Jan 18, 2018
Solutions for Hotel HDL-MHRCU.431 Description - This is Hotel
Demo Board. It has HDL-MSD08.40, HDL-MPL8.48, HDL-MP4B.48,
HDL-MPTB01RF.48, SB-RF-MSTR, HDL-MHRCU.433. - We can use this Hotel
Demo Board to simulate a Room to be checked-in/checked-out, turn
on/off AC/curtain/lights/fan, and so on. Connection Application
Loads: Devices:
5 on/off lights; wall light, down light, bathroom light, bed light,
reading light; 1 curtain; 1 FCU; 1 ventilation fan; Devices:
HDL-MSD08.40 (1-1), channel1 simulates the door open/closed;
HDL-MPL8.48 (1-2), utilize AC page to control FCU (air
conditioner), and utilize some keys to control wall light/down
light/bathroom light/bed light/reading light; HDL-MP4B.48 (1-3),
utilize four keys to control curtain and fan; HDL-MPTB01RF.48
(1-4), doorbell; SB-RF-MSTR (1-5), card reader; HDL-MP4B.48 (1-6),
key1 is for Check-out, key2 is for Help, key3 to control doorbell
to show DND status, key4 to control doorbell to show Clean status
HDL-MHRCU.433 (1-7), host module; SB-RF-Writer, Card Writer.
Application 8CH Relay Module Channel of host module Remark
CH1
Wall light CH2 Channel 7 Down light CH3 Channel 8 Bathroom light
CH4 Channel 9 Bed light CH5 Channel 10 Reading light CH6 Channel 11
Fan CH7 Channel 12 Door alarm CH8 Channel 13 Shows door status
Channel 16 For Doorbell Channel 17 For door lock Channel 22 For
bell Dry contact Simulates thedoor open/closed DLP Control FUC in
AC page; Button 1-5 control CH1 to CH5 Button panel Control curtain
and fan Doorbell Doorbell control channel 22 of host module; RF
switch control the door lock Key1 is for check-out;Key2 is for
help; Key3 is control doorbell show DND status; Key4 is control
doorbell show clean status Application Requirements: When the room
is in Vacancy status;
Lights: wall light, down light, bathroom light, bed light, reading
light are all off. Curtain: closed FCU: off Ventilation fan: closed
Doorbell: just card lamp on the doorbell is on, make sure the
Waiter Card/Purifier Card/Mender Card/Manager Card can open the
door; When the room is in Reserved-null card status (booked);
settings are the same with Vacancy; Application Requirements:
When the room is in Check-in-null card status (customer get the
card on reception desk); Lights: down light is 100% brightness,
wall light, bathroom light, bed light, reading light are off.
Curtain: open FCU: cooling & high wind & 20. Wait for 3
minutes, if the customer does not open the room and insert the card
to card reader module, then turn off the AC; Ventilation fan: open
Doorbell: just card lamp on the doorbell is on. When the room is in
Occupied-guest card status (customer checks in on reception desk,
enters the room and inserts the card to card reader module);
Lights: down light, bed light are 100% brightness, wall light,
reading light, bathroom light are off. Curtain: ignore FCU: cooling
& low wind & 25 Doorbell: card lamp and doorbell lamp on
the doorbell are on. Application Requirements:
When the room is in Occupied-null card status; settings are the
same with Vacancy status; Lights: wall light, down light, bathroom
light, bed light, reading light are off. Curtain: closed FCU: off
Ventilation fan: off Doorbell: just card lamp on the doorbell is
on. When the room is in Waiter card status; Lights: wall light,
down light, bathroom light, bed light, reading light are ignore.
Curtain: open. FCU: off and lock the AC page in DLP. Ventilation
fan: open. Application Requirements:
When the room is in Out of Service status;; settings are the same
with Vacancy status; Lights: wall light, down light, bathroom
light, bed light, reading light are all off. Curtain: closed FCU:
off Ventilation fan: closed Doorbell: just card lamp on the
doorbell is on, make sure the Waiter Card/Purifier Card/Mender
Card/Manager Card can open the door; Other; When the door is open
longer than 15s, a light (channel 12 of host module) will flicker
to warn the customer. Guest leave delay time is 30s, it is the
delay time to run the occupied-null card scene, in case the
customer goes back to the room to get missing stuff.
Setup/HDLMHRCU.433 1. Login the IHMS and add a room
Use Administrator to login the software and then search the online
HDL-MHRCU.433 Setup/HDL-MHRCU.433 2. Add lights: Assign channel
6/7/8/9/10 for wall
light/down light/bathroom light/bed light/reading light.
Setup/HDL-MHRCU.433 3. Add AC: 4/27/2017 Before change the room
data,
need to Read the room data first. Assign channel 1 to 5 for AC,
andvalid AC Panel control. Setup/HDLMHRCU.433 4. Add Curtain:
Assignchannel 14 and 15 for curtain. Setup/HDL-MHRCU.433 5. Add
Ventilation fan: Assign channel 11for fan. Setup/HDLMHRCU.433 6.
Timeout of opening the door:
Assign a channel 12 to flicker (open 1s, closed 1s) when the door
is open, but not closed over 15s. 2017/4/27 Setup/HDL-MHRCU.433 7.
Match the Doorbell and Card Reader:
Fill in the ID of doorbell and card reader, and assign channel 16
for doorbell. Setup/HDL-MHRCU.433 8. Guest settings:
Set 30s for guest leave delay time, and 3 minutes delay time to
turn off the AC when guest check-in but not entered the room.
Setup/HDL-MHRCU.433 9. Scene setup: (take Check-in-null card for
example) Lights: down light is 100% brightness, wall light,
bathroom light, bed light, reading light are off.
Setup/HDL-MHRCU.433 Scene setup: (take Check-in-null card for
example)
Curtain: open Setup/HDLMHRCU.433 Scene setup: (take Check-in-null
card for example)
FCU: cooling & high wind & 20 Setup/HDL-MHRCU.433 Scene
setup: (take Check-in-null card for example)
Ventilation fan: open Setup/HDL-RCU.433 Scene setup: (take
Check-in-null card for example)
Doorbell: just card lamp on the doorbell is on. Setup/HDLMHRCU.433
Finished the scenes setup: Setup/HDL-MHRCU.433 10. Status Scene:
Select the scene for Room Status. 2017/4/27 Setup/HDL-MHRCU.433 11.
After setting the Room Data (HDL-MHRCU.433):
After settings the room data, need to Save the data to module.
Close the Room System Data window, it will shows all rooms
elements. Setup/HDL-MHRCU.433 12. Save the room data as
Templet:
After settings the room data, we can save the room data as template
to backup, or other room can read this template. Setup/HDLMHRCU.433
13. Save the Templet as a file:
After save the room data as a template, we can save the template as
a file. Setup/Card Issued Card Issued: Issue a guest card for Room
0001.
2017/4/27 Setup/Magnetic contact
Dry contact module setup in HDL-BUS Pro Setup Tool; Enable the
switch function in host module via IHMS, then we can search the
devices via HDL-BUS Pro setup tool; Channel1 simulates the door
open/closed. Channel13 of host module is shows the status of door,
universal switch no.5 is used for Timeout of opening the door
Setup/DLP DLP setup in HDL-BUS Pro Setup Tool:
1. For AC control: In AC page, need to fill in the ID of host
module; for host module, we added the AC in Order 1, so we need to
fill in AC No.1 in DLP. Setup/DLP DLP setup in HDL-BUS Pro Setup
Tool:
2. For button control: used button 1 to 5 to control channel
6/7/8/9/10 of host module, so button 1 to 5 can control wall
light/down light/bathroom light/bed light/reading light.
Setup/Button panel 1 Button panel setup in HDL-BUS Pro Setup
Tool:
HDL-MP4B.48 (1-3), use four keys to control curtain and fan; Key1
control curtain open; Key2 control curtain close. Setup/Button
panel 1 Button panel setup in HDL-BUS Pro Setup Tool:
HDL-MP4B.48 (1-3), use four keys to control curtain and fan; Key3
control FAN open; Key4 control FAN close. Setup/Doorbell For
1-DoorBell, we can use Mechanical Switch mode to control channel22
of host module, and set the OFF delay time is 1s. because channel22
of host module is connected to a bell. Setup/Doorbell For 2-RF
switch, when we use a card to open the door.
Channel17 of host module simulates to control the door lock. After
open the door lock, the door lock will be locked 5s later.
Setup/Doorbell Hotel Panel Settings of Doorbell:
The Hotel Name/Building ID/Storey ID/Room ID must the same with the
host module. Setup/Doorbell Button Settings of Doorbell:
Set the status colors for doorbell/card. We can use Universal
switch commands to control the status of DND/Clean/Doorbell/Card.
Setup/Card Reader Hotel Panel Settings of Card Reader:
The Hotel Name/Building ID/Storey ID/Room ID must the same with the
host module. 2017/4/27 Setup/Button panel 2 Button panel setup in
HDL-BUS Pro Setup Tool:
HDL-MP4B.48 (1-6), key1 is for Check-out, key2 is for Help, key3 to
control doorbell to show DND status, key4 to control doorbell to
show Clean status Key1 is for Check-out status; Key2 is for Help
status. Setup/Button panel 2 Button panel setup in HDL-BUS Pro
Setup Tool:
HDL-MP4B.48 (1-6), key1 is for Check-out, key2 is for Help, key3 to
control doorbell to show DND status, key4 to control doorbell to
show Clean status Key3 control doorbell shows DND status; Key4
control doorbell shows Clean status. Control After setup, when we
turn to Control Mode in IHMS to simulate a customer to check-in or
check-out, then the host module will run the corresponding scene.
2017/4/27 Control Find the room: The reception desk can check the
rooms which was Vacancy/Waiter Card, and so on. 2017/4/27 Control
Check the Serve Status:
The reception desk can check the Serve Status of each room, like
check-out/laundry, and so on.