ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
ST500M/H Series Intelligent Type Electric Motor Controller
2-17-2007 1/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Su Zhou Wan Long Group Co., Ltd.
Table of Contents
■ General Description of the Products -----------------------------------------------------------1
■ Products Characters-------------------------------------------------------------------------------2
■ Products Classification---------------------------------------------------------------------------6
■ Products Design & Type Selection ------------------------------------------------------------10
■ Perfect Motor Protection Functions------------------------------------------------------------11
■ Various Kinds of Motor Control Modes-------------------------------------------------------21
■ Rich Monitoring Functions of Motor Operation---------------------------------------------24
■ Operation, Maintenance And Management Functions of Motor---------------------------25
■ Communication Functions-----------------------------------------------------------------------26
■ Terminals Allocation & Its Application--------------------------------------------------------27
■ Installation & Outline Diagram-----------------------------------------------------------------31
■ Typical Wiring Diagram-------------------------------------------------------------------------34
■ Products Technical Parameters------------------------------------------------------------------38
■ ST500M/H Series Intelligent Type Motor Controller Ordering Specification Table----42
2-17-2007 2/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
General Descriptions of the Products
For more than 5 years in electric power, petrifaction, light industry, coal industry, paper industry, steel and other industries, more than 100 thousand ST500 intelligence type electric motor controllers have been put into AC motor protection and control operation, which have accumulated a great deal of practical experience in engineering. On this basis, the ST500M/H Series intelligence type AC motor controller, a new generation of enhanced high-performance with microprocessor technology have emerged as the time requires. Working with contactor, soft starter,plastic moulded case circuit-breaker, the production provides a complete set of special solution to the low voltage AC motor including control, protection, monitoring and bus communication, replacing thermal relay, thermal protector, leakage protector, under-voltage protector and other protectors, canceling time relay, auxiliary relay , CT , meter, control and selection switching, indicator lighting, programmable controller, transmitter and other added components, which make the product the ideal choice of intelligent MCC.
2-17-2007 3/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Products Characters
2-17-2007 4/43
Protection function
Starting overtime /starting over-currentOver Load Inverse time ProtectionOver CurrentTE Time ProtectionUnder Current ProtectionCurrent unbalance ProtectionEarthing ProtectionDigital value process Interlocking ProtectionOver/Under Voltage ProtectionPhase Sequence Fault LockingUnder Power ProtectionAnalog Value process Interlocking ProtectionTemperature ProtectionLeakage Current Protection
Motor Operation & Controlling
Function
Direct Start-upReversible Start-upY- ∆ Start-up Reactor voltage reducing Start-up Autotransformer Start-up Soft Start-up Anti Fluctuanting ElectricityShort time power off self Start-upElectrifying device Self Start-up
Measuring function
Three Phase CurrentsThree Phase VoltagesPower , Power Factor, FrequencyEnergyThermal CapacityCurrent Unbalance RateLeakage Current ValueThermal Resistance4~20mA input
Maintenance&Manageme
ntFunction
Present Running TimePresent Stopping TimeAccumulated Running TimeAccumulated Stopping TimeStarting-up CurrentStarting-up TimeNumber of operating TimesInput & Output status8 Faults Record Fault Time RecordRunning Status Indication
Com. Function
ModbusDouble ModbusProfibus-DPDevice-NetIndusry Ether Net
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Uses 16 bits high-performance industrial grade microprocessor special protocol chip,
ASIC, directly sampling three-phase AC currents, three-phase AC voltages, thermal
resistance, 4-20mA analog value, leakage current; computer Current Imbalance Rates,
earthing current.
Protection function: The product is provided with many kinds of protection function, only
needs a simple choice to realize the protection or on /off, alarm / trip;
Overload “time-current characteristic” meets the standard of GB/T14048.4 -2003, and
increases more tripping rank, to satisfy the heavy load starting requirements.
“The tE time protection” meets the hot over-load protection standard of GB3636.3-2000 for
the safety-enhanced explosion-proof motors.
“Temperature protection” monitors the situation of giving off heat of the motor directly,
meets the standard of GB/T14048.X -200X " Low-voltage switchgear and control device----
Control units for built-in thermal protection for rotating electrical machines ".
“Leakage current protection”: sampling through the special-purpose transformer, the
measurement sensitivity is higher, meeting the standard of GB/T14048.4 -2001 appendix B;
process control and interlocking protection: through the inputs of digital value and the
inputs 4-20mA analog value it can realize a part of the non-electrical control and
protection of process interlocking
The reasonable starting protection: monitoring the starting process automatically,
distinguishing the initial starting-up current and the fault current effectively, ensuring
that the protection function does not have the misoperation, at the same time, uses many
ways such as the starting overtime and the starting over-current protection to realize the
starting-up protection.
Resolve “the over-current blind area protection”, diagnosis the fault current size
automatically, monitor correctly the over-current fault appearing between the breaking
current of the contact device and the short circuit tripping current of plastic casing
circuit-breaker, and control the trip of plastic casing circuit-breaker, to make the
protection more reliable.
The PT broken line monitoring function, (may connect in the secondary contact of MCB),
distinguishing function of the PT broken line or under-voltage protection;
2-17-2007 5/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
“Fluctuanting electricity” function: Guarantees that the phenomenon of short-time
fluctuanting of the electricity dose not affect the continuity of production for technological
process.
Less Voltage /Lost Voltage Re-starting function: after the main circuit cutting out power
in short-time or supply the power switching over , it can realize the time sharing
sequential starting according to the preset parameters .
Measuring parameters are complete: including current, voltage, power and electrical
energy parameters. The Precision of Current and voltage may reach 0.5 grade.
The transmitter function is stronger: For the internal setting of the 4-20mA analog value
output.It may select many kinds of electric value (current, voltage, power or electrical
energy), and the scope is adjustable;
The control mode is complete : internal setting of the control modes of direct, reversible,
Y-∆, resistor and Autotransformer reducing voltage start, soft start and transducer
starting co-ordination, it only needs the simple choice to realize the different control
function logic transformation, their flexibility and the versatility are very strong;
It has the choice function of operation jurisdiction for“two positions” or “four positions”;
Testing function:It may perform testing operation before the Swicth is being closed
Remember the 8 faults relevant parameters and information: It can record the year, the
month, the day, the hour, the minute, and the second when 8 breakdowns occur , and the
relevant information and parameters .
The maintenance & management of the controller is convenient, it can display the
breakdown parameters, the alarming information, the condition indication, the motor
operating information, the contact device operation life etc, it is advantageous for the
fault analysis, the productive efficiency statistics and the reasonable choice for repairing ;
Integrative design, with the optimization design of protection, monitoring control, and
communication function,it may substitute the ampere meter, the current transformer, the
thermal relay, the leakage protection relay, the transmitting instrument, the push-button,
indicator light etc
The display and indication is intuitionist, it uses Chinese liquid-crystal display, directly
display and indicates each kind of parameter, information and condition;
2-17-2007 6/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
The multiway relay output function, 7 relays output, 3 control relays (R3 is
independent,can be used for tripping of plastic casing circuit-breaker), 4 signal relays, the
control relay’s contact may directly control AC380 contact device load, also may directly
control DC contact device load;
The multiway digital input function: 12 circuit of digital input with power supply, the
external power supply for ST500M is AC220V, for ST500H is DC220V/DC110V;
The standard communication interface, it may choose several protocols, and it may
choose double communication interfaces to realize redundancy of communication
interface;
The modular structure, the main body, the mutual inductor module, the display module,
the accessories combination etc. make it more convenient, more economical and more
rationalized;
The external dimensions is more reasonable, it may be installed in 1/4 drawers.
2-17-2007 7/43
MNS、GCK、GCS、GHK、GWL。。。
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Product Classifications
Product composing
The ST500M/H series controller is composed of two parts :the main body and the special-
purpose current transformer module. The external dimensions of main body are unified, the
special-purpose mutual inductor has three kind of frame sizes:100A, 250A, 820A. The ST522B
display module, ZT30/100 special-purpose leakage CT, ST-9 power supply module etc.the TM
surge arrester etc. are Optional accessories.
ST500M/H Category Frame
current
Current Range Optional Accessories
100A 2A:0.5 A -2 A
5A:1 A -5 A
6.3A:1.6 A -6.3 A
25A:6.3A -25 A
100A:25A -100 A
ST522B display module
When connected with ST500M/H,it can
realize measuring display, control and
operation, also can see about information and
accomplish parameter setting
2-17-2007 8/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
250A 250A:63A-250A
820A 500A:125A-500A
820A:200A-820A
Product type
The product is divided into two kinds: ST500M, ST500H. Their main functions are shown in
the next table:
Classification Function description Applicable scope functions to be selected and matched
2-17-2007 9/43
ZT30/100.special leakage current transformer Available when leakage current protection function is selected The
current Range of ZT30 is 500mA ( 50-500 ) ;
Tate of is ZT100 1000mA(100-1000).
ST-9 Power supply Module It is for ST500M,Only it is used for realizing
“Anti electricity fluctuantion” , less voltage and lost voltage functions.It can maintain 9s power
TM surge arresterto improve the life span ti is connected to the two sides of contactor
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
ST500M Standard Protection
Measuring and controlling
Functions(Note ①)
AC controlling Relay
Output (Note⑤)
AC Auxiliary Power
supply(Note⑥)
AC Power supply
is AC
Voltage Function(Note ②)
Leakage current Protecting
Function(Note ③)
Temperature Protection function
tE time Protection function ( Note
④)
4-20mA Input Protection Function
4-20mA analog value Output
Com. Function(Note ⑦)
ST500H Standard Protection
Measuring and controlling
Functions
DC controlling Relay
Output(Note ⑤)
AC, DC Double circuit
Auxiliary Power
supply(Note ⑥)
Control Power
supply is DC
Note : The standard protection ① and Monitoring , And controling functions includes mainly:
Protection function:overload protection,under load protection, over-current protection(stalled), starting-up over-current protection(jammed), the starting acceleration overtime protection, current imbalance phase protection(lacking), earthing protection, external fault alarming, and external fault triping;
Monitoring content: three-phase current, three-phase current imbalance rates, the earth
current, the motor running status, fault information, the alarming information, thermal
capacity;
Note②: After selecting the“voltage function”, the protection function will be increased:with Under voltage protection, over voltage protection, under power protection, phase sequence fault locking function. Monitoring content will be increased: Three-phase voltage, frequency, power factor, active power, kilowatt-hour;Note③: The earthing protection function with the sum of internal three-phase current vectors
and the leakage electricity protection function which is realized by the additional special-
purpose leakage current transformer must be selected alternatively, when selects and matches
“the leakage protection function”, the earthing protection will be function automaticly
withdrawn.
2-17-2007 10/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Note ④: It can be used in continuous running working, including easy to start-up or the starts not frequently start-up process, which it cannot appear obvious additional temperature rise, and which can be used in over load inverse protection motor with safety enhanced explosion.Note⑤: For the ST500H product its relay output uses 3 DC control relays (DC220V, 3A,
DC110V, 5A) + 4 signal relays (resistant AC250V, 3A), it is applicable in control the make-and-
break of DC220V/DC110V control circuit. For the ST500M, relay outputs: 3 AC control relays
(resistant type AC250V, 8A) + 4 signal relays (resistant type AC250V, 3A).
Note⑥: The ST500H product uses the double-circuit power supply: From Ua, Un to input the
AC220 auxiliary working power fromUa.Un And input the DC220V/DC110V auxiliary
working power supply from A1(+)A2(-).The ST500M product uses the input of AC220
auxiliary working power supply, from A1(+) and A2(-).
Note⑦: ST500M/H all may select and match the communication interfaces,to realize
communication functions of several protocols, the last digital of ST500 denotes the
communication mode: the ST502 indicating provided with the Profibus-DP interface, ST503
indicating provided with the MODBUS interface, ST504 indicating provided with the
DeviceNet interface, ST505 indicating provided with the double MODBUS interface, ST506
indicating provided with the industry Ethernet interface.
Product design &Type Selection
2-17-2007 11/43
6. 3A
5A
2A
250A
100A
500A
25A
1
2
5
4
6
3
ST □ M / H - □ - □ - □
820A
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
For example, “ST503MA-5A-VM2”,indicate Direct start-up mode motor controller, The
provided with control power supply and auxiliary working power supply all of AC220V, rated
current is 5A,and with has MODBUS communication interface, voltage function and analog
value Output.
The Installation manner is flexible
The product satisfies with the commonly used of installation GCS, GCK, GHK168, MNS, GZT etc. including 1/4 drawer set counters and various kinds of control box, the product is of modular structure, fixed manner and flexible.
Perfect motor protection function
The controller carries out the judgment and operation for each kind of operating
condition and the gathering of electric quantity data in the process of motor operation, and
2-17-2007 12/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
can realize the overload, under load, the starting-up over-current(stalled), the over-current
(jammed), current imbalance (lacks phase) protection, the earthing/Leakage, starting-up
overtime etc various kinds of reliable and precise protections, so as to guarantee the
production security and operating continuity.
Engineering data of the controller
function item contents
Mutual Inductor
Rated Value
In 2A,5A, 25A,100A,250A,500A,820A
Leakage
eletricity Mutual
Inductor Rated
Value
I∆nm 0.5A ,1A
Motor setting
Current Range
Ie 2A(0.5A-2A),5A(1A-5A) ,25A(5A-25A),100A(25A-
100A),250A(50A-250A),500A(125A-
500A),800A(200A-820A)Start-up overtime
protection
Start-up time 0.5-60s
Underload
protection
Setting value
range
20%Ie-100%Ie+OFF,OFF means the under load
protection is closed
Acting time 0.5s-50s
Executing mode Tripping/Alarming
Overload
protection
non-acting
characteristic
<1.05Ie no action in 2h
acting
characteristic
>1.2Ieload acting in 1h
Curve speed K 10 16 24 40 60 80 100 130 180 280 400 600
800 1000 1200 1300
Cold and hot
curve ratio
20%-100%
Cooling time 5 min-1080 min,step length 1 minpermitted start-up
thermal capacity
Way one/way two
Fault restoration
mode
automatic/man act
Start-up over-
current
protection
Setting value
range100%Ie-contact device allowable breaking current
+OFF,continuous setting, OFF is the close of Starting-up over-current
protection
Acting time 0.5 s -50s
2-17-2007 13/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
over-current
protection mode
Tripping/ alarming
over-current
protection
Setting value
range100%Ie-contact device allowable breaking
current+OFF,continuous setting,OFF is the close of over-current protection function
Acting time 0.5-50s
over-current
protection mode
Tripping, alarming
tE time protection tE tripping time
under the
multiples of
starting-up time
1-15s
Protection mode Stopping
current
imbalance
protection
Setting value
range(5%-60%)+OFF,OFF is the close of imbalance protection
Acting time 0.5-50s
imbalance
protection mode
Tripping/ alarming
Earthing
protection
Setting value
range30% Ie~100% Ie +OFF ,OFF is the close of the function
delay time in start-up 0s~60.00s,step length 0.02sdelay time in running 0s~60.00s,step length 0.02scutting modulus C 1.5~6+OFF,step length 0.5executing mode tripping/alarming
leakage current
protection
Setting value
range
10% IΔnm~100% IΔnm +OFF,OFF is the close of the
function
delay time in start-up 0s~60.00s,0.02s step length
delay time in running 0s~60.00s,0.02s step lengthexecuting mode tripping/alarming
Under voltage
protection
Acting voltage (75%-95%)Ue+off OFF is the close of the under voltage function
Acting time 0.1S-60s,step length 0.1s
Acting mode Tripping/alarming
over voltage
protection
Acting voltage (105%-150%)Ue+off OFF is the close of the over voltage function
Acting time 0.1S-50s,step length 0.1sActing mode Tripping/alarming
Under power
protection(2)
Setting value
range(20%~95%)Pn+off
Acting time 1s~60s,step length 1sexecuting mode tripping/alarming
2-17-2007 14/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
temperature
protection(3)
executing mode tripping/alarming
Thermistor type Type Monitor/PT100/PTC/NTC
Acting resistance
setting value0.1kΩ~30kΩ(when PTC > return resistance setting value)
return resistance
setting value0.1kΩ~30kΩ(when NTC > Action resistance setting value)
Acting time Fixed on 1s
Phase sequence
locking
Acting value
setting
enable/disable
executing mode locking
External
faul(process
interlocking
protection)
Acting time 0.1s~60.0sexecuting mode tripping/alarming
analog value input
protection
Setting value
range
4-20mA
Acting time 0.1s~60.0sexecuting mode tripping/alarming
Contact device
separating
current
Setting value
range600%~1000% I e +OFF, off denotes not limited
Under
voltage/lost
voltage
restarting
function
Restarting
comeback voltage(75%-95%)Us+OFF
Self restarting
function of
electrifying delay
time
Self restarting
time of
electrifying
0.1S-60s
Overload protection
Management of frequentlystarting-up motor
○ Indicate start-up command
● Indicate stop command
Note:in the special circumstancein order to make motor continuousrunning, it may first eliminate the thermal capacity of
2-17-2007 15/43
100%
0
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
the memory forcefully,andimmediately start-up the motor.
The hot memory function is of vital significance to the situation of needing to start-up the motor frequently. The controller simulates the thermal capacity of the motor under various kind of running status, and monitors the situation of motor giving off heat in real-time, protected the motor re-starting-up effectively under the superheat condition, which can both use the motor under the maximum limit, and guarantee the security of the motor, so that can guarantee the continuous operation of the motor. The chart shows the thermal capacity schematic diagram for the frequently starting-up operation, only when the thermal capacity cools belowthe “prohibition” line of the chart then the signal of being ready can be sent outfor starting-up, permit to start the motor oncemore.
"The prohibition" thermal capacity is divided into two kinds, one kind with solid thermal capacity decided as 15% (mode1); Another kind with thermal capacity of satisfying only one condition (mode) of the two kinds:(thermal capacity equaling to 100%- thermal capacity produced during last starting-up -2%) or 15%(mode2) .
For motor provided with the imbedded thermal resistance, it may select the controller provided with the hot protection function, which will monitor the motor’s real-time temperature to see whether it has already dropped under the limiting value which was allowed for restarting, if it is YES then the motor is allowed to be restarted, otherwise the motor cannot be restarted.
2-17-2007 16/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Overload current-time characteristicsThe overload protection provides 16 kinds of inverse-time protection characteristic curve,
including 10A, 10, 20, 30 etc many kinds of tripping classes, which may be chosen and may realize the heavy load starting-up function. The user may choose their needing inverse-time protection tripping curve according to the actual engineering situation , the protection characteristic curves will be kept in EEPROM of the controller after the computing the analog value. The action value, the restoration mode, the permitted restart-up thermal capacity, the protection acting curve, the cooling time, the cold and hot curve ratio all may be completely adjusted through the protection setting.
K coefficient
tripping class
satisfying the
stipulation of
standard
Modulate
d
current
multiples
1.0 1.2 1.5 7.2
130, 180 10A
Tripping
time
not
acting in
2h
acting in
1h
≤2min 2s<Tp≤10s
280 10 ≤4min 4s<Tp≤10s
400, 600 20 ≤8min 6s<Tp≤20s
800, 1000 30 ≤12min 9s<Tp≤30s
2-17-2007 17/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Overload protection current-time characteristic table
K
I/ Ie
10 16 24 40 60 80 100 130 180 280 400 600 800 1000 1200 1300
1.2 13.93 22.30 33.44 55.74 83.61
111.4
8
139.3
5
181.1
5
250.8
3
390.1
8
557.4
0
836.1
0
1114.
8
1393.
5
1672.
2
1950.
9
1.3 9.92 15.87 23.81 39.68 59.53 79.37 99.21
128.9
7
178.5
8
277.7
9
396.8
4
595.2
6
793.6
8
992.1
0
1190.
5
1388.
9
1.4 7.68 12.29 18.44 30.74 46.10 61.47 76.84 99.89
138.3
1
215.1
5
307.3
6
461.0
4
614.7
2
768.4
0
922.0
9
1075.
8
1.5 6.22 9.96 14.93 24.89 37.34 49.78 62.23 80.90
112.0
1
174.2
4
248.9
1
373.3
7
497.8
2
622.2
8
746.7
3
871.1
9
2 2.95 4.72 7.07 11.79 17.69 23.58 29.48 38.32 53.06 82.53
117.9
0
176.8
6
235.8
1
294.7
6
353.7
1
412.6
7
2.5 1.77 2.83 4.24 7.07 10.61 14.15 17.68 22.99 31.83 49.51 70.73
106.0
9
141.4
5
176.8
2
212.1
8
247.5
5
3 1.19 1.90 2.85 4.76 7.13 9.51 11.89 15.45 21.40 33.29 47.55 71.33 95.10
118.8
8
142.6
6
166.4
3
3.5 0.86 1.37 2.06 3.43 5.14 6.86 8.57 11.14 15.43 24.00 34.29 51.43 68.58 85.72
102.8
7
120.0
1
4 0.65 1.04 1.56 2.59 3.89 5.19 6.49 8.43 11.67 18.16 25.94 38.92 51.89 64.86 77.83 90.80
4.5 0.51 0.81 1.22 2.03 3.05 4.07 5.08 6.61 9.15 14.24 20.34 30.50 40.67 50.84 61.01 71.18
5 0.41 0.66 0.98 1.64 2.46 3.28 4.09 5.32 7.37 11.47 16.38 24.57 32.76 40.95 49.14 57.33
5.5 0.34 0.54 0.81 1.35 2.02 2.70 3.37 4.38 6.07 9.44 13.48 20.22 26.96 33.70 40.44 47.18
6 0.28 0.45 0.68 1.13 1.69 2.26 2.82 3.67 5.08 7.90 11.29 16.94 22.58 28.23 33.88 39.52
6.5 0.24 0.38 0.58 0.96 1.44 1.92 2.40 3.12 4.32 6.72 9.60 14.40 19.20 24.00 28.80 33.60
7 0.21 0.33 0.50 0.83 1.24 1.65 2.07 2.68 3.72 5.78 8.26 12.39 16.52 20.65 24.78 28.91
7.2 0.20 0.31 0.47 0.78 1.17 1.56 1.95 2.54 3.51 5.46 7.80 11.70 15.61 19.51 23.41 27.31
7.5 0.18 0.29 0.43 0.72 1.08 1.44 1.80 2.34 3.23 5.03 7.18 10.78 14.37 17.96 21.55 25.15
8
0.1
6 0.25 0.38 0.63 0.95 1.26 1.58 2.05 2.84 4.41 6.31 9.46 12.61 15.77 18.92 22.07
The table is corresponding to different K coefficient, show us the action time under different
multiples of overload current, unit: S
Overload fault restoration After the tripping by overload fault, it there are two restoration modes
provided: automatic and manual, which is easy for users to choose. For“The automatic restoration” mode, after the motor is tripping by overload fault, and the thermal capacity drops to below the permission starting thermal capacity, motor can be reseted automatically , it can start again without needding the restoration operation; For“The manual reset” mode, after the motor is tripping
2-17-2007 18/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
by overload fault,and the thermal capacity drops to below the permission starting thermal capacity, the fault cannot be cleared automatically, which needs to be reset manually, otherwise it will not allow the motor to start.
Under load protection
When the transmission belt breaks or the water pump running without any load, the motor can appear the phenomenon of under load, which will bring the equipment damage.
It can be judged whether the load protection it shall be started or not according to the mean value of the motor’s three-phase currents.
The over current protection (jammed)
It can be judged whether the motor has over current fault or not according to the ratio of the biggest line current observed value and the motor rate current value. If the observed value of current
is bigger than the set value, then starts the over
current protection.
Contactor’s breaking ability protection
The permited breaking ability of the common contactor is 6~8 times of the rated current. If the contactor is operated when the circuit current is surpassing the scope, it will bring the damage to the contactor, and will cause the accident further spreaded. When short current fault occurs, controller will decide whether to separate the contactor or not by judging the fault current of the motor circuit whether it is bigger than the contactor’s greatest breaking current. If the fault current is smaller than the contactor’s greatest breaking current, the protection is carrying out by separating contactor. If the fault current is bigger than the contactor’s greatest breaking current, the controller will not separate the contactor, but separate the MCCB through a special relay output to cut off the motor circuit, thus it can realize a more reliable protection. (note: the MCCB shall be provided with the shunt release,)
Starting-up over-current (to stop running protection)
In the starting-up process, it can be judged whether to start the over current protection or not according to the ratio of the biggest line current observed value and the motor rate current . This function only works in the starting-up
2-17-2007 19/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
process, it will be locked automatically and changed in to running after the starting-up is ended .
Starting-up acceleration overtime protection
After reaching the starting-up acceleration time, controller will decide whether to start the starting-up acceleration overtime protection or not by the judging the current of the motor circuit whether it is dropped to 110%the rate current. In view of the safety-enhanced motor, the starting-up time is not to surpass 1.7 time of the tE time. The chart shows when the starting-up time is T1, because the current hasn’t fallen to below 110%Ir1, it is judged as the starting-up acceleration overtime, the controller will send out the protection signal. When the starting-up acceleration time is T2, it may enter into the normal operation.
110%I r1
0
800%I r1
600%I r1
T2T1
I r1:
tE time protection
It is suitable to be used protecting in two kinds of safety-enhanced motors: easy to started , not frequently started and cannot appear the obvious additional temperature rise. tE time protection has the inverse time characteristic. When the motor reaches the stable temperature under the highest ambient temperature, and the rotor-stalled current appears, the controller will trip and separate the power supply in time tE to assur the motor winding not surpassing the limiting temperature.
The current imbalance protection
Calculates the three-phase imbalance rates separately, according to three-
phase most imbalance rate and the set value of the imbalance protection, we can
compare and judge whether to start the imbalance protection or not. PhaseLack
2-17-2007 20/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
is the limiting condition of the imbalance. When in phase lack, the imbalance
rate is 100%, and the product will be in protection immediately. The imbalance
rate computing formula is |I-Iav|/Iav. Iav is the mean value of the three-phase
current. when Iav is smaller than the motor’s full load current, the denominator
may be indicated by Ie.
Earthing protection
The earthing protection has the characteristics of definite time-limit and
inverse time-limit protection, its current signal depends on the internal mutual
inductor current vector sum, it is used to protect the short circuit between the
phase line and the motor metal enclosure.
Earthing operation current
characteristics: If the theoretics value ≤
0.5Iq, don’t act; If ≥ 1.0Iq, time-lag act.
Earthing delay time characteristic: T =
Ie/I *C * Tq.
Among which: T---- fault delay time;
Ie --- motor rated current;
I--- earthing fault current;
C---- cutting coefficient
Tq----- setting delay time of earthing
protection.
When C is setting “OFF”, the
characteristic will be definite- time
delay.(start-up delay time)
When C is setting between
1.5 and 6 ,the earthing protection characteristic will be divided into two
kinds:①.I/Iq ≥C.the actuating characteristic is definite-time delay.②.
I/Iq <C. the actuating characteristic is inverse time delay.
The error of the time-delay of the earthing protection :action time-delay error is
2-17-2007 21/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
within ±10%; the Inherent error of action time is 40ms.
Leakage electricity protection
Whether to start the earthing protection or not is determined by the result of
comparing the vector sum secondary current of the three-phase transformer and
the setting value of earthing protection.
The leakage electricity protection needs a special-purpose leakage current
transformer. Whether to start-up the leakage electricity protection function is
determined by the result of comparing the residual current of sampling and the
setting value of leakage protection.
The monitoring current sensitivity is higher when using leakage electricity
protection of sampling mode (it should be selected alternatively, standard
allocation is earthing protection).
Leakage electricity protection characteristics:
When ≤ 0.5IΔn, it doesn’t act, when ≥ 1.0IΔn , it will acts time-delay.
The current-time characteristic is shown in the following table.
time Delay typeNon-delay
time type
2 time
limiting
non-
driving
time s
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0
Residua
l
current
Large cutoff time s
IΔn 0.36 0.6 1.2 1.8 2.4 3 3.6 4.2 4.8 5.4 6 0.04
2IΔn 0.18 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 0.04
5IΔn 0.07
20.12
0.2
40.36
0.4
80.6
0.7
2
0.8
40.96
1.0
8
1.
20.04
10IΔn
Temperature protection
The temperature protection is mainly realized by measuring the actual
temperature of the motor. It is through the change of PTC/NTC thermal value of
2-17-2007 22/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
resistance buried in the motor to reflect the temperature change. The controllers
implement the temperature protection to the motor through monitoring the
thermal resistance which is buried in advance in the motor. The protection is an
instantaneous protection.
External fault alarming
External fault alarming is mainly realized through the digital input
connected to the corresponding Alarm DI of the controller. When the controller
receives the DI input, it starts-up the alarming function.
External fault trip
External fault trip is mainly realized through the digital input connected to
the corresponding Trip DI of the controller. When the controller receives the DI
input, it starts-up the trip function by delay action.
Under voltage protection
When the main circuit voltage is lower than the setting value, it will start the
under voltage protection, the under voltage protection can simultaneously
monitor the three-phase voltage signal, and The PT breakdown,which makes the
protection function more reasonable.
Over voltage protection
When the main circuit voltage is higher than the setting value, it will start-
up the over voltage protection; over voltage protection may monitor the three
phase voltage signal simultaneously.
Under power protection
When the motor is running with low load, sometimes it may be due to the
power factor is lower, and the motor current may not be very small. The
controller may implement the protection through measuring the motor’s power
of the motor and make the motor protection more perfect.
2-17-2007 23/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Phase sequence locking
When the controller detects the phase sequence fault of the motor, it will
lock the starting-up function, and protects the security of the motor equipment.
4-20mA analog value input protection
The external 4-20mA analog value is connected to the corresponding terminal of the controller; the controller decides whether to start this protection or not. by comparing the examined current value with the setting value. The function of the 4-20mA analog value input protection is mainly used in the interlocking protection of a part of non-electrical values etc.
Various kinds of motor control modes
Under the control of the program, the controller may realize various
different motor starting-up mode, and through the feedback of the contactor’s
auxiliary contact, it can monitor the running status of the contactor, in order to
guarantee the reliability of electric interlocking.
The various required control way of motor has been integrated in the
controller. For choosing of the control mode it needs to carry out the ST522B
display module only.
The control mode is optional: It may be the direct start-up, the reversible
start-up, the two speed start-up, the resistance voltage reducing star-upt, the Y/
△ start-up,the autotransformer Start, the soft starter control, or the transducer
control. Part of control modes may be divided into the open circuit/closed
circuit , two relays/three relays etc. (see the following table):
Start-up control mode open circuit Closed circuit Two relays Three relays
Y/△ start-up-up ★ ★ ★ ★
Autotransformer
Start-up★ ★ ★ ★
soft starter control ★ ★
the transducer control ★ ★
2-17-2007 24/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
“Anti-fluctuating electricity” function
After the voltage falling suddenly and the AC contactor is released, the
control contact of the controller does not open, when the power supply is
restored, the motor may go on running, does not need to carry on the starting-up
process. When ST500M is selected, it must select the ST-9 power supply module
simultaneously.
Self-restarting-up function
The controller has the self-restarting-up function after under voltage/lost
voltage. When it is in use, it will realize self-restarting-up. by different ways
according to the time length of the power supply cutting.
When the voltage restores before immediately restarting-up time, the
automatic restarting function will be carried out immediately, by using the
inertia of the motor running it, will continue to maintain the motor in the normal
operation.
When the voltage restores after immediately restarting-up time, but still
before the time-delay restarting-up setting time, the controller will make the
motor starting-up by grouping sequentially, according to the preset delay time.
so that it can prevent the monitor from creating the load to be overweight by
simultaneously starting-up.
When the voltage supply restores after time-delay restarting-up setting time,
the controller will not be able to carry out restarting-up function, if it is required
that the motor be operated,it needs the manual operation.
2-17-2007 25/43
T6
T6-T7T4-T5
T1-T2T3-T4
T1 T2 T3 T4 T5 T7
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Auto restart-up
After the function is in use, in the process of electrifying the controller, the
controller will realize the time sharing restarting-up according to the system of
establishing after the power supply restoring.
If the “Auto restart-up” function is established as “permission”, and the
restarting mode is established as “restoration”, the controller will judge whether
the system will restart-up or not according to the condition before power cutting
off. If the motor is in running condition before power cutting off, controller will
automatically start-up the motor according to the delay time set when
electrifying. If the “Auto restart-up” function is established as “permission”, and
the restarting-up mode is established as “starting-up”, the controller will start-
up the motor automatically according to the delay time set when electrifying
directly. If the “Auto restart-up” function is established as “prohibition”, then
the function will be exited.
Motor control purview
ST500M/H operation control purview has two modes. mode one is the "two
positions", mode two is the "four positions"
The"two positions" control purview includes two kinds of controls: “local
control” and “remote control”, by the controlling of terminal "9DI" it can realize
the transformation of control purview, ST522B display module may also carry
out the purview choice. when theST522B display module’s operation purview is
"local control" (key may be locked); the DI’s purview is optional for"local" or
"remote"; the purview of communication interface is "remote control".
The"four positions" control purview includes: key-press operation of
control of ST522B display module, remote"automatic control" of DI terminal
(PLC, DCS etc), "local control” of DI terminal at site(control box at site),
2-17-2007 26/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
"remote control" of the communication interface. The terminal "9DI and 10DI"
shall be combined to realize "four positions" purview transformation. In the
following table "0" means that the digital input is not put through, "1" means
that it is put through. ST522B display module also may also carry out the
purview choice.
operation purview position
transformation condition of the DI input
terminal
9DI 10DI
ST522B display module 0 0
automatic control 0 1
local control 1 0
remote control 1 1
Rich Monitoring FunctionsFor Motor Operation
The controller provides the rich information for motor operation, including
many kinds of parameters and conditions, the monitoring data can be
transmited to PC for centralized management through the field bus, and also can
be directly displayed through the ST522B display module installed on the panel
of the switch cabinet. These information include electric parameter, running
status etc.
monitoring item for motor operation
Standard allocation
Standard allocation +voltage function
Standard allocation
+temperature function
Standard allocation +leakage electricity function
motor running status ★ ★ ★ ★
faulting information ★ ★ ★ ★
Alarming information ★ ★ ★ ★
Three-phase current ★ ★ ★ ★
Three-phase voltage ★
Power factor ★
Active power ★
kilowatt-hour ★
frequency ★
2-17-2007 27/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
leakage current ★
Earthing current ★ ★ ★
thermal resistance value ★
Current imbalance rate ★ ★ ★ ★
thermal capacity ★ ★ ★ ★
Operation Maintenance and Management Function of Motor
The scopes and precision degrees of various kinds of measuring parameter
item range precision Measure way
currentAccuracy degree 0.5 step
True virtual value measure120% Ie~800%Ie ±2.5%
leakage current 0.1I△nm~1I△nm ±2% True virtual value measure
voltage accuracy degree 0.5 step True virtual value measure
frequency 45Hz~65Hz ±0.05Hz
Power factor -1~1 ±1.5%
power 0~1100kW ±4.5%
kilowatt-hour 0~65535kWh ±4.5%
thermal
resistance
PT100/A type monitor
machine±5%
thermal capacity 0-100% ±5%
Current
imbalance rate0-200% ±5%
Analog value
out put4-20mA ±1%
Analog value in
put4-20mA ±0.1mA
The controller may provide the real-time condition information, the fault
analysis parameter, which will richen the motor routine maintenance
2-17-2007 28/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
management information it, is advantageous for understanding the motor
operation situation, the making of statistics of production efficiency, and
understanding the operation life of the contactor. It can assists the administrative
person to realize the more economical and reasonable maintenance management.
Management
information
Operation number of times
Tripping times
overall running time
overall stopping time
The latest running time
The latest stopping time
Alarming information
the parameter and information of
the latest 8 times of fault
fault time mark
type, parameters of faults
the residual action delay time
running/fault/alarming indications
monitoring of input/output status
Fault time mark function
In order to facilitate the fault analysis, the controller is provided with the clock
function, which may record the time after the fault occuring, and facilitated the
user's supervisory work enormously.
Communication Functions
The motor controller can realizes the data transmission and communication
with the PC management system through communication interface. Basic
parameters of different field buses are shown in the following table, the concrete
content of the communication transmission is shown in “the Communication
Protocol of ST500M/H Intelligent type motor Controller ".
item ST503 ST502 ST504 ST505
Communication
ProtocolModbus Profibus-DP DeviceNet Modbus
2-17-2007 29/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Communication
speed
4.8/9.6/19.2/
38.4kbps0.5/1.5/3 /6 /12Mbps 125/250 /500kbps
4.8/9.6/19.2/38.
4kbps
Bus capability 255 127 64 255
Communication
interfaceRS 485 RS 485 CAN interface
RS
485,Double
net redundancy
Product Terminals
Allocation and
ItsApplication
Controller principle and
logical diagram
The controller can realize the intellectualized protection monitoring and
control function of the motor application through the collection of the three
phase AC current, the three phase AC voltage, the zero phase current, the
thermal resistance, the 4-20mA analog value, multiway switch digital value etc.
2-17-2007 30/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
carries out the operation, and processing by CPU after the process of signal
processing electric circuit, according to requirement of each kind of protection
characteristic, measuring data, control logic, data transmission etc, through the
indicating lamp, the display port, communication port, the control and the
protection output connection, the signal alarming output connection, the 4-20mA
analog quantity output etc many kinds of mode. The controller logic functional
block diagram is as follows:
2-17-2007 31/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
Controller Face Plate Terminals Allocation Scheme
Analog value input and output terminals
E1、E2 Leakage electricity signal input
AO+、AO- 4~20mA output
AI+、AI- 4~20mA input
R1、R2 Motor Buried thermal resistance input
L1、T1 A phase current signal input,L1 In,T1 out going line
L2、T2 B phase current signal input,L2 In,T2 out going line
L3、T3 C phase current signal input,L3 In,T3 out going line
Ua、Ub、Uc Three phase voltage signal inputController working power supply terminals allocation
ST500M:AC220V,inputs from A1(+)、A2(-)
ST500H:AC220V,inputs from Ua、Un;
DC auxiliary working power supply inputs from A1(+)、A2(-)Communication interface terminals allocation
2-17-2007 32/43
E2E1R2R1AO-AO+AI-AI+R2R1AI-AI+ AO-AO+ E2E1
B2A2SB1A1A2SB1 B2A1
21DI
1DIDICA2 -( )4DI3DI2DI
DI
7DI 6DI10DI9DI 8DI 5DI12DI11DI
Profibus-DP
A1 +( )
ST522B
Ua
AI AO
UnUc Ub PE6DO 7DO2COM4DO2DO3DO13DO2
DO
5DO1COM 1DO
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
A1、B1 RS485 Communication Interface 1,The function is the same as the nine holes D-type connector in the controller face plate (only Profibus-DP
equipped with D-type connector)
A2、B2 RS485 Communication Interface 2 S RS485 Communication shielding Line
Note:The position of 5 terminals of Device Net protocol is allocated according
to the stipulation of standard.
DI input terminals allocation DIC DI input common end
1DI A contactor state input ( normally
closed / level)2DI B contactor state input ( normally
closed / level)3DI breaker state input ( normally
closed / level)4DI remote control starting-up A
command input(normally opened / pulse)5DI remote control starting-up B
command input(normally opened / pulse)6DI remote control stopping command
input(normally opened / pulse)7DI remote control Reset signal input
push button(normally opened / pulse)8DI emergency stop push button
(normally opened / pulse)9DI Local / remote switching
input(normally opened / pulse)10DI Programmable input ( normally
opened)11DI Programmable input (normally opened) 12DI Programmable input (normally opened) Note : The pulse input time can not be less than
300mS. When start mode is Y/ △ start-up,
Autotransformer Start-up or soft starter-up
control,10DI is fixed contactor input state;
DO relay output terminals allocation1COM 1DO、2DO common ends 1DO start-up A output (normally opened)
2DO start-up B output (normally opened)
3DO1 、 3DO2 overflow fault output ( normally
2-17-2007 33/43
Programmable DO options are as follows:Ready for starting-up output Operation OutputStopping output Fault outputAlarming outputUnder load fault outputOverload fault outputStarting-up over-current fault outputOver-current fault outputtE fault outputEarthing/leakage fault outputtemperature fault outputImbalance fault outputStarting acceleration overtime outputUnder power fault outputOver voltage fault outputUnder voltage fault outputPhase sequence fault outputCommon DO outputRemote control purview signal output
Programmable DI options are as follows:Local control starting-up A command input (Pulse) Local control starting-up B command input (Pulse) Local control stopping command input (Pulse) Local control reset input push button (Pulse) Local control starting-up /stopA command input(level)Local control starting-up /stopB command input(level)Remote control starting-up /stopA command input(level)Remote control starting-up /stopB command input(level)Interlocking stopping A(Pulse)Interlocking stopping B(Pulse)Protection of digital process interlocking (Pulse)with "9DI" to realize "four positions " purview conversion (level)Common DI input(level)External fault alarming/ External fault tripping External fault trip
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
opened)2COM 4DO、5DO、6DO、7DO common ends
4DO fault signal(normally opened)5DO device fault ( normally closed , and is opened in normal working
time) 6DO Programmable output(normally opened)7DO Programmable output(normally opened)Note1: Controller state input may be used to realize the “test” function with
the input of “circuit-breaker state”, if the circuit-breaker is not closed, the
protection will be automatically withdrawn;
Note2: When the short-circuit current exceeding the breaking current of the
contactor, the output of “overflow fault” relay may be used to shut off the
circuit-breaker;
Installation and Outline Diagram
ST500M/Hcontroller main body 100A Shell frame special-purpose transformer outline
dimensions(2A、5A、25A、100A)
250A Shell frame special-purpose transformer outline dimensions ZT40 Outside disposed transformer outline
dimensions
2-17-2007 34/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
note : ST500M/H-250A product may be divided into independent main
body: and special transformer two independent parts, also may be grouped as a
complete installment: The main body is fixed on the special-purpose transformer
according to the diagram.
ST522 display module
2-17-2007 35/43
ST500M/H Series Intelligent Type Electric Motor Controller
Su Zhou Wan Long Group Co., Ltd.
ST-9 power module
2-17-2007 36/43
Dimensions for Openings
ZT30 Leakage current transformerZT100 Special leakage current transformer
ST500M Typical application wiring principle
Diagram
ST500M direct-starting-up wiring connection principle diagram
ST500M-A SE1
M~
R1E2
R2AI+AI-
万龙电器
B2A2
ST522B
T2
L2
T3
L3
T1
L1
CJ1
4DI
7DI8DI9DI
5DI6DI
10DI11DI12DI
QF
CJ1
Ua
Uc
3DI
1DIDIC
2DI
Ub
L3L2L1
N
QF TM
A1(+)
AO+
A2(-)
AO-
B2A1
PE
2COM
7DO
4DO5DO6DO
2DO3DO1
1DO1COM
3DO2
CJ1
NL
PE
#N ST500M
#3 ST500M
QF
F
ST500M reversible-starting-up wiring principle diagram
QF
ST500M-B
万龙电器
M~
E2E1
R1R2
AI-AI+
A2S
B2
ST522
L3
T3
L1
T1
L2
T2
CJ2
CJ1
QFCJ2
CJ1
6DI5DI
9DI8DI7DI
4DI
12DI11DI10DI
UaUb
2DI
DIC1DI
3DI
Uc
L1L2L3N
QFF
AO+
2COM
6DO5DO4DO
7DO
AO-A1B2
A1(+)A2(-)
1COM1DO
3DO23DO12DO
PE
#N ST500M
#3 ST500M
CJ1 CJ2
NL
PE
TMTM
ST500H Typical application wiring principle
Diagram
ST500H direct-starting-up wiring principle diagram
ST500 -A SE1
M~
R1E2
R2AI+AI-
万龙电器
B2A2
ST522B
T2
L2
T3
L3
T1
L1
CJ1
4DI
7DI8DI9DI
5DI6DI
10DI11DI12DI
QF
CJ1
Ua
Uc
3DI
1DIDIC
2DI
Ub
L3L2L1
N
QF TM
A1(+)
AO+
A2(-)
AO-
B2A1
PE
2COM
7DO
4DO5DO6DO
2DO3DO1
1DO1COM
3DO2
CJ1
PE
#N ST500M
#3 ST500M
QF
F
ST500H reversible –starting-up wiring principle diagram
QF
ST500 -B
万龙电器
M~
E2E1
R1R2
AI-AI+
A2S
B2
ST522
L3
T3
L1
T1
L2
T2
CJ2
CJ1
QFCJ2
CJ1
6DI5DI
9DI8DI7DI
4DI
12DI11DI10DI
UaUb
2DI
DIC1DI
3DI
Uc
L1L2L3N
QFF
AO+
2COM
6DO5DO4DO
7DO
AO-A1B2
A1(+)A2(-)
1COM1DO
3DO23DO12DO
PE
#N ST500M
#3 ST500M
CJ1 CJ2
PE
TMTM
Products Technical Parameter
ProductS standard
GB/T 14048.1 Low Voltage Switch gear and Control Equipment General rulesGB/T 14048.4 Low Voltage Switch gear and Control Equipment Low-voltage electric mechanical type contacts and motor starters Electromechanical devices GB/T 14048.× Rotary electric machine built up thermal protection (PTC) Control UnitGB 3836.3-2000 Electrical Apparatus for Explosive Gas Environment Part 3: Safety-enhanced type:“e”JB /T××××-200× AC motor Protection deviceJB /T××××-200× Universal technology condition for digital AC motor protection & monitoring device Electrical parameters
Main circuit
Rate operating voltage(Ue) 400V/690V
Rated Insulation voltage (Ui) 690V
Controller Rated Current (In) 2A、5A、6.3A、25A、100A、250A、500A、820A
Rated operating frequency 50Hz
Insulation Resistance 100MΩ/500V
Insulation Test
Medium Strength Test
2kv(r.m.s.),50Hz,1min
Impulse voltage test
5kv(Peak),1.2/50uS,0.5J
3+,3-,Interval 5s
Auxiliary Power Supply
Rated Operating voltage (US) ST500M:AC220V、50Hz
ST500H:AC220V+ DC110V/220V
Power Consumption 15VA/15W
Operating environment
Ambient temperature -10℃ , 55℃
Storage temperature -25℃ , 70℃
Installation altitude 2000m
Installation category III
Degree of protection Body proper IP20,ST522B display module IP45
Control Relay Output
ST500M Control Relay output capacity
AC250V 8A(Resistant)
AC250V 5A(AC15)Maximum breaking voltage AC 400Vac
Maximum breaking capability 2000VA
ST500H Control Relay output
capacity AC250V 16A(Resistant)
AC250V,5A (AC15)
DC110V 5A (DC13)
DC220V 3A (DC13)Maximum breaking voltage AC 400Vac
Maximum breaking capability AC 4000VA
signal Relay output
Output capacity AC250V 3A(Resistance)
DC30V 3A(Resistance)Maximum breaking voltage 300Vac
Maximum breaking cut ability AC 1500VA
EMC
Immunity test for fast transient impulsing currents
Ⅲ for serious grade
Immunity magnetic field test for radiated high frequency
Magnetic field strength 10V/m.scanning velocity 1.5x10
ten times frequency/s
Immunity to electrostatic discharge Ⅲ degree
Immunity test for surge current shock waves
Power supply for Input and Output 2 kv,for Com. 1kv
Immunity test for operating frequency of
Magnetic Field
Class 4 for serious grade
Magnetic radiation test Radiation limiting value at a distance 10 m:40dB(µV/m)
Immunity test for Voltage instantaneous
Decreasing, Breaking, and Voltage
Changing
50 ms
-3
ST500M/H Series Intelligent Type Electric Motor Controller Ordering Specification TableOrder form number: User’s name: Contact Telephone:Requested delivery time: ordering date: Contact person:No. 1 2 3 4
specification and type number:ST501M/ST502M/ST503M/ST505MST501H/ST502H/ST503H/ST505H
Rated current:2A、5A、25A、100A、250A、500A、820A
Control
Mode(selecting one kind only)
Protection mode
Direct start-up Reversible start-up
Y-∆ starting-up Starting-up Reactor reducing voltage autotransformer Starting-up reducing voltagesoft starter starting-uptransducer starting-up
Additional function (reelection available)
Leakage electricity Protection Voltage Protection
Temperature Protection
Analog Value Input
Analog Value Output
quantity
Additional Electing Annex :ST522B Display Module 、 ST-
9、ZT30/ZT100、TM
Other explainations