Page 1
FAN DUTY : 1.269 m³/s
Item Description Size / QuantityUnit App. Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1 Fume Hood Total Pressure Drop 1 No. 500 500
2 Phoenix Flow Control Valve 1 No: 250 250
3 Manual/ Motorised Volume Control Dampers 1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6 Approximate Ducting Length,0.37 Pascal per Metre 3.5 m. 0.37 Pascal per Metre 1.3
7Approximate Ducting Length, 1.93 Pascal per
Metre14.2 m 1.93 Pascal per Metre 27.5
8Approximate Ducting Length, 2.51 Pascal per
Metre ( horizontal 87+35+31.5 )153.5 m 2.51 Pascal per Metre 385.3
9Approximate Ducting Length, 2.51 Pascal per
Metre ( vertical riser )48 m 2.51 Pascal per Metre 120
10 Approximate Duct Fittings 20 % of Duct pressure drop 106.8
11 Duct & Fittings safety factor 10 % safety factor 153.60
1689.50
Static Pressure Calculations
H-M2-45-24-HDE-20
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 2
FAN DUTY : 0.741 m³/s
Item Description Size / QuantityUnit App. Pressure Drop
(Pascal)
Total App. Pressure Drop
(Pascal)
1 Fume Hood Total Pressure Drop 1 No. 500 500
3 Phoenix Flow Control Valve 1 No: 250 250
3Manual/ Motorised Volume Control
Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6Approximate Ducting Length,0.54
Pascal per Metre (horizontal)25.2 m. 0.54 Pascal per Metre 13.6
7Approximate Ducting Length, 0.19
Pascal per Metre (horizontal )8.5 m 0.19 Pascal per Metre 1.6
8Approximate Ducting Length, 0.49
Pascal per Metre ( horizontal )4.5 m 0.49 Pascal per Metre 2.2
9Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )60 m 0.91 Pascal per Metre 54.6
10Approximate Ducting Length, 0.91
Pascal per Metre ( vertical )25 m 0.91 Pascal per Metre 22.8
11Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )67 m 0.91 Pascal per Metre 61
Approximate Ducting Length, 0.91
Pascal per Metre ( horizontal )13 m 0.91 Pascal per Metre 11.8
12 Approximate Duct Fittings 20 % of Duct pressure drop 36.2
13 Duct & Fittings safety factor 10 % safety factor 109.80
1208.6
H-M2-45-24-HDE-15
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 3
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
58 m.2.69 Pascal per
Metre156
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
20 m2.69 Pascal per
Metre53.8
9 Approximate Duct Fittings20 % of Duct
pressure drop55.4
11Duct & Fittings safety
factor10 % safety factor 122.70
1350.2
H-M2-45-24-HDE-01
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 4
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
62 m.2.69 Pascal per
Metre166.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
22 m2.69 Pascal per
Metre59.2
9 Approximate Duct Fittings20 % of Duct
pressure drop58.7
10Duct & Fittings safety
factor10 % safety factor 124.70
1371.7
H-M2-45-24-HDE-02
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 5
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
20 m.2.69 Pascal per
Metre53.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
38 m2.69 Pascal per
Metre102.2
9 Approximate Duct Fittings20 % of Duct
pressure drop44.7
10Duct & Fittings safety
factor10 % safety factor 116.30
1279.3
H-M2-45-24-HDE-04
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 6
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m2.69 Pascal per
Metre131.8
9 Approximate Duct Fittings20 % of Duct
pressure drop55.9
10Duct & Fittings safety
factor10 % safety factor 122.40
1353.1
H-M2-45-24-HDE-05
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 7
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m2.69 Pascal per
Metre131.8
9 Approximate Duct Fittings20 % of Duct
pressure drop55.9
10Duct & Fittings safety
factor10 % safety factor 123.10
1353.8
H-M2-45-24-HDE-06
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 8
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre67.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m2.69 Pascal per
Metre131.8
9 Approximate Duct Fittings20 % of Duct
pressure drop55.9
10Duct & Fittings safety
factor10 % safety factor 123.10
1353.8
H-M2-45-24-HDE-07
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 9
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m2.69 Pascal per
Metre131.8
9 Approximate Duct Fittings20 % of Duct
pressure drop54.9
10Duct & Fittings safety
factor10 % safety factor 122.40
1347.1
H-M2-45-24-HDE-08
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 10
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
49 m2.69 Pascal per
Metre131.8
9 Approximate Duct Fittings20 % of Duct
pressure drop54.9
10Duct & Fittings safety
factor10 % safety factor 122.40
1347.1
H-M2-45-24-HDE-09
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 11
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
34 m.2.69 Pascal per
Metre91.5
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
36 m2.69 Pascal per
Metre96.8
9 Approximate Duct Fittings20 % of Duct
pressure drop50.1
10Duct & Fittings safety
factor10 % safety factor 119.60
1315.3
H-M2-45-24-HDE-10
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 12
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
30 m.2.69 Pascal per
Metre80.7
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
25 m2.69 Pascal per
Metre62.3
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
36 m2.69 Pascal per
Metre96.8
9 Approximate Duct Fittings20 % of Duct
pressure drop48
10Duct & Fittings safety
factor10 % safety factor 118.30
1301.1
H-M2-45-24-HDE-11
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 13
FAN DUTY : 0.382 m³/s
Item Description Size / QuantityUnit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
18 m.2.69 Pascal per
Metre48.4
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
53 m2.69 Pascal per
Metre142.6
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
32 m2.69 Pascal per
Metre86.1
9
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
75 m2.69 Pascal per
Metre201.8
10 Approximate Duct Fittings20 % of Duct
pressure drop95.7
11Duct & Fittings safety
factor10 % safety factor 146.90
1616.5
H-M2-45-24-HDE-14
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 14
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
50 m.2.69 Pascal per
Metre134.5
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
6.5 m2.69 Pascal per
Metre17.5
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
75 m2.69 Pascal per
Metre201.8
9 Approximate Duct Fittings20 % of Duct
pressure drop70.8
10Duct & Fittings safety
factor10 % safety factor 132.00
1451.6
H-M2-45-24-HDE-13
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 15
FAN DUTY : 0.382 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised
Volume Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.69 Pascal per
Metre (horizontal)
20 m.2.69 Pascal per
Metre53.8
7
Approximate Ducting
Length, 2.69 Pascal per
Metre (vertical )
4.5 m2.69 Pascal per
Metre12.1
8
Approximate Ducting
Length, 2.69 Pascal per
Metre ( horizontal )
12 m2.69 Pascal per
Metre32.3
9 Approximate Duct Fittings20 % of Duct
pressure drop19.6
10Duct & Fittings safety
factor10 % safety factor 101.30
1114.1
H-M2-45-24-HDE-03
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 16
FAN DUTY : 0.575 m³/s
Item Description Size / QuantityUnit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 2.37 Pascal per
Metre (horizontal)
90 m.2.37 Pascal per
Metre213.3
7
Approximate Ducting
Length, 2.37 Pascal per
Metre (vertical )
50 m2.37 Pascal per
Metre118.5
8
Approximate Ducting
Length, 2.37 Pascal per
Metre ( horizontal )
42 m2.37 Pascal per
Metre99.5
9
Approximate Ducting
Length, 2.37 Pascal per
Metre ( horizontal )
35 m2.37 Pascal per
Metre82.9
10 Approximate Duct Fittings20 % of Duct
pressure drop102.8
11Duct & Fittings safety
factor10 % safety factor 151.20
1663.2
H-M2-45-24-HDE-12
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 17
FAN DUTY : 0.844 m³/s
Item Description Size / QuantityUnit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
28 m.0.91 Pascal per
Metre25.5
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
23 m0.91 Pascal per
Metre20.9
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
25 m0.91 Pascal per
Metre22.8
9
Approximate Ducting
Length, 1.17 Pascal per
Metre ( horizontal )
15 m1.17 Pascal per
Metre17.6
10 Approximate Duct Fittings20 % of Duct
pressure drop17.4
11Duct & Fittings safety
factor10 % safety factor 99.90
1099.1
H-M2-45-24-HDE-21
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 18
FAN DUTY : 0.634 m³/s
Item Description Size / QuantityUnit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
25 m.0.91 Pascal per
Metre22.8
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
64 m0.91 Pascal per
Metre58.2
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
14 m0.91 Pascal per
Metre12.7
9
Approximate Ducting
Length, 1.31 Pascal per
Metre ( horizontal )
13 m1.31 Pascal per
Metre17
10 Approximate Duct Fittings20 % of Duct
pressure drop22.14
11Duct & Fittings safety
factor10 % safety factor 102.78
1130.6
H-M2-45-24-HDE-23
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 19
FAN DUTY : 0.634 m³/s
Item Description Size / QuantityUnit App. Pressure
Drop (Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
17.5 m.0.91 Pascal per
Metre15.9
7
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
65 m0.91 Pascal per
Metre59.2
8
Approximate Ducting
Length, 0.91 Pascal per
Metre ( vertical )
14 m0.91 Pascal per
Metre12.7
9
Approximate Ducting
Length, 1.31 Pascal per
Metre ( horizontal )
13 m1.31 Pascal per
Metre17
10 Approximate Duct Fittings20 % of Duct
pressure drop20.96
11Duct & Fittings safety
factor10 % safety factor 102.08
1122.8
H-M2-45-24-HDE-22
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 20
FAN DUTY : 0.844 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
19 m.0.91 Pascal per
Metre17.3
7
Approximate Ducting
Length, 0.18 Pascal per
Metre (horizontal)
3 m0.18 Pascal per
Metre0.5
8
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizonta )
81 m0.65 Pascal per
Metre52.7
9
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizontal )
66 m0.65 Pascal per
Metre42.9
10
Approximate Ducting
Length, 0.65 Pascal per
Metre ( horizontal )
13 m0.65 Pascal per
Metre8.5
11
Approximate Ducting
Length, 0.65 Pascal per
Metre (vertical )
33 m0.65 Pascal per
Metre21.5
12 Approximate Duct Fittings20 % of Duct
pressure drop28.7
13Duct & Fittings safety
factor10 % safety factor 106.71
1173.8
H-M2-45-24-HDE-16
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 21
FAN DUTY : 0.951 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 0.91 Pascal per
Metre (horizontal)
27 m.0.91 Pascal per
Metre24.6
7
Approximate Ducting
Length, 0.95 Pascal per
Metre (horizontal)
52 m0.95 Pascal per
Metre49.4
8
Approximate Ducting
Length, 0.95 Pascal per
Metre ( horizonta )
25 m0.95 Pascal per
Metre23.8
9
Approximate Ducting
Length, 0.95 Pascal per
Metre ( horizontal )
37 m0.95 Pascal per
Metre35.2
10
Approximate Ducting
Length, 0.95 Pascal per
Metre ( vertical )
50 m0.95 Pascal per
Metre47.5
11
Approximate Ducting
Length, 0.81 Pascal per
Metre (horizontal )
13 m0.81 Pascal per
Metre10.5
12 Approximate Duct Fittings20 % of Duct
pressure drop38.2
13Duct & Fittings safety
factor10 % safety factor 112.42
1236.6
H-M2-45-24-HDE-19
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 22
FAN DUTY : 0.899 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
Total App. Pressure
Drop (Pascal)
1Fume Hood Total Pressure
Drop1 No. 500 500
3Phoenix Flow Control
Valve1 No: 250 250
3Manual/ Motorised Volume
Control Dampers1 No. 30 30
4 Back draft damper 1 No. 35 35
5 Sound Attenuator 1 No. 80 80
6
Approximate Ducting
Length, 1.93 Pascal per
Metre (horizontal)
10.5 m.1.93 Pascal per
Metre20.3
7
Approximate Ducting
Length, 1.93 Pascal per
Metre (vertical)
23 m1.93 Pascal per
Metre44.4
8
Approximate Ducting
Length, 1.93 Pascal per
Metre ( horizontal )
35 m1.93 Pascal per
Metre67.6
9
Approximate Ducting
Length, 1.93 Pascal per
Metre ( horizontal )
30 m1.93 Pascal per
Metre57.9
10
Approximate Ducting
Length, 1.93 Pascal per
Metre ( vertical )
27 m1.93 Pascal per
Metre52.1
11
Approximate Ducting
Length, 1.31 Pascal per
Metre (horizontal )
13 m1.31 Pascal per
Metre17
12 Approximate Duct Fittings20 % of Duct
pressure drop51.8
13Duct & Fittings safety
factor10 % safety factor 120.61
1326.7
H-M2-45-24-HDE-18
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Total ESP For the fan
Page 23
FAN DUTY : 1.864 m³/s
Item Description Size / Quantity
Unit App.
Pressure Drop
(Pascal)
1 Grille (450x600) 1 No. 50
2350x200 Ducting, 0.32
Pa/m6 m
0.32 Pascal per
Metre
3Phoenix Flow Control
Valve1 No: 250 Pascal
4 Sound Attenuator 1 No. 80
5200x150 Ducting, 0.95
Pa/m4.5 m
0.95 Pascal per
Metre
5300x250 Ducting, 0.47
Pa/m1.6 m
0.47 Pascal per
Metre
6 300x250 Ducting, 0.8 Pa/m 95 m0.8 Pascal per
Metre
7Motorised Fire Dampers/
Fire damper4 No. 30 Pascal
8300x250 Ducting, 0.93
Pa/m4 m
0.93 Pascal per
Metre
8 300x250 Ducting, 1.5 Pa/m 5 m1.5 Pascal per
Metre
7 Motorised Fire Dampers 1 No. 30 Pascal
8 300x250 Ducting, 2.2 Pa/m 2.5 m2.2 Pascal per
Metre
8 300x250 Ducting, 2.9 Pa/m 11 m2.9 Pascal per
Metre
8400x300 Ducting, 1.87
Pa/m4 m
1.87 Pascal per
Metre
8 400x300 Ducting, 2.3 Pa/m 2 m2.3 Pascal per
Metre
8 400x300 Ducting, 3.2 Pa/m 20 m3.2 Pascal per
Metre
8500x300 Ducting, 2.88
Pa/m (vertical)14 m
2.88 Pascal per
Metre
H-PL-45-21-HDE-03A / 03B
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Page 24
8500x300 Ducting, 2.88
Pa/m (horizontal diversion)25 m
2.88 Pascal per
Metre
8500x300 Ducting, 2.88
Pa/m (vertical)32.5 m
2.88 Pascal per
Metre
8500x300 Ducting, 2.88
Pa/m (horizontal)13 m
2.88 Pascal per
Metre
8400x400 Ducting, 2.88
Pa/m (horizontal)7 m
2.88 Pascal per
Metre
NRD 1 No: 35 Pascal
12 Approximate Duct Fittings20 % of Duct
pressure drop
13Duct & Fittings safety
factor10 % safety factor
Total ESP For the fan
Page 25
Total App. Pressure
Drop (Pascal)
50
1.9
250
80
4.3
0.8
76
30
3.7
7.5
30
5.8
31.9
7.4
4.6
64
40.32
H-PL-45-21-HDE-03A / 03B
Static Pressure Calculations
Exhaust of Contaminated Lab fume air to outside.
Page 26
72
93.6
37.5
20.2
35
94.3
104.08
1144.9
Page 27
Sn Fan Ref. Location Flow Rate (m³/s)
1 H-M2-45-24-HDE-01 Roof 0.382
2 H-M2-45-24-HDE-02 Roof 0.382
3 H-M2-45-24-HDE-03 Roof 0.382
4 H-M2-45-24-HDE-04 Roof 0.382
5 H-M2-45-24-HDE-05 Roof 0.382
6 H-M2-45-24-HDE-06 Roof 0.382
7 H-M2-45-24-HDE-07 Roof 0.382
8 H-M2-45-24-HDE-08 Roof 0.382
9 H-M2-45-24-HDE-09 Roof 0.382
10 H-M2-45-24-HDE-10 Roof 0.382
11 H-M2-45-24-HDE-11 Roof 0.382
12 H-M2-45-24-HDE-12 Roof 0.575
13 H-M2-45-24-HDE-13 Roof 0.382
14 H-M2-45-24-HDE-14 Roof 0.382
15 H-M2-45-24-HDE-15 Roof 0.741
16 H-M2-45-24-HDE-16 Roof 0.846
17 H-M2-45-24-HDE-17 Roof 0.951
18 H-M2-45-24-HDE-18 Roof 0.899
19 H-M2-45-24-HDE-19 Roof 0.951
20 H-M2-45-24-HDE-20 Roof 1.269
21 H-M2-45-24-HDE-21 Roof 0.846
22 H-M2-45-24-HDE-22 Roof 0.634
23 H-M2-45-24-HDE-23 Roof 0.634