pdu0428a Dell™ Basic Rack Power Distribution Unit (PDU) K562N Product Overview and Specifications
pdu0428a
Dell™ Basic RackPower Distribution Unit (PDU)
K562N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has four (4) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 32 A plug.
K562N
Electrical Input connection IEC-309 32 A cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (4) C19
Maximum output current (outlet) C19; 16 A
Maximum output current (phase) 32 A
Maximum output current (bank) 16 A
Overcurrent protection (internal) (2) 16 A, 1-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
43.81 x 4.36 x 9.29 cm(17.25 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
47.80 x 20.80 x 18.00 cm(18.82 x 8.19 x 7.09 in)
Weight 2.78 kg (6.12 lb)
Shipping weight 3.75 kg (8.25 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals VDE, IRAM, SABS, GOST-R, SONCAP, KC, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0429a
Dell™ Basic RackPower Distribution Unit (PDU)
G795N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has four (4) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 32 A plug.
G795N
Electrical Input connection IEC-309 32 A (AUS) cord included
Acceptable input voltage 120–250 VAC +6% to -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Output voltage 120–250 VAC +6% to -10%
Output connections (4) C19
Maximum output current (outlet) C19; 16 A
Maximum output current (phase) 32 A
Maximum output current (bank) 16 A
Overcurrent protection (internal) (2) 16 A, 1-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
43.81 x 4.36 x 9.29 cm(17.25 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
47.80 x 20.80 x 18.00 cm(18.82 x 8.19 x 7.09 in)
Weight 3.10 kg (6.82 lb)
Shipping weight 4.00 kg (8.80 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals energysafe Victoria
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0430a
Dell™ Basic RackPower Distribution Unit (PDU)
H588N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has four (4) C19 outlets.
P OWER C OR D— This Rack PDU requires hardwiring of the unit to the power source.
H588N
Electrical Input connection Hardwire
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (4) C19
Maximum output current (outlet) C19; 16 A
Maximum output current (phase) 32 A
Maximum output current (bank) 16 A
Overcurrent protection (internal) (2) 16 A, 1-pole breakers
Physical Dimensions(H x W x D)
43.81 x 4.36 x 9.29 cm(17.25 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
47.80 x 20.80 x 18.00 cm(18.82 x 8.19 x 7.09 in)
Weight 1.88 kg (4.14 lb)
Shipping weight 2.80 kg (6.16 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0432a
Dell™ Basic RackPower Distribution Unit (PDU)
J559N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has three (3) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 32 A 3-phase plug.
J559N
Electrical Input connection IEC-309 32 A 3-phase cord included
Acceptable input voltage 200/346–240/415 VAC +6% to -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (3) C19
Maximum output current (outlet) C19; 16 A
Maximum output current (phase) 32 A
Maximum output current (bank) 16 A
Overcurrent protection (internal) (3) 16 A, 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 12.57 cm(15.28 x 1.72 x 4.95 in)
Shipping dimensions(H x W x D)
45.49 x 33.19 x 19.50 cm(17.91 x 13.07 x 7.68 in)
Weight 4.54 kg (10.00 lb)
Shipping weight 6.00 kg (13.24 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals VDE, IRAM, SABS, GOST-R, SONCAP, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
G791N
Product Overview and Specifications
pdu0431a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has three (3) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with a NEMA L15-30P cord.
G791N
Electrical Input connection NEMA L15-30P 3-phase cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 30 A (24 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (3) C19
Maximum output current (outlet) C19; 16 A (UL(C-UL) derated)C19; 20 A (PSE)
Maximum output current (phase) 30 A (24 A UL(C-UL) derated)
Maximum output current (bank) 20 A (16 A UL(C-UL) derated)
Overcurrent protection (internal) (3) 20 A, 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 12.57 cm(15.28 x 1.72 x 4.95 in)
Shipping dimensions(H x W x D)
45.49 x 33.19 x 19.50 cm(17.91 x 13.07 x 7.68 in)
Weight 3.60 kg (7.92 lb)
Shipping weight 5.06 kg (11.13 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0433a
Dell™ Basic RackPower Distribution Unit (PDU)
K579N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has three (3) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 63 A plug.
K579N
Electrical Input connection IEC-309 63 A cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 48 A
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (3) C19
Maximum output current (outlet) C19; 16 A
Maximum output current (phase) 48 A
Maximum output current (bank) 16 A
Overcurrent protection (internal) (3) 16 A, 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 12.57 cm(15.28 x 1.72 x 4.95 in)
Shipping dimensions(H x W x D)
50.01 x 39.49 x 19.50 cm(19.69 x 15.55 x 7.68 in)
Weight 5.40 kg (11.88 lb)
Shipping weight 8.30 kg (18.26 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals VDE, IRAM, SABS, GOST-R, SONCAP, KC, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0433a
Dell™ Basic RackPower Distribution Unit (PDU)
H579N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has three (3) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with an IEC-309 60 A plug.
H579N
Electrical Input connection IEC-309 60 A cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 60 A (48 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (3) C19
Maximum output current (outlet) C19; 16 A (UL(C-UL) derated)
Maximum output current (phase) 48 A
Maximum output current (bank) 16 A (UL(C-UL) derated)
Overcurrent protection (internal) (3) 20 A 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 12.57 cm(15.28 x 1.72 x 4.95 in)
Shipping dimensions(H x W x D)
50.01 x 39.49 x 19.50 cm(19.69 x 15.55 x 7.68 in)
Weight 6.92 kg (15.22 lb)
Shipping weight 9.80 kg (21.56 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL)
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
pdu0427a
Dell™ Basic RackPower Distribution Unit (PDU)
H575N
Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has four (4) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with a NEMA L5-30P plug.
H575N
Electrical Input connection NEMA L5-30P cord included
Acceptable input voltage 100–120 VAC ± 10%
Maximum input current (phase) 30 A (24 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 100–120 VAC ± 10%
Output connections (4) C19
Maximum output current (outlet) C19;16 A (UL(C-UL) derated)
Maximum output current (phase) 30 A (24 A UL(C-UL) derated)
Maximum output current (bank) 16 A (UL(C-UL) derated)
Overcurrent protection (internal) (2) 20 A 1-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
43.81 x 4.36 x 9.29 cm(17.25 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
47.80 x 20.80 x 18.00 cm(18.82 x 8.19 x 7.09 in)
Weight 3.21 kg (7.06 lb)
Shipping weight 4.20 kg (9.25 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL)
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
K558N
Product Overview and Specifications
pdu0437a
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has thirteen (13) C13 outlets.
P OWER C OR D— The Rack PDU has an IEC-320 C14 inlet and can be used with a detached power cord (not provided).
K558NElectrical Input connection IEC-320 C14 inlet
Acceptable input voltage 100–240 VAC ± 10% (UL(C-UL))200–240 VAC ± 10% (International)
Maximum input current (phase) 16 A (UL(C-UL) derated)20 A (PSE)16 A (International)
Input frequency 50/60 Hz
Output voltage 100–240 VAC ± 10% (UL(C-UL))200–240 VAC ± 10% (International)
Output connections (13) C13
Maximum output current (outlet) C13; 12 A (UL(C-UL) derated)C13; 15 A (PSE)C13; 10 A (International)
Maximum output current (phase) 16 A (UL(C-UL) derated)20 A (PSE)16 A (International)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 9.29 cm(15.28 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
43.61 x 21.03 x 7.59 cm(17.17 x 8.28 x 2.99 in)
Weight 1.50 kg (3.30 lb)
Shipping weight 2.00 kg (4.44 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), VDE, IRAM, SABS, GOST-R, PSE, SONCAP, KC, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
Dell™ Basic RackPower Distribution Unit (PDU)
J541N
Product Overview and Specifications
pdu0438a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has eight (8) C13 outlets.
P OWER C OR D— The Rack PDU has an IEC-320 C14 inlet and can be used with a detached power cord (not provided).
J541N
Electrical Input connection IEC-320 C14 inlet
Acceptable input voltage 100–240 VAC ± 10% (UL(C-UL))200–240 VAC ± 10% (International)
Maximum input current (phase) 15 A (12 A UL(C-UL) derated)10 A (International)
Input frequency 50/60 Hz
Output voltage 100–240 VAC ± 10% (UL(C-UL))200–240 VAC ± 10% (International)
Output connections (8) C13
Maximum output current (outlet) C13; 12 A (UL(C-UL) derated)C13; 10 A (International)
Maximum output current (phase) 12 A (UL(C-UL) derated)10 A (International)
Physical Dimensions(H x W x D)
23.97 x 4.36 x 9.29 cm(9.44 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
28.60 x 21.03 x 13.00 cm(11.26 x 8.28 x 5.12 in)
Weight 0.90 kg (2.00 lb)
Shipping weight 1.37 kg (3.01 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), VDE, IRAM, SABS, GOST-R, SONCAP, KC, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
H553N
Product Overview and Specifications
pdu0443a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has twelve (12) 5-15 R outlets.
P OWER C OR D— The Rack PDU has a IEC-320 C20 inlet and can be used with a detached power cord (not provided).
H553N
Electrical Input connection IEC-320 C20 inlet
Acceptable input voltage 100–120 VAC ± 10%
Maximum input current (phase) 15 A (12 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 100–120 VAC ± 10%
Output connections (12) 5-15 R
Maximum output current (outlet) 5-15 R; 12 A (UL(C-UL) derated)5-15 R; 15 A (PSE)
Maximum output current (phase) 15 A (12 A UL(C-UL) derated)
Physical Dimensions(H x W x D)
52.29 x 5.58 x 4.69 cm(20.59 x 2.20 x 1.85 in)
Shipping dimensions(H x W x D)
61.21 x 12.29 x 10.66 cm(24.10 x 4.84 x 4.20 in)
Weight 1.90 kg (4.14 lb)
Shipping weight 2.60 kg (5.60 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
G761N
Product Overview and Specifications
pdu0442a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has five (5) 5-15 R outlets.
P OWER C OR D— The Rack PDU has an IEC-320 C14 inlet and can be used with a detached power cord (not provided).
G761N
Electrical Input connection IEC-320 C14 inlet
Acceptable input voltage 100–120 VAC ± 10%
Maximum input current (phase) 15 A (12 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 100–120 VAC ± 10%
Output connections (5) 5-15 R
Maximum output current (outlet) 5-15 R; 12 A (UL(C-UL) derated)5-15 R; 15 A (PSE)
Maximum output current (phase) 15 A (12 A UL(C-UL) derated)
Physical Dimensions(H x W x D)
23.97 x 4.36 x 9.29 cm(9.44 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
28.60 x 21.03 x 13.00 cm(11.26 x 8.28 x 5.12 in)
Weight 0.90 kg (2.00 lb)
Shipping weight 1.37 kg (3.01 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
K559N
Product Overview and Specifications
pdu0438a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has fourteen (14) C13 and two (2) C19 outlets.
P OWER C OR D— The 3.04-m (10.00-ft) power cord terminates with a NEMA L6-30P plug.
K559N
Electrical Input connection NEMA L6-30P cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 30 A (24 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (14) C13 and (2) C19
Maximum output current (outlet) C19; 16 A, C13; 12 A (UL(C-UL) derated)C19; 20 A, C13; 15 A (PSE)
Maximum output current (phase) 30 A (24 A UL(C-UL) derated)
Maximum output current (bank) 20 A (16 A UL(C-UL) derated)
Overcurrent protection (internal) (2) 20 A, 2-pole breakers
Cord length 3.04 m (10.00 ft)
Physical Dimensions(H x W x D)
83.33 x 5.56 x 4.69 cm(32.81 x 2.19 x 1.85 in)
Shipping dimensions(H x W x D)
96.59 x 15.59 x 13.71 cm(38.03 x 6.14 x 5.40 in)
Weight 2.88 kg (6.12 lb)
Shipping weight 3.23 kg (7.13 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
J544N
Product Overview and Specifications
pdu0435a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has fourteen (14) C13 outlets.
P OWER C OR D— The Rack PDU has a IEC-320 C20 inlet and can be used with a detached power cord (not provided).
J544N
Electrical Input connection IEC-320 C20 inlet
Acceptable input voltage 100–240 VAC ± 10%
Maximum input current (phase) 20 A (16 A UL(C-UL) derated/International)20 A (PSE)
Input frequency 50/60 Hz
Output voltage 100–240 VAC ± 10%
Output connections (14) C13
Maximum output current (outlet) C13; 12 A (UL(C-UL) derated)C13; 15 A (PSE)C13; 10 A (International)
Maximum output current (phase) 16 A (UL(C-UL) derated/International)20 A (PSE)
Physical Dimensions(H x W x D)
52.29 x 5.58 x 4.69 cm(20.59 x 2.20 x 1.85 in)
Shipping dimensions(H x W x D)
61.21 x 12.29 x 10.66 cm(24.10 x 4.84 x 4.20 in)
Weight 1.90 kg (4.14 lb)
Shipping weight 2.60 kg (5.60 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), VDE, IRAM, SABS, GOST-R, PSE, SONCAP, KC, CE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
G789N
Product Overview and Specifications
pdu0438a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has seven (7) C13 and two (2) C19 outlets.
P OWER C OR D— The Rack PDU has a IEC-320 C20 inlet and can be used with a detached power cord (not provided).
G789N
Electrical Input connection IEC-320 C20 inlet
Acceptable input voltage 100–240 VAC ± 10% (UL(C-UL)/PSE)200–240 VAC +6% to -10% (International)
Maximum input current (phase) 16 A (UL(C-UL) derated/International)20 A (PSE)
Input frequency 50/60 Hz
Output voltage 100–240 VAC ± 10% (UL(C-UL)/PSE)200–240 VAC +6% to -10% (International)
Output connections (7) C13 and (2) C19
Maximum output current (outlet) C19; 16 A, C13; 12 A (UL(C-UL) derated)C19; 20 A, C13; 15 A (PSE)C19; 16 A, C13; 10 A (International)
Maximum output current (phase) 16 A (UL(C-UL) derated/International)20 A (PSE)
Physical Dimensions(H x W x D)
38.81 x 4.36 x 9.29 cm(15.28 x 1.72 x 3.66 in)
Shipping dimensions(H x W x D)
43.61 x 21.03 x 7.59 cm(17.17 x 8.28 x 2.99 in)
Weight 1.56 kg (3.43 lb)
Shipping weight 2.00 kg (4.44 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals VDE, IRAM, SABS, GOST-R, PSE, SONCAP, KC, CE, UL(C-UL)
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Dell™ Basic RackPower Distribution Unit (PDU)
J542N
Product Overview and Specifications
pdu0440a
Product Overview and SpecificationsThe Dell Basic Rack PDU distributes power to the devices in the rack.O UTLETS — The Rack PDU has four (4) C19 outlets.
P OWER C OR D— The 3.65-m (12.00-ft) power cord terminates with a NEMA L6-30P plug.
J542N
Electrical Input connection NEMA L6-30P cord included
Acceptable input voltage 200–240 VAC +6% to -10%
Maximum input current (phase) 30 A (24 A UL(C-UL) derated)
Input frequency 50/60 Hz
Output voltage 200–240 VAC +6% to -10%
Output connections (4) C19
Maximum output current (outlet) C19; 16 A (UL(C-UL) derated)C19; 20 A (PSE)
Maximum output current (phase) 30 A (24 A UL(C-UL) derated)
Maximum output current (bank) 16 A (UL(C-UL) derated)20 A (PSE)
Overcurrent protection (internal) (2) 20 A, 2-pole breakers
Cord length 3.65 m (12.00 ft)
Physical Dimensions(H x W x D)
43.81 x 4.36 x 12.57 cm(17.25 x 1.72 x 4.95 in)
Shipping dimensions(H x W x D)
47.29 x 28.09 x 18.00 cm(18.62 x 11.06 x 7.09 in)
Weight 3.80 kg (8.36 lb)
Shipping weight 4.60 kg (10.12 lb)
Environmental Maximum elevation (above MSL)OperatingStorage
0 to 3048 m (0 to 10,000 ft)0 to 15 240 m (0 to 50,000 ft)
TemperatureOperatingStorage
0 to 50°C (32 to 122°F) –15 to 60°C (5 to 140°F)
HumidityOperatingStorage
5 to 95%, non-condensing5 to 95%, non-condensing
Compliance
Safety approvals UL(C-UL), PSE
ROHS Dell 6T198EU DIRECTIVE 2002/95/EC–latest revision
2 Dell Basic Rack Power Distribution Unit—Product Overview and Specifications