ASHRAE Standard 90.1- 2010 Hugh Crowther P. Eng Hugh Crowther P. Eng Director at Large
Jan 14, 2015
ASHRAE Standard 90.1-
2010
Hugh Crowther P. EngHugh Crowther P. Eng
Director at Large
Agenda• ASHRAE Standards
Development
– Jargon
• Std 90.1 layout• Std 90.1 layout
• Review of changes to each section
• How Improvements are evaluated
• Questions
Compliance Approaches
Envelope
HVAC
Building SystemsBuilding Systems Compliance OptionsCompliance Options
Prescriptive Option
HVAC
SHW
Power
Lighting
Other
Mandatory Provisions
Trade Off Option
Energy Cost Budget
Simplified
Compliance
Std 90.1 Sections
• Section 1: Purpose
• Section 2: Scope
• Section 3: Definitions
• Section 7: Service Water Heating
• Section 8: Power
• Section 9: Lighting• Section 3: Definitions
• Section 4: Admin and
Enforcement
• Section 5: Building Envelope
• Section 9: Lighting
• Section 10: Other Equipment
• Section 11: Energy Cost Budget
(ECB) method
• Section 12: Normative References
• Appendices
Std 90.1 -2010• Significant Savings
over 2004 version
• Site energy savings is in kWh
National Weighted Energy
With Receptacle Loads
Without Receptacle Loads
in kWh
• Site energy cost savings is in $
– Std 90.1 evaluates itself
on energy cost
• How did they do that?
Energy Savings
Loads Loads
Site Energy
25.5% 32.6%
Energy Cost
24.0% 30.1%
How did they do that?
30% Improvement
109 AddendaTPS Change
Lets talk about changes from 2007 version to the 2010 version
2004 20102007
17%
9%
3%
14%
11%Lighting 17%
Cooling 9%
Heating 21%
Ventilation 5%
Water Heating 9%
Refrigeration 3%
Change in Scope• Process (plug) loads
can now be included
• The TPS change allows the committee to write rules on plug loads if they deem it necessary
64%
Regulated
Section 2
21%
5%9%
3%
5%
3%
3%Electronics 5%
Computers 3%
Cooking 3%
Other 14%
Adjust to SEDS 11%
necessary
• If the Std does not specifically address a process load, then it is unregulated
Source: Building Energy Data Book 2009, Table 3.1.4
25%
Unregulated
A 30% total site reduction would require a 47% reduction in regulated loads
A 50% total site reduction would require a 78% reduction in regulated loads
Building Envelope• Building envelope
requirements change based on location
• Approximately 20 changes between
Section 5
changes between 2007 and 2010 versions
• Informative Appendix F lists changes by addenda
Building Envelope• Continuous air barrier
for most buildings
– 5.4.3.1
– Material leakage rate
under 0.004 cfm/ft² @
Section 5
under 0.004 cfm/ft² @
0.3 in. w.c.
– Assembly leakage rate
under 0.04 cfm/ft² @ 0.3
in. w.c.
Goal: Minimize infiltration by 83% and HVAC energy usage by 40% - NIST
Building Envelope• Tightened air leakage
rates for fenestration and doors
– 5.4.3.2
Section 5
– 1 cfm/ft² @ 1.57 PSF for
doors
– 0.06 cfm/ft² @ 1.57 PSF
for curtain wall
Goal: Minimize infiltration
Building Envelope• Vestibule
Requirements changed
– 5.4.3.4
Section 5
• Insulation requirements for metal buildings more stringent
– 5.5.3.1 and 5.5.3.2
Building Envelope• Cool roofs required in
some climate zones
– 5.5.3.1.1
– Zones 1,2 and3
Section 5
– Solar reflectance = 0.55
– SRI = 64 (ASTM E1980)
Goal: Minimize roof loads
Building Envelope• Vertical fenestration must
have more area on south side than on either east or west side– 5.5.4.5
Section 5
– 5.5.4.5
• Large spaces with tall ceilings must have minimum skylight area and automatic daylighting controls– 5.5.4.2.3
Building Envelope• Exceptions are
provided to SHGC requirements for dynamic glazing
5.5.4.4.1
Section 5
– 5.5.4.4.1
HVAC Systems• Process cooling can now be
included– Scope change
• New data center requirements– Added CRAC units based on ASHRAE
Section 6
– Added CRAC units based on ASHRAE
Std 127
– Introduced sensible Coefficient of
Performance (SCOP)
– 6.4.1.1, 6.5.1, Table 6.8.1k
– A/C equipment primarily serving
computer rooms must meet Table
6.8.1kExample of process loads now being
considered
HVAC Systems• Upgraded efficiencies
to most HVAC equipment categories
– 6.8.1 tables
Section 6
• New term for Unitary equipment
– Integrated Energy
Efficiency Ratio (IEER)
– Brings focus to part load
efficiency rather than just
full load performance Goal: Promote Part load performance
HVAC Systems• Increased efficiency for water-
cooled and evaporatively cooled air conditioners/heatpumps
– 3 to 5% more stringent as of June 2011
Section 6
– IEER increase from 5 to 13%
– Two position valves required on water
cooled unitary equipment (WSHPs)
– Pumps larger than 5 hp serving W/C
unitary equipment need VFD
HVAC Systems• Water to water heat pumps
– Added to standard
– Efficiencies based on application
(Watersource, ground water, ground
source)
Section 6
source)
HVAC Systems• Increased efficiency for PTACs
and PTHPs as of Oct 2012
– Created standard (16 x 42 size) and non
standard efficiency tables
– Standard size for new construction
Section 6
– Standard size for new construction
– Non standard size for replacement
(existing wall sleeves)
Standard
Non -standard
HVAC Systems• Two path compliance for
chillers (addendum M)– Both paths have a full and part
load target
– Path A targets high full load
Section 6
– Path A targets high full load performance
– Path B targets high part load performance
– Chillers with glycol now under Std 90.1
– Glycol chiller performance criteria based on just water when checking with 90.1 Goal: Promote full operating range
performance
HVAC Systems• Recent Chiller Interpretations
– Where customers request more
strict conditions than required in
AHRI 550/590, the chillers will be
compared to Std 90.1 at standard
Section 6
compared to Std 90.1 at standard
rating conditions.
– Power usage shall be measured at
the line side of starter or VFD.
– Starter and VFD losses must be
included in chiller performance
HVAC Systems• Chiller scope expansion
– Air and water cooled positive
displacement chillers now included
in Std 90.1 with LFT > 32 °F
• Non standard chiller equation
Section 6
• Non standard chiller equation
– 6.4.1.2.1
– Covers chillers with LFT ≥ 36 °F
– Covers chillers with CWT ≤ 115 °F
– 20 °F to 80 °F of lift
• About 98% of centrifugal chillers now covered by Std 90.1
Goal: Avoid gaming by picking 85.1 °F CWT
HVAC Systems• VRF systems added
– Based on new AHRI 1230 test standard
– The IEER levels will increase in 2012
Section 6
in 2012
• New rating system for water to water HX– 6.4.1.4
– Encouraging manufacturers to certify their products
– No performance targets yet
HVAC Systems• Restrictions on pump
head sizing and pipe sizing
– 6.4.2.2
Section 6
– Need to calculate the
pressure drop through
piping and components
for critical path
• Pipe sizing as per table 6.5.4.5
– Flow rate by Dia. And
hours operation
Goal: Make sure pumps are not oversized
HVAC Systems• Pump differential
pressure flow control shall
– Not exceed pressure
required for 110% of
Section 6
required for 110% of
design flow through heat
exchanger
– Shall reset down during
part load until one
control valve is nearly
open.
– 6.5.4.1
HVAC Systems• Hydronic systems
other than unitary systems must have VFD over 10 hp
6.5.4.1
Section 6
– 6.5.4.1
– No caveats any more
– No pump curve riding etc
Goal: Promote Variable flow systems
HVAC Systems• VAV requirement for DX and
chilled water systems that serve single zone– 6.4.3.10
– Chilled water systems ≥ 5 hp fan
Section 6
– Chilled water systems ≥ 5 hp fan
motors must be variable flow
– 2 spd or VFD
– As of Jan. 1, 2012 DX systems >
110kBtu/h must be able to reduce
fan speed 2/3 or less at 50% load
– 2 spd or VFD
• Fan power ratings based on constant volume power limits
Goal: Promote fan power savings
HVAC Systems• Increased insulation
requirements for pipes and ducts
– 6.4.4
Section 6
• New requirements for radiant panel systems
– 6.4.4
– Ineffective panel areas
shall have r-3.5
HVAC Systems• Limitations on centrifugal
fan cooling towers– 6.5.5.3
– 1100 gpm or greater, must meet axial fan efficiency
Section 6
axial fan efficiency
– 38.2 USgpm per fan hp
– Exempt if they are ducted
• New tower category for closed circuit cooling towers– Avoid confusion with Fluid
coolers
Goal: Promote fan power savings
HVAC Systems• Economizer changes
– 6.5.1
• With more stringent envelopes and higher internals loads,
Section 6
internals loads, cooling required at lower ambients– Promotes economizers
• Economically justified in all but Zones 1a and ab.
Goal: Promote economizers. The improvements in building envelopes make economizers economically justified in more climate zones
HVAC Systems• Sizes 54 kBtu/h and larger
require economizers
– Individual unit (not system)
– Air or water economizers
Section 6
– Economizer is 1st stage cooling
– 2nd stage mechanical cooling
– Economizer goes to minimum
when high limit reached
– High limit settings by region
• 12 exceptions
HVAC Systems• Economizer exception for
computer rooms– 6.5.1j
– Total design below 3,000 kBtu/h and not served by
Section 6
kBtu/h and not served by chiller plant
– Total design below 600 kBtu/h and is served by chiller plant
– Local authority prohibits cooling towers
– Less than 600 kBtu/h computer load being added to existing building
HVAC Systems• Water economizer sizing
for computer rooms
– 6.5.1.2
– Load must be met at 40 °F db/
35°F wb with evaporative type
Section 6
35°F wb with evaporative type
water economizers
– Load must be met at 35 °F db
with dry type water
economizers
HVAC Systems• Changes to damper
leakage requirements
– 6.5.1.1.4
– Comply with changes to
Section 6
– Comply with changes to
controls section
– Motorized intake and
exhaust dampers in most
climate zones
Goal: Limit infiltration during off hours and slow down heat up or cool down
HVAC Systems• Dynamic ventilation
control for multi zone VAV systems following Std 62.1 Appendix A
Section 6
Appendix A– 6.5.3.3
– VAV systems with DDC controls shall lower ventilation air below design rate in response to ventilation efficiency
HVAC Systems• Supply air reset
– Removed from 1999
version
– Back in 2010 version
– 6.5.3.4
Section 6
– 6.5.3.4
• Goal is to reset SAT up to max level when boxes at minimum flow
– Fan penalty should be
offset by reheat savings
– Can be based on outdoor
air reset
Goal: Mechanical cooling savings that more than offset additional fan work
HVAC Systems• SAT Reset exceptions
– Climate zones 1a, 2a,3a
– Systems that prevent
reheating, re-cooling or
mixing
Section 6
mixing
– Systems where 75% of
reheat comes from recovery
or solar.
HVAC Systems• Additional requirements
for reheat/re-cool minimums– 20% zone design peak supply
rate during deadband and
Section 6
rate during deadband and 50% zone peak design rate for full heating
– Meant to help with stratification in heating from ceiling diffusers
• Overheat heating SAT limited to 20 °F above temperature set point
Goal: Reduce heating air flow to minimum level where overhead distribution is still effective
HVAC Systems• Climatic based
requirement for energy recovery– 6.5.6
– Based on climate zone, size and % outdoor air
Section 6
and % outdoor air
• New requirements for garage and kitchen hood ventilation– 6.4.3.4.5 and 6.5.7
– Garage systems shall modulate to 50% based on contaminants Goal: Fan power savings in garages and
kitchen exhaust systems
HVAC Systems• New requirements for
lab exhaust
– 6.5.7.2
– Need to be VAV above
5000 cfm
Section 6
5000 cfm
Service Water Heating• No changes from
2007 version
Section 7
Power• Half of all convenience
power outlets shall be controlled such that power is turned off when space is not occupied
Section 8
not occupied– 8.4.2
• Efficiency requirements added for dry type transformers– 8.1.2
– Reflect 2005 Federal requirements Goal: Std 90.1 in line with Federal codes
Lighting• Increased documentation
requirements– 9.7
• Lighting alteration requirements now– Take effect at 10%
Section 9
– Take effect at 10% replacement
– Include exterior areas
– Include renovations even when it is just lamp/ballast replacement
– Require compliance with auto shut requirements
– 9.1.2
Lighting• Changes to lighting
power density (LPD) values – tables 9.5.1 and 9.6.1
• Adjustment Factor added
Section 9
• Adjustment Factor added for tall spaces– 9.6.3
• Additional LPD allowed when using certain non mandatory controls– 9.6.2c
Lighting• Allowances for retail
lighting have been reduced
– 9.6.2b
Section 9
• Multi-use spaces now use multiple LPD valves
– 9.6.1
Lighting• Exterior lighting now
broken into 5 zones based on ambient light levels
9.6.1
Section 9
– 9.6.1
– Undeveloped park area
to high traffic
commercial zone
Lighting• Light control changes include
(9.4)– Bi level control
– Auto shut off based on occupancy required in more spaces
– Certain required controls must be
Section 9
– Certain required controls must be manual/auto on to no more than 50% power
– Deleted 5000 ft² threshold for auto shutoff
– Functional testing of some lighting controls now required (9.4.4)
– Daylight harvesting required in certain situations 5.5.4.2.3
Other Equipment• Control requirements
for water pressure booster pump systems
10.4.2
Section 10
– 10.4.2
– Variable flow design
– Don’t dead head a pump
Goal: Avoid pump work during low or no flow requirement periods
Other Equipment• Requirements added
to limit lighting and fan power in elevator cabs and de-energize during stand by mode
Section 10
during stand by mode– 10.4.3
• Motor efficiency tables changed for motors built after 12/19/2010– Table 10.8a,b,c
Goal: Keep Std 90.1 in line with Federal motor requirements
ECB Method• No changes to 2010
version
• Case sample provided in previous
Section 11
Large Office
provided in previous Users manual has been deleted
– Can be downloaded
from ASHRAE
Secondary School
Performance Rating Method• Can use Appendix G to rate
buildings for other than compliance with Std 90.1– LEED
– Appendix G is nota compliance path
• A building complies with Std
Appendix G
High-rise Apartment
• A building complies with Std 90.1 (section 11) if the proposed design energy cost ≤ energy cost budget
• In Appendix G Proposed building performance ≥ baseline building performance
Hospital
Performance Rating Method• Now normative part of the
Standard whereas it was informative
• Heated only storage spaces have been added
Appendix G
High-rise Apartment
spaces have been added– G3.1.1
• 2 rules added to ventilation rules for baseline HVAC systems– G3.1.2.6
Hospital
Questions?