SPAU 110 CResidual overvoltage relay
Users manual and Technical description
-
2SPAU 110 CResidual
overvoltage relay
Contents Features
..........................................................................................................................
2Application
.....................................................................................................................
3Description of function
..................................................................................................
3Connections
...................................................................................................................
4Configuration of output relays
........................................................................................
6Operation indicators
.......................................................................................................
7Combined power supply and I/O module
......................................................................
7Technical data (modified 2002-04)
.................................................................................
8Applications
..................................................................................................................
10Testing
.........................................................................................................................
17Maintenance and repair
................................................................................................
20Spare parts
....................................................................................................................
20Ordering numbers
........................................................................................................
20Dimensions and instructions for mounting
..................................................................
21Information required with order
...................................................................................
22
The complete users manual for the residual overvoltage relay
SPAU 110 C includesthe following documents:
Residual overvoltage relay SPAU 110 C, general part 1MRS
750607-MUM ENResidual voltage relay module SPCU 1C6 1MRS 750509-MUM
ENGeneral characteristics of C-type relay modules 1MRS 750328-MUM
EN
Features Definite-time residual overvoltage
earth-faultprotection
Two independent operation stages, e.g. one forsignalling and the
other for tripping
Freely selectable output relay functions
Flexible adaptation to different protection ap-plications
Digital display of setting values, residual voltageand recorded
fault values
Data communications via serial interface
Continuous internal self-supervision with faultdiagnosis
1MRS 750607-MUM EN
Issued 1997-01-09Modified 2002-04-25Version B (replaces 34 SPAU
14 EN1)Checked MKApproved OL
Data subject to change without notice
-
3Application The residual overvoltage relay SPAU 110 C
isdesigned to be used for earth fault protection inisolated
neutral, resistance earthed or reactanceearthed systems. In
resonant earthed systemsrelay starting can be used to control the
switch-ing device of the neutral resistor. The protection
relay can also be used for the earth fault protec-tion of
generators and motors and for the unbal-ance protection of
capacitor banks. The protec-tion relay forms an integrated
protection scheme,including two-stage earth fault protection
andflexible trip and signal functions.
Description offunction
The residual overvoltage relay SPAU 110 C is asecondary relay
which is to be connected to thevoltage transformers of the
protected object.When a fault occurs, the residual overvoltagerelay
can be used for tripping a circuit breaker orfor signalling an
earth-fault only, as required bythe protection application.
When the energizing voltage exceeds the set startvalue of the
low-set voltage stage U0>, the re-sidual overvoltage relay
starts. After the set oper-ate time t> the low-set stage
operates, if the faultstill persists. The high-set voltage stage
operatesin the same way. When the measured voltage
exceeds the set start value U0>>, the high-set
stagestarts, and after the set time t>> the high-set
stageoperates, if the fault still persists.
Start information from the residual overvoltagerelay is obtained
as a contact function, whichfurther can be used for controlling
other coop-erating protection relays, e.g. neutral currentmeasuring
earth fault relays.
The relay contains one optically isolated logicinput to be
controlled by an external controlvoltage. In the residual
overvoltage relay thecontrol input is used as a blocking input.
TRIP 1
TRIP 2
START 1
IRF
SIGNAL 1
SERIAL I/O
U o LOW-SET DEFINITE TIMERESIDUAL OVERVOLTAGE STAGE
HIGH-SET DEFINITE TIMERESIDUAL OVERVOLTAGE STAGE
BLOCKING FUNCTION FOR BOTH OVERVOLTAGE STAGES
SERIAL COMMUNICATION
59N
59N
BLOCKING
START 2
Fig. 1. Protection functions of the residual overvoltage relay
SPAU 110 C. The encircled numbersrefer to the ANSI (= American
National Standards Institute) number of the concerned
protectionfunction.
-
4@
100V110V
SGR/1
U2
U3U3 1 1 1 1
D C B A
+ -
Uaux
E
+-
(~)(~)
L1L2L3
A
N
dadn
SGR
28 29 30 10 11 61 62 70 71 72 74 75 77 78 80 81 68 69 65 66
7 53 2 4 68
SPAU 110 C
_
SPA-ZC_
Rx Tx
START1 SIGNAL1 TRIP2 TRIP1IRFBS
IRF
73 74 75
START2
F
TS2
TS1SGB
SS1
SS2
U1
54
I/O
t >>
t >Uo>
Uo>>
SERIALPORT
Fig. 2. Connection diagram for the residual overvoltage relay
SPAU 110 C.
Uaux Auxiliary supply voltageA,B,C,D,E,F Output relaysIRF
Self-supervision outputBS Blocking signalSS Start signalTS Trip
signalSGR Switchgroup for configuring trip and alarm signalsSGB
Switchgroup for configuring blocking signalsTRIP_ Trip
outputSIGNAL1 Signal on relay operationSTART_ Start information or
relay operationU1 Residual voltage relay module SPCU 1C6U2 Power
supply and I/O module SPTU 240S1 or SPTU 48S1U3 I/O module SPTE
1E11SERIAL PORT Serial communication portSPA-ZC_ Bus connection
moduleRx/Tx Receiver input Rx and transmitter output Tx of the bus
connection module
Connections
-
5Mad
e in
Fin
land
28
29
30
73
74
75
70
71
72
61
62
65
66
68
69
80
81
77
78
10
11
TTL
B470
497
Rx
Tx
Fig.3. Rear view of residual overvoltage relay SPAU 110 C.
Specification of input and output terminals
Terminals Function
28-29 Residual voltage U0 (Un = 100 V)28-30 Residual voltage U0
(Un = 110 V)10-11 External blocking signal (BS)61-62 Auxiliary
power supply. When DC voltage is used the positive pole is
connected
to terminal 61.65-66 Trip output 1 of stages U0> and
U0>> (TRIP 1)68-69 Trip output 2 of stages U0> and
U0>> (TRIP 2)80-81 Signal on tripping of U0> and
U0>> stages (SIGNAL 1)77-78 Signal on tripping of U0>>
stage, start of U0> and U0>> stages (START 1)73-74-75
Start of U0> stage (START 2).
In normal conditions the contact interval 73-75 is closed.When
the U0> stage starts, the contact interval 74-75 closes.
70-71-72 Self-supervision (IRF) alarm output.In normal
conditions the contact interval 70-72 is closed. When the
auxiliaryvoltage is lost or an internal fault is detected the
contact interval 71-72 closes.Protective earth terminal
The protection relay is connected to the fibreoptic data
communication bus over the busconnection module SPA-ZC 17 or SPA-ZC
21.
The bus connection module is fitted to the D-type connector on
the rear panel of the relay.The pre-mounted opto-connectors of the
opti-cal fibres are plugged into the counter connec-tors Rx and Tx
on the bus connection module.
-
6addition, the following functions can be se-lected with the
switches of the SGR switchgrouplocated on the front panel:
Configuration ofoutput relays
The start signal of the U0> stage is permanentlywired to
output relay F and the trip signal tooutput relay A. The trip
signal of the U0>> stageis permanently wired to output relay
B. In
Switch Function Default Userssettings settings
SGR/1 Links the BS blocking signal to the residual
overvoltagerelay module 1
SGR/2 Links the start signal of the U0>> stage to output
relay D 1
SGR/3 Links the start signal of the U0> stage to output relay
D 1
SGR/4 Links the trip signal of the U0>> stage to output
relay D 1
SGR/5 Links the trip signal of the U0>> stage to output
relay C 1
SGR/6 Links the trip signal of the U0>> stage to output
relay A 1
SGR/7 Links the trip signal of the U0> stage to output relay
C 1
SGR/8 Links the trip signal of the U0> stage to output relay
B 1
The circuit breakers can be operated directlyboth via output
relay A and output relay B. Thusthe protection stages may have
their own output
relay or two separate circuit breakers can becontrolled with one
protection relay.
-
7Operationindicators
RS 422 Ser.No.
SPAU 110 C
2
5
1306
fn = 50Hz60Hz
12345
/ >tt
n )( >n )( >>
>>/ tt%[ ]%[ ]
Uaux80...265V
~
18...80V
SPCU 1C6
REGISTERS
0 0 0 0
12345678
0 1
SGR
n/U Uo %[ ]UoUo
nU = 100V 110V IRF
1310
[ ]s>t0.5
0.05 1.0
50
10
0.5
0.05 1.0
2
10
20STEP
RESET
SG1
0 1
12345678
>U >>U
SPCU 1C6
B
>>
[ ]s>>t
U o
nU>U o
nUUo 80
o o
[ ]%
[ ]%
U
STEP
1. Either voltage stage has its own start/opera-tion indicator
(U0> and U0>>), located in theright bottom corner of the
front panel of therelay module. Yellow light indicates that
theconcerned stage has started and red light thatthe stage has
operated (tripped).
With the SG2 switchgroup the start and tripindicators can be
given a latching feature,which means that the LEDs remain lit,
al-though the signal that caused operation fallsbelow the set
value. The indicators are resetwith the RESET push-button. An
unresetindicator does not affect the operation of therelay.
2. The yellow LED (U0) above the display is litwhen the measured
residual voltage is shownon the display.
3. The red IRF indicator of the self-supervisionsystem indicates
that a permanent fault hasbeen detected. The fault code appearing
onthe display once a fault has been detectedshould be recorded and
notified when serviceis ordered.
4. The green Uaux LED on the front panel is litwhen the power
supply module operates prop-erly.
5. The LED indicator below each one of thesetting knobs is lit
to indicate that the settingvalue displayed refers to the concerned
set-ting knob.
6. The LED of the SG1 switchgroup is lit, whenthe checksum of
the switchgroup is displayed.
The operation indicators, the SG2 selectorswitchgroup and the
LEDs of the setting knobsare described more detailed in manual for
theresidual overvoltage relay module SPCU 1C6.
Combined powersupply and I/Omodule
The power supply and I/O module (U2) islocated behind the system
front panel of theprotection relay and can be withdrawn
afterremoval of the system front panel. The powersupply and I/O
module incorporates the powersource, the output relays, the control
circuits ofthe output relays and the electronic circuitry ofthe
external control input.
The power supply module is transformer con-nected, that is, the
primary side and the second-ary circuits are galvanically isolated.
The pri-mary side is protected by a slow 1 A fuse F1,placed on the
PC board of the module. Whenthe power source operates properly, the
greenUaux LED on the front panel is lit.
The power supply and I/O module is availablein two versions with
different input voltageranges:
- module SPTU 240 S1Uaux = 80...265 V ac/dc
- module SPTU 48 S1Uaux = 18...80 V dc
The permitted input voltage range of the powersupply and I/O
module inserted in the relay ondelivery is marked on the system
panel panel ofthe relay.
-
8Technical data(modified 2002-04)
Energizing inputs 100 V 110 VTerminals 28-29 28-30Rated voltage
Un 100 V 110 VContinuous voltage withstand 2 x Un 2 x UnPower
consumption at rated voltage
-
9Residual overvoltage relay module SPCU 1C6Low-set stage
U0>Start voltage U0> 2...100% x UnOperate time t>
0.05...100 s
High-set stage U0>>Start voltage U0>> 2...80% x Un
and , infiniteOperate time t>> 0.05...100 s
Data communicationTransmission mode Fibre optic serial busData
code ASCIISelectable data transfer rates 300, 1200, 2400,
4800 or 9600 BdFibre optic bus connection module,power supply
from host relay- for plastic fibre cables SPA-ZC 21 BB- for glass
fibre cables SPA-ZC 21 MMFibre optic bus connection module,
providedwith integral power supply unit- for plastic fibre cables
SPA-ZC 17 BB- for glass fibre cables SPA-ZC 17 MM
Insulation Tests *)Dielectric test IEC 60255-5 2 kV, 50 Hz, 1
minImpulse voltage test IEC 60255-5 5 kV, 1.2/50 s, 0.5 JInsulation
resistance measurement IEC 60255-5 >100 M, 500 Vdc
Electromagnetic Compatibility Tests *)High-frequency (1 MHz)
burst disturbance testIEC 60255-22-1- common mode 2.5 kV-
differential mode 1.0 kVElectrostatic discharge test IEC 60255-22-2
andIEC 61000-4-2- contact discharge 6 kV- air discharge 8 kVFast
transient disturbance test IEC 60255-22-4and IEC 61000-4-4- power
supply 4 kV- I/O ports 2 kV
Environmental conditionsSpecified ambient service temperature
range -10...+55CLong term damp heat withstand as per IEC
60068-2-3
-
10
@
100V110V
SGR/1
U2
U3U3 1 1 1 1
D C B A
+ -
Uaux
E
+
-
(~)(~)
SGR
28 29 30 10 11 61 62 70 71 72 77 78 80 81 68 69 65 66
7 53 2 4 68
SPAU 110 C
_
SPA-ZC_
Rx Tx
START1 SIGNAL1 TRIP2 TRIP1IRFBS
0
I
0
I
-
-
+
+
L1 L3
+
IRF
SGB
SS1
U1
54
I/O
t >>
t >Uo>
Uo>>
TS1
SS2
TS2
747573
F
START2
R
1)
AN
dadn
SERIALPORT
Applications
Example 1.The residualovervoltage relaySPAU 110 Cused for the
earthfault protection ofisolated neutralsystems.
1) Enable signal to the neutral current relay of the feeder
Fig. 4. The residual overvoltage relay SPAU 110 C used for the
earth fault protection of isolatedneutral systems.
An earth fault somewhere in a galvanically con-nected power
system causes residual voltage. Forthis reason the residual
overvoltage relay SPAU110 C is well adapted to be used as a
generalearth fault alarm relay that monitors a definedpart of the
power system.
The residual overvoltage relay SPAU 110 Cmeasures the residual
voltage from the opendelta winding of the voltage transformers.
Thisprocedure provides a relatively good accuracyof measurement.
The ferroresonances of thevoltage transformers are suppressed by a
resistorR incorporated in the open delta connection.
-
11
Switch SG1/SPCU 1C6 SGB/SPCU 1C6 SGR
1 1 0 Not in use 0 No blocking signal from feeders2 1 0 Not in
use 1 U0>> start signal to output
relay D3 0 Not in use 0 Not in use 0 No U0> start signal to
output
relay D4 0 No latching 0 No blocking to t> 0 No U0>>
trip signal to output
relay D5 0 U0>= 2...20%xUn 0 No blocking to t>> 1
U0>> trip signal to output
relay C6 0 U0>>=10...80%xUn 0 Not in use 0 No U0>>
trip signal to output
relay A7 1 0 Not in use 0 No U0> trip signal to output
relay C8 0 0 Not in use 0 No U0> trip signal to output
relay B 67
The low-set stage of the residual overvoltagerelay indicates
imminent earth faults. The re-sidual voltage in a sound isolated
neutral net-work is normally very small, even less than 1%of the
maximum residual voltage value. Thusthe low-set residual voltage
stage can be given alow setting value.
The low-set stage can be used for enabling theneutral current
measuring non-directional earthfault relays of the feeders. When an
earth faultoccurs on a feeder both the neutral current earthfault
relay of the feeder and the low-set stage ofthe busbar system
residual voltage relay have tostart to enable tripping of the
feeder circuitbreaker. The enabling system prevents unneces-sary
operation of the neutral current earth faultrelay at short
circuits, when a motor is started orunder normal service
conditions. If a directionalearth fault relay is used on the
feeder, no enablesignal is required.
The high-set stage is due to protect the busbarsystem and to
serve as unselective back-up pro-tection for the feeder erth fault
protection. Thesetting of the back-up protection stage of
theresidual voltage relay must not be lower thanthat of the earth
fault relays of the feeders. Alsopossible changes in the service
preconditionsshould be considered.
The high-set stage also serves as earth faultprotection for the
infeeder, if the trip signal isrouted to the HV side circuit
breaker of thepower transformer as well as to the LV sidecircuit
breaker. The trip signal for the HV sidecircuit breaker can be
taken, for instance, fromthe contacts 80-81 and be routed to the
circuitbreaker via an intermediate relay.
The switches of the residual overvoltage relaySPAU 110 C can be
set as follows:
}
t>>= 0,5...10 s
t>= 5...100 s
}
When the switches are set as above the outputcontacts of SPAU
110 C have the followingfunctions:
Contact Function
65-66 Signal on delayed operation of U0> stage68-69 Circuit
breaker trip signal from U0>> stage80-81 Alarm signal on
final trip of U0>> stage77-78 Start signal of U0>>
stage70-71-72 Self-supervision signal73-75 Blocking signal to the
neutral current earth fault relay of the feeder74-75 Start signal
of U0> stage, enable signal to the neutral current earth
fault
relay of the feeder
-
12
SPA-ZC_
Rx Tx
TRIP2
A
N
0
I
0
I
-
-
+
+
R an
G
@
100V110V
SGR/1
U2
U3U3 1 1 1 1
D C B A
+ -
Uaux
E
+
-
(~)(~)
SGR
28 29 30 10 11 61 62 70 71 72 74 75 77 78 80 81 68 69 65 66
7 53 2 4 68
SPAU 110 C
_
START1 SIGNAL1 TRIP2 TRIP1IRFBS
IRF
73 74 75
START2
F
TS2
TS1SGB
SS1
SS2
U1
54
I/O
t >>
t >Uo>
Uo>>
+
L1 L3
SERIALPORT
Example 2.Earth faultprotection ofgenerators andmotors.
Fig. 5. Residual overvoltage relay SPAU 110 C used for the
protection of a power generator.
-
13
Instead of using an open delta connection theresidual voltage
can be measured over a voltagetransformer connected to the neutral,
providedthe neutral is available. In the case of a blockconnected
generator the galvanically connectednetwork is limited by the
transformer, so a re-sidual overvoltage relay alone will form a
satisfac-tory earth fault protection. In the connectionabove the
residual voltage relay operates on earthfaults occurring in the
stator winding of thegenerator or in the deltawinding of the
trans-former. The low-set stage can be used for earthfault
signalling. Due to the risk of a double earth
fault in the system, the high-set stage of theresidual
overvoltage protection should be trip-ping. The signal tripping the
generator excitationis taken, for instance, from the contacts
77-78.
A resistor connected in parallel with the voltagetransformer
prevents HV side earth faults fromreflecting via the capacitances
over the blocktransformers to the LV side, where they couldcause
relay operations.
The switches of the residual overvoltage relaySPAU 110 C can be
set as follows:
Switch SG1/SPCU 1C6 SGB/SPCU 1C6 SGR
1 1 0 Not in use 0 No blocking signal from feeders2 0 0 Not in
use 0 no U0>> start signal to output
relay D3 0 Not in use 0 Not in use 0 No U0> start signal to
output
relay D4 0 No latching 0 No blocking to t> 1 U0>> trip
signal to output
relay D5 0 U0>= 2...20%xUn 0 No blocking to t>> 1
U0>> trip signal to output
relay C6 0 U0>>= 10...80%xUn 0 Not in use 0 No U0>>
trip signal to output
relay A7 0 0 Not in use 0 No U0>> trip signal to
output
relay C8 0 0 Not in use 0 No U0> trip signal to output
relay B 1
} t>= 0,5...10 s
t>>= 0.05...1.0 s}
When the switches are set as above the outputcontacts of SPAU
110 C have the followingfunctions:
Contact Function
65-66 Signal on delayed operation of U0> stage68-69 Circuit
breaker trip signal from U0>> stage80-81 Signal on final trip
of U0>> stage77-78 Trip signal to excitation circuit
breaker73-74-75 Start signal of U0> stage70-71-72
Self-supervision signal
-
14
L1L2L3
a
b
B A
0
I
0
I
-
-
+
+
@
100V110V
SGR/1
U2
U3U3 1 1 1 1
D C B A
+ -
Uaux
E
+-
(~)(~)
SGR
28 29 30 10 11 61 62 70 71 72 74 75 77 78 80 81 68 69 65 66
7 53 2 4 68
SPAU 110 C
_
SPA-ZC_
Rx Tx
START1 SIGNAL1 TRIP2 TRIP1IRFBS
IRF
73 74 75
START2
F
TS2
TS1SGB
SS1
SS2
U1
54
I/O
t >>
t >Uo>
Uo>>
SERIALPORT
Example 3.Unbalanceprotection ofcapacitor banks.
Fig. 6. Residual overvoltage relay SPAU 110 C used for unbalance
protection of a capacitor bank.
-
15
The unbalance protection of a star-connectedcapacitor bank can
also be implemented byusing the open delta connection for
measuringthe unbalance voltage. The capacitor bank iscomposed of
small units which are protected byinternal fuses. Burning of one or
more fusescauses unbalance, and to detect this unbalancethe
residual overvoltage relay SPAU 110 C isused. The function of the
low-set stage of the
relay is signalling and that of the high-set stagetripping. The
relay setting is determined by themanufacturer of the capacitor
bank, because thesetting depends on the number of capacitorunits
connected in parallel and in series andtheir rated values.
The switches of the residual overvoltage relaySPAU 110 C can be
set as follows:
}
Switch SG1/SPCU 1C6 SGB/SPCU 1C6 SGR
1 1 0 Not in use 0 No blocking signal from feeders2 0 0 Not in
use 1 U0>> start signal to output
relay D3 0 Not in use 0 Not in use 0 No U0> start signal to
output
relay D4 0 No latching 0 No blocking to t> 0 No U0>>
trip signal to output
relay D5 0 U0>= 2...20%xUn 0 No blocking to t>> 1
U0>> trip signal to output
relay C6 0 U0>>= 10...80%xUn 0 Not in use 0 No U0>>
trip signal to output
relay A7 0 0 Not in use 0 No U0> trip signal to output
relay C8 0 0 Not in use 0 No U0> trip signal to output
relay B 1
t>= 0.5...10 s
t>>=0.05...1 s}
When the switches are set as above the outputcontacts of SPAU
110 C have the followingfunctions:
Contact Function
65-66 Signal on delayed operation of U0> stage68-69 Circuit
breaker trip from U0>> stage80-81 Alarm signal on final trip
of U0>> stage77-78 Start signal of U0>> stage73-74-75
Start signal of U0> stage70-71-72 Self-supervision signal
-
16
Recorded data andfault analysis
The registers of the residual voltage relay mod-ule SPCU 1C6
provide a general view of theearth fault situations of the
substation and of thebehaviour of the network during normal
service.
Register 1 records the maximum measured re-sidual voltage as a
multiple of the rated voltageof the relay energizing input. If the
relay trips,the voltage at the moment of tripping is memo-rized. A
new trip erases the old value and updatesthe register. The
procedure is the same if avoltage measured exceeds the old value
recorded.
The data of register 1 show how close the settingvalues are to
actual values during normal opera-tion, by comparing the residual
voltage indi-cated by the relay with the setting value.
By using the information of register 1 it is alsopossible to
determine the smallest fault resist-ance at which an earth fault
extinguishes by itselfor by auto-reclosures. By giving the
low-setresidual voltage stage a signalling function andby selecting
an operate time that is equal to thefinal trip delay of the feeder
earth fault relay,register 1 allows the smallest fault
resistance,that caused operation, to be determined, whenthe total
earth fault current of the galvanicallyconnected network is
known.
The relay should be reset after start, to preventthe updating
level of the register from getting tohigh. Should the relay be
linked to an event
reporting unit, the residual voltage value onstarting of the
relay can be read and the registerscan be reset, when the start
signals reset. Thusthe residual voltage value measured on
startingof the relay is always known.
The number of times the different stages havestarted, registers
2 and 3, gives a picture of theoccurrence and distribution of the
earth faults inrespect of the fault resistances of the earth
faults.Frequent starts may indicate imminent earthfaults, e.g.
insulation faults or orther faults, thateasily may develop to a
total earth fault.
Registers 4 and 5 show the duration of the lateststart situation
of the stages, expressed in per centof the set operate time. Any
new start restarts thecounter from zero. If the stage trips, the
registerwill show 100 [%].
Registers 4 and 5 contain information on theduration of an earth
fault , or, if final trip hasbeen performed, the safety margin of
the grad-ing times of selective protection. Generally, theresidual
voltage does not disappear immediatelyafter opening of the circuit
breaker of the faultyfeeder, so the start situation of the
residualvoltage relay may continue for a short time afterthe
circuit breaker has opened.
Registers 1...5 are reset either by pressing theSTEP and RESET
push-buttons simultaneouslyor with a command, V102, over the SPA
bus.
-
17
Testing Testing should always be performed in accord-ance with
national regulations.
The protection relay incorporates an IRF func-tion that
continuously monitors the internalstate of the relay and produces
an alarm signal ondetection of a fault. According to the
manufac-turers recommendations the relay should besubmitted to
primary testing at five years inter-vals. These tests include the
entire protectionchain from the measurement transformers tothe
circuit breakers.
The secondary testing described in this manualis based on the
relays setting values duringnormal operation. If necessary, the
secondarytesting can be extended, for instance, by testingthe
protection stages with several different set-ting values.
As switch positions and setting values have to bealtered during
the test procedure the correctpositions of switches and correct
values of therelay during normal operation have to be re-corded,
for instance, on the reference card ac-companying the relay.
To enable secondary testing the relay has to bedisconnected from
the pilot circuits, either atthe disconnectable terminal blocks or
by usingthe test adapter fitted on the relay. It is extremely
important that the relay is disconnected fromthe residual
voltade transformers. A possible tripsignal wired from the residual
voltage relay tothe main circuit breaker should also be consid-ered
when the relay is tested.
When auxiliary voltage is connected to theprotection relay, the
relay performs a self-testingprogram, which excludes only the
matchingtransformers and the contacts of the outputrelays. The
operational condition of the relay istested by means of an ordinary
relay test set. Thetest includes the matching transformers,
theoutput relays and the accuracy of the operatevalues.
Equipment required for testing:
- adjustable voltage transformer 0...260 V, 1 A- isolating
transformer 220/220 V- voltmeter- clock or timer for time
measurement- DC voltage source for auxiliary voltage
supply- switches and lamps- supply and pilot wires-
multimeter
Note the rated voltage prior to connecting thepilot wires to the
relay terminals, see "Specifica-tion of input and output
terminals".
-
18
SIG
NAL1
V
TIM
ERST
ART
S1
L1N
+(~
)
-(~
)
S2
BSST
ART2
STAR
T1
L2
Uaux
TIM
ER S
TOP
TRIP
1TR
IP2
L3
@
100V110V
SGR/
1
U2
U3U3
11
11
DC
BA
+-
E
SGR
2829
3010
1161
6270
7172
7475
7778
8081
6869
6566
68
SPAU
110
C
_
IRF
7374
75
F
TS2
TS1
SGB
SS1
SS2
U1
54
I/O
t >>
t >Uo
>
Uo>>
IRF
L4L1
32
47
5
Fig. 7. Secondary test connection of residual overvoltage relay
SPAU 110 C.
After finishing the test connection and settingthe selector
switches, connect the auxiliary volt-age to the relay.
-
19
voltmeter. The measurement can be made at therated voltage of
the relay.
Starting
Carry out the test according to Fig. 7. Close theS1 switch and
raise the voltage slowly until therelay operates (L2 is lit). Then
read the startvoltage indicated on the voltmeter.
Operate time
Set the voltage to be fed to the relay for measur-ing the relay
operate time at 2 x the set start valueof stage U0>. The clock
is started by closing ofswitch S1 and stopped via contact 65-66
whenoutput relay A operates.
The operation of output relay C is indicated by L4.
When the relay starts, the U0> LED in the rightbottom corner
is lit with yellow light. When therelay trips, the light of the
same LED turns red.
Blocking
Set switches 4 and 5 of switchgroup SGB andswitch SGR/1 in
position 1 (ON).
Close switch S2. Increase the test voltage untilthe relay
starts, indicator U0> turns yellow.Wait until the set operate
time t> has elapsed.The low-set stage must not operate, i.e. the
U0>indicator must not turn red.
Testing of matchingtransformers
Apply voltage to the relay terminals and checkthat the voltage
value indicated on the relaydisplay is equal to the value measured
by the
Testing of low-setstage U0>
Set the switches of the SGR switchgroup asfollows before testing
of the low-set stage:
Switch Position
1 12 03 04 05 06 07 18 0
When the switches are set as above the outputrelays have the
following functions
Output relays Function(terminals)
A (65-66) Trip signal of U0> stageB (68-69) (Trip signal of
U0>> stage)C (80-81) Information on trip of U0>
stageD (77-78) Not in useE (70-71-72) Self-supervision signalF
(73-74-75) Start signal of U0>stage
Testing of high-setstage U0>>
Set the switches of the SGR switchgroup asfollows before
starting the test of the high-setstage:
Switch Position
1 12 13 04 05 16 07 08 0
When the switches are set as above, the outputrelays have the
following functions
Output relays Function(terminals)
A (65-66) (Trip signal of U0> stage)B (68-69) Trip signal of
U0>> stageC (80-81) Information on trip of U0>>
stageD (77-78) Start signal of U0>> stageE (70-71-72)
Self-supervision signalF (73-74-75) (Start signal of
U0>stage)
The test procedure is the same as that of the low-set stage, but
with the exception that when theoperate times are measured, the
clock is stoppedvia contact 68-69 on the operation of outputrelay
B.
The function of the IRF LED and the outputrelay E, when the
self-supervision alarm signal isactivated, can be tested with the
Trip test func-
tion described in the manual "General character-istics of C-type
SPC relay modules". The opera-tion of output relay E is indicated
by the L1 lamp.
Testing of self-supervisionoutput relay (IRF)
-
20
When used under the conditions specified inthe section
"Technical data", the relay is practi-cally maintenance-free. The
relay modules in-clude no parts or components sensitive to
ab-normal physical or electrical wear under normaloperating
conditions.
If the environmental conditions on site differfrom those
specified, as to temperature andhumidity, or if the atmosphere
around the relaycontains chemically active gases or dust, therelay
should be visually inspected during therelay secondary testing. The
visual inspectionshould focus on:
- Signs of mechanical damage to relay case andterminals
- Dust inside the relay cover or case; removecarefully by
blowing compressed air
- Signs of corrosion on terminals, case or insidethe relay
If the relay fails in operation or if the operationvalues
considerably differ from those mentionedin the relay
specifications, the relay should begiven a proper overhaul. Minor
measures can betaken by personnel from the customers instru-ment
work-shop, but major measures involvingthe overhaul of the
electronics are to be taken bythe manufacturer. Please contact the
manufac-turer or his nearest representative for furtherinformation
about checking, overhaul and cali-bration of the relay.
Note!The protection relays contain electronic circuitswhich are
liable to serious damage due to elec-trostatic discharge. Before
removing a module,ensure that you are at the same
electrostaticpotential as the equipment by touching the case.
Note!Static protective relays are measuring instru-ments and
should be handled with care andprotected against damp and
mechanical stress,especially during transport.
Maintenanceand repair
Spare parts Residual voltage relay module SPCU 1C6Combined power
supply and I/O module- Uaux = 80...265 V ac/dc SPTU 240 S1- Uaux =
18...80 V dc SPTU 48 S1Case (including I/O module) SPTK 1E11I/O
module SPTE 1E11Bus connection module SPA-ZC 17_ or SPA-ZC 21_
Residual overvoltage relay without test adapter
SPAU 110 C RS 422 010 -AA, CA, DA, FA
Residual overvoltage relay with test adapter RTXP 18
SPAU 110 C RS 422 210 -AA, CA, DA, FA
The two last letters of the ordering number designate the rated
frequency fnand the Uaux voltage range of the relay as follows:
AA correspond to fn = 50 Hz and Uaux = 80...265 V ac/dcCA
correspond to fn = 50 Hz and Uaux = 18...80 V dcDA correspond to fn
= 60 Hz and Uaux = 80...265 V ac/dcFA correspond to fn = 60 Hz and
Uaux = 18...80 V dc
Orderingnumbers
-
21
Dimensions andinstructions formounting
The relay case is basically designed for flush-mounting. The
mounting depth can be reducedby the use of a raising frame: type
SPA-ZX 111reduces the depth behind the mounting panelby 40 mm, type
SPA-ZX 112 reduces the depth
by 80 mm and type SPA-ZX 113 reduces thedepth by 120 mm. The
relay can also be mountedin a case for surface mounting, type
designationSPA-ZX 115.
Raising frameSPA-ZX 111SPA-ZX 112SPA-ZX 113
176136 96
74114154
a b
a b
Panel cut-out
129 1
139
1
142
162
136
3034
250
186216
Fig. 8. Dimensions of the residual overvoltage relay SPAU 110
C
The relay case is made of beige anodized alu-minium section.
A rubber gasket fitted on the mounting collarprovides an IP 54
degree of protection betweenrelay case and mounting panel, when the
relay isflush mounted.
The hinged cover of the relay case is made of aclear, UV
stabilized polycarbonate, and pro-
vided with a sealable fastening screw. A gasketalong the edge of
the cover provides an IP54degree of protection between the case and
thecover.
All input and output wires are connected to thescrew terminal
blocks on the rear panel. Eachterminal is dimensioned for one max.
6 mm2
wire or two max. 2.5 mm2 wires. The D connec-tor is intended for
serial communications.
-
22
Informationrequired withorder
1. Quantity and type designation 15 SPAU 110 C unit2. Order
number RS 422 010 -AA3. Rated frequency fn = 50 Hz4. Auxiliary
voltage Uaux = 110 V dc5. Accessories 15 bus connection modules
SPA-ZC 21 MM
2 fibre optic cables SPA-ZF MM 10014 fibre optic cables SPA-ZF
MM 5
6. Special requirements -
-
IRF
1310
[ ]s>t0.5
0.05 1.0
50
10
0.5
0.05 1.0
2
10
20STEP
RESET
SG1
0 1
12345678
>U >>U
SPCU 1C6
B
>>
[ ]s>>t
U o
nU>U o
nUUo 80
o o
[ ]%
[ ]%
U
STEP
SPCU 1C6Residual overvoltage relay module
Users manual and Technical description
-
2SPCU 1C6Residual overvoltage
relay module
Contents Features
..........................................................................................................................
2Description of operation
.................................................................................................
3Block
diagram.................................................................................................................
4Front panel
.....................................................................................................................
5Operation indicators
.......................................................................................................
5Settings
...........................................................................................................................
6Selector switches
.............................................................................................................
6Measured
data.................................................................................................................
7Recorded information
.....................................................................................................
8Menu chart
.....................................................................................................................
9Technical data
...............................................................................................................
10Serial communication parameters
.................................................................................
11
Event codes
..............................................................................................................
11Data to be transferred over the serial bus
.................................................................
12
Fault codes
....................................................................................................................
15
Features Low-set residual overvoltage stage U0> withdefinite
time operation characteristic, settingranges 2...20% x Un and
10...100% x Un
High-set residual overvoltage stage U0>> withdefinite time
operation characteristic, settingranges 10...80% x Un or 2...16% x
Un
The operation of the high-set residual over-voltage stage can be
set out of function by se-lecting the setting , infinitive
Effective suppression of harmonics of the inputenergizing
voltages
Local display of measured and set values as wellas data recorded
at the moment of a relay op-eration
Flexible selection of special operational featuresfor particular
applications
Continuous self-supervision of hardware andsoftware. At a
permanent fault the alarm out-put relay picks up and the other
outputs areblocked.
1MRS 750509-MUM EN
Issued 96-12-02Version A (replaces 34 SPCU 2 EN1)Checked L-W
UApproved TK
Data subject to change without notice
-
3Description ofoperation
The residual overvoltage relay module typeSPCU 1C6 is used in a
variety of different pro-tection relay units where it constitutes a
non-directional general earth-fault protection mod-ule which
measures the residual voltage of theelectrical power system.
The residual overvoltage module contains twoovervoltage
stages,that is a low-set stage U0> anda high-set stage
U0>>.
The low-set or high-set voltage stage starts ifthe measured
voltage exceeds the set start valueof the stage concerned. When
starting, the con-cerned stage delivers a starting signal SS1 or
SS2and simultaneously the operation indicator ofthe stage is lit
with yellow colour. If the over-voltage situation lasts long enough
to exceed theset operation delay, the stage that started
alsooperates generating a trip signal, TS1 alt. TS2.The operation
indicator of the stage that oper-ated turns red. The start and
operation indica-tors are provided with memory control, whichmeans
that they can be given the self-reset orthe latching mode of
operation. The latchingindicators are reset with the RESET
push-but-ton on the front panel or by means of the com-mand V101 or
V102 via the serial port.
The tripping of the low-set overvoltage stageU0> can be
blocked by routing a blocking sig-nal BTS1 to the low-set stage.
Similarly, the trip-ping of the high-set stage U0>> is
blocked by ablocking signal BTS2. The blocking signals arerouted by
means of switchgroup SGB on thePC board of the relay module.
The setting range of the operation time t> ofthe low-set
overvoltage stage U0> is selected withswitches SG1/1 and SG1/2.
Three setting rangesare available.
Switches SG1/7 and SG1/8 are used for select-ing the setting
range for the operation time t>>of the high-set stage
U0>>. Three setting rangesare available.
The setting range of the start value of the low-set stage U0>
is selected with switch SG1/5. Twosetting ranges are available,
that is 2...20% x Unand 10...100% x Un.
The setting range of the start value of the high-set stage
U0>> is selected with switch SG1/6. Twosetting ranges are
available, that is 2...16% x Unor 10...80% x Un.
The operation of the two operating stages isprovided with a so
called latching facility, whichmeans that the operation output is
kept alerted,although the signal which caused the
operationdisappears. The latching function is selectedwith switch
SG1/4. The latched output and theoutput relay can be reset in three
different ways;(i) by pressing push buttons STEP and
RESETsimultaneously, (ii) via the serial inter-face us-ing the
command V101 or (iii) via the serialinterface using the command
V102. When al-ternative (ii) is used all recorded information
ismaintained but if the alternatives (i) or (iii) isused the
recorded information is erased.
The residual voltage signal input is providedwith an effective
filter by means of whichhamonics of the measured residual voltage
issuppressed, see Fig. 1.
dB 10
0
-10
-20
-30
-40
-50
-600 1 2 3 4 5 6 7 f / fn
Fig. 1. Filter characteristics of the residual volt-age input
circuit.
-
4Block diagram
Fig. 2. Block schematic diagram of the residual overvoltage
relay module SPCU 1C6.
U0 Measured residual voltageBS1, BS2, BS3 Incoming external
blocking signalsBTS1 Blocking of tripping of stage U0>BTS2
Blocking of tripping of stage U0>>SG1 Selector switchgroup on
the relay module front panelSG2 Function selector switchgroup for
the operation indicatorsSGB Selector switchgroup on the PC board
for blocking signalsSS1 Start signal of stage U0>TS1 Trip signal
of stage U0>SS2 Start signal of stage U0>>TS2 Trip signal
of stage U0>>Y Yellow indicator, startingR Red indicator,
tripping
NOTE!All input and output signals of the relay mod-ule are not
necessarily wired to the terminals ofevery protection relay unit
utilizing this mod-
ule. The signals wired to the terminals are shownin the signal
diagram in the manual of the con-cerned protection relay unit.
-
5Front panel
Voltage measurement indicator
Start voltage setting knoband indicator of stage U0>
Operation time setting knoband indicator of stage U0>
Start voltage setting knob andindicator of stage U0>>
Operation time setting knoband indicator of stage U0>>
IRF
1310
[ ]s>t0.5
0.05 1.0
50
10
0.5
0.05 1.0
2
10
20STEP
RESET
SG1
0 1
12345678
>U >>U
SPCU 1C6
B
>>
[ ]s>>t
U o
nU>U o
nUUo 80
o o
[ ]%
[ ]%
U
STEP
Simplified device symbol
Self-supervision alarmindicator
Display for set andmeasured values
Display step push-button
Selector switchgroup
Switchgroup indicator
Reset push-button
Operation indicators
Relay module typedesignation
Fig. 3. Front panel of the residual overvoltage relay module
SPCU 1C6.
Operationindicators
Both voltage stages have their own yellow/redLED indicators.
Yellow light indicates startingof the concerned overvoltage stage
and red lightindicates that the overvoltage stage has operated.
The four LED indicators can, independently ofone another, be
given a non-latching or a latch-ing mode of operation. The latching
modemeans that the indicator remains lit after beingswitched on,
although the overvoltage stage,which controls the indicator,
resets. If, for in-stance, the yellow start indicator is given
thelatching mode and the red indicator the non-latching mode, the
yellow indicator is lit, whenthe stage starts, which then turns red
if and whenthe stage operates. When the overvoltage stageresets
only the yellow indicator remains lit. Theindicators, which have
been given the latchingmode, are reset locally by pushing the
RESETpush-button or by remote control over the SPAbus using the
command V102.
An unreset operation indicator does not affectthe protective
functions of the relay module.
The self-supervision alarm indicator IRF indi-cates that the
self-supervision system has de-tected a permanent internal relay
fault. The in-dicator is lit with red light shortly after the
faulthas been detected. At the same time the relaymodule puts
forward a control signal to the self-supervision system output
relay of the protec-tion relay unit.
Additionally, in most fault cases, a fault codeshowing the
nature of the fault appears on thedisplay of the module. The fault
code, consist-ing of a red number one (1) and a green three-digit
code number, indicates what type of in-ternal fault that has been
detected. When a faultmessage appears, the fault code should be
noteddown for later use when relay overhaul or re-pair is to be
carried out.
-
6Settings The setting values are shown by the threerightmost
digits of the display. A LED indica-
tor below the setting knob shows, when lit,which setting value
is presented on the display.
U0>/Un Start voltage value of the U0> stage, expressed as
a percentage of the rated voltageof the energizing input used. The
setting range is 2...20% x Un when SG1/5 = 0,and 10...100% x Un
when SG1/5 = 1.
t> [s] Operate time of the U0> stage, expressed in
seconds. The setting range is deter-mined by the position of
switches SG1/1 and SG1/2. Selectable operate time set-ting ranges
0.05...1.00 s, 0.5...10.0 s and 5...100 s.
U0>>/Un Start voltage value of the U0>> stage,
expressed as a percentage of the rated voltageof the energizing
input used. The setting range is 10...80% x Un when SG1/6 = 0,and
2...16% x Un when SG1/6 = 1. The setting , infinite, (displayed as
- - -) setsthe high-set stage U0>> out of operation.
t>> [s] Operate time of the U0>> stage, expressed in
seconds. The required setting range,0.05...1.00 s, 0.5...10.0 s or
5.00...100 s, is selected with switches SG1/7 andSG1/8.
Further, the checksum of the selector switch-group SG1 is shown
on the display when theLED indicator below the switchgroup is lit.
Bymeans of the displayed checksum and thechecksum manually
calculated the proper op-
eration of the switchgroup SG1 can be verified.An example of how
the checksum is calculatedis shown in the manual "General
characteristicsof C type relay modules".
Selector switches Additional functions required by
individualapplications are selected by means of the func-tion
selector switches of switchgroup SG1 lo-cated on the front panel.
The numbering of the
switches, 1...8, as well as the switch positions 0and 1 are
marked on the relay module frontpanel.
Switch Function
SG1/1 Selection of setting range for the operate time t> of
low-set stage U0>.SG1/2
SG1/1 SG1/2 Operate time t>
0 0 0.05...1.00 s1 0 0.5...10.0 s0 1 0.5...10.0 s1 1 5...100
s
SG1/3 Not in use. Has to be set in position 0.
SG1/4 Selection of latching function for the tripping signals
TS1 and TS2.
When SG1/4 = 0, the trip signals reset to the initial state (=
the output relay drops off ),when the measuring signal causing the
operation falls below the set start voltage level.When SG1/4 = 1,
the trip signals remain activated (= the output relay remains
pickedup), although the measuring signal falls below the set start
voltage level. Then the tripsignals are reset by pressing the
push-buttons STEP and RESET simultaneously orwith the commands V101
or V102 via the serial port.
SG1/5 Selection of setting range for the start voltage value of
the low-set stage U0>.
When SG1/5 = 0, the setting range is 2...20% x Un.When SG1/5 =
1, the setting range is 10...100% x Un.
-
7Switch Function
SG1/6 Selection of setting range for the start voltage value of
the high-set stage U0>>.
When SG1/6 = 0, the setting range is 10...80% x Un and ,
infinite.When SG1/6 = 1, the setting range is 2...16% x Un and ,
infinite.
SG1/7 Selection of setting range for the operate time t>>
of the high-set stage U0>>.SG1/8
SG1/7 SG1/8 Operate time t>>
0 0 0.05...1.00 s1 0 0.5...10.0 s0 1 0.5...10.0 s1 1 5...100
s
Switchgroup SG2 is a so called software switch-group, which is
located in the third submenuof switchgroup SG1. The mode of
operation,i.e. self-reset or manually reset, of the LED in-dicators
U0> and U0>> is determined by theswitches of switchgroup
SG2. The mode of op-
eration can be separately set for each indicator.The mode of
operation is set by means of thechecksum, which can be calculated
from thefollowing table. Normally the start indicationsare
self-reset and the operation indicationsmanually reset.
Indicator Manually reset Factory default
Start indicator U0> 1 0Operation indicator U0> 2 2Start
indicator U0>> 4 0Operation indicator U0>> 8 8
Checksum 15 10
The PC board of the relay module contains aswitchgroup SGB
including switches 1...8. Theswitches 1...3 are used for selecting
the startingsignals, whereas switches 4...8 are used for rout-ing
the blocking signals to the voltage module
in various protection relay units. Instructionsfor setting of
switchgroup SGB are given in theuser's manual of the different
protection relayunits.
Measured data The measured values are displayed by the
threerightmost digits on the display. The measured
data to be displayed are indicated by a lit LEDindicator.
Indicator Measured data
U0 Residual voltage measured by the relay module, expressed as a
percentage of therated voltage of the energizing input used.
-
8Recordedinformation
The leftmost red digit displays the addressnumber of the
register, the rightmost three greendigits display the recorded
data.
Register/ Recorded dataSTEP
1 Maximum residual voltage measured by the module, as a
percentage of the ratedvoltage Un of the used energizing input. If
the module operates, the voltage value atthe moment of operation is
stored in the memory. Any new operation erases the oldvalue and
updates the register with the new value. The same thing happens if
themeasured voltage exceeds a previously recorded maximum
value.
2 Number of starts of the low-set overvoltage stage U0>, n
(U0>) = 0...255.
3 Number of starts of the high-set overvoltage stage U0>>,
n (U0>>) = 0...255.
4 Duration of the latest start situation of stage U0> as a
percentage of the set operatetime t>. Any new start resets the
counter, which then starts counting from zero.When the stage has
operated, the counter reading is 100.
5 Duration of the latest start situation of stage U0>> as
a percentage of the set operatetime t>>. Any new start resets
the counter, which then starts recounting from zero.When the stage
has operated, the counter reading is 100.
0 Display of blocking signals and other external control
signals. The rightmost digitindicates the state of the blocking
inputs of the relay module. The following statesmay be indicated:0
= no blockings1 = operation of the U0> stage blocked2 =
operation of the U0>> stage blocked3 = operation of both
stages blocked
In this register the second digit from he right is constantly
zero. The leftmost digitindicates the state of the remote reset
control input, if applicable. The followingstates may be
indicated:0 = remote reset control input not energized1 = remote
reset control input energized
From this register it is possible to move on to the TEST mode,
where the start andoperation signals of the module can be activated
one by one. For further details seemanual "General characteristics
of C type relay modules".
A The address code of the protection relay module in the serial
communication sys-tem. The serial communication is broken if the
relay module is given the addresscode 0 (zero). Register A is
provided with the following subregisters:1. Selection of data
transfer rate for the serial communication. Selectable values
300, 1200, 2400, 4800 and 9600 Bd. Default value 9600 Bd.2. Bus
communication monitor. If the relay module is connected to a serial
com-
munication system and the serial communication system is in
operation the coun-ter of the bus communication monitor will show
the value 0 (zero). If the com-munication is broken the numbers
0255 are scrolling in the counter.
3. Password required when changing relay module settings via
remote control
Registers 1...5 are set to zero by pressing thepush buttons STEP
and RESET simultaneouslyor by remote control using the command
V102.The register values are also erased if the auxil-iary power
supply of the module is interrupted.The address code of the relay
module, the set
data transfer rate of the serial communicationand the password
are not erased by a supplyvoltage interruption. Instructions for
setting theaddress code and the data transfer rate are givenin the
manual "General characteristics of C typerelay modules".
-
9Menu chart
Display off. Normal state SUBMENU FORWARD STEP 1 sBACKWARD STEP
0.5 s
MAIN
MENU
STEP
BACKWARD
.5s
STEP
FORWARD
1s
MAIN MENU SUBMENUSTEP 0.5 s RESET 1 s
0 000 SS1 TS1 TS2IRF SS2
Residual voltage U
Remotely setpercentage p1
Alerted start voltage, stage
Remotely set startvoltage x p1
Remotely setpercentage p2
Alerted operation time t>, stage
Remotely set ope-ration time t> x p2
Remotely setpercentage p3
Alerted start voltage, stage
Remotely set start voltage x p3
Remotely setpercentage p4
Alerted operation time t>>, stage
Remotely set ope-ration time t>> x p4
Alerted checksum,switchgroup SG1
Remotely set checksum of SG1
Remotely set checksum of SG1
Chechsumof SG2
Recorded maximum value of the residual voltage
Number of starts of the residual voltage stage
Number of starts of the residual voltage stage
Duration of the latest start event stage
1
2
3
4
Duration of the latest start event of stage 5
Incoming blocking signals0
Relay module address code
Data transfer rate (Bd)
Bus communication monitor 0 ... 255 Password A
= Value that can be set in the setting mode0
U >0
U >>0
U >0
U >>0
U 0
U >0
U >>0
U >0
U >>0
U >>0
U >0
Fig. 4. Main menu and submenus of the residual overvoltage relay
module SPCU 1C6.
The procedure for entering a submenu or a set-ting mode and
configuring the module is de-
scribed in detail in "General characteristics ofC type relay
modules".
-
10
Technical data Low-set overvoltage stage U0>Start voltage
U0> 2...20% x Un or 10...100% x UnStart time, typically 70
msOperate time 0.05...1.00 s, 0.5...10.0 s or 5...100 sReset time
>Start voltage U0>> 10...80% x Un and , infinite or
2...16% x Un and , infiniteStart time, typically 70 msOperate
time 0.05...1.00 s, 0.5...10.0 s or 5...100 sReset time
-
11
Serialcommunicationparameters
Event codes
The substation level control data communica-tor is able to read,
over the SPA serial bus, theevent messages of the relay module,
e.g. startand trip messages, from the residual overvoltagerelay
module SPCU 1C6. The events can beprinted out in the format: time
(ss.sss) and eventcode. The event codes of the relay module
areE1...E8 , E50 and E51. Additional event codesrelating to the
data communication are gener-ated by the data communication
equipment.
The event codes E1...E8 and the events repre-sented by these can
be included in or excludedfrom the event reporting by writing, via
the SPAbus, an event mask (V155) to the relay module.The event mask
is a binary number coded to adecimal number. The event codes
E1...E8 arerepresented by the numbers 1, 2, 4...128. The
event mask is formed by multiplying the abovenumbers either with
0, event not included or 1,event included in reporting and by
adding theproducts, see instructions for checksum calcu-lation.
The event mask may take a value within therange 0...255. The
default value of the residualovervoltage relay module SPCU 1C6 is
85,which means that any start or operation eventis included in the
reporting, but no resettings.The event codes E50...E54 and the
events rep-resented by these cannot be excluded from
thereporting.
Event codes of residual voltage relay moduleSPCU 1C6:
Code Event Weighting Defaultcoefficient setting
E1 Starting of stage U0> 1 1E2 Starting of stage U0> reset
2 0E3 Tripping of stage U0> 4 1E4 Operation of stage U0>
reset 8 0E5 Starting of stage U0>> 16 1E6 Starting of stage
U0>> reset 32 0E7 Tripping of stage U0>> 64 1E8
Operation of stage U0>> reset 128 0
Default value of event mask V155 85
E50 Restart of microprocessor * -E51 Overflow of event register
* -E52 Temporary interruption in the data communication * -E53 No
response from the relay module over the data
communication bus * -E54 The relay module responds again over
the data
communication bus * -
0 not included in the event reporting1 included in the event
reporting* no code number, always included in event reporting-
cannot be set
NOTE!In the SPACOM system the event codes E52...E54 are
generated by the station level controldata communicator, e.g. type
SRIO 1000M.
-
12
Data to betransferred overthe serial bus
In addition to the event code data transfer, theinput data (I
data), output data (O data), set-ting values (S), memorized data (V
data) andsome other data can be read from the relay
module over the serial communication bus.Further, part of the
data can be changed overthe SPA bus by separate commands. All
datainformation is available in channel 0.
Data Code Data Valuesdirect.
Input data
Energizing input voltage I1 R 0...250% x UnBlocking of operation
of stage U0> I2 R 0 = no blocking
1 = operation of stage U0>blocked
Blocking of operation of stage U0>> I3 R 0 = no blocking1
= operation of stage I0>>
blocked
Output data
Starting of stage U0> O1 R 0 = stage U0> not started1 =
stage U0> started
Operation of stage U0> O2 R 0 = stage U0> not tripped1 =
stage U0> tripped
Starting of stage Uo>> O3 R 0 = stage U0>> not
started1 = stage U0>> started
Operation of stage U0>> O4 R 0 = stage U0>> not
tripped1 = stage U0>> tripped
Setting values
Alerted start value of stage U0> S1 R 2...100% x UnAlerted
operate time of stage U0> S2 R 0.05...100 sAlerted start value
of stage U0>> S3 R 2...80% x Un
999 = , infiniteAlerted operate time of stage U0>> S4 R
0.05...100 sAlerted checksum of switchgroup SG1 S5 R 0...255
Start value of stage U0>, S11 R 2...100% x Unset with the
setting knobOperate time of stage U0>, S12 R 0.05...100 sset
with the setting knobStart value of stage U0>>, S13 R 2...80%
x Unset with the setting knob 999 = , infiniteOperate time of stage
U0>>, S14 R 0.05...100 sset with the setting knobChecksum of
switchgroup SG1, S15 R 0...255set with the switches
Remotely setting percentage of the S21 R, W 0...999%start value
of stage U0>Remotely setting percentage of the operate S22 R, W
0...999%time of stage U0> or time multiplierRemotely set
percentage for the S23 R, W 0...999%start value of stage
U0>>Remotely setting percentage for the S24 R, W
0...999%operate time of stage U0>>Remotely set checksum of
switchgroup SG1 S25 R, W 0...255
-
13
Data Code Data Valuesdirect.
Remotely set start value of stage U0> S31 R 2...100% x
UnRemotely set operate time of stage U0> S32 R 0.05...100
sRemotely set start value of stage U0>> S33 R 2...80% x
Un
999 = , infiniteRemotely set operate time of stage U0>>
S34 R 0.05...100 sRemotely set checksum of switchgroup SG1 S35 R
0...255
Max. measured voltage or voltage V1 R 0...250% x Unat
operationNumber of starts of stage U0> V2 R 0...255Number of
starts of stage U0>> V3 R 0...255Duration of the latest start
V4 R 0...100%situation of stage U0>Duration of the latest start
V5 R 0...100%situation of stage U0>>
Resetting of output relays and V101 W 1 = output relays
andoperation indicators operation indicators resetResetting of
output relays and operation V102 W 1 = output relays andindicators
and erasing of recorded data operation indicators
reset and registers(codes V1V5) erased
Remote control of settings V150 R, W 0 = setting with
knobsS11...S15 activated
1 = remote settingsS31...S35 activated
Event mask word V155 R, W 0...255, see section"Event codes"
Manual reset or self-reset mode of V156 R, W 015, see
sectionoperation of the LED indicators "Selector switches"
Opening of password for remote settings V160 W 1...999Changing
or closing of password V161 W 0...999for remote settings
Activation of self-supervision function V165 W 1 =
self-supervision outputis activated and the IRFindicator turns on
inabout 5 seconds, where-after the self-supervisionsystem and the
IRFindicator reset
Internal fault code V169 R 0255
Data communication address of V200 R 1...254the relay module
Program version V205 R 070_
-
14
Data Code Data Valuesdirect.
Type designation of the relay module F R SPCU 1C6
Reading of event register L R Time, channel numberand event
code
Re-reading of event register B R Time, channel numberand event
code
Reading of module status data C R 0 = normal state1 = module
been subject
to automatic reset2 = overflow of event register3 = events 1 and
2 together
Resetting of module status data C W 0 = resetting
Time reading or setting T R, W 00.000...59.999 s
R = data to be read from the moduleW = data to be written to the
module
The data transfer codes L, B, C and T have beenreserved for the
event data transfer between therelay module and the control data
communi-cator.
The event register can be read by the L com-mand only once.
Should a fault occur, for ex-ample, in the data transfer, it is
possible, by us-ing the B command, to re-read the contents ofthe
event register once already read by means ofthe L command. When
required, the B com-mand can be repeated.
The setting values S1...S5 are the alerted setvalues currently
used by the protection relaymodule. These values are set either by
remotecontrol or by means of the setting knobs. Thevalues S11...S15
are set with the setting knobsand the selector switches. Variables
S21...S25are set as percentage values via remote control.
The settings S21...S25 allow reading or writ-ing. A condition
for writing is that the pass-word V160, for remote setting has been
opened.The variables S31...S35 contain the remote set-ting
values.
When the values of the variables S21...S24 areto be changed, the
variables can be given a per-centage factor within the range
0...999. It ispossible to alter a setting value beyond the set-ting
ranges specified in the technical data of therelay module. However,
the validity of the set-ting values are guaranteed only within the
set-ting ranges specified in the technical data.
Activation of the self-supervision function(V165) prevents the
relay module from operat-ing as long as the self-supervision output
is ac-tivated and the IRF indicator is lit.
-
15
Fault codes Once the self-supervision system has detected
apermanent relay fault, the IRF LED on the frontpanel of the module
is lit, and at the same timethe normally operated signal relay of
the self-supervision system drops off.
In most fault situations an auto-diagnostic faultcode is shown
on the relay display. The faultcode cannot be reset. The fault code
consists of
a red digit one (1) and a green code numberthat indicates the
fault type. The fault codeshould be recorded and stated when
service isordered.
The fault codes of the residual overvoltage relaymodule SPCU 1C6
are explained in the follow-ing table:
Fault code Explanation
4 Faulty output relay path or missing output relay card30 Faulty
program memory (ROM)50 Faulty working memory (RAM)
195 Too low a value in reference channel with multiplier 1131
Too low a value in reference channel with multiplier 5
67 Too low a value in reference channel with multiplier 25203
Too high a value in reference channel with multiplier 1139 Too high
a value in reference channel with multiplier 5
75 Too high a value in reference channel with multiplier 25253
No interruptions from the A/D-converter
-
L1 IRF
>I
L2I L3II
1309
[ ]sk
>t0.5
0.05 1.0
13
2.5
0.5
0.04 1.0
0.5
1.5
2.5STEP
RESET
SG1
0 1
1234567820
STEP
>>I
nI>I
nI>>I
>>t [ ]s
>I >>I
SPCJ 3C3
B
Indicators for measured values
Setting knob 1with indicator
Stage 1
Setting knob 2with indicator
Setting knob 3with indicator
Stage 2
Setting knob 4with indicator
Self-supervision alarm indicator(Internal Relay Fault)
Display, 1 + 3 digits
Step push-button (STEP)
Programming switches SG1
Switchgroup indicator
Reset push-button (RESET)
Start/operation indicators
General characteristics ofC-type relay modules
Users manual and Technical description
-
2General characteristics ofC-type relay modules
Contents Push-buttons
..................................................................................................................
2Programming switches SG1
............................................................................................
2Setting knobs
..................................................................................................................
3Display
...........................................................................................................................
3
Display main menu
...................................................................................................
3Display submenu
.......................................................................................................
4Setting mode
.............................................................................................................
4Example: Operation in setting mode
.........................................................................
5Stored information
....................................................................................................
6Trip-test
mode...........................................................................................................
7Example: Trip-test function
......................................................................................
8
Operation indicators
.......................................................................................................
9Fault codes
......................................................................................................................
9
Push-buttons The front panel of the relay module containstwo
push-buttons. The STEP button is used forstepping forward in the
display and the RESETbutton for resetting the red indicators.
Addi-tionally, the push-buttons are used for certain
settings, e.g. for setting the address of the relaymodule and
the data transfer rate for the serialcommunication when the modules
are used inrelay packages provided with this quality. (Seesection
Display).
Programmingswitches SG1
Part of the settings and the selections of theoperating
characteristics for the relay modulesin various applications are
made with the pro-gramming switches SG1 on the front panel.
Theindicator of the switchgroup glows when the
checksum of the switchgroup is shown on thedisplay. The checksum
can be used for checkingthat the switches are properly set. Fig. 2
gives anexample of calculating the checksum.
Fig. 2. Example of calculating the checksum of programming
switchgroup SG1.
When the checksum calculated according to theexample is equal to
the checksum indicated onthe display of the relay module, the
switches areproperly set.
The function of the programming switches ofthe individual
measuring relay modules is speci-fied in the description of the
module concerned.
1MRS 750328-MUM EN
Issued 96-02-19Version A (replaces 34 SPC 2 EN1)Checked L-W
UApproved TK
Data subject to change without notice
-
3Setting knobs Most of the operating values and operatingtimes
are set by means of the setting knobs onthe front panel of the
relay module. Each settingknob has its own (LED) indicator which
glowswhen the concerned setting value is shown onthe display.
If a setting knob is turned while the display isshowing another
measured or set value, thevalue being set automatically appears on
thedisplay. Simultaneously, the indicator for theconcerned setting
starts glowing.
In addition to the settings made with the settingknobs, most
modules allow so called remotesetting. This means that the settings
made bymeans of the setting knobs of the module andthe checksum of
the programming switchgroupmay be altered through an instruction
over theserial communication bus. Remote setting ispossible if the
password in the register A isknown, and the remote settings are not
acti-vated, i.e. parameter V150=0. The circumstancethat the remote
settings are activated is shownwith a flashing light of the
indicator of thesetting knob, the value of which currently isbeing
displayed.
Display The measured and set values as well as the datarecorded
are shown on the display of the meas-uring relay module. The
display consists of fourdigits. The three digits (green) to the
rightindicate the measured, set or stored value andthe digit at the
extreme left (red) the number ofthe register. The measured or set
value displayedis indicated by a yellow LED indicator. Thenumber of
the register glows only when a storedvalue is displayed.
When the auxiliary voltage is connected to ameasuring relay
module, the module initiallytests the display by stepping through
the digits1...9 for about 15 seconds. When the test isfinished the
display turns dark. The testing canbe interrupted by pressing the
STEP button.The protective functions of the module areoperative
throughout the testing.
Display main menu All the data required during normal
operatingconditions are accessible from the main menuwhich presents
the measured values in real-time,the normal setting knob settings
as well as themost important memorized data.
The data to be shown in the main menu areselected to the display
in a certain sequence bymeans of the STEP button. When pressing
theSTEP button for about one second, the displaymoves forward in
the display sequence. Whenpressing it for about 0.5 seconds, the
displaymoves backwards in the display sequence.
From a dark display only forward movement ispossible. When
keeping the STEP button de-pressed, the display is continuously
moving inforward direction stopping for a while at thedark
point.
Unless the display is switched off by stepping tothe dark point,
it remains activated for about 5minutes from the last pressing of
the STEPbutton and then goes out.
-
4Display submenu Less important values and values not very
oftenset are displayed in the submenus. The numberof submenus
varies with different relay moduletypes. The submenus are presented
in the de-scription of the concerned module.
A submenu is entered from the main menu bypressing the RESET
button for about one sec-ond. When the button thereafter is
released, thered digit (STEP) of the display starts
flashing,indicating that one is in a submenu. Going fromone submenu
to another or back to the mainmenu follows the same principle as
when mov-ing from the main menu display to another; the
display moves forward when pressing the STEPbutton for one
second and backward whenpressing it for 0.5 seconds. The return to
themain menu has taken place when the red STEPdisplay turns
dark.
When entering a submenu from a measured orset value indicated by
a LED indicator, theindicator remains glowing and the address
win-dow (STEP) of the display starts flashing. Aflashing address
window when no LED indica-tor is lit indicates that the submenu of
a registerhas been entered.
Fig. 3. Example of the main and submenus for the settings of the
overcurrent relay module SPCJ3C3. The settings made with the
setting knobs are in the main menu and they are displayed
bypressing the STEP button. In addition to the setting knob
settings the main menu contains themeasured current values as well
as the registers 15, as well as 0 and A. The remote
settingpercentage and remote setting value are located in the
submenus for the settings and are activatedon the display by
pressing the RESET button.
Setting mode The registers of the main menu and the submenusalso
contain parameters to be set. The settingsare made in the so called
setting mode, which isaccessible from the main menu or a submenu
bypressing the RESET button, until the digit atthe extreme right
starts flashing (about 10 s).The flashing digit is set by means of
the STEPbutton. The flashing is moved on from digit todigit by
pressing the RESET button.
A set value is stored in the memory by pressingthe push-buttons
STEP and RESET simultane-ously. In practice the RESET button must
be
pressed slightly in excess of the STEP button.Return from the
setting mode to the main menuor submenu is possible by pressing
(for about 10s) the RESET button until the green digits onthe
display stop flashing. If the module is left inthe setting mode, it
will return automatically tothe start condition after about 5
minutes.
The values to be set in the setting mode are forinstance the
address code of the relay moduleand the data transfer rate for the
serial commu-nication. Further the percentage values for theremote
settings can be changed.
-
5Example 1: Function in the setting mode. Manual setting ofthe
address code of a relay module and the datatransfer rate for the
serial communication. Theinitial value for the address code is
146.
a)Press push-button STEP until register address Aappears on the
display.
b)Press the RESET button for about 10 s until theright most
digit starts flashing.
c)Press the STEP button repeatedly to set the digitto the value
desired.
d)Press the RESET button to make the middle ofthe green digits
flash.
e)Set the middle address digit by means of theSTEP button.
f)Press the RESET button to make the left mostgreen digit
flash.
g)Set the digit by means of the STEP button.
h)Store the set address number in the memory ofthe relay module
by pressing the RESET andSTEP button simultaneously. At the
momentthe information enters the memory, the threegreen dashes
flash in the display, i.e. A.
i)Leave the setting mode by pressing the RESETbutton for about
10 s, until the display stopsflashing.
j)Then enter submenu 1 of register A by pressingthe RESET button
for approx. one second. Theregister address A is then replaced by a
flashing1. This submenu is used for setting the datatransfer rate
of the serial communication.
k)The data transfer rate for the serial communica-tion is set
and stored in the same way as theaddress, see sections b...i,
except that the con-tinuously glowing register address has been
re-placed by a flashing 1.
l)After storing the data transfer rate for the
serialcommunication you may return to the mainmenu of register A by
pressing the STEP buttonfor about 0.5 second.
-
6Stored information The parameter values measured at the
momentwhen a fault occurs are recorded in the registers,in some
modules also the setting values. Therecorded data, except for some
setting param-eters, are set to zero by pressing the push-buttons
STEP and RESET simul-taneously.The data in normal registers are
erased if theauxiliary voltage supply to the relay is
disrupted,only the set values and the number ofautoreclosings are
maintained in the registers ata voltage failure.
The number of the registers varies with differentmodule types.
The function of the registers areillustrated in the descriptions of
the separaterelay modules. Additionally, the system panelcontains a
simplified list of the data recorded bythe various relay modules of
the relay assembly.
All C-type relay modules are provided with twogeneral registers:
register 0 and register A.
Register 0 contains, in coded form, the informa-tion about e.g.
external blocking signals andstatus information for the circuit
breaker. Thecodes are explained in the descriptions of therelay
modules.
Register A contains the address code of the relaymodule as
required by the serial communicationsystem. Example 1 on page 4
shows how theaddress code is altered. Submenu 1 of register
Acontains the data transfer rate value expressed inkilobaud for the
serial communication.
Submenu 2 of register A contains a bus trafficmonitor for the
SPACOM system. If the protec-tive relay, which contains the relay
module, islinked to a system including the control datacommunicator
and the data communicationsystem is operating, the counter reading
of themonitor will be zero. Otherwise the digits 1...255are
continuously rolling in the monitor.
Submenu 3 contains the password required forchanging the remote
settings. The address code,the data transfer rate for the serial
communica-tion and the password can be set manually or viathe
serial communication bus. For manual set-ting see example 1.
The start value for the address code and thepassword is 001 and
that for the data transferrate 9.6 kilobaud.
-
7Trip-test mode Register 0 also allows access to the so
calledTrip-test function, which allows the outputsignals of the
relay module to be activated one byone. If the auxiliary relay
module of the protec-tion assembly is in place, the auxiliary
relays willbe included in the testing.
When pressing the RESET button for about 10seconds, the three
green digits to the right startflashing to indicate that the relay
module is intest position. The indicators of the setting
knobsindicate by flashing which output signal can beactivated. The
required output function is se-lected by pressing the RESET button
for about1 second, until the following LED indicatorstarts
flashing.
The indicators of the setting knobs refer to thefollowing output
signals:Setting knob 1 SS1 Starting of stage 1Setting knob 2 TS1
Tripping of stage 1Setting knob 3 SS2 Starting of stage 2Setting
knob 4 TS2 Tripping of stage 2No indication IRF
Self-supervision
The selected starting or tripping is activated bysimultaneous
pressing of the push-buttons STEPand RESET. The signal remains
activated aslong as the two push-buttons are being pressed.
The self-supervision output is activated by press-ing the STEP
button once when no setting knobindicator is flashing. The IRF
output is acti-vated in about 5 seconds after pressing of theSTEP
button, and resets after that. Simultane-ously, the display returns
to the main menu andperforms the initial testing indicated by
rollingdigits 0...9 in the display several times.
The signals are selected in the order illustrated infig. 4.
REGISTER 0IRF SS1 TS1 SS2 TS2
STEP STEP+RESET
STEP+RESET
STEP+RESET
STEP+RESET
RESET10 s
RESET1 s
RESET1 s
RESET1 s
RESET1 s
RESET1 s
Fig. 4. Sequence order for selecting the output signals in the
Trip-test mode.
If e.g. the indicator of the setting knob 2 (secondfrom the top)
is flashing, and the push-buttonsSTEP and RESET are being pressed,
the signalTS1 (tripping of stage 1) is activated. Return tothe main
menu is possible at any stage of the
Trip-test sequence scheme, by pressing theRESET button for about
10 seconds. If themodule is left in the Trip-test mode, it
willreturn automatically after approx. 5 minutes.
-
8Example 2: Trip-test function. Forced activation of the
out-puts is made as follows:
a)Step forward on the display to register 0.
b)Press the RESET button for about 10 secondsuntil the three
green digits to the right and theLED indicator of the uppermost
setting knobstart flashing.
c)Press the push-buttons RESET and STEP si-multaneously. Then
the starting of stage 1 (e.g.the I>-stage of the overcurrent
module SPCJ3C3) is activated and, simultaneously, the indi-cator of
the stage starts glowing yellow.
d)Press the RESET button for about 1 seconduntil the indicator
of the second setting knobstarts flashing.
e)Press the push-buttons RESET and STEP si-multaneously to
activate tripping of stage 1 (e.g.the I>-stage of the
overcurrent module SPCJ3C3). The indicator of the concerned
stagestarts glowing red.
f)Starting and tripping of the second stage isactivated in the
same way as stage 1. The indica-tor of the third or fourth setting
starts flashing toindicate that the concerned stage has been
acti-vated.
g)To activate the self-supervision output step to-wards the test
position, where no indicator isflashing. Press the STEP button
once. In about5 seconds the red IRF indicator starts glowingand the
IRF output is activated. Shortly thereaf-ter the indicator goes out
and the output auto-matically resets. At the same time the
moduleleaves the test position.
h)It is possible to leave the trip test mode at anystep of the
sequence scheme by pressing theRESET button for about 10 seconds
until thethree digits to the right stop flashing.
-
9Operationindicators
A measuring relay module is provided with twoseparate operating
stages, each of which with itsown yellow/red operation indicator on
the lowerpart of the front plate of the relay module.
The operation indicator starts glowing yellowwhen the operating
stage starts and red when adelayed tripping operates. The functions
of thestart and operation indicators are described indetail in the
different protection relay modulemanuals.
Fault codes In addition to the protective functions the
relaymodule is provided with a self-supervision sys-tem which
continuously supervises the functionof the microprocessor, its
program executionand the electronics.
When the self-supervision system has detected apermanent fault
in the relay module, the redIRF indicator on the panel starts
glowing soonafter the fault was discovered. At the same timethe
module puts forward a signal to the self-supervision contact of the
relay assembly.
In most fault situations a fault code, indicatingthe nature of
the fault, appears on the display ofthe module. The fault code,
which consists of ared digit (1) and a three digit green code
number,cannot be removed from the display by reset-ting. When a
fault occurs, the fault code shouldbe recorded and stated when
service is ordered.
-