SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. March 2022 SS-SVX001D-EN Installation, Operation, and Maintenance Split System Air Conditioners Odyssey™™ with Symbio™™ Controls Cooling Condenser, R-410A 5 to 25 Tons and R-22 Dry Charge 7.5, 10, 15 and 20 Tons (60 Hz) TTA0724*A/D TTA0904*A/D TTA1204*C/D TTA1504*D TTA1804*C/D TTA2404*C/D TTA3004*C TTA0902*A TTA1202*A TTA1802*D TTA2402*D (50 Hz) TTA0604DA/D TTA0764DA/D TTA1014DC/D TTA1264DD TTA1564DC/D TTA2014DC/D TTA2514DC
40
Embed
Split System Air Conditioners Odyssey™ with Symbio™ Controls
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioningequipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified personcould result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels thatare attached to the equipment.
March 2022 SSSS--SSVVXX000011DD--EENN
Installation, Operation, and Maintenance
Split System Air ConditionersOdyssey™™with Symbio™™ControlsCooling Condenser, R-410A 5 to 25 Tons andR-22 Dry Charge 7.5, 10, 15 and 20 Tons
IntroductionRead this manual thoroughly before operating orservicing this unit.
Warnings, Cautions, and NoticesSafety advisories appear throughout this manual asrequired. Your personal safety and the properoperation of this machine depend upon the strictobservance of these precautions.
The three types of advisories are defined as follows:
WARNINGIndicates a potentially hazardous situationwhich, if not avoided, could result in death orserious injury.
CAUTIONIndicates a potentially hazardous situationwhich, if not avoided, could result in minor ormoderate injury. It could also be used to alertagainst unsafe practices.
NOTICEIndicates a situation that could result inequipment or property-damage onlyaccidents.
Important Environmental ConcernsScientific research has shown that certain man-madechemicals can affect the earth’s naturally occurringstratospheric ozone layer when released to theatmosphere. In particular, several of the identifiedchemicals that may affect the ozone layer arerefrigerants that contain Chlorine, Fluorine and Carbon(CFCs) and those containing Hydrogen, Chlorine,Fluorine and Carbon (HCFCs). Not all refrigerantscontaining these compounds have the same potentialimpact to the environment. Trane advocates theresponsible handling of all refrigerants-includingindustry replacements for CFCs and HCFCs such assaturated or unsaturated HFCs and HCFCs.
Important Responsible RefrigerantPracticesTrane believes that responsible refrigerant practicesare important to the environment, our customers, andthe air conditioning industry. All technicians whohandle refrigerants must be certified according to localrules. For the USA, the Federal Clean Air Act (Section608) sets forth the requirements for handling,reclaiming, recovering and recycling of certainrefrigerants and the equipment that is used in theseservice procedures. In addition, some states ormunicipalities may have additional requirements thatmust also be adhered to for responsible managementof refrigerants. Know the applicable laws and followthem.
CopyrightThis document and the information in it are theproperty of Trane, and may not be used or reproducedin whole or in part without written permission. Tranereserves the right to revise this publication at any time,and to make changes to its content without obligationto notify any person of such revision or change.
TrademarksAll trademarks referenced in this document are thetrademarks of their respective owners.
Revision History• Updated the Model Number Description chapter.
• Updated the Installation chapter.
• Updated the Charging Data and Pressure Curveschapter.
• Updated the Dimensional Data chapter.
• Updated the Wiring Diagram Matrix and DeviceLocation chapter.
1 = Standard Coil w/ Hail Guard5 = Complete Coat Condenser Coil with HailGuard (MCHE)
Digit 18, 19, 20— None
0 = None
Digit 21— Communications Options
0 = No Option1 = Advanced Diagnostics and BACnet® BAS2 = Advanced Diagnostics and LonTalk®Communications Interface (LCI)
Digit 22 to 40 —None
0 = None
6 SS-SVX001D-EN
General InformationThis manual describes proper installation, operation,and maintenance procedures for air-cooled systems.By carefully reviewing the information within thismanual and following the instructions, the risk ofimproper operation and/or component damage will beminimized. It is important that periodic maintenance beperformed to help assure trouble free operation.Should equipment failure occur, contact a qualifiedservice organization with qualified, experienced HVACtechnicians to properly diagnose and repair thisequipment.
IImmppoorrttaanntt:: All phases of this installation must complywith the NATIONAL, STATE & LOCALCODES. In addition to local codes, theinstallation must conform with NationalElectric Code -ANSI/NFPA NO. 70 LATESTREVISION.
Any individual installing, maintaining, or servicing thisequipment must be properly trained, licensed andqualified.
IImmppoorrttaanntt:: Do not remove the VFD without firstcontacting technical support! Forperformance-related questions anddiagnostic support in North America call 1-877-872-6363. Any return requires a claimnumber FIRST. Removal of the VFD prior tothis step will void the unit’s warranties.
Installation procedures should be performed in thesequence that they appear in this manual. Do notdestroy or remove the manual from the unit. The
manual should remain weather-protected with the unituntil all installation procedures are complete.
NNoottee:: It is not the intention of this manual to cover allpossible variations in systems that may occur orto provide comprehensive informationconcerning every possible contingency that maybe encountered during an installation. Ifadditional information is required or if specificproblems arise that are not fully discussed in thismanual, contact your local sales office.
Use the “Installation Checklist,” p. 8 provided in thismanual to verify that all necessary installationprocedures have been completed. Do not use thechecklist as a substitute for reading the informationcontained in this manual. Read this entire manualbefore beginning installation procedures.
Unit DescriptionThese condensers come with single, dual andmanifolded compressor options. Single compressoroutdoor units feature a single refrigeration circuitrequiring only one set of refrigerant lines. Dualcompressor/dual circuit models give true stand-byprotection; if one compressor fails, the second willautomatically start-up. During light load conditions,only one compressor will operate to save energy.Thedual manifolded scroll compressors come with twostages of capacity modulation and a singlerefrigeration circuit.
SS-SVX001D-EN 7
Pre-InstallationUnit InspectionInspect material carefully for any shipping damage. Ifdamaged, it must be reported to, and claims madeagainst the transportation company. Compare theinformation that appears on the unit nameplate withordering and submittal data to ensure the proper unitwas shipped. Available power supply must becompatible with electrical characteristics specified oncomponent nameplates. Replace damaged parts withauthorized parts only.
IImmppoorrttaanntt:: Units ordered with a VFD cannot be fieldconverted to 460 V from 208-230 or from208-230 V to 460 V.
Inspection ChecklistTo protect against loss due to damage incurred intransit, complete the following checklist upon receipt ofthe unit.
☐ Inspect individual pieces of the shipment beforeaccepting the unit. Check for obvious damage to theunit or packing material.
☐ Inspect the unit for concealed damage before it isstored and as soon as possible after delivery.Concealed damage must be reported within 15days. If concealed damage is discovered, stopunpacking the shipment. Do not remove damagedmaterial from the receiving location. Take photos ofthe damage if possible. The owner must providereasonable evidence that the damage did not occurafter delivery.
☐ Notify the carrier’s terminal of damage immediatelyby phone and by mail. Request an immediate jointinspection of the damage by the carrier and theconsignee.
☐ Notify the sales representative and arrange forrepair. Do not repair the unit until the damage isinspected by the carrier’s representative.
Testing for LeaksAll units are shipped with a holding charge of nitrogenin each circuit and should be leak tested beforeinstallation.
1. Remove the access panel.
2. Locate the liquid line or suction line access valve foreach circuit.
3. Install gauges to determine if the circuits are stillpressurized. If not, the charge has escaped andshould be repaired as required to obtain a leak-freecircuit.
Before preparing the unit for lifting, estimate theapproximate center of gravity for lifting safety. Becauseof placement of internal components, the unit weightmay be unevenly distributed. See “Weights,” p. 19 forapproximate unit weights.
The crated unit can be moved using a forklift of suitablecapacity. For lifting the unit, attach lifting straps orslings securely to the lifting holes at each corner (seeunit drawings in “Weights,” p. 19). Use spreader barsto protect the unit casing from damage. Test lift theunit to determine proper balance and stability.
ClearancesProvide enough space around the unit to allowunrestricted access to all service points. Refer to the“Dimensional Data,” p. 10 for unit dimensions andminimum required service and free air clearances.Observe the following points to ensure proper unitoperation.
1. Do not install the unit under a low overhang.Condenser discharge must not be restricted—referto notes in “Dimensional Data drawings,” p. 10.
IImmppoorrttaanntt:: Do not obstruct condenser dischargeair. This can result in warm airrecirculation through the coil.
2. Do not locate the unit in a position where runoffwater, or falling snow from roof, can fall into the fandischarge openings.
3. Condenser intake air is supplied from three or foursides of the unit. Adhere to the minimum requiredclearances given in unit dimensional drawings (see
IImmppoorrttaanntt:: Refer to local building codes for properinstallation. All installation must complywith local building codes.
Rooftop MountingIf the unit will be roof mounted, determine for certainthat the structure is strong enough to support the unitand any required accessories, see “Weights,” p. 19.The unit should be elevated on a level, field fabricatedfour-inch steel or wood 4" x 4" mounting frame.Complete the frame and secure it into position beforelifting the unit to the roof. The mounting frame mustsupport a minimum of three of the unit’s four sides andshould span roof supports to distribute the load on theroof.
Figure 1. Roof mounted unit
Outdoor Unit
Gas (Suction)Line - Insulated
Liquid LineInsulated
Unit MountingChannels
Elevation(Mounting Frame)
Roof Trussing
Ceiling
Roof Construction
6”Radius
Ground Level MountingFor ground level installation, the unit base should beadequately supported and hold the unit near level. Theinstallation must meet the guidelines set forth in localcodes. The support should extend two inches beyondthe unit base channels at all points. The unit andsupport must be isolated from any adjacent structureto prevent possible noise or vibration problems. Anyground level location must comply with requiredclearances given in the unit dimensional drawings (see“Dimensional Data,” p. 10).
Installation ChecklistComplete this checklist once the unit is installed toverify that all recommended procedures have beenaccomplished before starting the system. Do notoperate the system until all items covered by thischecklist are complete.
☐ Inspect unit location for proper required serviceclearances.
☐ Inspect unit location for proper free air clearances.
☐ Inspect unit location for secure, level mountingposition.
☐ Remove coil protection boards on microchannelunits.
☐ Verify condenser fans turn freely without rubbingand are properly tightened on the shafts.
Refrigerant Piping☐ Properly sized/constructed liquid and suction lines
connected to stubs at both the indoor and outdoorunits?
☐ Insulated the entire suction line?
PPrree--IInnssttaallllaattiioonn
SS-SVX001D-EN 9
☐ Insulated portions of liquid line exposed toextremes in temperature?
☐ Performed initial leak test?
☐ Evacuated each refrigerant circuit to 500 microns?
☐ Charged each circuit with proper amount of R-410A/R-22?
Electrical Wiring☐ Provided unit power wiring (with disconnect) to
proper terminals in the unit control enclosure?
☐ Installed system indoor thermostat or zone sensor?
☐ Installed system low voltage interconnecting wiringto proper terminals of outdoor unit, indoor unit andsystem thermostat or zone sensor?
☐ Checked all electrical connections to verify all areproperly tightened and connected?
☐ Verified operation of crankcase heaters?
PPrree--IInnssttaallllaattiioonn
10 SS-SVX001D-EN
Dimensional DataCooling CondenserFigure 2. Height, width and depth measurements
SEE NOTE 3 NOTES:1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
DDiimmeennssiioonnaall DDaattaa
12 SS-SVX001D-EN
Figure 4. 5, 6, 6.25, 7.5 ton condensing, dual compressor – in (mm)
1/16”(1.2)
SERVICE PANEL
SERVICE PANEL SIDE
6”(152)
6”(152)
34 11/16”(881)
22 11/16”(577)
34 15/16”(887)
36 5/16”(922)
WITH HAIL GUARD
1 7/8” (47)
2 7/8” (74)
41 2/16”(1044)
41 15/16”(1065)
WITH HAIL GUARD
20 15/16”(531)
39 3/16”(996)
17 7/16”(442)
11 13/16”(300)
3” (76)
35 1/16”(890)41 1/16”
(1042)
1 13/16” (47) 28 11/16”(729)
2 5/16” (59)
2 5/16” (59)
SERVICE PANEL
SERVICE CLEARANCE48” (1219.2) (SEE NOTE 2FOR CLEARANCE)
SEE NOTE 3NOTES:1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
4 5/16” (109)
27 13/16”(706)
11 5/16”(288)
7 13/16”(199)
9 5/16”(236)
6 3/8”(162)
35 3/8”(898)
HAIL GUARD(OPTIONAL) LINE VOLTAGE
CONTROL WIRING
SUCTION LINE
LIQUID LINE
1 5/16” (33)
2 1/4” (57)4 3/8” (111)
DDiimmeennssiioonnaall DDaattaa
SS-SVX001D-EN 13
Figure 5. 8.33, 10 ton R-410A and 10 ton R-22 condensing, manifolded compressor – in (mm)
11 13/16”(300)
17 7/16”(442)
20 15/16”(531)
1 7/8” (47)
2 7/8” (73) 50 7/8”(1293)
51 11/16”(1312)
WITH HAIL GUARD
39 3/16”(996)
HAIL GUARD(OPTIONAL)
HAIL GUARD(OPTIONAL)
SEE NOTE 1
CONTROLWIRING(OPTIONAL)
REFRIGERANT GAUGE ACCESS
NOTES:1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SERVICE CLEARANCE48” (1219.2) (SEE NOTE 2FOR CLEARANCE)
9 5/16”(236)
16 5/16”(415)
27 13/16”(706)
35 3/8”(898)
2 13/16” (72)
4 1/4” (109)
1 1/4” (33)
3 3/16” (81)
LINE VOLTAGE
CONTROL WIRING
SUCTION LINE
LIQUID LINE
SERVICE PANEL
SEE NOTE 4
SEE NOTE 3
DDiimmeennssiioonnaall DDaattaa
14 SS-SVX001D-EN
Figure 6. 8.33, 10 ton condensing, dual compressor – in (mm)
11 13/16”(300)
17 3/8”(441)
20 15/16”(531)
1 7/8” (47)
2 7/8” (73) 50 3/4”(1290)
51 11/16”(1312)
WITH HAIL GUARD
6 3/8”(162)
7 13/16”(199)
9 5/16”(236)
11 5/16”(288)
[288]
27 13/16”(706)
35 3/8”(898)
2 1/4” (56)
4 3/8” (110)
1 5/16” (33)
4 5/16” (109)
39 3/16”(996)
HAIL GUARD(OPTIONAL)
SERVICE PANEL
HAIL GUARD(OPTIONAL) LINE VOLTAGE
CONTROL WIRING
SUCTION LINE
LIQUID LINE
SEE NOTE 1
CONTROLWIRING(OPTIONAL)
REFRIGERANT GAUGE ACCESS
SEE NOTE 4
SEE NOTE 3 NOTES:1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SERVICE CLEARANCE48” (1219.2) (SEE NOTE 2FOR CLEARANCE)
DDiimmeennssiioonnaall DDaattaa
SS-SVX001D-EN 15
Figure 7. 10.4, 12.5 ton condensing, dual compressor – in (mm)
14 5/16”(363)
23 7/16”(595)
26 15/16”(684)
1 7/8” (47)
2 7/8” (73) 50 7/8”(1293)
51 11/16”(1312)
WITH HAIL GUARD
6 3/8”(162)
7 7/8”(199)
9 5/16”(236)
11 3/8”(288)
[288]
33 13/16”(859)
41 3/8”(1050)
2 1/4” (56)
3 3/16” (80)
1 5/16” (33)
4 5/16” (109)
45 1/4”(1150)
HAIL GUARD(OPTIONAL)
SERVICE PANEL
HAIL GUARD(OPTIONAL) LINE VOLTAGE
CONTROL WIRING
SUCTION LINE
LIQUID LINE
SEE NOTE 1
CONTROLWIRING(OPTIONAL)
REFRIGERANT GAUGE ACCESS
SEE NOTE 3
SEE NOTE 2 NOTES:1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
NOTES:1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
DDiimmeennssiioonnaall DDaattaa
SS-SVX001D-EN 17
Figure 9. 13, 15, 16.7 and 20 ton condensing, manifolded compressor – in (mm)
45 3/8”(1152)
WITH HAIL GUARD
44”(1118)
25 5/8”(651)
9”(229)
9”(229)
1/16”(2)
93 11/32”(2363)
3/16” (5)
35 1/16”(891)
10 9/16” (268)
13 9/16”(344)
14 5/16” (364)
10 1/4” (260)
94 3/4”(2407)
WITH HAIL GUARD
11 1/8” (283)
12 1/4”(311)
35 7/16”(900) 40 11/16”
(1033) 44 3/4”(1137)
1/2” (13)
9 1/4 (235)
7 1/16” (179)
9 3/16” (233)
6 9/16” (167)
37 1/16”(941)
20 1/16”(510)
5 5/8”(143)
4 1/4”(108)
12 9/16”(321)
14 1/2”(368)
14 1/2”(368)
31 7/8”(810)
34 5/8”(879)
3 3/16 (81)
93 3/8”(2372)
87”(2210)
2 5/16”(59)
6 15/16”(176)
36 15/16”(938)
41 9/16”(1056)
SEE NOTE 2
SEE NOTE 3
DETAIL A
SERVICE PANELSERVICE CLEARANCE48” (1219.2) (SEE NOTE 1FOR CLEARANCE)
NOTES:1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
15/16 (24)
6 5/8 (168)6 5/16 (160)3 11/16 (94)3 3/8 (86)
DDiimmeennssiioonnaall DDaattaa
18 SS-SVX001D-EN
Figure 10. 20.9 and 25 ton condensing, manifolded compressor – in (mm)
93 1/4” (2369)
10 7/16” (266)13 5/8”(346)
35 3/16”(893)
10 1/4”(260)
12”(304)
41 7/16”(1052)
46 11/16”(1186)
1/2”(13)10 1/8”
(257)
14 3/16”(360)
45 3/8”(1152)
44 3/16”(1122)
9”(229)
9”(229)
25 5/8”(651)
13/16” (21)1 9/16” (40)
8 1/4”(210)
7” (177)6 1/2” (164)
9 1/16” (230)
14 1/2”(368)
24 3/8”(620)
37 7/8”(962)
40 5/8”(1032)43 1/16”
(1093)
6 3/16” (157)
4 3/16”(107)
2 3/16”(55)
4 5/8”(118)
34 5/8”(880)
4 5/8”(118)
3”(76)
87” (2211)
93” (2363)
50 3/4”(1289)
SERVICE PANEL
DETAIL A
SEE NOTE 2
OPTIONAL REAR ACCESSDIMENSIONAL DETAIL
CONTROL WIRINGLINE VOLTAGE
SUCTION LINE
LIQUID LINE
BOTTOM OF UNIT
SERVICE PANEL SIDE
LIQUID LINE
REFRIGERANT GAUGE ACCESS
SUCTION LINE
LINE VOLTAGECONTROL WIRING
FRONT DETAIL ADIMENSIONAL DETAIL
SEE NOTE 3
NOTES:1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36” ( 914.4) FROM WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72” (1828.8). RECOMMENDED SERVICE CLEARANCE 48” (1219.2)2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100” (2540) MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER OR FALLING SNOW FROM ROOF DOES NOT POUR/FALL DIRECTLY ON UNIT3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
HAIL GUARD(OPTIONAL)
HAIL GUARD(OPTIONAL)
HAIL GUARD(OPTIONAL)
SERVICE CLEARANCE48” (1219.2) (SEE NOTE 1FOR CLEARANCE)
Each unit ships with a holding charge of dry nitrogen.The nitrogen should be removed and the entire systemevacuated (at the proper time) to avoid possiblecontamination.
1. Remove the compressor service access panel.
2. Locate the liquid and suction line access valves.Check that the piping connection stubs (Figure 15,p. 22) line up properly with the holes in the unitcabinet.
Figure 15. Outdoor units - refrigerant piping (with drynitrogen)
Gas Line Gauge Port
ManifoldGauges
Liquid Line Gauge Port
3. Install gauges to determine if the circuits are stillpressurized. If not, the charge has escaped andshould be repaired as required to obtain a leak-freecircuit. If the circuits are still pressurized, use thegauges to slowly release the nitrogen charge to theatmosphere and remove both seal caps from theoutdoor unit connection stubs.
5. Shut off nitrogen supply. Shut off the manifoldvalve for the line that is connected to the suctionline access valve. Disconnect the line from theaccess valve.
Refrigerant Piping Procedures(Indoor Unit)Once liquid and suction lines are complete to therefrigerant connections on the indoor unit, remove thegauge port core(s) on the indoor unit connection stubsto release the dry nitrogen charge.
2. Turn on nitrogen supply. Nitrogen enters throughthe liquid line gauge port.
3. Braze the liquid line connections.
4. Open the gauge port on the suction line and thenbraze the suction line to the connection stub.Nitrogen will bleed out the open gauge port on thesuction line.
After the brazing operation of refrigerant lines to boththe outdoor and indoor unit is completed, the fieldbrazed connections must be checked for leaks.Pressurize the system through the gauge port with drynitrogen to 200 psi. Use soap bubbles or other leak-checking methods to ensure that all field joints are leakfree. If not, release pressure, repair and repeat leak test.
System Evacuation1. After completion of leak check, evacuate the
system.
2. Attach appropriate hoses from manifold gauge togas and liquid line pressure taps.
NNoottee:: Unnecessary switching of hoses can beavoided and complete evacuation of all linesleading to sealed system can beaccomplished with manifold center hose andconnecting branch hose to a cylinder of R-410A/R–22 and vacuum pump.
3. Attach center hose of manifold gauges to vacuumpump.
4. Evacuate the system to hold a 500 micron vacuum.
5. Close off valve to vacuum pump and observe themicron gauge. If gauge pressure rises above 500microns in one minute, then evacuation isincomplete or the system has a leak.
6. If vacuum gauge does not rise above 500 microns in10 minutes, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off,open valve on refrigerant cylinder and allowrefrigerant pressure to build up to about 80 psig.
8. Close valve on the refrigerant supply cylinder. Closevalves on manifold gauge set and removerefrigerant charging hoses from liquid and gasgauge ports.
9. Leak test the entire system. Using properprocedures and caution, as described in theprevious section, repair any leaks found and repeatthe leak test.
Insulating and IsolatingRefrigerant LinesInsulate the entire suction line with refrigerant pipinginsulation. Also insulate any portion of the liquid lineexposed to temperature extremes. Insulate and isolateliquid and suction lines from each other. Isolaterefrigerant lines from the structure and any duct work.
IImmppoorrttaanntt::
1. To prevent possible noise or vibrationproblems, be certain to isolaterefrigerant lines from the building.
2. All suction and hot gas bypass piping (ifinstalled) should be insulated from thetermination in the air handler to thecondensing unit cabinet entry. Failureto do so can cause condensate drip offand performance degradation.
3. Prior to starting a unit, it is advisable tohave the approved oils available in theevent oil needs to be added to thesystem.
4. Refer to Application Guide SS-APG008*-EN for units needingadditional oil and for oil amounts.
For units equipped with compressors containing siteglasses, the oil level must be visible through the sight
IInnssttaallllaattiioonn
SS-SVX001D-EN 25
glass when the compressor is running under stabilizedconditions and a few minutes after the compressor hasstopped.
Refrigerant Charging ProcedureIf charging by weight, refer to “Charging Levels,” p. 26for starting change. If refrigerant adjustments areneeded because of length of line, refer to the ChargingCharts and Superheat values available on unit accesspanels.
Refer to Wiring Matrix and Device Location Matrix forlist of charging charts and super heat tables available ine-Library. Charge by weight through the gauge port onthe liquid line.
NNootteess::
• Refrigerant should only be charged in theliquid state.
• When possible, always charge therefrigerant into the liquid line of the unit.
• If the entire charge can’t be charged into theliquid line, the balance of the unit chargecan be metered through a chargingmanifold set as liquid — preferably througha schrader valve into the suction line to thecompressor — only while the compressor isrunning.
• Check and adjust superheat using thesuperheat table, then re-check chargingcharts to determine if charge corrections arenecessary. Refer to Charging Data for list ofsuper heat tables available in e-Library.
Notes:1. For line lengths other than 25', please refer to the Application Guide (SS-APG008*-EN) for charge levels, oil addition and line sizes.2. TTA0604DA and TTA0724*A need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8” to 1 1/8”).3. TTA2514DC and TTA3004*C are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to
2.125 inch) (1 5/8" to 2 1/8"). See Refrigerant Charging Procedure for transition tube location and electrical connections.
IInnssttaallllaattiioonn
SS-SVX001D-EN 27
Liquid ChargingThis procedure is accomplished with the unitoperating. Electrical connections must be complete. Donot proceed until the system is ready to operate.
NNoottee:: The compressor access panel must be installedwhen the unit is running and being charged.Manifold hoses must be routed throughrefrigerant gauge access hole(s). See“Dimensional Data,” p. 10 for specific locations.
1. Turn on power to the unit. Allow the system to runfor 15 minutes to stabilize operating conditions.
2. Measure airflow across the indoor coil. Comparethe measurements with the fan performance data inthe Data/Submittal. Once proper airflow isestablished, compare discharge pressure and liquidtemperature to the charging charts. Add or removerefrigerant (liquid only) as required to obtain correctdischarge pressure and liquid temperature.
3. Check suction line superheat and condenser sub-cooling to ensure the unit is operating properly.
4. Disconnect all power to the unit.
IImmppoorrttaanntt:: If the unit is charged and left withoutpower until a later date, the crankcaseheater should be energized for aminimum of 8 hours prior to poweringthe compressor(s).
Field wiring consists of providing power supply to theunit, installing the system indoor thermostat or zonesensor and providing low voltage systeminterconnecting wiring. Access to electrical connectionlocations is shown in “Dimensional Data,” p. 10.Determine proper wire sizes and unit protective fusingrequirements by referring to the unit nameplate. Fieldwiring diagrams for accessories are shipped with theaccessory.
IInnssttaallllaattiioonn
28 SS-SVX001D-EN
Unit Power SupplyThe installer must provide line voltage circuit(s) to theunit main power terminals as shown by the unit wiringdiagrams. Adhesive backed diagrams are affixed insidethe control box cover panel. Wiring diagrams are alsoavailable through e-Library or by contacting a localsales office. Power supply must include a disconnectswitch in a location convenient to the unit. Ground theunit according to local codes and provide flexibleconduit if codes require and/or if vibration transmissionmay cause noise problems.
IImmppoorrttaanntt:: All wiring must comply with applicablelocal and national (NEC) codes. Type andlocation of disconnect switches mustcomply with all applicable codes.
Low Voltage WiringMount the indoor thermostat, zone sensor, orprogrammable zone sensor in accordance with thecorresponding thermostat installation instructions.Install color-coded, weather-proof, multi-wire cableaccording to the Condenser and Air Handler Pairingguide (SS-SVN016*-EN).
NNoottee:: Refer to thermostat or zone sensor wireinstallation guide for proper wire gauge.
Symbio™™ ControlsWiring shown with dashed lines is to be furnished andinstalled by the customer. All customer supplied wiringmust be copper only and must conform to NEC andlocal electrical codes. Codes may require line of sightbetween disconnect switch and unit.
Figure 17. Symbio™™ jobsite connections
Zone Sensor See Note 2
T’statSee Note 2
Air Handler
Disconnect Switch(By Others)
Disconnect Switch(By Others)See Note 1
ElectricHeat Accessory
Disconnect Switch(By Others)See Note 1
B
A
B
D
EC
PPoowweerr WWiirreess
AA.. 3 wires, line voltage for 3 phase, 1 grounding wire**
BB.. 3 wires, line voltage for 3 phase, (2 wires for singlephase) 1 grounding wire**
CCoonnttrrooll WWiirreess
CC.. Cooling only (or Cooling with Heat) thermostat: 4 to7 wires depending on stages of cooling and electricheat
DD.. Wiring between indoor and outdoor unit: 5 to 11wires depending on unit control options*
EE.. Zone Sensor: 4 to 7 wires depending on zone sensormodel*
Use factory-supplied 165 ft. length of Comlink cablewith a PVC jacket, 18/1 PR, stranded shield, 25 PF/FTplenum rated for the field communication signalwiring. Refer to wiring diagram schematics foridentification of shielded twisted pairs.
IInnssttaallllaattiioonn
SS-SVX001D-EN 29
NNootteess::
1. When electric heater accessory is used,single point power entry or dual point powerentry is field optional. Single point powerentry option is through electric heater only.
2. *Choose only one of the following;Thermostat, Mechanical Zone Sensor,Programmable Zone Sensor Panel or BASZone Sensor.
IImmppoorrttaanntt:: For the EDC switch to be functional andthereby facilitate reliable unit operation,make the EDC connections from the indoorto the outdoor control boxes.
Field WiringRefer to the latest version of Condenser and AirHandler Pairing guide (SS-SVN016*-EN) forinstructions on field wiring connections.
IInnssttaallllaattiioonn
30 SS-SVX001D-EN
Refrigerant Circuit
Figure 18. Typical split system cooling refrigerant circuit — microchannel
FILTER DRIER
NOTE A: ONLY ONE INDOOR COIL REFRIGERANT ENTRY AND EXIT CIRCUIT IS SHOWN. ALL MODELS HAVE MULTIPLE ENTRY AND EXIT CIRCUITS.NOTE B: DUAL CIRCUIT MODELS HAVE 2 REFRIGERATION CIRCUITS. MANIFOLD CIRCUIT MODELS HAVE 2 COMPRESSORS BUT 1 REFRIGERATION CIRCUIT.
TXV
S
D
COMPRESSOR
LOW PRESSURESWITCH (LPCO)
FIELD SUPPLIEDINTER-CONNECTING
TUBING
OU
TD
OO
R C
OIL
IND
OO
R C
OIL
EXPANSIONVALVE BULB
EQUALIZERTUBE
NOTE A
NOTE A
HIGH PRESSURESWITCH (HPCO)
GAUGECONNECTION
DISCHARGETEMPERATURE
LIMIT (DTL)
AIR
AIR
GAUGECONNECTION
INDICATES DIRECTION OFREFRIGERANT FLOW
COOLING ONLY CIRCUIT DIAGRAM
IInnssttaallllaattiioonn
SS-SVX001D-EN 31
Pre-StartControl Circuit FeaturesNNoottee:: Not all of these features may be required for your
unit, check electrical schematic.
Discharge Temperature Limit (DTL)The control’s sensor is located on the discharge line.This device will shut off the compressor and theoutdoor fan(s) if the discharge temperature exceeds theDTL setting. Once the discharge temperature hasreturned to normal, the compressor will cycle back on.
Low Outdoor Ambient CoolingAll Odyssey units with Symbio™ 700 controls havecooling capabilities down to 0°F as standard. Attemperatures below 50°F, some reduction in coolingcapacity can be expected. When the optional LowAmbient Accessory kit is field installed, the full capacityof the unit is available down to 0°F.
Evaporator Defrost Control (EDC)This control is located in the Air Handler. The control’ssensing tube is embedded vertically in the evaporatorcoil, near the center. This device will stop thecompressor if the indoor coil temperature drops belowits setting. The indoor air will still circulate across thecoil bringing the temperature of the coil back up to thecut-in temperature of the evaporator defrost control.
Low Pressure Cut-Out (LPC)This control’s sensor is located in the suction (gas) line,near the compressor. This control will stop the
compressor and the outdoor fans if suction pressuredrops below the Low Pressure Cut-Out setting. Oncethe suction pressure has returned to normal, thecompressor and outdoor fans will cycle back on.
High Pressure Cut-Out (HPCO)This control’s sensor is located in the discharge line.This device will shut off the compressor and theoutdoor fan(s) if the discharge pressure exceeds theHigh Pressure Cut-Out’s setting. Once the dischargepressure has returned to normal, the compressor willcycle back on.
Internal Overload Protector (IOL)This device is embedded in the compressor. It will shutoff the compressor if the discharge temperature of thecompressor exceeds its design trip temperature.
NNoottee:: The IOL will put the compressor back inoperation once the compressor motor heat hasdropped below the trip setting; however, a checkof the refrigerant and electrical systems shouldbe made to determine the cause and becorrected.
Refer to the latest version of the Symbio™ 700Applications Guide (ACC-APG001*-EN) for details ontroubleshooting the control system.
SS-SVX001D-EN 33
Service Test Mode
The Symbio™ 700 supports a Service Test Mode thatcan be used to energize the various components of thesystem, either to support general system startup tasksor to support troubleshooting. The user can initiateService Test Mode through the controller userinterfaces, including the Symbio Service andInstallation mobile application.
The modes shown below can be initiated. Dependingon the equipment configuration, the controller will
energize the appropriate outputs. A user-selectedtimeout value will determine how long the controllerwill remain in any given state once initiated. Fordetailed information on how each Service Test State isinterpreted based on the equipment’s configuration,refer to the Symbio 700 Odyssey Controls ApplicationGuide ((ACC-APG001*-EN).
Perform all of the indicated maintenance procedures atthe intervals scheduled. This will prolong the life of theunit and reduce the possibility of costly equipmentfailure.
MonthlyConduct the following maintenance inspections onceper month.
☐ Check unit wiring to ensure all connections are tightand that the wiring insulation is intact.
☐ Inspect the condenser coils for dirt and debris. If thecoils appear dirty, clean them.
☐ With the unit operating in the cooling mode, checkthe suction and discharge pressures and comparethem with Pressure Curve values. Record thesereadings on the “Maintenance Log,” p. 36.
Annually (Cooling Season)The following maintenance procedures must beperformed at the beginning of each cooling season toensure efficient unit operation.
☐ Perform all of the monthly maintenanceinspections.
☐ With the unit operating, check unit superheat andrecord the reading in the “Maintenance Log,” p. 36.
☐ Remove any accumulation of dust and/or dirt fromthe unit casing.
☐ Remove corrosion from any surface and repaint.Check the gasket around the control panel door toensure it fits correctly and is in good condition toprevent water leakage.
☐ Inspect the control panel wiring to ensure that allconnections are tight and that the insulation isintact.
NNoottee:: Condenser fan motors are permanentlylubricated.
☐ Check refrigerant piping and fittings for leaks
☐ Inspect the condenser coils for dirt and debris. If thecoils appear dirty, clean them.
Coil CleaningRegular coil maintenance, including annual cleaning-enhances the unit's operating efficiency by minimizing:
• compressor head pressure and amperage draw• water carryover• fan brake horsepower• static pressure losses
At least once each year — or more often if the unit islocated in a “dirty” environment — clean the coil usingthe instructions outlined below. Be sure to follow theseinstructions as closely as possible to avoid damagingthe coils.
Due to the soft material and thin walls of the MCHEcoils, the traditional field maintenance methodrecommended for Round Tube Plate Fin (RTPF) coilsdoes not apply to microchannel coils. Moreover,chemical cleaners are a risk factor to MCHE due to thematerial of the coil. The manufacturer does notrecommend the use of chemical cleaners to cleanmicrochannel coils. Using chemical cleaners could leadto warranty claims being further evaluated for validityand failure analysis.
The recommended cleaning method for microchannelcondenser coils is pressurized water or air with a non-pinpoint nozzle and an ECU of at least 180 withpressure no greater than 600 psi. To minimize the risk
SS-SVX001D-EN 35
of coil damage, approach the cleaning of the coil withthe pressure washer aimed perpendicular to the face of
the coil during cleaning. Optimum clearance betweenthe sprayer nozzle and the microchannel coil is 1”–3”.
Condenser Air HandlerRefrigerant Charging CurveSuperheat and Charge Table Pressure Curves
TTA0604DA* TWE0764DA* 436759020001 436759020001
TTA0724*A* TWE0904*A* 436759030001 436759030001
TTA0604DD* TWE0724DB* 436759040001 436759530001
TTA0724*D* TWE0724*B* 436759050001 436759540001
TTA0764DA* TWE0764DA* 436765800001 436765800001
TTA0764DA* TWE1014DA* 436760750001 436760750001
TTA0904*A* TWE0904*A* 436765810001 436765810001
TTA0904*A* TWE1204*A* 436759750001 436759750001
TTA0764DD* TWE0764DB* 436765820001 436766300001
TTA0904*D* TWE0904*B* 436765830001 436766240001
TTA1014DA* TWE1014DA* 436759100001 436759100001
TTA1204*A* TWE1204*A* 436759110001 436759110001
TTA1014DC* TWE1014DA* 436759120001 436759120001
TTA1204*C* TWE1204*A* 436759130001 436759130001
TTA1014DD TWE1014DB* 436759140001 436759570001
TTA1204*D TWE1204*B 436759150001 436759580001
TTA1264DD* TWE1264DB* 436765880001 436766310001
TTA1504*D* TWE1504*B* 436765890001 436766250001
TTA1564DD* TWE1564DB* 436765900001 436765900001
TTA1564DD* TWE2014DB* 436760760001 436760760001
TTA1804*D* TWE1804*B* 436765910001 436765910001
TTA1804*D* TWE2404*B* 436759740001 436759740001
TTA1564DC* TWE1564DB* 436765920001 436765920001
TTA1804*C* TWE1804*B* 436765930001 436765930001
TTA2014DD* TWE2014DB* 436759220001 436759220001
TTA2404*D* TWE2404*B* 436759230001 436759230001
TTA2014DC* TWE2014DB* 436759240001 436759240001
TTA2404*C* TWE2404*B* 436759250001 436759250001
TTA2514DC* TWE2514DB* 436759260001 436759260001
TTA3004*C* TWE3004*B* 436759270001 436759270001
TTA0902*A* TWE0902*A* 436759440001 N/A
TTA1202*A* TWE1202*A* 436759450001 N/A
TTA1802*D* TWE180B* 436759460001 N/A
TTA2402*D* TWE240B* 436759470001 N/A
38 SS-SVX001D-EN
Wiring DiagramMatrix and Device Location
Table 10. TTA wiring diagrams
Part Number Description Applicability
1213-4177Power Schematic (Wiring Diagram) for units with DualCompressors and Dual Fans
All Units with Digit 4-6 = 156/180/201/240/251/300
1213-4178Power Schematic (Wiring Diagram) for units with DualCompressors and Single Fans
All Units with Digit 4-6 = 060/072/076/090/101/120/126/150 AND Digit 9 = "C" or "D"
1213-4176Power Schematic (Wiring Diagram) for units with SingleCompressors and Single Fan
All Units with Digit 4-6 = 060/072/076/090/120and Digit 9 = "A"
1213–4267Control Schematic (Wiring Diagram) for units with Singlecompressor and Single Fan
All TTA Units with Digit 4-6 = 060/072/090/120and Digit 9 = "A"
1213–4268Control Schematic (Wiring Diagram) for units with Dualcompressor and Single Fan
All TTA Units with Digit 4-6 = 060/072/090/120/150 AND Digit 9 = "D" Digit 4-6 = 101/120 andDigit 9 = "C"
1213–4269Control Schematic (Wiring Diagram) for units with Dualcompressor and Dual Fans
All TTA Units with Digit 4-6 = 156/180/240/300AND Digit 9 = "C" or "D" Digit 4-6 = 201/251 andDigit 9 = "C"
1213–4179Control Schematic (Wiring Diagram) for units with SingleCompressor (Unloading) and Single Fan
All TTA Units with Digit 4-6 = 076/090 and Digit 9= "A"
1213–4180Control Schematic (Wiring Diagram) for units with Dualcompressor (Unloading) and Single Fan
All TTA Units with Digit 4-6 = 076/090/101/120/126/150 Digit 9 = "D"
1213–4181Control Schematic (Wiring Diagram) for units with Dualcompressor (Unloading) and Dual Fans
All TTA Units with Digit 4-6 = 201/240 Digit 9 ="D"
Table 11. TTA device location
Part Number Description Applicability
1213–3583 Device Location Print All TTA Units with Digit 4-6 = 060/072/076/090/101/120/126/150
1213–3584 Device Location Print All TTA Units with Digit 4-6 = 156/180/201/240/251/300
SS-SVX001D-EN 39
WarrantyFor Commercial UnitaryEquipment Rated 25 Tons andUnder and Related AccessoriesPPrroodduuccttss CCoovveerreedd — This warranty is extended byTrane, and applies to the following products:
• All packaged and split system air conditioners andheat pumps have a rated capacity of 25 tons andunder.
• All packaged combinations gas/electric airconditioners having a rated capacity of 25 tons andunder.
• All packaged combination gas/electric airconditioners having a rated capacity of 1.5 through5 tons single phase electric power and used forcommercial applications. (As used in this warranty,a commercial application is any application wherethe end purchaser uses the product for other thanpersonal, family or household purposes.)
• All accessories for the above products which aresold by Trane and applied in accordance with Tranespecifications.
Basic WarrantyThe warrantor warrants for a period of twelve (12)months from the initial start-up or eighteen (18)months from date of shipment, whichever is sooner,that the products covered by this warranty (1) are freefrom defects in material and manufacture, and (2) havethe capacities and ratings set forth in the warrantor’scatalogs and bulletins. If any part of your airconditioner fails because of a manufacturing defect,Warrantor will furnish without charge the requiredreplacement part.
If the heat exchanger fails because of a manufacturingdefect within five years from the date of start-up,Warrantor will furnish without charge a replacementheat exchanger. In addition, if the optional, factoryinstalled, stainless steel heat exchanger fails becauseof a manufacturing defect within ten years from thedate of start-up, Warrantor will furnish without chargea replacement heat exchanger.
Any local transportation, related service labor anddiagnosis calls are not included. In addition, if thesealed motor-compressor fails because of amanufacturing defect within the second through fifthyear from the date of original purchase, Warrantor willfurnish without charge the required replacementcompressor.
Exclusions and LimitationsThe warrantor’s obligations and liabilities under thiswarranty are limited to furnishing F.O.B. factory orwarehouse at the warrantor-designated shipping point,freight allowed to Buyer’s city (or port of export forshipments outside the conterminous United States) areplacement product or, at the option of the warrantor,parts for the repair of the product not conforming tothis warranty and which have been returned to thewarrantor.
The warrantor’s warranty is conditional on theCustomer providing written notice to the warrantorwithin thirty (30) days of the discovery of the defect. Noproduct shall be returned to the warrantor without thewarrantor’s written permission. No liability whatevershall attach to warrantor until said products have beenfully paid for and then said liability shall be limited tothe purchase price of the equipment shown to bedefective.
The warranty does not apply to any compressor or gas-fired heat exchanger which has been repaired oraltered in such manner as, in the judgement of thewarrantor, affects its stability or reliability. Thiswarranty does not cover (1) any heat exchanger whichhas been fired with an improper type of fuel (2) a heatexchanger which is installed in a beauty parlor, drycleaning establishment, de-greasing plant or in anycorrosive atmosphere; or (3) any heat exchanger whichis not shown to be defective by the warrantor’sinspection.
This warranty does not cover damage due to accident,abuse, improper use, external causes, freezing,corrosion, erosion or deterioration. Localtransportation, related service labor, air filters,diagnosis calls, refrigerant and related items are notcovered.
THE WARRANTY AND LIABILITY SET FORTH HEREINARE IN LIEU OF ALL OTHER WARRANTIES ANDLIABILITIES, WHETHER IN CONTRACT OR INNEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR INFACT, INCLUDING IMPLIED WARRANTIES ORMERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE AND ANY IMPLIEDWARRANTIES OTHERWISE ARISING FROM THECOURSE OF DEALING OR TRADE. IN NO EVENTSHALL THE WARRANTOR BE LIABLE FOR ANYINCIDENTAL OR CONSEQUENTIAL DAMAGES.
The warrantor makes certain further warrantyprotection available on an optional, extra-cost basis.Any further warranty must be in writing. If you wishfurther help or information concerning this warranty,contact: Trane — Warrantor, 2701 Wilma RudolphBlvd., Clarksville, TN 37040
Trane and American Standard create comfortable, energy efficient indoor environments forcommercial and residential applications. For more information, please visit trane. com oramericanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design andspecifications without notice. We are committed to using environmentally conscious print practices.