SMART I/O www.elmeasure.com SMARTEST WAY TO CAPTURE THE INPUT & COMMUNICATE DATA OUTPUT! Universal Input | Universal Output | Digital Output SMART INPUT & OUTPUT MODULE
SMART I/O
www.elmeasure.com
SMARTEST WAY TO CAPTURE
THE INPUT & COMMUNICATE
DATA OUTPUT!
Universal Input | Universal Output | Digital Output
SMART INPUT & OUTPUT
MODULE
PC
/SI-
O/V
3/1
017
Up to 8 Universal Inputs field configurable
Up to 4 Universal Outputs field configurable
6 SSR outputs and 2 relay outputs (optional)
Communication LON / RS 485
Fire resistant enclosure
Pluggable terminal blocks, for installation wiring and ease
of maintenance
UO
-CH
1
UO
-CO
M
UO
-CH
2
UO
-CH
3
UO
-CO
M
UO
-CH
4
DO
1
CO
M1
DO
2
CO
M2
DO
3
CO
M3
DO
4
CO
M4
DO
5
CO
M5
DO
6
DO
7
CO
M7-8
DO
8
AU
X2
AU
X1
CO
M
UI-
CH
8
LO
N-
LO
N+
LO
N-
LO
N+
UI-
CH
1
CO
M
UI-
CH
2
UI-
CH
3
CO
M
UI-
CH
4
UI-
CH
5
CO
M
UI-
CH
6
UI-
CH
7
CO
M6
+
GN
D
-
AUXUniversal Output
UO
1
UO
2
G OP
UO
3
UO
4
G OP
DO1+
DO2+
DO3 DO4 DO5 DO6+ + + +
DO7 DO8+ +
Digital Output
UI1
UI2
CO
M
UI3
UI4
CO
M
Universal Input
UI5
UI6
CO
M
UI7
UI8
CO
M
A B A B
12 - 36V AC/DC
G +
Wiring Diagram:
Configuration Software
Models Available UI / DI
SIO 9000 -1
SIO 9000 -2
SIO 9000 -3
8
8
8
DO
8
6
8
UO
4
2
0
SIO 9000 - 4 A 16DI 24V
SIO 9000 - 4 B 16DI PFC
Features:
Specification Description
Technical Specification:
Voltage
Consumption
Protection
13-28VAC, 50 / 60 Hz, 12-36V DC
1A max
Under voltage, over voltage (Max 40V), over current, reverse voltage
Universal Input
Digital
Voltage
Current
RTD
Thermistor
User defined
Accuracy Class
5V to 24V
0 to 5V, 0 to 10 VDC
4 to 20 mA, 0 to 20 mA factory set for loop powered
PT 100 (2 wire )
Thermistor 10K (Type 2) (Type 3 Optional)
1%+-
00.8 C+-
00.8 C+-
1%+-
Non standard 10K Potentiometer ->
temperature curve up to 60 points, user configurable transition table
up to 16 points
2/4 Universal Output (configurable only at factory)
Digital 0 or 12VDC, 60mA, RL 200 ohm
Voltage
Current
PWM
One Shot Pulse
0 to 10 VDC
4 to 20 mA, 0 to 20 mA (optional)
Configurable period 1 - 999 seconds (programmable on time and duty)
Configurable pulse width 100 ms to 1000 ms
2 - 8 SSR output (Configurable only at factory)
PWM
One Shot Pulse
Digital (Dry/Wet
Contact)
0 OR 24V @100mA
Configurable period 1 - 999 seconds
Configurable pulse width 100 ms - 1000 ms
Communication
Lon Talk TP/FT - 10
Mechanical
Enclosure Poly Carbonate
Environmental
LONMARK
CE Mark
Operating Temperature
Storage Temperature
Relative humidity
Connector
-10 °C to +55 °C
-25 °C to +70 °C
51
2 Part pluggable
5 to 95 % (Non-condensing)
Mod Bus RS 485
Isolation RS 485 - 5 KV, LON - Polarity free
Flammability class UL94-V0 (non-flammable)
Dimensions 145x90x 45(LxBXH)
Mounting DIN rail / wall mounting
Weight 300 gm
Compliance
CO2
Pressure
Sensor
CO2 Flow
Sensor
Level
Sensor
Humidity
Sensor
Occupancy
Sensor
LON
Fan
A/C Lighting
Pump
Chiller
VAV’s
Boiler
MODBUS
UI1
UI2
CO
M
UI3
UI4
CO
M
Universal Input
UI5
UI6
CO
M
UI7
UI8
CO
M
A B A B G +
AUXUniversal Output
UO
1
UO
2
G OP
UO
3
UO
4
G OP
DO1+
DO2+
DO3 DO4 DO5 DO6+ + + +
DO7 DO8+ +
Digital Output
12 - 36V AC/DC
IP
Ordering Information :
Range of Products: Building Energy Management System (BEMS) | EMS | Demand Controller | Multifunction Meters | Electronic Energy Meters | Dual Energy Meter | Digital Panel Meters
| Automatic Changeover with Current Limiter (ACCL) |Power Factor Controller (PFC) | Earth Leakage Relay (ELR) | Earth Fault Relay (EFR) | Gateway | Branch Monitoring Unit | Smart Input
Output | Transducers | Converters
HO & Unit-I:
Plot No.: 47-P, Hardware Park, KIADB,
Huvinayakanahalli, Jala Hobli, Yelahanka Taluk,
Bengaluru - 562149 Karnataka INDIA.
Unit-II:
Goutham Garden, No. 4, Veerapandi,
Coimbatore - 641019 Tamilnadu INDIA
T: 0422 2697200 TF: 0244 2695200
Unit-III:
#764, 4th Phase, 707, Yelahanka New Town,
Bengaluru - 560 064 Karnataka INDIA
T: +91 80 28461744
ELMEASURE INDIA PRIVATE LIMITED
Sales Offices: BANGALORE | CHENNAI | COIMBATORE | MUMBAI | DELHI | HYDERABAD | USA | UAE
18 months warranty
ECO friendly lead free 18 months warranty