Top Banner
ASHRAE Standard 90.1- 2010 Hugh Crowther P. Eng Hugh Crowther P. Eng Director at Large
53
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Standard 90.1-2010 Update

ASHRAE Standard 90.1-

2010

Hugh Crowther P. EngHugh Crowther P. Eng

Director at Large

Page 2: Standard 90.1-2010 Update

Agenda• ASHRAE Standards

Development

– Jargon

• Std 90.1 layout• Std 90.1 layout

• Review of changes to each section

• How Improvements are evaluated

• Questions

Page 3: Standard 90.1-2010 Update

Compliance Approaches

Envelope

HVAC

Building SystemsBuilding Systems Compliance OptionsCompliance Options

Prescriptive Option

HVAC

SHW

Power

Lighting

Other

Mandatory Provisions

Trade Off Option

Energy Cost Budget

Simplified

Compliance

Page 4: Standard 90.1-2010 Update

Std 90.1 Sections

• Section 1: Purpose

• Section 2: Scope

• Section 3: Definitions

• Section 7: Service Water Heating

• Section 8: Power

• Section 9: Lighting• Section 3: Definitions

• Section 4: Admin and

Enforcement

• Section 5: Building Envelope

• Section 9: Lighting

• Section 10: Other Equipment

• Section 11: Energy Cost Budget

(ECB) method

• Section 12: Normative References

• Appendices

Page 5: Standard 90.1-2010 Update

Std 90.1 -2010• Significant Savings

over 2004 version

• Site energy savings is in kWh

National Weighted Energy

With Receptacle Loads

Without Receptacle Loads

in kWh

• Site energy cost savings is in $

– Std 90.1 evaluates itself

on energy cost

• How did they do that?

Energy Savings

Loads Loads

Site Energy

25.5% 32.6%

Energy Cost

24.0% 30.1%

Page 6: Standard 90.1-2010 Update

How did they do that?

30% Improvement

109 AddendaTPS Change

Lets talk about changes from 2007 version to the 2010 version

2004 20102007

Page 7: Standard 90.1-2010 Update

17%

9%

3%

14%

11%Lighting 17%

Cooling 9%

Heating 21%

Ventilation 5%

Water Heating 9%

Refrigeration 3%

Change in Scope• Process (plug) loads

can now be included

• The TPS change allows the committee to write rules on plug loads if they deem it necessary

64%

Regulated

Section 2

21%

5%9%

3%

5%

3%

3%Electronics 5%

Computers 3%

Cooking 3%

Other 14%

Adjust to SEDS 11%

necessary

• If the Std does not specifically address a process load, then it is unregulated

Source: Building Energy Data Book 2009, Table 3.1.4

25%

Unregulated

A 30% total site reduction would require a 47% reduction in regulated loads

A 50% total site reduction would require a 78% reduction in regulated loads

Page 8: Standard 90.1-2010 Update

Building Envelope• Building envelope

requirements change based on location

• Approximately 20 changes between

Section 5

changes between 2007 and 2010 versions

• Informative Appendix F lists changes by addenda

Page 9: Standard 90.1-2010 Update

Building Envelope• Continuous air barrier

for most buildings

– 5.4.3.1

– Material leakage rate

under 0.004 cfm/ft² @

Section 5

under 0.004 cfm/ft² @

0.3 in. w.c.

– Assembly leakage rate

under 0.04 cfm/ft² @ 0.3

in. w.c.

Goal: Minimize infiltration by 83% and HVAC energy usage by 40% - NIST

Page 10: Standard 90.1-2010 Update

Building Envelope• Tightened air leakage

rates for fenestration and doors

– 5.4.3.2

Section 5

– 1 cfm/ft² @ 1.57 PSF for

doors

– 0.06 cfm/ft² @ 1.57 PSF

for curtain wall

Goal: Minimize infiltration

Page 11: Standard 90.1-2010 Update

Building Envelope• Vestibule

Requirements changed

– 5.4.3.4

Section 5

• Insulation requirements for metal buildings more stringent

– 5.5.3.1 and 5.5.3.2

Page 12: Standard 90.1-2010 Update

Building Envelope• Cool roofs required in

some climate zones

– 5.5.3.1.1

– Zones 1,2 and3

Section 5

– Solar reflectance = 0.55

– SRI = 64 (ASTM E1980)

Goal: Minimize roof loads

Page 13: Standard 90.1-2010 Update

Building Envelope• Vertical fenestration must

have more area on south side than on either east or west side– 5.5.4.5

Section 5

– 5.5.4.5

• Large spaces with tall ceilings must have minimum skylight area and automatic daylighting controls– 5.5.4.2.3

Page 14: Standard 90.1-2010 Update

Building Envelope• Exceptions are

provided to SHGC requirements for dynamic glazing

5.5.4.4.1

Section 5

– 5.5.4.4.1

Page 15: Standard 90.1-2010 Update

HVAC Systems• Process cooling can now be

included– Scope change

• New data center requirements– Added CRAC units based on ASHRAE

Section 6

– Added CRAC units based on ASHRAE

Std 127

– Introduced sensible Coefficient of

Performance (SCOP)

– 6.4.1.1, 6.5.1, Table 6.8.1k

– A/C equipment primarily serving

computer rooms must meet Table

6.8.1kExample of process loads now being

considered

Page 16: Standard 90.1-2010 Update

HVAC Systems• Upgraded efficiencies

to most HVAC equipment categories

– 6.8.1 tables

Section 6

• New term for Unitary equipment

– Integrated Energy

Efficiency Ratio (IEER)

– Brings focus to part load

efficiency rather than just

full load performance Goal: Promote Part load performance

Page 17: Standard 90.1-2010 Update

HVAC Systems• Increased efficiency for water-

cooled and evaporatively cooled air conditioners/heatpumps

– 3 to 5% more stringent as of June 2011

Section 6

– IEER increase from 5 to 13%

– Two position valves required on water

cooled unitary equipment (WSHPs)

– Pumps larger than 5 hp serving W/C

unitary equipment need VFD

Page 18: Standard 90.1-2010 Update

HVAC Systems• Water to water heat pumps

– Added to standard

– Efficiencies based on application

(Watersource, ground water, ground

source)

Section 6

source)

Page 19: Standard 90.1-2010 Update

HVAC Systems• Increased efficiency for PTACs

and PTHPs as of Oct 2012

– Created standard (16 x 42 size) and non

standard efficiency tables

– Standard size for new construction

Section 6

– Standard size for new construction

– Non standard size for replacement

(existing wall sleeves)

Standard

Non -standard

Page 20: Standard 90.1-2010 Update

HVAC Systems• Two path compliance for

chillers (addendum M)– Both paths have a full and part

load target

– Path A targets high full load

Section 6

– Path A targets high full load performance

– Path B targets high part load performance

– Chillers with glycol now under Std 90.1

– Glycol chiller performance criteria based on just water when checking with 90.1 Goal: Promote full operating range

performance

Page 21: Standard 90.1-2010 Update

HVAC Systems• Recent Chiller Interpretations

– Where customers request more

strict conditions than required in

AHRI 550/590, the chillers will be

compared to Std 90.1 at standard

Section 6

compared to Std 90.1 at standard

rating conditions.

– Power usage shall be measured at

the line side of starter or VFD.

– Starter and VFD losses must be

included in chiller performance

Page 22: Standard 90.1-2010 Update

HVAC Systems• Chiller scope expansion

– Air and water cooled positive

displacement chillers now included

in Std 90.1 with LFT > 32 °F

• Non standard chiller equation

Section 6

• Non standard chiller equation

– 6.4.1.2.1

– Covers chillers with LFT ≥ 36 °F

– Covers chillers with CWT ≤ 115 °F

– 20 °F to 80 °F of lift

• About 98% of centrifugal chillers now covered by Std 90.1

Goal: Avoid gaming by picking 85.1 °F CWT

Page 23: Standard 90.1-2010 Update

HVAC Systems• VRF systems added

– Based on new AHRI 1230 test standard

– The IEER levels will increase in 2012

Section 6

in 2012

• New rating system for water to water HX– 6.4.1.4

– Encouraging manufacturers to certify their products

– No performance targets yet

Page 24: Standard 90.1-2010 Update

HVAC Systems• Restrictions on pump

head sizing and pipe sizing

– 6.4.2.2

Section 6

– Need to calculate the

pressure drop through

piping and components

for critical path

• Pipe sizing as per table 6.5.4.5

– Flow rate by Dia. And

hours operation

Goal: Make sure pumps are not oversized

Page 25: Standard 90.1-2010 Update

HVAC Systems• Pump differential

pressure flow control shall

– Not exceed pressure

required for 110% of

Section 6

required for 110% of

design flow through heat

exchanger

– Shall reset down during

part load until one

control valve is nearly

open.

– 6.5.4.1

Page 26: Standard 90.1-2010 Update

HVAC Systems• Hydronic systems

other than unitary systems must have VFD over 10 hp

6.5.4.1

Section 6

– 6.5.4.1

– No caveats any more

– No pump curve riding etc

Goal: Promote Variable flow systems

Page 27: Standard 90.1-2010 Update

HVAC Systems• VAV requirement for DX and

chilled water systems that serve single zone– 6.4.3.10

– Chilled water systems ≥ 5 hp fan

Section 6

– Chilled water systems ≥ 5 hp fan

motors must be variable flow

– 2 spd or VFD

– As of Jan. 1, 2012 DX systems >

110kBtu/h must be able to reduce

fan speed 2/3 or less at 50% load

– 2 spd or VFD

• Fan power ratings based on constant volume power limits

Goal: Promote fan power savings

Page 28: Standard 90.1-2010 Update

HVAC Systems• Increased insulation

requirements for pipes and ducts

– 6.4.4

Section 6

• New requirements for radiant panel systems

– 6.4.4

– Ineffective panel areas

shall have r-3.5

Page 29: Standard 90.1-2010 Update

HVAC Systems• Limitations on centrifugal

fan cooling towers– 6.5.5.3

– 1100 gpm or greater, must meet axial fan efficiency

Section 6

axial fan efficiency

– 38.2 USgpm per fan hp

– Exempt if they are ducted

• New tower category for closed circuit cooling towers– Avoid confusion with Fluid

coolers

Goal: Promote fan power savings

Page 30: Standard 90.1-2010 Update

HVAC Systems• Economizer changes

– 6.5.1

• With more stringent envelopes and higher internals loads,

Section 6

internals loads, cooling required at lower ambients– Promotes economizers

• Economically justified in all but Zones 1a and ab.

Goal: Promote economizers. The improvements in building envelopes make economizers economically justified in more climate zones

Page 31: Standard 90.1-2010 Update

HVAC Systems• Sizes 54 kBtu/h and larger

require economizers

– Individual unit (not system)

– Air or water economizers

Section 6

– Economizer is 1st stage cooling

– 2nd stage mechanical cooling

– Economizer goes to minimum

when high limit reached

– High limit settings by region

• 12 exceptions

Page 32: Standard 90.1-2010 Update

HVAC Systems• Economizer exception for

computer rooms– 6.5.1j

– Total design below 3,000 kBtu/h and not served by

Section 6

kBtu/h and not served by chiller plant

– Total design below 600 kBtu/h and is served by chiller plant

– Local authority prohibits cooling towers

– Less than 600 kBtu/h computer load being added to existing building

Page 33: Standard 90.1-2010 Update

HVAC Systems• Water economizer sizing

for computer rooms

– 6.5.1.2

– Load must be met at 40 °F db/

35°F wb with evaporative type

Section 6

35°F wb with evaporative type

water economizers

– Load must be met at 35 °F db

with dry type water

economizers

Page 34: Standard 90.1-2010 Update

HVAC Systems• Changes to damper

leakage requirements

– 6.5.1.1.4

– Comply with changes to

Section 6

– Comply with changes to

controls section

– Motorized intake and

exhaust dampers in most

climate zones

Goal: Limit infiltration during off hours and slow down heat up or cool down

Page 35: Standard 90.1-2010 Update

HVAC Systems• Dynamic ventilation

control for multi zone VAV systems following Std 62.1 Appendix A

Section 6

Appendix A– 6.5.3.3

– VAV systems with DDC controls shall lower ventilation air below design rate in response to ventilation efficiency

Page 36: Standard 90.1-2010 Update

HVAC Systems• Supply air reset

– Removed from 1999

version

– Back in 2010 version

– 6.5.3.4

Section 6

– 6.5.3.4

• Goal is to reset SAT up to max level when boxes at minimum flow

– Fan penalty should be

offset by reheat savings

– Can be based on outdoor

air reset

Goal: Mechanical cooling savings that more than offset additional fan work

Page 37: Standard 90.1-2010 Update

HVAC Systems• SAT Reset exceptions

– Climate zones 1a, 2a,3a

– Systems that prevent

reheating, re-cooling or

mixing

Section 6

mixing

– Systems where 75% of

reheat comes from recovery

or solar.

Page 38: Standard 90.1-2010 Update

HVAC Systems• Additional requirements

for reheat/re-cool minimums– 20% zone design peak supply

rate during deadband and

Section 6

rate during deadband and 50% zone peak design rate for full heating

– Meant to help with stratification in heating from ceiling diffusers

• Overheat heating SAT limited to 20 °F above temperature set point

Goal: Reduce heating air flow to minimum level where overhead distribution is still effective

Page 39: Standard 90.1-2010 Update

HVAC Systems• Climatic based

requirement for energy recovery– 6.5.6

– Based on climate zone, size and % outdoor air

Section 6

and % outdoor air

• New requirements for garage and kitchen hood ventilation– 6.4.3.4.5 and 6.5.7

– Garage systems shall modulate to 50% based on contaminants Goal: Fan power savings in garages and

kitchen exhaust systems

Page 40: Standard 90.1-2010 Update

HVAC Systems• New requirements for

lab exhaust

– 6.5.7.2

– Need to be VAV above

5000 cfm

Section 6

5000 cfm

Page 41: Standard 90.1-2010 Update

Service Water Heating• No changes from

2007 version

Section 7

Page 42: Standard 90.1-2010 Update

Power• Half of all convenience

power outlets shall be controlled such that power is turned off when space is not occupied

Section 8

not occupied– 8.4.2

• Efficiency requirements added for dry type transformers– 8.1.2

– Reflect 2005 Federal requirements Goal: Std 90.1 in line with Federal codes

Page 43: Standard 90.1-2010 Update

Lighting• Increased documentation

requirements– 9.7

• Lighting alteration requirements now– Take effect at 10%

Section 9

– Take effect at 10% replacement

– Include exterior areas

– Include renovations even when it is just lamp/ballast replacement

– Require compliance with auto shut requirements

– 9.1.2

Page 44: Standard 90.1-2010 Update

Lighting• Changes to lighting

power density (LPD) values – tables 9.5.1 and 9.6.1

• Adjustment Factor added

Section 9

• Adjustment Factor added for tall spaces– 9.6.3

• Additional LPD allowed when using certain non mandatory controls– 9.6.2c

Page 45: Standard 90.1-2010 Update

Lighting• Allowances for retail

lighting have been reduced

– 9.6.2b

Section 9

• Multi-use spaces now use multiple LPD valves

– 9.6.1

Page 46: Standard 90.1-2010 Update

Lighting• Exterior lighting now

broken into 5 zones based on ambient light levels

9.6.1

Section 9

– 9.6.1

– Undeveloped park area

to high traffic

commercial zone

Page 47: Standard 90.1-2010 Update

Lighting• Light control changes include

(9.4)– Bi level control

– Auto shut off based on occupancy required in more spaces

– Certain required controls must be

Section 9

– Certain required controls must be manual/auto on to no more than 50% power

– Deleted 5000 ft² threshold for auto shutoff

– Functional testing of some lighting controls now required (9.4.4)

– Daylight harvesting required in certain situations 5.5.4.2.3

Page 48: Standard 90.1-2010 Update

Other Equipment• Control requirements

for water pressure booster pump systems

10.4.2

Section 10

– 10.4.2

– Variable flow design

– Don’t dead head a pump

Goal: Avoid pump work during low or no flow requirement periods

Page 49: Standard 90.1-2010 Update

Other Equipment• Requirements added

to limit lighting and fan power in elevator cabs and de-energize during stand by mode

Section 10

during stand by mode– 10.4.3

• Motor efficiency tables changed for motors built after 12/19/2010– Table 10.8a,b,c

Goal: Keep Std 90.1 in line with Federal motor requirements

Page 50: Standard 90.1-2010 Update

ECB Method• No changes to 2010

version

• Case sample provided in previous

Section 11

Large Office

provided in previous Users manual has been deleted

– Can be downloaded

from ASHRAE

Secondary School

Page 51: Standard 90.1-2010 Update

Performance Rating Method• Can use Appendix G to rate

buildings for other than compliance with Std 90.1– LEED

– Appendix G is nota compliance path

• A building complies with Std

Appendix G

High-rise Apartment

• A building complies with Std 90.1 (section 11) if the proposed design energy cost ≤ energy cost budget

• In Appendix G Proposed building performance ≥ baseline building performance

Hospital

Page 52: Standard 90.1-2010 Update

Performance Rating Method• Now normative part of the

Standard whereas it was informative

• Heated only storage spaces have been added

Appendix G

High-rise Apartment

spaces have been added– G3.1.1

• 2 rules added to ventilation rules for baseline HVAC systems– G3.1.2.6

Hospital

Page 53: Standard 90.1-2010 Update

Questions?