Rev. Status Date Prepared Reviewed Approved Description Status Code (Status): 1 = issued for Approval 3 = issued for order 5 = issued for construction 2 = issued for information 4 = issued for site fabrication 6 = As-built Document Acceptance Code A Approved B Approved as noted D Rejected C Revise and resubmit Signature : ………………………… Date : / / 1 0 2-Mar-16 Calculation Note Design Of Sluice Valve Chamber 1
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Rev. Status Date Prepared Reviewed Approved Description
Status Code (Status):1 = issued for Approval 3 = issued for order 5 = issued for construction2 = issued for information 4 = issued for site fabrication 6 = As-built
Document Acceptance CodeA Approved B Approved as noted
D Rejected C Revise and resubmit
Signature : ………………………… Date : / /
10 2-Mar-16
Calculation NoteDesign Of Sluice Valve Chamber
1
Design Of Sluice Valve Chamber For Pipe 300 Dia.DESIGN CRITERIADesign Code BS 8110 & 8007Compressive strength Fcu = 40 N\mm2
Steel yield stress Fy = 460 N\mm2
Live Load Surcharge Q = 10 KN\m2
Height of Ground water Table hGwt = 0 mmConcrete density gc = 24 KN\m3
FloorFloor Thickness tf = 300 mmCover C = 75 mmFloor Depth d = 225 mmBase Length L = 1500 mmBase Width B = 700 mmWallsWall Thickness tw = 300 mmCover C = 75 mmWall Depth dw = 225 mmWall clear Height Hw = 1100 mm
Net Bearing Capacity qnc = 150 KN\m2
Water Density gw = 10 KN\m2
Dry Soil Density gsd = 18 KN\m2
Angle of repose f = 30 degreeSoil Height Hs = 4100 mm
Sever ExposureDesign Crack width w = 0.2Steel Modulus of Elasticity Es = 200000 N\mm2Constant depends on the modulus of elasticity of aggregate K0 = 20 KN\mm2
Direct tensile strength of concrete at 3 days (BS8007) Fct = 1.6 N\mm2 P.20Allowable Tensile stress in steel (BS8007) Fs = 100 N\mm2 table 3.1 P.9Hydration temperture to ambient tempreture for wall (BS8007) T1w = 35 degree table A.2 P.24Hydration temperture to ambient tempreture for floor (BS8007) T1f = 35 degree table A.2 P.24Variation in temperture due to seasonal changes T2 = 0 degreePartial safety factor gm = 1.25Partial safety factor for load gf = 1.4
2
ANALYSIS Loads :-
0.333
3.333 KN\m2
24.600 KN\m2
18.000 KN\m2
Check of Bearing Capacity :-7.56 KN
22.968 KN
30.528 KN
1.050 m2
29.074 KN\m2
7.200 KN\m2
21.874 KN\m2 < 150 KN\m2
External Soil and Water Pressures
For External Walls
K = ∅∅ =
= Ka =ℎ = =
= Ka ( − ) =
Wf = =
Ww = 2 =
Wtotal = + + = = =
= Wtotal
= =
= − =
3
Reinforcement Design :-
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 174.7997 mm < 213.75 mm
Take 174.7997 mm
27.45727 KN.m
0.013559 < 0.156
5.5 KN.m < 27.45727137 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 174.7997 mm < 213.75 mm
Take 174.7997 mm
27.45727 KN.m
0.013559 < 0.156
4.67 KN.m < 27.45727137 KN.m
Accepted design.
No compression steel required.
No compression steel required.
Accepted design.
For Walls
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
4
CONT'D
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 174.7997 mm < 213.75 mm
Take 174.7997 mm
27.45727 KN.m
0.013559 < 0.156
7.6 KN.m < 27.45727137 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 174.7997 mm < 213.75 mm
Take 174.7997 mm
27.45727 KN.m
0.013559 < 0.156
7.52 KN.m < 27.45727137 KN.m
For Floor
No compression steel required.
Accepted design.
No compression steel required.
Accepted design.
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
5
CONT'D
Check of Shear Strength :-
11.3715 N
5.05E-05 N\mm2
5.059644 N\mm2
5 N\mm2
0.4769199 N\mm2
24.82 N
0.00011 N\mm2
2.529822 N\mm2
5 N\mm2
0.4769199 N\mm2
For Walls
For Floor
Accepted design.
Accepted design.
Accepted design.
Accepted design.
v= == 0.8 =
=
= 0.79 100 400 25 =
=
v= == 0.8 =
=
= 0.79 100 400 25 =
=
6
CONT'D
Check early thermal crack :-
28000 N\mm2
14.286
10 200
785 mm2
150 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.007088 mm < 0.2 mm
For Walls
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
7
CONT'D
28000 N\mm2
14.286
10 200
785 mm2
150 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.007088 mm < 0.2 mm
For Floor
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
8
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
3/2/16 8:27:32
9
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units
Design Of Sluice Valve Chamber For Pipe 200 Dia.DESIGN CRITERIADesign Code BS 8110 & 8007Compressive strength Fcu = 40 N\mm2
Steel yield stress Fy = 460 N\mm2
Live Load Surcharge Q = 10 KN\m2
Height of Ground water Table hGwt = 0 mmConcrete density gc = 24 KN\m3
FloorFloor Thickness tf = 200 mmCover C = 75 mmFloor Depth d = 125 mmBase Length L = 1200 mmBase Width B = 700 mmWallsWall Thickness tw = 200 mmCover C = 75 mmWall Depth dw = 125 mmWall clear Height Hw = 1000 mm
Net Bearing Capacity qnc = 150 KN\m2
Water Density gw = 10 KN\m2
Dry Soil Density gsd = 18 KN\m2
Angle of repose f = 30 degreeSoil Height Hs = 4000 mm
Sever ExposureDesign Crack width w = 0.2Steel Modulus of Elasticity Es = 200000 N\mm2Constant depends on the modulus of elasticity of aggregate K0 = 20 KN\mm2
Direct tensile strength of concrete at 3 days (BS8007) Fct = 1.6 N\mm2 P.20Allowable Tensile stress in steel (BS8007) Fs = 100 N\mm2 table 3.1 P.9Hydration temperture to ambient tempreture for wall (BS8007) T1w = 35 degree table A.2 P.24Hydration temperture to ambient tempreture for floor (BS8007) T1f = 35 degree table A.2 P.24Variation in temperture due to seasonal changes T2 = 0 degreePartial safety factor gm = 1.25Partial safety factor for load gf = 1.4
13
ANALYSIS Loads :-
0.333
3.333 KN\m2
24.000 KN\m2
18.000 KN\m2
Check of Bearing Capacity :-4.032 KN
12.480 KN
16.512 KN
0.840 m2
19.657 KN\m2
4.800 KN\m2
14.857 KN\m2 < 150 KN\m2
External Soil and Water Pressures
For External Walls
K = ∅∅ =
= Ka =ℎ = =
= Ka ( − ) =
Wf = =
Ww = 2 =
Wtotal = + + = = =
= Wtotal
= =
= − =
14
Reinforcement Design :-
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 97.11093 mm < 118.75 mm
Take 97.11093 mm
15.25404 KN.m
0.024406 < 0.156
5.045 KN.m < 15.25403965 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 97.11093 mm < 118.75 mm
Take 97.11093 mm
15.25404 KN.m
0.024406 < 0.156
3.79 KN.m < 15.25403965 KN.m
Accepted design.
No compression steel required.
No compression steel required.
Accepted design.
For Walls
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
15
CONT'D
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 97.11093 mm < 118.75 mm
Take 97.11093 mm
15.25404 KN.m
0.024406 < 0.156
7.53 KN.m < 15.25403965 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 97.11093 mm < 118.75 mm
Take 97.11093 mm
15.25404 KN.m
0.024406 < 0.156
7.45 KN.m < 15.25403965 KN.m
For Floor
No compression steel required.
Accepted design.
No compression steel required.
Accepted design.
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
16
CONT'D
Check of Shear Strength :-
11.3715 N
9.1E-05 N\mm2
5.059644 N\mm2
5 N\mm2
0.6719771 N\mm2
21.78 N
0.000174 N\mm2
2.529822 N\mm2
5 N\mm2
0.6719771 N\mm2
For Walls
For Floor
Accepted design.
Accepted design.
Accepted design.
Accepted design.
v= == 0.8 =
=
= 0.79 100 400 25 =
=
v= == 0.8 =
=
= 0.79 100 400 25 =
=
17
CONT'D
Check early thermal crack :-
28000 N\mm2
14.286
10 200
785 mm2
100 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.005930 mm < 0.2 mm
For Walls
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
18
CONT'D
28000 N\mm2
14.286
10 200
785 mm2
100 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.005930 mm < 0.2 mm
For Floor
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
19
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
3/2/16 8:39:30
20
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units
Design Of Sluice Valve Chamber For Pipe 150&100 Dia.DESIGN CRITERIADesign Code BS 8110 & 8007Compressive strength Fcu = 40 N\mm2
Steel yield stress Fy = 460 N\mm2
Live Load Surcharge Q = 10 KN\m2
Height of Ground water Table hGwt = 0 mmConcrete density gc = 24 KN\m3
FloorFloor Thickness tf = 150 mmCover C = 75 mmFloor Depth d = 75 mmBase Length L = 1050 mmBase Width B = 700 mmWallsWall Thickness tw = 150 mmCover C = 75 mmWall Depth dw = 75 mmWall clear Height Hw = 750 mm
Net Bearing Capacity qnc = 150 KN\m2
Water Density gw = 10 KN\m2
Dry Soil Density gsd = 18 KN\m2
Angle of repose f = 30 degreeSoil Height Hs = 3750 mm
Sever ExposureDesign Crack width w = 0.2Steel Modulus of Elasticity Es = 200000 N\mm2Constant depends on the modulus of elasticity of aggregate K0 = 20 KN\mm2
Direct tensile strength of concrete at 3 days (BS8007) Fct = 1.6 N\mm2 P.20Allowable Tensile stress in steel (BS8007) Fs = 100 N\mm2 table 3.1 P.9Hydration temperture to ambient tempreture for wall (BS8007) T1w = 35 degree table A.2 P.24Hydration temperture to ambient tempreture for floor (BS8007) T1f = 35 degree table A.2 P.24Variation in temperture due to seasonal changes T2 = 0 degreePartial safety factor gm = 1.25Partial safety factor for load gf = 1.4
24
ANALYSIS Loads :-
0.333
3.333 KN\m2
22.500 KN\m2
18.000 KN\m2
Check of Bearing Capacity :-2.646 KN
6.615 KN
9.261 KN
0.735 m2
12.600 KN\m2
3.600 KN\m2
9.000 KN\m2 < 150 KN\m2
External Soil and Water Pressures
For External Walls
K = ∅∅ =
= Ka =ℎ = =
= Ka ( − ) =
Wf = =
Ww = 2 =
Wtotal = + + = = =
= Wtotal
= =
= − =
25
Reinforcement Design :-
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 58.26656 mm < 71.25 mm
Take 58.26656 mm
9.152424 KN.m
0.040677 < 0.156
3.32 KN.m < 9.152423791 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 58.26656 mm < 71.25 mm
Take 58.26656 mm
9.152424 KN.m
0.040677 < 0.156
1.94 KN.m < 9.152423791 KN.m
Accepted design.
No compression steel required.
No compression steel required.
Accepted design.
For Walls
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
26
CONT'D
Vertical ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 58.26656 mm < 71.25 mm
Take 58.26656 mm
9.152424 KN.m
0.040677 < 0.156
3.81 KN.m < 9.152423791 KN.m
Horizontal ReinforcementProposed steel RFT. T 10 - 200
392.5 mm2
0.156
Z 58.26656 mm < 71.25 mm
Take 58.26656 mm
9.152424 KN.m
0.040677 < 0.156
3.79 KN.m < 9.152423791 KN.m
For Floor
No compression steel required.
Accepted design.
No compression steel required.
Accepted design.
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87 As Fy Z =
K= Mb d2 Fcu
=
As =
K′ =
= 0.5 + 0.25 − . = Z=0.95 d =
Mu=0.87As Fy Z =K= M
b d2 Fcu=
As =
K′ =
Mdesign=
Mdesign=
Z=
Z=
27
CONT'D
Check of Shear Strength :-
7.0875 N
9.45E-05 N\mm2
5.059644 N\mm2
5 N\mm2
0.9052452 N\mm2
12 N
0.00016 N\mm2
2.529822 N\mm2
5 N\mm2
0.9052452 N\mm2
For Walls
For Floor
Accepted design.
Accepted design.
Accepted design.
Accepted design.
v= == 0.8 =
=
= 0.79 100 400 25 =
=
v= == 0.8 =
=
= 0.79 100 400 25 =
=
28
CONT'D
Check early thermal crack :-
28000 N\mm2
14.286
10 200
785 mm2
75 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.005097 mm < 0.2 mm
For Walls
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
29
CONT'D
28000 N\mm2
14.286
10 200
785 mm2
75 mm
0.15
1.20E-05 /0C
0.000032
75 mm
123 mm
0.005097 mm < 0.2 mm
For Floor
= == + 0.2 =
∅ = =
=
= =
= 0.5 =
= 3 1 + 2 − ℎ −
=
. =
= ℎ2 =
= 2 + + ∅2 − ∅
2 =
30
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
3/2/16 8:52:30
31
SAP2000
SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units