Since the Trane Company has a policy of continuous product improvement, it reserves the right to change specifications and design without notice. Wiring Manual RAUC-W-21 Library Service Literature Product Section Unitary Product Split System Air Conditioning Model RAUC Literature Type Wiring Sequence 21 Date December 2001 File No. SV-UN-S/S-RAUC-W-21-12/01 Supersedes New TM Split System Remote Condensing Units and EVP Chillers This wiring manual contains; Field Wiring Schematics for; No Controls, Variable Air Volume, and EVP Control applications, Power Schematics for all controls, Various Control Schematics, and Connection Diagrams. Models "V" and Later Design Sequence RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C50 RAUC-C30 RAUC-C60 With 3-D TM Scroll Compressors Caution: The installation of this equipment must comply with all National, State, and Local Codes. Important! This document is customer property and must be retained by the unit's maintenance personnel. American Standard Inc, 2001 http://www.trane.com
28

Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

May 14, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

Since the Trane Company has a policy of continuous productimprovement, it reserves the right to change specifications anddesign without notice.

Wiring Manual RAUC-W-21

Library Service Literature

Product Section Unitary

Product Split System Air Conditioning

Model RAUC

Literature Type Wiring

Sequence 21

Date December 2001

File No. SV-UN-S/S-RAUC-W-21-12/01

Supersedes New

TM

Split SystemRemote Condensing Unitsand EVP Chillers

This wiring manual contains; Field Wiring Schematicsfor; No Controls, Variable Air Volume, and EVP Controlapplications, Power Schematics for all controls, VariousControl Schematics, and Connection Diagrams.

Models"V" and Later Design SequenceRAUC-C20 RAUC-C40RAUC-C25 RAUC-C50RAUC-C30 RAUC-C60

With 3-D TM Scroll Compressors

Caution: The installation of this equipment mustcomply with all National, State, and LocalCodes.

Important! This document iscustomer property and must beretained by the unit'smaintenance personnel.

American Standard Inc, 2001http://www.trane.com

Page 2: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

2

Table of ContentsGeneral Information

Literature Change History ............................................... 2Warnings and Cautions ................................................... 2Model Number Description .............................................. 3

Wiring DiagramsFigure 1

Wire Selection & Fuse Replacement Table for20 through 60 Ton Units .................................................. 4Field Control Wiring Diagram Notes ................................ 5

Figure 2Typical Field Control Wiring Diagram for "No SystemControls" Application ....................................................... 6

Figure 3Typical Field Control Wiring Diagram for "ConstantVolume" Application ......................................................... 7

Figure 4Typical Field Control Wiring Diagram for "Variable AirVolume" Application ......................................................... 8

Figure 5Typical Field Control Wiring Diagram for "EVP"Application ....................................................................... 9

Figure 6Typical Power Schematic Diagram for 20 through60 Ton Units ................................................................... 10

Figure 7Typical "No System Control" Schematic Diagramfor 20 through 60 Ton Units ........................................... 12

Figure 8Typical "Constant Volume" Schematic Diagram for20 through 60 Ton Units ................................................ 14

Figure 9Typical "Variable Air Volume" Schematic Diagramfor 20 through 60 Ton Units ........................................... 16

Figure 10Typical "EVP" Schematic Diagram for 20 through60 Ton Units ................................................................... 18

Figure 11Typical Low Ambient Control and ConnectionDiagram for 20 through 60 Ton Units ............................. 20

Figure 12Typical Connection Diagram for 20 through 60 TonUnits with "No System Controls" Plate .......................... 22Typical "Control Plate" Connection Diagram Notes ....... 24

Figure 13Typical Connection Diagram with "Constant Volume"Control Plate .................................................................. 25

Figure 14Typical Connection Diagram with "Variable AirVolume" Control Plate ................................................... 26

Figure 15Typical Connection Diagram with "EVP"Control Plate .................................................................. 27

Literature Change History

RAUC-W-21 (December 2001)Original issue of wiring manual; provides typical field wiringand electrical schematics for "V" and later design sequenceon RAUC-C20 through C60 Ton units with; no controls, con-stant volume (CV), variable air volume (VAV) and EVP con-trols.

Note: The customer connection diagrams andelectrical schematics are typical illustrations andare published for general reference only. Thesediagrams may not reflect the actual wiring in yourunit, always refer to the wiring diagrams thatshipped with the unit for specific electricalschematic and connection information.

Warnings and Cautions

Warnings are provided to alert installing contractors, opera-tors, and service personnel of potential hazards that couldresult in personal injury or death.

Cautions are designed to alert personnel that equipmentdamage could occur if specific instructions are not followed.

Page 3: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

3

Model Number DescriptionAll Trane products are identified by a multiple-charactermodel number that precisely identifies a particular type ofunit. An explanation of the alphanumeric identification codesused for RAUC units is provided on this page. Its use will en-able the owner/operator, installing contractors, and serviceengineers to define the unit's specific components, type ofapplication, i.e. CV, VAV, EVP or No System Controls andoptions for any particular unit.

When ordering replacement parts or requesting service, besure to refer to the specific model number, serial number,and DL number (if applicable) stamped on the unit name-plate.

Sample Model No.: RAUC - C60 E B L 1 3 A, F, G, 1, etc Digit No.: 1 2 3 4 5,6,7 8 9 10 11 12 13+

Digit 1 - Unit Type Digit 8 - Power Supply Digit 11 - Ambient ControlR = Remote Condensing Unit E = 200/60/3 XL 0 = Standard

F = 230/60/3 XL 1 = Low Ambient 0o FDigit 2 - Condenser 4 = 460/60/3 XL A = Air Cooled 5 = 575/60/3 XL Digit 12 - Agency Approval

9 = 380/50/3 XL 0 = NoneDigit 3 - Air Flow D = 415/50/3 XL 3 = UL / CSAU = Up Flow

Digit 9 - System Control Digit 13 - Miscellaneous OptionsDigit 4 - Development Sequence B = No System Control A = Unit Mounted Disconnect SwitchC = Third C = Constant Volume Control B = Hot Gas Bypass Valves *

E = Supply Air VAV Control D = Suction Service ValvesDigits 5, 6, 7 - Nominal Capacity P = EVP Control F = Pressures Gauges & Gauge Piping *C20 = 20 Tons G = Return Air Sensor *C25 = 25 Tons Digit 10 - Design Sequence H = Condenser Coils with Copper FinsC30 = 30 Tons V = Disconnect Redesign T = Flow Switch (EVP Only) *C40 = 40 Tons 1 = Spring Isolators *C50 = 50 Tons 2 = Neoprene Isolators *C60 = 60 Tons 9 = Packed Stock

* Field Installed Options

Page 4: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

4

Figure 1Wire Selection & Fuse Replacement Table for 20 through 60 Ton Units

Page 5: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

5

Field Control Wiring Diagram NotesUse with Figures 2, 3, 4 & 5

Page 6: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

6

Figure 2Typical Field Control Wiring Diagram for "No System Controls" Application(Refer to the Wire Sizing Table & Notes on page 4 & 5)

Page 7: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

7

Figure 3Typical Field Control Wiring Diagram for "Constant Volume" Application(Refer to the Wire Sizing Table & Notes on pages 4 & 5)

Page 8: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

8

Figure 4Typical Field Control Wiring Diagram for "Variable Air Volume" Application(Refer to the Wire Sizing Table & Notes on pages 4 & 5)

Page 9: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

9

Figure 5Typical Field Control Wiring Diagram for "EVP" Application(Refer to the Wire Sizing Table & Notes on pages 4 & 5)

Page 10: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

10

Figure 6Typical Power Schematic Diagram for 20 through 60 Ton Units

Page 11: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

11

Page 12: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

12

Figure 7Typical "No System Control" Schematic Diagram for 20 through 60 Ton Units

Page 13: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

13

Page 14: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

14

Figure 8Typical "Constant Volume" Schematic Diagram for 20 through 60 Ton Units

Page 15: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

15

Page 16: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

16

Figure 9Typical "Variable Air Volume" Schematic Diagram for 20 through 60 Ton Units

Page 17: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

17

Page 18: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

18

Figure 10Typical "EVP" Schematic Diagram for 20 through 60 Ton Units

Page 19: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

19

Page 20: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

20

Figure 11Typical Low Ambient Control and Connection Diagram for 20 through 60 Ton Units

Page 21: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

21

Page 22: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

22

Figure 12Typical Connection Diagram for 20 through 60 Ton Units with "No System Controls" Plate(Use with Figures 13, 14 & 15)

Page 23: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

23

Page 24: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

24

Typical Connections Diagram NotesUse with Figures 13, 14 & 15

Page 25: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

25

Figure 13Typical "Constant Volume" Control Plate Connection Diagram(Use with Figure 12)

Page 26: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

26

Figure 14Typical "Variable Air Volume" Control Plate Connection Diagram(Use with Figure 12)

Page 27: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

27

Figure 15Typical "EVP" Control Plate Connections Diagram(Use with Figure 12)

Page 28: Split System Remote Condensing Units and EVP Chillers · All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit.

28