressure drop20.96

11Duct & Fittings safety

factor10 % safety factor 102.08

1122.8

H-M2-45-24-HDE-22

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 20: Static Pressure

FAN DUTY : 0.844 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

19 m.0.91 Pascal per

Metre17.3

7

Approximate Ducting

Length, 0.18 Pascal per

Metre (horizontal)

3 m0.18 Pascal per

Metre0.5

8

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizonta )

81 m0.65 Pascal per

Metre52.7

9

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizontal )

66 m0.65 Pascal per

Metre42.9

10

Approximate Ducting

Length, 0.65 Pascal per

Metre ( horizontal )

13 m0.65 Pascal per

Metre8.5

11

Approximate Ducting

Length, 0.65 Pascal per

Metre (vertical )

33 m0.65 Pascal per

Metre21.5

12 Approximate Duct Fittings20 % of Duct

pressure drop28.7

13Duct & Fittings safety

factor10 % safety factor 106.71

1173.8

H-M2-45-24-HDE-16

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 21: Static Pressure

FAN DUTY : 0.951 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 0.91 Pascal per

Metre (horizontal)

27 m.0.91 Pascal per

Metre24.6

7

Approximate Ducting

Length, 0.95 Pascal per

Metre (horizontal)

52 m0.95 Pascal per

Metre49.4

8

Approximate Ducting

Length, 0.95 Pascal per

Metre ( horizonta )

25 m0.95 Pascal per

Metre23.8

9

Approximate Ducting

Length, 0.95 Pascal per

Metre ( horizontal )

37 m0.95 Pascal per

Metre35.2

10

Approximate Ducting

Length, 0.95 Pascal per

Metre ( vertical )

50 m0.95 Pascal per

Metre47.5

11

Approximate Ducting

Length, 0.81 Pascal per

Metre (horizontal )

13 m0.81 Pascal per

Metre10.5

12 Approximate Duct Fittings20 % of Duct

pressure drop38.2

13Duct & Fittings safety

factor10 % safety factor 112.42

1236.6

H-M2-45-24-HDE-19

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 22: Static Pressure

FAN DUTY : 0.899 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

Total App. Pressure

Drop (Pascal)

1Fume Hood Total Pressure

Drop1 No. 500 500

3Phoenix Flow Control

Valve1 No: 250 250

3Manual/ Motorised Volume

Control Dampers1 No. 30 30

4 Back draft damper 1 No. 35 35

5 Sound Attenuator 1 No. 80 80

6

Approximate Ducting

Length, 1.93 Pascal per

Metre (horizontal)

10.5 m.1.93 Pascal per

Metre20.3

7

Approximate Ducting

Length, 1.93 Pascal per

Metre (vertical)

23 m1.93 Pascal per

Metre44.4

8

Approximate Ducting

Length, 1.93 Pascal per

Metre ( horizontal )

35 m1.93 Pascal per

Metre67.6

9

Approximate Ducting

Length, 1.93 Pascal per

Metre ( horizontal )

30 m1.93 Pascal per

Metre57.9

10

Approximate Ducting

Length, 1.93 Pascal per

Metre ( vertical )

27 m1.93 Pascal per

Metre52.1

11

Approximate Ducting

Length, 1.31 Pascal per

Metre (horizontal )

13 m1.31 Pascal per

Metre17

12 Approximate Duct Fittings20 % of Duct

pressure drop51.8

13Duct & Fittings safety

factor10 % safety factor 120.61

1326.7

H-M2-45-24-HDE-18

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Total ESP For the fan

Page 23: Static Pressure

FAN DUTY : 1.864 m³/s

Item Description Size / Quantity

Unit App.

Pressure Drop

(Pascal)

1 Grille (450x600) 1 No. 50

2350x200 Ducting, 0.32

Pa/m6 m

0.32 Pascal per

Metre

3Phoenix Flow Control

Valve1 No: 250 Pascal

4 Sound Attenuator 1 No. 80

5200x150 Ducting, 0.95

Pa/m4.5 m

0.95 Pascal per

Metre

5300x250 Ducting, 0.47

Pa/m1.6 m

0.47 Pascal per

Metre

6 300x250 Ducting, 0.8 Pa/m 95 m0.8 Pascal per

Metre

7Motorised Fire Dampers/

Fire damper4 No. 30 Pascal

8300x250 Ducting, 0.93

Pa/m4 m

0.93 Pascal per

Metre

8 300x250 Ducting, 1.5 Pa/m 5 m1.5 Pascal per

Metre

7 Motorised Fire Dampers 1 No. 30 Pascal

8 300x250 Ducting, 2.2 Pa/m 2.5 m2.2 Pascal per

Metre

8 300x250 Ducting, 2.9 Pa/m 11 m2.9 Pascal per

Metre

8400x300 Ducting, 1.87

Pa/m4 m

1.87 Pascal per

Metre

8 400x300 Ducting, 2.3 Pa/m 2 m2.3 Pascal per

Metre

8 400x300 Ducting, 3.2 Pa/m 20 m3.2 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (vertical)14 m

2.88 Pascal per

Metre

H-PL-45-21-HDE-03A / 03B

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Page 24: Static Pressure

8500x300 Ducting, 2.88

Pa/m (horizontal diversion)25 m

2.88 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (vertical)32.5 m

2.88 Pascal per

Metre

8500x300 Ducting, 2.88

Pa/m (horizontal)13 m

2.88 Pascal per

Metre

8400x400 Ducting, 2.88

Pa/m (horizontal)7 m

2.88 Pascal per

Metre

NRD 1 No: 35 Pascal

12 Approximate Duct Fittings20 % of Duct

pressure drop

13Duct & Fittings safety

factor10 % safety factor

Total ESP For the fan

Page 25: Static Pressure

Total App. Pressure

Drop (Pascal)

50

1.9

250

80

4.3

0.8

76

30

3.7

7.5

30

5.8

31.9

7.4

4.6

64

40.32

H-PL-45-21-HDE-03A / 03B

Static Pressure Calculations

Exhaust of Contaminated Lab fume air to outside.

Page 26: Static Pressure

72

93.6

37.5

20.2

35

94.3

104.08

1144.9

Page 27: Static Pressure

Sn Fan Ref. Location Flow Rate (m³/s)

1 H-M2-45-24-HDE-01 Roof 0.382

2 H-M2-45-24-HDE-02 Roof 0.382

3 H-M2-45-24-HDE-03 Roof 0.382

4 H-M2-45-24-HDE-04 Roof 0.382

5 H-M2-45-24-HDE-05 Roof 0.382

6 H-M2-45-24-HDE-06 Roof 0.382

7 H-M2-45-24-HDE-07 Roof 0.382

8 H-M2-45-24-HDE-08 Roof 0.382

9 H-M2-45-24-HDE-09 Roof 0.382

10 H-M2-45-24-HDE-10 Roof 0.382

11 H-M2-45-24-HDE-11 Roof 0.382

12 H-M2-45-24-HDE-12 Roof 0.575

13 H-M2-45-24-HDE-13 Roof 0.382

14 H-M2-45-24-HDE-14 Roof 0.382

15 H-M2-45-24-HDE-15 Roof 0.741

16 H-M2-45-24-HDE-16 Roof 0.846

17 H-M2-45-24-HDE-17 Roof 0.951

18 H-M2-45-24-HDE-18 Roof 0.899

19 H-M2-45-24-HDE-19 Roof 0.951

20 H-M2-45-24-HDE-20 Roof 1.269

21 H-M2-45-24-HDE-21 Roof 0.846

22 H-M2-45-24-HDE-22 Roof 0.634

23 H-M2-45-24-HDE-23 Roof 0.634