Model F1Model F1 RecessedStandard ResponseSprinklers
The Designer Model F1 SprinklerStandard UprightStandard
PendentExtended Coverage PendentConventionalVertical
SidewallHorizontal Sidewall HSW1 Deflector
The DesignerII Model F1 Recessed SprinklerRecessed
PendentRecessed Extended Coverage Pendent
Approval Organizations1. Underwriters Laboratories Inc.2.
Underwriters Laboratories of Canada3. Factory Mutual Research
Corp.4. Loss Prevention Council5. NYC BS&A No. 587-75-SA6.
Pleniere Assemblee7. Verband der Schadenversicherer8. NYC MEA
258-93-E
UL Listing CategorySprinklers, Automatic & Open (VNIV)
Patents: U.S. Patent No. 6,374,92Applies to Model F1 Vertical
Sidewall Sprinklers.
Product DescriptionThe F1 Glass Bulb Sprinkler combines the
durability
of a standard sprinkler with the attractive low profile ofa
decorative sprinkler. Whether installed on exposedpiping or in an
office ceiling, it is functional andattractive. The Horizontal and
Vertical SidewallSprinklers provide an equally attractive
appearancewhen ceiling piping cannot be used.
Beautifully versatile is the description for the ReliableModel
F1 Recessed Designer glass bulb sprinkler.Recessing The Designer
enhances its already lowprofile decorative appearance, and
facilitates a rapidand perfect installation.
Model F1 Recessed Designers escutcheon is highlyadjustable. The
two piece construction makes fieldinstallation a very easy and
rapid task. This also allowsceiling panels to later be removed
without shuttingdown the fire protection system, thus
facilitatingmaintenance of above ceiling services.
The Designer Automatic Sprinkler utilizes a frangibleglass bulb.
The glass bulb consists of an accuratelycontrolled amount of
special fluid hermetically sealedinside of a precisely manufactured
glass capsule. Thisglass bulb is specially constructed to provide
fastthermal response.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park
Drive, Elmsford, New York, 10523
At normal temperatures, the glass bulb contains thefluid in both
the liquid phase and in the vapor phase.The vapor phase can be seen
as a small bubble. Asheat is applied, the liquid expands forcing
the bubblesmaller and smaller as the liquid pressure
increases.Continued heating forces the liquid to push out
againstthe bulb, causing the glass to shatter, opening thewaterway
and allowing the deflector to distribute thedischarging water.
The F1 Sprinkler temperature rating is identified bythe color of
the glass bulb capsule as well as framecolor where applicable.
Upright Pendent
Horizontal Sidewall
Conventional
Recessed Pendent
Extended CoveragePendent
Recessed ExtendedCoverage Pendent
Bulletin 117 Rev.T
Vertical Sidewall
Bulle
tin117
Re
v.T
-
Model F1 Upright, Pendent & Conventional
SprinklersInstallation Wrench: Model D Sprinkler Wrench
Upright Pendent Conventional
2.
NominalOrifice Thread Size
Nominal K Factor SprinklerHeight
ApprovalOrganization
Sprinkler Identification Numbers(SIN)
US Metric Upright PendentStandard-Upright (SSU) and pendent
Deflectors Marked to Indicate Position
"(15mm)
" NPT(R1/2)
5.6 802.2"
(56mm)1,2,3,4,5,6,7 R1725(4) R1715
17/32"(20mm)
" NPT(R3/4)(1)
8.0 1152.3"
(58mm)1,2,3,4,7,8 R1722(4) R1712
"(15mm)(3)
" NPT(R1/2)
5.6 802.2"
(56mm)7
17/32"(20mm)(3)
" NPT(R3/4)
8.0 1152.3"
(58mm)7
7/16"(11mm)
" NPT(R1/2)
4.2 602.2"
(56mm)1,2,8 R1723(4) R1713
3/8"(10mm)
" NPT(R1/2)(2)
2.8 402.54"
(65mm)1,2,8 R1721(4) R1711
10mm XLH R3/8 4.2 60 56.1mm 4,6,7 R1724 R1714
Conventional-Install in Upright or Pendent Position
10mm XLH R3/8 4.2 60 56.1mm ---------- R1774
15mm" NPT(R1/2)
5.6 80 56.1mm 4,6,7 R1775
20mm" NPT(R3/4)
8.0 115 58.1mm 4,7 R1772
Installation Data:
(1) LPC Approval up to 286F (141C)(2) FM Approval for SSU up to
and including 200F (93C) only.(3) (F1S5) VdS Approval for
Intermediate Response 155F (68C) only.(4) Polycoated upright UL and
ULC listed corrosion resistant.
-
Model F1 Recessed Pendent SprinklerInstallation Wrench: Model
GFR1 Sprinkler Wrench
Recessed Pendent
(1) When installed directly into a tee, the escutcheon
dimension's
adjustment will be reduced.
NominalOrifice Thread Size
Nominal K FactorSprinkler Height ApprovalOrganization
Sprinkler IdentificationNumbers (SIN)US Metric
"(15mm)
" NPT(R1/2)
5.6 802.2"
(56mm)1,2,3,4,5,7 R1715
17/32"(20mm)
" NPT(R3/4)
8.0 1152.3"
(58mm)1,2,3,4,8 R1712
"(15mm)(4)
" NPT(R1/2)
5.6 802.2"
(56mm)7
17/32"(20mm)(4)
" NPT(R3/4)
8.0 1152.3"
(58mm)7
7/16"(11mm)
" NPT(R1/2)
4.2 602.2"
(56mm)1,2,8 R1713
3/8"(10mm)
" NPT(R1/2)
2.8 402.2"
(56mm)1,2,8 R1711
10mm R3/8 4.2 60 56.1mm 4,7 R1714
Installation Data:
(2) FM Approval
Light Hazard - No Limitations
Ordinary Hazard - Groups 1 & 2, Wet Systems only.
(3) LPC Approval is for 57C through 93C ratings.(4) VdS Approval
for Intermediate Response 155F (68C) only.
3.
-
4.
Model F1 Vertical Sidewall SprinklerInstallation Wrench: Model D
Sprinkler WrenchInstallation Position: Upright or PendentApproval
Type: Light Hazard Occupancy
Model F1 Horizontal Sidewall SprinklerDeflector: HSW
1Installation Wrench: Model D Sprinkler Wrench
Horizontal Sidewall
Nominal Orifice Thread SizeNominal K Factor Sprinkler
HeightApproval
OrganizationsSprinkler
IdentificationNumbers (SIN)US Metric
" (15mm) " NPT (R1/2) 5.6 8.0 2.2" (56.1mm) 1,2,3,4,6,8
R1785
Installation Data:
Sprinkler Type Deflector to Ceiling Distance(Min. - Max.)Upright
4" (102mm) - 12" (305mm)
Pendent 4" (102mm) - 12" (305mm)
U.S. Patent No. 6,374,920
(1) LPC Approval is pendent only, 57C through 141C ratings.
Vertical Sidewall
NominalOrifice Thread Size
Nominal K FactorSprinkler
HeightApproval Organizations Sprinkler
IdentificationNumbers (SIN)US Metric Light Hazard
OrdinaryHazard
" (15mm)" NPT(R1/2)
5.6 80 2.63" (67mm) 1,2,3,5 1,2,5 R1735
Installation Data:
Note: UL and ULC Listing permits use with F1 escutcheons, light
hazard only.
-
5.
(1) When installed directly into a tee, the
escutcheondimension's adjustment will be reduced.
Extended Coverage Pendent
Extended CoverageRecessed
Model F1 Extended Coverage Pendent SprinklerDeflector: EC
PendentInstallation Wrench: Model D Sprinkler WrenchApproval Type:
Extended Coverage - Light Hazard Occupancy
Model F1 Recessed Extended Coverage Pendent SprinklerDeflector:
EC PendentInstallation Wrench: Model GFR1 Sprinkler WrenchApproval
Type: Extended Coverage - Light Hazard Occupancy
NominalOrifice
ThreadSize
Nominal K Factor SprinklerHeight
ApprovalOrganizations
Temperature Rating SprinklerIdentification
Numbers (SIN)US Metric F C17/32"
(20mm)" NPT(R3/4)
8.0 115 2.2" (56mm) 1,2,8 135, 155 57, 68 R1742
" (15mm)" NPT(R1/2)
5.6 80 2.2" (56mm) 1,2,8 135, 155 57, 68 R1745
Installation Data:
Coverage Area
Flow RatePressure
Max. AreaWidth x LengthNominal
K=8.0 (115) K=5.6 (80)gpm L/min psi bar psi bar ft. x ft. m x
m
263340
98.4125.0151.4
10.617.025,0
0,71,21,7
21.634.751.0
1,52,43,5
16 x 1618 x 1820 x 20
4.9 x 4.95.5 x 5.56.0 x 6.0
NominalOrifice
ThreadSize
Nominal K Factor SprinklerHeight
ApprovalOrganizations
Temperature Rating SprinklerIdentification
Numbers (SIN)US Metric F C17/32"
(20mm)" NPT(R3/4)
8.0 115 2.2" (56mm) 1,2,8 135, 155 57, 68 R1742
" (15mm)" NPT(R1/2)
5.6 80 2.2" (56mm) 1,2,8 135, 155 57, 68 R1745
Installation Data:
Coverage Area
Flow RatePressure
Max. AreaWidth x LengthNominal
K=8.0 (115) K=5.6 (80)gpm L/min psi bar psi bar ft. x ft. m x
m
263340
98.4125.0151.4
10.617.025,0
0,71,21,7
21.634.751.0
1,52,43,5
16 x 1618 x 1820 x 20
4.9 x 4.95.5 x 5.56.0 x 6.0
-
Model F1 & F1 Recessed SprinklersApplication
Model F1 and F1 Recessed sprinklers are used infixed fire
protection systems: Wet, Dry, Deluge orPreaction. Care must
exercised that the orifice size,temperature rating, deflector style
and sprinkler typeare in accordance with the latest published
standardsof the National Fire Protection Association or
theapproving Authority Having Jurisdiction.
InstallationModel F1 sprinklers are standard response
sprinklers
intended for installation as specified in NFPA 13. Theymust also
be installed with the Model D SprinklerWrench specifically designed
by Reliable for use withthese sprinklers.
The Model F1 Recessed Sprinklers are to be installedwith a
maximum recess of inch (19mm). The Model
F1 Escutcheon illustrated is the only recessedescutcheon to be
used with the Model F1 Pendent andEC Sprinklers. The use of any
other recessedescutcheon will void all approvals and negate
allwarranties. When installing Model F1 RecessedPendent and EC
Pendent Sprinklers, use the ModelGFR1 Sprinkler Wrench. Any other
type of wrench maydamage these sprinklers.
Glass bulb sprinklers have orange covers to protectthe bulb
during the installation process. REMOVE THISPROTECTION ONLY AFTER
THE SYSTEM HAS BEENHYDROSTATICALLY TESTED AND, WHEN APPLICABLE,THE
ESCUTCHEONS HAVE BEEN INSTALLED. RASCOwrenches are designed to
install sprinklers whencovers are in place.
MaintenanceThe Models F1 and F1 Recessed Sprinklers should
be inspected quarterly and the sprinkler systemmaintained in
accordance with NFPA 25. Do not cleansprinklers with soap and
water, ammonia or any othercleaning fluid. Remove any sprinkler
which has beenpainted (other than factory applied) or damaged in
anyway. A stock of spare sprinklers should be maintainedto allow
quick replacement of damaged or operatedsprinklers. Prior to
installation, sprinklers should bemaintained in the original
cartons and packaging untilused to minimize the potential for
damage to sprinklersthat would cause improper operation or
non-operation.
Ordering InformationSpecify:1. Sprinkler Model2. Sprinkler
Type3. Orifice Size4. Deflector Type5. Temperature Rating6.
Sprinkler Finish7. Escutcheon Finish (where applicable)
ClassificationSprinkler
TemperatureMaximumAmbient
Temperature BulbColorF C F C
OrdinaryOrdinaryIntermediateIntermediateHigh(1)
Extra High(1)
135155175200286360
57687993141182
100100150150225300
38386666107149
OrangeRed
YellowGreenBlue
Mauve
Temperature Ratings
(1) Not Available for F1 Recessed
Patents: U.S. Patent No. 6,374,920Applies to Model F1 Vertical
Sidewall Sprinklers.
Standard FinishesSprinkler Escutcheon
BronzeChromeWhite Polyester Coated(3)(6)
BrassChromeWhite Painted
Special Application FinishesSprinkler Escutcheon
Bright Brass(2)
Black PlatedBlack Paint(3)(4)
Off White(3)
Satin ChromeLead Plated(3)(4)
Wax Coated(3)(4)(5)
Wax Over Lead(3)(4)
Bright BrassBlack PlatedBlack PaintOff WhiteSatin Chrome
Finishes
(1) Other colors and finishes are available on special order.
Consultfactory for details.(2) 200F (93C) maximum.(3) UL and ULC
listed, and NYC approved only.(4) 155F to 200F (68C to 93C) ratings
only.(5) 286F (141C) sprinklers may be coated for ambient
conditions notexceeding 150F (66C).(6) UL and ULC listed corrosion
resistant SIN numbers: R1721, R1722,R1723 and R1725.
Note: For " orifice pendent FM approved whitepolyester coated
and UL approved white polyestercorrosion resistant sprinklers refer
to Bulletin 013.
The equipment presented in this bulletin is to be installed in
accordance with the latest pertinent Standards of the National Fire
Protection Association,Factory Mutual Research Corporation, or
other similar organizations and also with the provisions of
governmental codes or ordinances wheneverapplicable.Products
manufactured and distributed by Reliable have been protecting life
and property for over 80 years, and are installed and serviced by
the mosthighly qualified and reputable sprinkler contractors
located throughout the United States, Canada and foreign
countries.
(800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914)
829-2042 Corporate Officeswww.reliablesprinkler.com Internet
Address
Manufactured by
E.G. Printed in U.S.A. 11/08 P/N 9999970011