Service Man
ual / R-410A Heat Pump ,
Heat Recovery RX(E)YQ72-240PYDN, PTJU
SiUS34-801A
RXYQ72-240PYDN, PTJUR-410A Heat Pump 60HzREYQ72-240PYDN,
PTJU
R-410A Heat Recovery 60Hz
RXYQ72, 96, 120PYDNRXYQ72, 96, 120PTJU
RXYQ144-240PYDNRXYQ168-240PTJU
REYQ72, 96, 120PYDNREYQ72, 96, 120, 144PTJURXYQ144PTJU
REYQ144-240PYDNREYQ168-240PTJU
SiUS34 - 801A_b
SiUS34-801APrinted in U.S.A. 09/2008 AK
Specifications, designs and other content appearing in this
brochure are current as of September 2008 but subject to change
without notice.
1645 Wallace Drive, Suite 110Carrollton, TX75006
[email protected]
AMERICAS
-
SiUS34-801A_bR-410A Heat Pump/Heat Recovery
60Hz1. Introduction
..............................................................................................
vii
1.1 Safety Considerations
................................................................................vii
1.2 PREFACE
..................................................................................................
xiii
Part 1General Information1
1. Model Names of Indoor/Outdoor
Units........................................................22.
External
Appearance...................................................................................3
2.1 Indoor Units
..................................................................................................
32.2 Outdoor Units
...............................................................................................
4
3. Combination of Outdoor
Units.....................................................................54.
Model
Selection...........................................................................................6
Part 2VRVIII R-410A Heat Pump 60Hz9
1. Specifications
............................................................................................111.1
Outdoor Units
.............................................................................................
11
2. Refrigerant Circuit
....................................................................................172.1
RXYQ72P, 96P, 120P
................................................................................
172.2 RXYQ144PTJU
..........................................................................................
18
3. Functional Parts Layout RXYQ72P, 96P, 120P
........................................213.1 RXYQ144PTJU
..........................................................................................
21
4. Refrigerant Flow for Each Operation
Mode...............................................235. Function
General.......................................................................................41
5.1 Symbol
.......................................................................................................
415.2 Operation
Mode..........................................................................................
42
6. Basic
Control.............................................................................................436.1
Normal Operation
.......................................................................................
436.2 Compressor PI
Control...............................................................................
446.3 Electronic Expansion Valve PI
Control.......................................................
476.4 Step Control of Outdoor Unit Fans
............................................................. 476.5
Outdoor Unit Fan Control in Cooling Operation
......................................... 486.6 Heat Exchanger
Control
.............................................................................
49
7. Special
Control..........................................................................................507.1
Startup Control
...........................................................................................
50Table of Contents i
-
SiUS34-801A_b7.2 Large Capacity Start Up Control
(Heating)................................................. 517.3
Oil Return Operation
..................................................................................
527.4 Defrost Operation
.......................................................................................
567.5 Pump-down Residual Operation
................................................................
587.6 Standby
......................................................................................................
607.7 Stopping Operation
....................................................................................
61
8. Protection Control
.....................................................................................638.1
High Pressure Protection
Control...............................................................
638.2 Low Pressure Protection
Control................................................................
658.3 Discharge Pipe Protection Control
............................................................. 678.4
Inverter Protection Control
.........................................................................
688.5 STD Compressor Overload
Protection.......................................................
70
9. Other
Control.............................................................................................719.1
Backup
Operation.......................................................................................
719.2 Demand Operation
.....................................................................................
719.3 Heating Operation Prohibition
....................................................................
71
10.Test Operation
..........................................................................................7210.1
Installation Process
....................................................................................
7210.2 Procedure and Outline
...............................................................................
7310.3 Operation when Power is Turned On
......................................................... 91
11.Outdoor Unit PC Board Layout
.................................................................9312.Field
Settings
............................................................................................94
12.1 Field Settings on the Outdoor Unit
.............................................................
94
Part 3VRVIII R-410A Heat Recovery 60Hz119
1. Specifications
..........................................................................................1211.1
Outdoor Units
...........................................................................................
1211.2 BS Units
...................................................................................................
126
2. Refrigerant Circuit
...................................................................................1282.1
REYQ72, 96, 120PYDN, PTJU
................................................................
1282.2 REYQ144PTJU
........................................................................................
1302.3 REMQ72PYDN, PTJU (Multi
6ton)...........................................................
1322.4 REMQ96, 120PYDN, PTJU (Multi 8,
10ton)............................................. 1342.5 BS Unit
Functional Parts
..........................................................................
136
3. Functional Parts Layout
..........................................................................1373.1
REYQ72P, 96P, 120P
..............................................................................
1373.2 REYQ144PTJU
........................................................................................
1383.3 REMQ72P
................................................................................................
1393.4 REMQ96P,
120P......................................................................................
140
4. Refrigerant Flow for Each Operation
Mode.............................................1415. Function
General.....................................................................................185
5.1 Symbol
.....................................................................................................
1855.2 Operation
Mode........................................................................................
187
6. Basic
Control...........................................................................................188ii
Table of Contents
-
SiUS34-801A_b6.1 Normal Operation
.....................................................................................
1886.2 Compressor PI
Control.............................................................................
1896.3 Electronic Expansion Valve PI
Control..................................................... 1936.4
Step Control of Outdoor Unit Fans
........................................................... 1946.5
Outdoor Unit Fan Control in Cooling Operation
....................................... 1946.6 Heat Exchanger
Control
...........................................................................
195
7. Special
Control........................................................................................1977.1
Startup Control
.........................................................................................
1977.2 Large Capacity Start Up Control
(Heating)............................................... 1987.3 Oil
Return Operation
................................................................................
1997.4 Defrost Operation
.....................................................................................
2037.5 Pump-down Residual Operation
..............................................................
2057.6 Standby
....................................................................................................
2077.7 Stopping Operation
..................................................................................
208
8. Protection Control
...................................................................................2108.1
High Pressure Protection
Control.............................................................
2108.2 Low Pressure Protection
Control..............................................................
2118.3 Discharge Pipe Protection Control
........................................................... 2138.4
Inverter Protection Control
.......................................................................
2148.5 STD Compressor Overload
Protection.....................................................
216
9. Other
Control...........................................................................................2189.1
Backup
Operation.....................................................................................
2189.2 Demand Operation
...................................................................................
2189.3 Heating Operation Prohibition
..................................................................
218
10.Test Operation
........................................................................................21910.1
Installation Process
..................................................................................
21910.2 Procedure and Outline
.............................................................................
21910.3 Operation when Power is Turned On
....................................................... 238
11.Outdoor Unit PC Board Layout
...............................................................24012.Field
Setting
............................................................................................241
12.1 Field Setting from Outdoor
Unit................................................................
241
Part 4 Indoor
Unit.........................................................................
2691. Specifications
..........................................................................................2702.
Refrigerant Circuit
...................................................................................2843.
Operation Flow Chart
..............................................................................2854.
Thermostat Sensor in Remote
Controller................................................287
4.1 Thermostat Control While in Normal Operation
....................................... 2894.2 Thermostat Control
in Dry Operation
....................................................... 2894.3
Thermostat Control with Operation Mode Set to AUTO
........................... 290
5. Drain Pump
Control.................................................................................2915.1
When the Float Switch is Tripped while the Cooling Thermostat is
ON: .. 2915.2 When the Float Switch is Tripped while the Cooling
Thermostat is OFF: 2915.3 When the Float Switch is Tripped During
Heating Operation:.................. 2925.4 When the Float Switch
is Tripped and AF is Displayed on the Remote Con-
troller:
.......................................................................................................
292Table of Contents iii
-
SiUS34-801A_b6. Control of Electronic Expansion Valve
....................................................2937. Freeze
Prevention...................................................................................2948.
Heater Control (Optional PC Board KRP1B ... is
required.)....................2959. List of Louver Operations
........................................................................29610.Hot
Start Control (In Heating Operation Only)
........................................29711.Louver Control for
Preventing Ceiling
Dirt...............................................29812.Field
Setting
............................................................................................299
12.1 Field Setting from Remote Controller
....................................................... 299
Part 5Troubleshooting
................................................................
315
1. Symptom-based Troubleshooting
..........................................................3182.
Troubleshooting by Remote Controller
...................................................321
2.1 The INSPECTION / TEST
Button.............................................................
3212.2 Self-diagnosis by Wired Remote Controller
............................................. 3222.3 Self-diagnosis
by Wireless Remote Controller
......................................... 3232.4 Inspection Mode
.......................................................................................
3262.5 Remote Controller Service Mode
.............................................................
3272.6 Test Run
Mode.........................................................................................
3292.7 Remote Controller Self-Diagnosis Function
............................................. 329
3. Troubleshooting by Indication on the Remote Controller
........................3363.1 A0 Indoor Unit: Error of External
Protection Device ................................. 3363.2 A1
Indoor Unit: PC Board Defect
............................................................ 3373.3
A3 Indoor Unit: Malfunction of Drain Level Control System (S1L)
.......... 3383.4 A6 Indoor Unit: Fan Motor (M1F) Lock, Overload
..................................... 3403.5 A7 Indoor Unit:
Malfunction of Louver Motor (M1S) ...............................
3443.6 A9 Indoor Unit: Electronic Expansion Valve
Malfunction / Dust Clogging
.....................................................................
3463.7 AF Indoor Unit: Drain Level above
Limit.................................................. 3503.8 AJ
Indoor Unit: Malfunction of Capacity Determination
Device................ 3513.9 C4 Indoor Unit: Malfunction of
Thermistor (R2T) for Heat Exchanger..... 3523.10 C5 Indoor Unit:
Malfunction of Thermistor (R3T) for Gas Pipes................
3533.11 C9 Indoor Unit: Malfunction of Thermistor (R1T) for Suction
Air ............... 3543.12 CJ Indoor Unit: Malfunction of
Thermostat Sensor in Remote Controller 3553.13 E1 Outdoor Unit: PC
Board
Defect..........................................................
3563.14 E2 Outdoor Unit: Detection of ground leakage by leak
detection PC board
assy
.........................................................................................................
3573.15 E3 Outdoor Unit: Actuation of High Pressure Switch
.............................. 3593.16 E4 Outdoor Unit: Actuation
of Low Pressure Sensor .............................. 3613.17 E5
Outdoor Unit: Inverter Compressor Motor Lock
................................. 3633.18 E6 Outdoor Unit: STD
Compressor Motor Overcurrent/Lock .................. 3653.19 E7
Outdoor Unit: Malfunction of Outdoor Unit Fan Motor
....................... 3673.20 E9 Outdoor Unit: Malfunction of
Moving Part of Electronic Expansion Valve
(Y1E~Y5E)
...............................................................................................
3703.21 F3 Outdoor Unit: Abnormal Discharge Pipe Temperature
...................... 3723.22 F6 Outdoor Unit: Refrigerant
Overcharged ............................................. 374iv
Table of Contents
-
SiUS34-801A_b3.23 H7 Outdoor Unit: Abnormal Outdoor Fan Motor
Signal ............................ 3753.24 H9 Outdoor Unit:
Malfunction of Thermistor (R1T) for Outdoor Air ......... 3773.25
J2 Outdoor Unit: Current Sensor
Malfunction......................................... 3783.26 J3
Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R31, 32T) .
3803.27 J4 Outdoor Unit: Malfunction of Temperature Sensor for Heat
Exchanger Gas
(R2T or R11T)
..........................................................................................
3813.28 J5 Outdoor Unit: Malfunction of Thermistor (R8T or R10T)
Suction Pipe. 3823.29 J6 Outdoor Unit: Malfunction of Thermistor
(R4T or R12T) for Outdoor Unit
Heat
Exchanger........................................................................................
3833.30 J7 Outdoor Unit: Malfunction of Liquid Pipe Thermistor 1
(R6T), (R9T) or
(R14T)
......................................................................................................
3843.31 J8 Outdoor Unit: Malfunction of Liquid Pipe Thermistor 2
(R7T or R15T) 3853.32 J9 Outdoor Unit: Malfunction of Subcooling
Heat Exchanger Gas Pipe Ther-
mistor (R5T or R13T)
...............................................................................
3863.33 JA Outdoor Unit: Malfunction of High Pressure Sensor
............................ 3873.34 JC Outdoor Unit: Malfunction
of Low Pressure Sensor............................. 3893.35 L1
Outdoor Unit: Defective Inverter PC
Board.......................................... 3913.36 L4 Outdoor
Unit: Malfunction of Inverter Radiating Fin Temperature Rise3933.37
L5 Outdoor Unit: Momentary Overcurrent of Inverter
Compressor........... 3963.38 L8 Outdoor Unit: Momentary
Overcurrent of Inverter Compressor........... 3983.39 L9 Outdoor
Unit: Inverter Compressor Starting Failure
............................ 4003.40 LC Outdoor Unit: Malfunction
of Transmission between Inverter and Control
PC
Board..................................................................................................
4033.41 P1 Outdoor Unit: Inverter Over-Ripple Protection
..................................... 4063.42 P4 Outdoor Unit:
Malfunction of Inverter Radiating Fin Temperature Rise Sen-
sor
............................................................................................................
4083.43 PJ Outdoor Unit: Faulty Field Setting after Replacing Main
PC Board or Faulty
Combination of PC
Board.........................................................................
4103.44 U0 Outdoor Unit: Gas Shortage Alert
........................................................ 4123.45 U1
Reverse Phase, Open Phase
..............................................................
4143.46 U2 Outdoor Unit: Power Supply Insufficient or Instantaneous
Failure ...... 4153.47 U3 Outdoor Unit: Check Operation not
Executed...................................... 4183.48 U4
Malfunction of Transmission between Indoor Units
............................. 4193.49 U5 Indoor Unit: Malfunction
of Transmission between Remote Controller and
Indoor
Unit................................................................................................
4243.50 U7 Outdoor Unit: Transmission Failure (Across Outdoor
Units)................ 4253.51 U8 Indoor Unit: Malfunction of
Transmission between Main and Sub Remote
Controllers
................................................................................................
4313.52 U9 Indoor Unit: Malfunction of Transmission between Indoor
and Outdoor
Units in the Same System
........................................................................
4323.53 UA Improper Combination of Indoor and Outdoor Units, Indoor
Units and Re-
mote
Controller.........................................................................................
4333.54 UC Address Duplication of Centralized Controller
..................................... 4393.55 UE Malfunction of
Transmission between Centralized Controller and Indoor
Unit
...........................................................................................................
4403.56 UF System is not Set yet
...........................................................................
4433.57 UH Malfunction of System, Refrigerant System Address
Undefined ......... 444
4. Troubleshooting (OP: Central Remote Controller)
..................................446Table of Contents v
-
SiUS34-801A_b4.1 M1 PC Board Defect
.................................................................................
4464.2 M8 Malfunction of Transmission between Optional Controllers
for Centralized
Control......................................................................................................
4474.3 MA Improper Combination of Optional Controllers for
Centralized Control4494.4 MC Address Duplication, Improper
Setting................................................ 451
5. Troubleshooting (OP: Unified ON/OFF Controller)
.................................4535.1 Operation Lamp Blinks
.............................................................................
4535.2 Display [Under Centralized Control] Blinks (Repeats Single
Blink).......... 4555.3 Display [Under Centralized Control] Blinks
(Repeats Double Blink) ........ 458
Part 6
Appendix............................................................................
4731. Piping
Diagrams......................................................................................474
1.1 Outdoor Unit
.............................................................................................
4741.2 Indoor
Unit................................................................................................
4841.3 BS Unit
.....................................................................................................
486
2. Wiring Diagrams for
Reference...............................................................4872.1
Outdoor Unit
.............................................................................................
4872.2 Field Wiring
..............................................................................................
4972.3 Indoor
Unit................................................................................................
5052.4 BS Unit
BSVQ36P/60PVJU.....................................................................
509
3. List of Electrical and Functional Parts
.....................................................5103.1 Outdoor
Unit
.............................................................................................
5103.2 Indoor Side
...............................................................................................
514
4. Option List
...............................................................................................5184.1
Option List of
Controllers..........................................................................
5184.2 Option Lists (Outdoor
Unit).......................................................................
519
5. Piping Installation
Point...........................................................................5205.1
Piping between Outside Units
..................................................................
520
6. Thermistor Resistance / Temperature
Characteristics............................5237. Pressure Sensor
.....................................................................................5258.
Method of Checking Inverters Power Transistors & Diode Modules
......5269. Example of Connection
...........................................................................529
Part 7 Precautions for New Refrigerant (R-410A)
....................... 5351. Precautions for New Refrigerant
(R-410A) .............................................536
1.1 Service
Tools............................................................................................
538
Index
................................................................................................
i
Drawings & Flow Charts
...................................................... ivvi Table
of Contents
-
Introduction SiUS34-801A_b1. Introduction1.1 Safety
ConsiderationsCautions and Warnings
Read these SAFETY CONSIDERATIONS carefully before installing air
conditioning equipment, and be sure to install it correctly. After
completing the installation, make sure that the unit operates
properly during the start-up operation.Instruct the customer how to
operate and maintain the unit. Inform customers that they should
store this Installation Manual with the Operation Manual for future
ref-erence.
Always use a licensed installer or contractor to install this
product. Improper installation can result in water or refrigerant
leakage, electrical shock, fire, or explosion.Meanings of DANGER,
WARNING, CAUTION, and NOTE Symbols:
DANGER ............... Indicates an imminently hazardous
situation which, if not avoided, will result in death or serious
injury.
WARNING ............. Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious
injury.
CAUTION .............. Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe practices.
NOTE .....................Indicates situations that may result
in equipment or property-damage accidents only. Be sure to read the
following safety cautions before
conducting conducting repair work.
1.1.1 Caution in RepairWarning
Be sure to disconnect the power cable plug from the plug socket
before disassembling the equipment for a repair.Working on the
equipment that is connected to a power supply can cause an
electrical shock. If it is necessary to supply power to the
equipment to conduct the repair or inspecting the circuits, do not
touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not
touch the discharging refrigerant gas.The refrigerant gas can cause
frostbite.
vii
-
SiUS34-801A_bWhen disconnecting the suction or discharge pipe of
the compressor at the welded section, release the refrigerant gas
completely at a well-ventilated place first.If there is a gas
remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected,
and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate
the area. The refrigerant gas can generate toxic gases when it
contacts flames.
The step-up capacitor supplies high-voltage electricity to the
electrical components of the outdoor unit.Be sure to discharge the
capacitor completely before conducting repair work.A charged
capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging
or unplugging the power cable plug.Plugging or unplugging the power
cable plug to operate the equipment can cause an electrical shock
or fire.
Warningviii
-
Introduction SiUS34-801A_b1.1.2 Cautions Regarding Products
after Repair
CautionDo not repair the electrical components with wet
hands.Working on the equipment with wet hands can cause an
electrical shock.
Do not clean the air conditioner by splashing water.Washing the
unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in
a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.The internal fan rotates at a high
speed, and can cause injury.
Do not tilt the unit when removing it.The water inside the unit
can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled
down sufficiently before conducting repair work.Working on the unit
when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.Using the welder in an
enclosed room can cause oxygen deficiency.
WarningBe sure to use parts listed in the service parts list of
the applicable model and appropriate tools to conduct repair work.
Never attempt to modify the equipment. The use of inappropriate
parts or tools can cause an electrical shock, excessive heat
generation or fire.ix
-
SiUS34-801A_bWhen relocating the equipment, make sure that the
new installation site has sufficient strength to withstand the
weight of the equipment.If the installation site does not have
sufficient strength and if the installation work is not conducted
securely, the equipment can fall and cause injury.Be sure to
install the product correctly by using the provided standard
installation frame.Incorrect use of the installation frame and
improper installation can cause the equipment to fall, resulting in
injury.
For integral units only
Be sure to install the product securely in the installation
frame mounted on a window frame.If the unit is not securely
mounted, it can fall and cause injury.
For integral units only
Be sure to use an exclusive power circuit for the equipment, and
follow the technical standards related to the electrical equipment,
the internal wiring regulations and the instruction manual for
installation when conducting electrical work.Insufficient power
circuit capacity and improper electrical work can cause an
electrical shock or fire.
Be sure to use the specified cable to connect between the indoor
and outdoor units. Make the connections securely and route the
cable properly so that there is no force pulling the cable at the
connection terminals.Improper connections can cause excessive heat
generation or fire.When connecting the cable between the indoor and
outdoor units, make sure that the terminal cover does not lift off
or dismount because of the cable.If the cover is not mounted
properly, the terminal connection section can cause an electrical
shock, excessive heat generation or fire.
Do not damage or modify the power cable.Damaged or modified
power cable can cause an electrical shock or fire.Placing heavy
items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant
(R-410A) in the refrigerant system.If air enters the refrigerating
system, an excessively high pressure results, causing equipment
damage and injury.If the refrigerant gas leaks, be sure to locate
the leak and repair it before charging the refrigerant. After
charging refrigerant, make sure that there is no refrigerant leak.
If the leak cannot be located and the repair work must be stopped,
be sure to perform pump-down and close the service valve, to
prevent the refrigerant gas from leaking into the room. The
refrigerant gas itself is harmless, but it can generate toxic gases
when it contacts flames, such as fan and other heaters, stoves and
ranges.When replacing the coin battery in the remote controller, be
sure to dispose of the old battery to prevent children from
swallowing it.If a child swallows the coin battery, see a doctor
immediately.
Warningx
-
Introduction SiUS34-801A_b1.1.3 Inspection after Repair
CautionInstallation of a leakage breaker is necessary in some
cases depending on the conditions of the installation site, to
prevent electrical shocks.Do not install the equipment in a place
where there is a possibility of combustible gas leaks.If a
combustible gas leaks and remains around the unit, it can cause a
fire.
Be sure to install the packing and seal on the installation
frame properly.If the packing and seal are not installed properly,
water can enter the room and wet the furniture and floor.
For integral units only
WarningCheck to make sure that the power cable plug is not dirty
or loose, then insert the plug into a power outlet all the way.If
the plug has dust or loose connection, it can cause an electrical
shock or fire.
If the power cable and lead wires have scratches or have
deteriorated, be sure to replace them.Damaged cable and wires can
cause an electrical shock, excessive heat generation or fire.
Do not use a joined power cable or extension cable, or share the
same power outlet with other electrical appliances, since it can
cause an electrical shock, excessive heat generation or fire.
CautionCheck to see if the parts and wires are mounted and
connected properly, and if the connections at the soldered or
crimped terminals are secure.Improper installation and connections
can cause excessive heat generation, fire or an electrical
shock.
If the installation platform or frame has corroded, replace
it.Corroded installation platform or frame can cause the unit to
fall, resulting in injury.Check the grounding, and repair it if the
equipment is not properly grounded.Improper grounding can cause an
electrical shock.xi
-
SiUS34-801A_bBe sure to measure the insulation resistance after
the repair, and make sure that the resistance is 1 ohm or
higher.Faulty insulation can cause an electrical shock.Be sure to
check the drainage of the indoor unit after the repair.Faulty
drainage can cause the water to enter the room and wet the
furniture and floor.
Cautionxii
-
Introduction SiUS34-801A_b1.2 PREFACEThank you for your
continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2008 VRVIII
series Heat Pump System.Daikin offers a wide range of models to
respond to building and office air conditioning needs. We are
confident that customers will be able to find the models that best
suit their needs.
This service manual contains information regarding the servicing
of VRVIII series Heat Pump, Heat Recovery System.
May, 2008
After Sales Service Divisionxiii
-
SiUS34-801A_bxiv
-
SiUS34-801A_b
General Information 1
Part 1General Information
1. Model Names of Indoor/Outdoor
Units........................................................22.
External
Appearance...................................................................................3
2.1 Indoor Units
..................................................................................................
32.2 Outdoor Units
...............................................................................................
4
3. Combination of Outdoor
Units.....................................................................54.
Model
Selection...........................................................................................6
-
Model Names of Indoor/Outdoor Units SiUS34-801A_b1. Model Names
of Indoor/Outdoor UnitsIndoor Units
BS Units
Outdoor Units (Inverter Series)
Combination of Outdoor UnitsHeat Pump
Heat Recovery
Type Model Name Power Supply, Compatibility
SymbolCeiling-Mounted Cassette Type(Multi Flow)
FXFQ 12M 18M 24M 30M 36M
VJU
4 Way Ceiling Mounted Cassette Type Unit (22)
FXZQ 07M7 09M7 12M7 18M7
Slim Ceiling-MountedDuct Type FXDQ 07M 09M 12M 18M 24M
Ceiling Mounted Built-In Type FXSQ 12M 18M 24M 30M 36M 48M
Ceiling Mounted Duct Type FXMQ 30M 36M 48M
Ceiling Suspended Type FXHQ 12M 24M 36M
Wall Mounted Type FXAQ 07M 09M 12M 18M 24M
Floor Standing Type FXLQ 12M 18M 24M
Concealed Floor Standing Type FXNQ 12M 18M 24M
Type Model Name Power Supply, Compatibility SymbolHeat Recovery
Series BSVQ 36P 60P VJU
TypeModel Name Power Supply,
Compatibility Symbol6 ton 8 ton 10 ton 12 ton 14 ton 16 ton 18
ton 20 ton
Heat Pump230V RXYQ- 72P 96P 120P 144P 168P 192P 216P 240P
TJU460V RXYQ- 72P 96P 120P 144P 168P 192P 216P 240P YDN
Heat Recovery230V REYQ- 72P 96P 120P 144P 168P 192P 216P 240P
TJU460V REYQ- 72P 96P 120P 144P 168P 192P 216P 240P YDN
Model Name RXYQ72P RXYQ96P RXYQ120P RXYQ144P RXYQ168P RXYQ192P
RXYQ216P RXYQ240P230V 460V
Outdoor unit 1 RXYQ72P RXYQ96P RXYQ120P RXYQ144P RXYQ72P RXYQ72P
RXYQ72P RXYQ96P RXYQ120POutdoor unit 2 RXYQ72P RXYQ96P RXYQ120P
RXYQ120P RXYQ120P
Model Name REYQ72P REYQ96P REYQ120P REYQ144P REYQ168P REYQ192P
REYQ216P REYQ240P230V 460V
Outdoor unit 1 REYQ72P REYQ96P REYQ120P REYQ144P REMQ72P REMQ72P
REMQ72P REMQ96P REMQ120POutdoor unit 2 REMQ72P REMQ96P REMQ120P
REMQ120P REMQ120P
VJ: 1, 208~230V, 60HzYDN: 3, 460V, 60HzTJ: 3, 208~230V,
60HzU(VJU, TJU): Standard Compatibility Symbol2 General
Information
-
SiUS34-801A_b External Appearance2. External Appearance2.1
Indoor Units2.1.1 Indoor Units Heat Pump, Heat Recovery
(60Hz)Ceiling-mounted cassette type (Multi flow)
FXFQ12MVJUFXFQ18MVJUFXFQ24MVJUFXFQ30MVJUFXFQ36MVJU
Ceiling suspended type
FXHQ12MVJUFXHQ24MVJUFXHQ36MVJU
4 way ceiling-mounted cassette unit (22)
FXZQ07M7FXZQ09M7FXZQ12M7FXZQ18M7
Wall mounted type
FXAQ07MVJUFXAQ09MVJUFXAQ12MVJUFXAQ18MVJUFXAQ24MVJU
Slim ceiling-mounted duct type
FXDQ07MVJUFXDQ09MVJUFXDQ12MVJUFXDQ18MVJUFXDQ24MVJU
Floor standing type
FXLQ12MVJUFXLQ18MVJUFXLQ24MVJU
Ceiling mounted built-in type
FXSQ12MVJUFXSQ18MVJUFXSQ24MVJUFXSQ30MVJUFXSQ36MVJUFXSQ48MVJU
Concealed floor standing type
FXNQ12MVJUFXNQ18MVJUFXNQ24MVJU
Ceiling-mounted duct type
FXMQ30MVJUFXMQ36MVJUFXMQ48MVJU
BS Units
BSVQ36PVJUBSVQ60PVJUGeneral Information 3
-
External Appearance SiUS34-801A_b2.2 Outdoor UnitsRXYQ72P, 96P,
120PYDNRXYQ72P, 96P, 120PTJU
H/P (460V)H/P (230V)
H/P (230V)H/P (460V)H/P (230V)RXYQ144PTJU
RXYQ144P, 168P, 192P, 216P, 240PYDNRXYQ168P, 192P, 216P,
240PTJU
REYQ72P, 96P, 120PYDNREYQ72P, 96P, 120P, 144PTJU
REYQ144P, 168P, 192P, 216P, 240PYDNREYQ168P, 192P, 216P,
240PTJU
H/R (460V)H/R (230V)
H/R (460V)H/R (230V)4 General Information
-
SiUS34-801A_b Combination of Outdoor Units3. Combination of
Outdoor UnitsHeat PumpSingle Use
Multiple Use
Heat RecoverySingle Use
Multiple Use
Note: For multiple connection of 12 ton system or more, an
optional Daikin Outdoor Unit Multi Connection Piping Kit is
required.
Ton Number of units
Single Unit Outdoor Unit Multi Connection Piping Kit (Option)72
96 120 144
6 ton 1 O
8 ton 1 O10 ton 1 O12 ton (230V) 1 O
Ton Number of units
Multi Unit Module Outdoor Unit Multi Connection Piping Kit
(Option)72 96 120
12 ton(460V) 2 OO
Heat Pump: BHFP22P100U14 ton 2 O O16 ton 2 O O18 ton 2 O O20 ton
2 OO
Ton Number of unitsSingle Unit Outdoor Unit Multi Connection
Piping Kit (Option)72 96 120 1446 ton 1 O
8 ton 1 O10 ton 1 O12 ton (230V) O
Ton Number of unitsMulti Unit Module Outdoor Unit Multi
Connection
Piping Kit (Option)72 96 12012 ton(460V) 2
OO
Heat Recovery: BHFP26P90U14 ton 2 O O16 ton 2 O O18 ton 2 O O20
ton 2 OOGeneral Information 5
-
Model Selection SiUS34-801A_b4. Model SelectionVRVIII
SeriesConnectable Indoor Units Number and CapacityHeat Pump
Heat Recovery
Connectable Indoor Unit
Ton 6 ton 8 ton 10 ton 12 ton (230V)12 ton (460V) 14 ton 16 ton
18 ton 20 ton
System name RXYQ72P RXYQ96P RXYQ120P RXYQ144PTJU RXYQ144P
RXYQ168P RXYQ192P RXYQ216P RXYQ240POutdoor unit 1 RXYQ72P RXYQ96P
RXYQ120P RXYQ144PTJU RXYQ72P RXYQ72P RXYQ72P RXYQ96P
RXYQ120POutdoor unit 2 RXYQ72P RXYQ96P RXYQ120P RXYQ120P
RXYQ120PTotal number of connectable indoor units 12 16 20 24 24 29
33 37 41
Total Capacity Index of Indoor Units to be Connected 36~93.5
48~124.5 60~156 72~187 72~187 84~218 96~249.5 108~280.5 120~312
Ton 6ton 8ton 10ton 12ton (230V)12ton (460V) 14ton 16ton 18ton
20ton
System name REYQ72P REYQ96P REYQ120P REYQ144PTJU REYQ144P
REYQ168P REYQ192P REYQ216P REYQ240POutdoor unit 1 REYQ72P REYQ96P
REYQ120P REYQ144PTJU REMQ72P REMQ72P REMQ72P REMQ96P
REMQ120POutdoor unit 2 REMQ72P REMQ96P REMQ120P REMQ120P
REMQ120PTotal number of connectable indoor units 12 16 20 24 24 29
33 37 41
Total Capacity Index of Indoor Units to be Connected 36~93.5
48~124.5 60~156 72~187 72~187 84~218 96~249.5 108~280.5 120~312
Type Model Name Power SupplyCapacity Range 0.6ton 0.8ton 1ton
1.5ton 2ton 2.5ton 3ton 4ton
VJU
Capacity Index 7.5 9.5 12 18 24 30 36 48Ceiling Mounted-Cassette
Type (Multi Flow) FXFQ 12M 18M 24M 30M 36M 4 Way Ceiling Mounted
Cassette Unit (2 2) FXZQ 07M 09M 12M 18M Slim Ceiling-MountedDuct
Type FXDQ 07M 09M 12M 18M 24M Ceiling Mounted Built-In Type FXSQ
12M 18M 24M 30M 36M 48MCeiling Mounted Duct Type FXMQ 30M 36M
48M
Ceiling Suspended Type FXHQ 12M 24M 36M
Wall Mounted Type FXAQ 07M 09M 12M 18M 24M
Floor Standing Type FXLQ 12M 18M 24M Concealed Floor Standing
Type FXNQ 12M 18M 24M 6 General Information
-
SiUS34-801A_b Model SelectionIndoor Unit Capacity
Use the above tables to determine the capacities of indoor units
to be connected. Make sure the total capacity of indoor units
connected to each outdoor unit is within the specified value
(Btu/h). The total capacity of connected indoor units can be within
a range of 50 to 200% of the rated
capacity of the outdoor unit (rules apply). In some models, it
is not possible to connect the maximum number of connectable indoor
units.
Select models so that the total capacity of connected indoor
units conforms to the specification.
Unit Number and Capacity of Indoor Unit Connectable to BS
Unit
Differences from Conventional Models
New refrigerant model code 07 type 09 type 12 type 18 type 24
type 30 type 36 type 48 type
Selecting model capacity 7,500Btu/h9,500Btu/h
12,000Btu/h
18,000Btu/h
24,000Btu/h
30,000Btu/h
36,000Btu/h
48,000Btu/h
Equivalent output 0.6 ton 0.8 ton 1 ton 1.5 ton 2 ton 2.5 ton 3
ton 4 ton
Capacity of BS unit BSVQ36P BSVQ60PUnit number of connectable
indoor unit Five units or less Eight units or less
Total capacity of connectable indoor unit Less than 36000
Btu/h
36000 Btu/h or more, less than60000 Btu/h
Connectable indoor unit Types 07M to 36M Types 07M to 48M
ItemDifferences
Object New model (P Model) Conventional model (M Model)
Compressor Connection of equalizer oil pipez NONE
(No particular changes in terms of service)
z YES
Workability
Equalizer oil pipe for multi-outdoor-unit system z NONE z
YES
Procedure for calculating refrigerant refilling quantity
z Refilling quantity due to piping length + Adjustment quantity
according to models of outdoor units
z Refilling quantity due to piping length - Adjustment quantity
according to models of outdoor units
Optional accessories Branch pipe for outdoor unit connectionz Y
branch
Type: BHFP26P90Uz T branch
Type: BHFP26M90UGeneral Information 7
-
Model Selection SiUS34-801A_b8 General Information
-
SiUS34-801A_bPart 2VRVIII R-410A Heat Pump
60Hz
1. Specifications
............................................................................................111.1
Outdoor Units
.............................................................................................
11
2. Refrigerant Circuit
....................................................................................172.1
RXYQ72P, 96P, 120P
................................................................................
172.2 RXYQ144PTJU
..........................................................................................
18
3. Functional Parts Layout RXYQ72P, 96P, 120P
........................................213.1 RXYQ144PTJU
..........................................................................................
21
4. Refrigerant Flow for Each Operation
Mode...............................................235. Function
General.......................................................................................41
5.1 Symbol
.......................................................................................................
415.2 Operation
Mode..........................................................................................
42
6. Basic
Control.............................................................................................436.1
Normal Operation
.......................................................................................
436.2 Compressor PI
Control...............................................................................
446.3 Electronic Expansion Valve PI
Control.......................................................
476.4 Step Control of Outdoor Unit Fans
............................................................. 476.5
Outdoor Unit Fan Control in Cooling Operation
......................................... 486.6 Heat Exchanger
Control
.............................................................................
49
7. Special
Control..........................................................................................507.1
Startup Control
...........................................................................................
507.2 Large Capacity Start Up Control
(Heating)................................................. 517.3
Oil Return Operation
..................................................................................
527.4 Defrost Operation
.......................................................................................
567.5 Pump-down Residual Operation
................................................................
587.6 Standby
......................................................................................................
607.7 Stopping Operation
....................................................................................
61
8. Protection Control
.....................................................................................638.1
High Pressure Protection
Control...............................................................
638.2 Low Pressure Protection
Control................................................................
658.3 Discharge Pipe Protection Control
............................................................. 678.4
Inverter Protection Control
.........................................................................
688.5 STD Compressor Overload
Protection.......................................................
70
9. Other
Control.............................................................................................719.1
Backup
Operation.......................................................................................
719.2 Demand Operation
.....................................................................................
71VRVIII R-410A Heat Pump 60Hz 9
-
SiUS34-801A_b9.3 Heating Operation Prohibition
....................................................................
7110.Test Operation
..........................................................................................72
10.1 Installation Process
....................................................................................
7210.2 Procedure and Outline
...............................................................................
7310.3 Operation when Power is Turned On
......................................................... 91
11.Outdoor Unit PC Board Layout
.................................................................9312.Field
Settings
............................................................................................94
12.1 Field Settings on the Outdoor Unit
............................................................. 9410
VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Specifications1. Specifications1.1 Outdoor
UnitsHeat Pump 60Hz 460V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+2 Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB /
Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+3 Anechoic chamber conversion value, measured under JISB8616
conditions. During actual operation,
these values are normally somewhat higher as a result of ambient
conditions.
Model Name RXYQ72PYDN RXYQ96PYDN RXYQ120PYDNPower Supply 3 Phase
60Hz 460V 3 Phase 60Hz 460V 3 Phase 60Hz 460V+1 Cooling Capacity
Btu / h 72,000 96,000 120,000+2 Heating Capacity Btu / h 81,000
108,000 135,000Casing Color Ivory White (5Y7.5/1) Ivory White
(5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (HWD) in(mm) 66-1/8 36-5/8 30-1/8 (1680 x 930 x 765
mm)
66-1/8 36-5/8 30-1/8 (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Hermetically Sealed Scroll Type Piston Displacement m3/h
10.53+13.34 10.53+13.34 10.53+13.34Number of Revolutions r.p.m
(2900, 6300) 2900, 6300 2900, 6300Motor OutputNumber of Units kW
(4.7) 1 (2.2+4.5) 1 (3.5+4.5) 1Starting Method Soft Start Soft
Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor Output kW
(0.75) 1 (0.75) 1 (0.75) 1Air Flow Rate cfm 6,530 6,530 7,060Drive
Direct Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe in(mm) 3/8 (9.5 mm) C1220T(Brazing Connection)3/8
(9.5 mm) C1220T(Brazing Connection)
1/2 (12.7 mm) C1220T(Brazing Connection)
Gas Pipe in(mm) 3/4 (19.1 mm) C1220T(Brazing Connection)7/8
(22.2 mm) C1220T(Brazing Connection)
1-1/8 (28.6 mm) in C1220T(Brazing Connection)
Mass Lbs (kg) 573 (260 kg) 573 (260 kg) 573 (260 kg)+3 Sound
Level (Reference Value) dBA 58 58 60
Safety DevicesHigh Pressure Switch, Fan Driver
Overload Protector, Overcurrent Relay, Inverter Overload
Protector
High Pressure Switch, Fan Driver Overload Protector, Overcurrent
Relay,
Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Overcurrent
Relay,
Inverter Overload ProtectorDefrost Method Deicer Deicer
DeicerCapacity Control % 20~100 14~100 14~100
RefrigerantRefrigerant Name R-410A R-410A R-410ACharge Lbs 18.1
19.8 20.1 Control Electronic Expansion Valve Electronic Expansion
Valve Electronic Expansion Valve
Standard Accessories Installation Manual, Operation Manual,
Connection Pipes, CrampsInstallation Manual, Operation Manual,
Connection Pipes, CrampsInstallation Manual, Operation
Manual,
Connection Pipes, CrampsDrawing No. 4D058599B 4D058600A
4D058601AVRVIII R-410A Heat Pump 60Hz 11
-
Specifications SiUS34-801A_bHeat Pump 60Hz 460V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+2 Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB /
Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+3 BHFP22P100U is necessary for the connection.
Concerning about the piping connection for each outdoor unit to
the main line as shown above, use REFNET.
Model Name (Combination Unit) RXYQ144PYDN RXYQ168PYDN
RXYQ192PYDNModel Name (Independent Unit) RXYQ72PYDNRXYQ72PYDN
RXYQ72PYDNRXYQ96PYDN
RXYQ72PYDNRXYQ120PYDN
Power Supply 3 Phase 60Hz 460V 3 Phase 60Hz 460V 3 Phase 60Hz
460V+1 Cooling Capacity Btu / h 144,000 168,000 192,000+2 Heating
Capacity Btu / h 162,000 189,000 216,000Casing Color Ivory White
(5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (HWD) in(mm)66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8
30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Hermetically Sealed Scroll TypePiston Displacement m3/h 16.90
+ (10.53+13.34) 16.90 + (10.53+13.34) 16.90 + (10.53+13.34)Number
of Revolutions r.p.m 7980, (2900, 6300) 7980, (2900, 6300) 7980,
(2900, 6300)Motor OutputNumber of Units kW (4.7) 2 (4.7) 1 +
(2.2+4.5) 1 (4.7) 1 + (3.5+4.5) 1Starting Method Soft Start Soft
Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor Output kW
(0.75) 1 + (0.75) 1 (0.75) 1 + (0.75) 1 (0.75) 1 + (0.75) 1Air Flow
Rate cfm 6,530+6,530 6,530+6,530 6,530+7,060Drive Direct Drive
Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe +3 in(mm) 1/2 (12.7 mm) C1220T(Brazing Connection)
5/8 (15.8 mm) C1220T(Brazing Connection) 5/8 (15.8 mm)
C1220T(Brazing Connection)High Pressure Equalizer Pipe in(mm)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Gas Pipe +3 in(mm) 1-1/8 (28.6 mm) C1220T(Brazing
Connection)1-1/8 (28.6 mm) C1220T
(Brazing Connection)1-1/8 (28.6 mm) C1220T
(Brazing Connection)Low Pressure Equalizer Pipe in(mm)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Mass Lbs (kg) 573 + 573 (260 + 260 kg) 573 + 573 (260 + 260 kg)
573 + 573 (260 + 260 kg)
Safety DevicesHigh Pressure Switch, Fan Driver
Overload Protector, Overcurrent Relay, Inverter Overload
Protector
High Pressure Switch, Fan Driver Overload Protector, Overcurrent
Relay,
Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Overcurrent
Relay,
Inverter Overload ProtectorDefrost Method Deicer Deicer
DeicerCapacity Control % 13~100 9~100 7~100
RefrigerantRefrigerant Name R-410A R-410A R-410ACharge Lbs
18.1+18.1 18.1+19.8 18.1+20.1Control Electronic Expansion Valve
Electronic Expansion Valve Electronic Expansion Valve
Standard Accessories Installation Manual, Operation Manual,
Connection Pipes, CrampsInstallation Manual, Operation Manual,
Connection Pipes, CrampsInstallation Manual, Operation
Manual,
Connection Pipes, CrampsDrawing No. 4D059661B 4D059662B
4D059663B12 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b SpecificationsHeat Pump 60Hz 460V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+2 Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB /
Equivalent piping length : 25 ft (7.5 m), level difference : 0
ft.+3 BHFP22P100U is necessary for the connection.
Concerning about the piping connection for each outdoor unit to
the main line as shown above, use REFNET.
Model Name (Combination Unit) RXYQ216PYDN RXYQ240PYDNModel Name
(Independent Unit) RXYQ96PYDNRXYQ120PYDN
RXYQ120PYDNRXYQ120PYDN
Power Supply 3 Phase 60Hz 460V 3 Phase 60Hz 460V+1 Cooling
Capacity Btu / h 216,000 240,000+2 Heating Capacity Btu / h 243,000
270,000Casing Color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Dimensions: (HWD) in(mm)66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8
30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Piston Displacement m3/h (10.53+13.34) 2 (10.53+13.34) 2Number
of Revolutions r.p.m (2900, 6300) 2 (2900, 6300) 2Motor
OutputNumber of Units kW (2.2+4.5) 1 + (3.5+4.5) 1 (3.5+4.5)
2Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller FanMotor Output kW (0.75) 1 +
(0.75) 1 (0.75) 1 + (0.75) 1Air Flow Rate cfm 6,530+7,060
7,060+7,060Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe +3 in(mm) 5/8 (15.8 mm) C1220T(Brazing Connection)
5/8 (15.8 mm) C1220T(Brazing Connection)High Pressure Equalizer
Pipe in(mm)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Gas Pipe +3 in(mm) 1-1/8 (28.6 mm) C1220T(Brazing
Connection)1-3/8 (34.9 mm) C1220T
(Brazing Connection)Low Pressure Equalizer Pipe in(mm)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Mass Lbs (kg) 573 + 573 (260 + 260 kg) 573 + 573 (260 + 260
kg)Safety Devices High Pressure Switch, Fan Driver Overload
Protector, Overcurrent Relay, Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Overcurrent
Relay, Inverter Overload Protector
Defrost Method Deicer DeicerCapacity Control % 7~100 6~100
RefrigerantRefrigerant Name R-410A R-410ACharge Lbs 19.8+20.1
20.1+20.1Control Electronic Expansion Valve Electronic Expansion
Valve
Standard Accessories Installation Manual, Operation Manual,
Connection Pipes, CrampsInstallation Manual, Operation Manual,
Connection Pipes,
CrampsDrawing No. 4D059664A 4D059665AVRVIII R-410A Heat Pump
60Hz 13
-
Specifications SiUS34-801A_bHeat Pump 60Hz 230V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length : 25 ft (7.5 m), level difference: 0
ft.+2 Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB /
Equivalent piping length : 25 ft (7.5 m), level difference: 0 ft.+3
Anechoic chamber conversion value, measured under JISB8616
conditions. During actual operation,
these values are normally somewhat higher as a result of ambient
conditions.
Model Name RXYQ72PTJU RXYQ96PTJU RXYQ120PTJUPower Supply 3 Phase
60Hz 208V-230V 3 Phase 60Hz 208V-230V 3 Phase 60Hz 208V-230V+1
Cooling Capacity Btu / h 72,000 96,000 120,000+2 Heating Capacity
Btu / h 81,000 108,000 135,000Casing Color Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)Dimensions: (HWD) in
(mm) 66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 mm)66-1/8 36-5/8 30-1/8 (1680 x 930 x 765
mm)
66-1/8 36-5/8 30-1/8 (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Hermetically Sealed Scroll Type Piston Displacement m3/h
10.53+13.34 10.53+13.34 10.53+13.34Number of Revolutions r.p.m
(2900, 6300) 2900, 6300 2900, 6300Motor OutputNumber of Units kW
(4.7) 1 (2.2+4.5) 1 (3.5+4.5) 1Starting Method Soft Start Soft
Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor Output kW
(0.75) 1 (0.75) 1 (0.75) 1Air Flow Rate cfm 6,530 6,530 7,060Drive
Direct Drive Direct Drive Direct Drive
Connecting Pipes Liquid Pipe in (mm)
3/8 (9.5 mm) C1220T(Brazing Connection)
3/8 (9.5 mm) C1220T(Brazing Connection)
1/2 (12.7 mm) C1220T(Brazing Connection)
Gas Pipe in (mm) 3/4 (19.1 mm) C1220T(Brazing Connection) 7/8
(22.2 mm) C1220T
(Brazing Connection)1-1/8 (28.6 mm C1220T
(Brazing Connection)
Mass Lbs (kg) 560 (254 kg) 560 (254 kg) 560 (254 kg)+3 Sound
Level (Reference Value) dBA 58 58 60
Safety DevicesHigh Pressure Switch,
Fan Driver Overload Protector,Overcurrent Relay,
Inverter Overload Protector
High Pressure Switch,Fan Driver Overload Protector,
Overcurrent Relay,Inverter Overload Protector
High Pressure Switch,Fan Driver Overload Protector,
Overcurrent Relay,Inverter Overload Protector
Defrost Method Deicer Deicer DeicerCapacity Control % 20~100
14~100 14~100
RefrigerantRefrigerant Name R-410A R-410A R-410ACharge Lbs 18.1
19.8 20.1Control Electronic Expansion Valve Electronic Expansion
Valve Electronic Expansion Valve
Standard AccessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, ClampsDrawing No. 4D058605A 4D058606A
4D058607A14 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b SpecificationsHeat Pump 60Hz 230V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length :25 ft (7.5 m), level difference: 0
ft.+2 Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB /
Equivalent piping length : 25 ft (7.5 m), level difference: 0 ft.+3
BHFP22P100U is necessary for the connection.
Concerning about the piping connection for each outdoor unit to
the main line as shown above, use REFNET.+4 Anechoic chamber
conversion value, measured under JISB8616 conditions. During actual
operation,
these values are normally somewhat higher as a result of ambient
conditions.
Model Name RXYQ144PTJU RXYQ168PTJU RXYQ192PTJU
Model (Independent Unit) RXYQ72PTJURXYQ96PTJURXYQ72PTJU
RXYQ120PTJUPower Supply 3 Phase 60Hz 208V-230V 3 Phase 60Hz
208V-230V 3 Phase 60Hz 208V-230V+1 Cooling Capacity Btu / h 144,000
168,000 192,000+2 Heating Capacity Btu / h 162,000 189,000
216,000Casing Color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Dimensions: (HWD) in (mm) 66-1/8 51-3/16 30-1/8 (1680 x 1300 x
765 mm)66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Hermetically Sealed Scroll Type
Piston Displacement m3/h 16.90+16.90 16.90 + (10.53+13.34) 16.90
+ (10.53+13.34)Number of Revolutions r.p.m 7980, 7980 7980, (2900,
6300) 7980, (2900, 6300)Motor OutputNumber of Units kW (3.8+3.8)1
(4.7) 1 + (2.2+4.5) 1 (4.7) 1 + (3.5+4.5) 1Starting Method Soft
Start Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan Propeller FanMotor Output kW
0.75 2 (0.75) 1 + (0.75) 1 (0.75) 1 + (0.75) 1Air Flow Rate cfm
8,299 6,530+6,530 6,530+7,060Drive Direct Drive Direct Drive Direct
Drive
Connecting Pipes
Liquid Pipe in (mm) 1/2 (12.7 mm) C1220T(Flare Connection)5/8
(15.8 mm) C1220T
(Brazing Connection)+35/8 (15.8 mm) C1220T
(Brazing Connection)+3 High Pressure Equalizer Pipe in (mm)
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Gas Pipe in (mm) 1-1/8 (28.6 mm) C1220T(Brazing Connection)7/8
(22.2) C1220T
(Brazing Connection)+3 1-1/8 (28.6 mm) C1220T
(Brazing Connection)+3
Low Pressure Gas Pipe in (mm) 3/4 (19.1 mm) C1220T(Brazing
Connection)3/4 (19.1) C1220T
(Brazing Connection)Mass Lbs (kg) 747 (338.8 kg) 560 + 560 (254
+ 254 kg) 560 + 560 (254 + 254 kg)+4 Sound Level (Reference Value)
dBA 62
Safety Devices
High Pressure Switch,Fan Driver Overload
Protector,Overcurrent Relay,Inverter Overload
Protector
High Pressure Switch,Fan Driver Overload Protector,
Overcurrent Relay,Inverter Overload Protector
High Pressure Switch,Fan Driver Overload Protector,
Overcurrent Relay,Inverter Overload Protector
Defrost Method Deicer Deicer DeicerCapacity Control % 10~100
9~100 7~100
Refrigerant
Refrigerant Name R-410A R-410A R-410ACharge Lbs 24.5 18.1+19.8
18.1+20.1
Control Electronic Expansion Valve Electronic Expansion Valve
Electronic Expansion Valve
Standard AccessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, ClampsDrawing No. 4D058608A 4D060126A
4D060127AVRVIII R-410A Heat Pump 60Hz 15
-
Specifications SiUS34-801A_bHeat Pump 60Hz 230V
Notes: +1 Indoor temp. : 80FDB or 67FWB / outdoor temp. : 95FDB
/ Equivalent piping length : 25 ft (7.5 m), level difference: 0.+2
Indoor temp. : 70FDB / outdoor temp. : 47FDB or 43FWB / Equivalent
piping length : 25 ft (7.5 m), level difference: 0.+3 BHFP22P100U
is necessary for the connection.
Concerning about the piping connection for each outdoor unit to
the main line as shown above, use REFNET.
Model Name (Combination Unit) RXYQ216PTJU RXYQ240PTJUModel Name
(Independent Unit) RXYQ96PTJURXYQ120PTJU
RXYQ120PTJURXYQ120PTJU
Power Supply 3 Phase 60Hz 208V-230V 3 Phase 60Hz 208V-230V+1
Cooling Capacity Btu / h 216,000 240,000+2 Heating Capacity Btu / h
243,000 270,000Casing Color Ivory White (5Y7.5/1) Ivory White
(5Y7.5/1)
Dimensions: (HWD) in66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8
30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
66-1/8 36-5/8 30-1/8 +66-1/8 36-5/8 30-1/8
(1680 x 930 x 765 + (1680 x 930 x 765 mm)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll
Type Piston Displacement m3/h (10.53+13.34) 2 (10.53+13.34) 2Number
of Revolutions r.p.m (2900, 6300) 2 (2900, 6300) 2Motor
OutputNumber of Units kW (2.2+4.5) 1 + (3.5+4.5) 1 (3.5+4.5)
2Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller FanMotor Output kW (0.75) 1 +
(0.75) 1 (0.75) 1 + (0.75) 1Air Flow Rate cfm 6,530+7,060
7,060+7,060Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe +3 in 5/8 (15.8 mm) C1220T(Brazing Connection)5/8
(15.8 mm) C1220T
(Brazing Connection)High Pressure Equalizer Pipe in
3/4 (19.1mm) C1220T(Brazing Connection)
3/4 (19.1mm) C1220T(Brazing Connection)
Gas Pipe +3 in 1-1/8 (28.6 mm) C1220T(Brazing Connection)1-3/8
(34.9 mm) C1220T
(Brazing Connection)Low Pressure Equalizer Pipe in
3/4 (19.1 mm) C1220T(Brazing Connection)
3/4 (19.1 mm) C1220T(Brazing Connection)
Mass Lbs (kg) 560 + 560 (254 + 254 kg) 560 + 560 (254 + 254
kg)
Safety DevicesHigh Pressure Switch,
Fan Driver Overload Protector,Overcurrent Relay,
Inverter Overload Protector
High Pressure Switch,Fan Driver Overload Protector,
Overcurrent Relay,Inverter Overload Protector
Defrost Method Deicer DeicerCapacity Control % 7~100 6~100
RefrigerantRefrigerant Name R-410A R-410ACharge Lbs 19.8+20.1
20.1+20.1Control Electronic Expansion Valve Electronic Expansion
Valve
Standard AccessoriesInstallation Manual,Operation Manual,
Connection Pipes, Clamps
Installation Manual,Operation Manual,
Connection Pipes, ClampsDrawing No. 4D060128A 4D060129A16 VRVIII
R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Circuit2. Refrigerant Circuit 2.1
RXYQ72P, 96P, 120P
No. in refrigerant
system diagram
Symbol Name Major Function
1 M1C Inverter compressor (INV) Inverter compressor is operated
on frequencies between 52Hz and 210Hz by using the inverter, while
Standard compressor is operated with commercial power supply only.
The number of operating steps is as follows when Inverter
compressor is operated in combination with Standard
compressor.Compressor operation steps : Refer to page 45~46.
2 M2C Standard compressor 1 (STD1)
4 M1F Inverter fan Since the system is of the outdoor unit heat
exchanging type, the fan is operated at 9-step rotation speed by
using the inverter. 6 Y1E Electronic expansion valve (Main:
EVM)
While in heating operation, PI control is applied to keep the
outlet superheated degree of the outdoor unit heat exchanger
constant.
7 Y3E Electronic expansion valve (Subcool: EVT)PI control is
applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
8 Y2E Electronic expansion valve (Refrigerant charge EVJ)
Opens/closes refrigerant charge port.9 Y6S Solenoid valve (Main
bypass SVE) Opens in cooling operation.
10 Y5S Solenoid valve (Hot gas: SVP) Prevents the low pressure
from transient falling.11 Y4S Solenoid valve (Refrigerant regulator
liquid pipe SVL) Collects refrigerant to the refrigerant
regulator.
12 Y1SSolenoid valve (Refrigerant regulator gas purging pipe
SVG)
Collects refrigerant to the refrigerant regulator.
13 Y7S Solenoid valve (Refrigerant regulator discharge pipe SVO)
Discharges refrigerant from the refrigerant regulator.14 Y8S
Solenoid valve (Discharge pipe of refrigerant regulator) Bypasses
the high pressure gas to the refrigerant regulator.15 Y3S 4 way
valve (Heat exchanger switch 20SA) Switches outdoor heat exchanger
to evaporator or condenser.16 Y2S 4 way valve (Dual pressure gas
pipe switch 20SB) Switches dual pressure gas pipe to high pressure
or low pressure.17 S1NPH High pressure sensor Detects high
pressure.18 S2NPL Low pressure sensor Detects low pressure.19 S1PH
HP pressure switch (For INV compressor) Functions when pressure
increases to stop operation and avoid high pressure increase in
the event of a fault.20 S2PH HP pressure switch (For STD
compressor 1)22 Pressure regulating valve (Liquid pipe)
Used when pressure increases, to prevent any damage on
components caused by pressure increase in transport or storage.
23 Pressure regulating valve (Refrigerant regulator) Used when
pressure increases, to prevent any damage on components caused by
pressure increase in transport or storage.
24 Subcooling heat exchanger Applies subcooling to liquid
refrigerant. 25 Refrigerant regulator Surplus refrigerant is held
according to the operation conditions.26 Capillary tube Used to
return the refrigerating oil separated through the oil separator to
the INV compressor.27 Capillary tube Used to return the
refrigerating oil separated through the oil separator to the STD1
compressor.29 Capillary tube Used to discharge refrigerant from the
refrigerant regulator.30 R1T Thermistor (Outdoor air: Ta) Detects
outdoor temperature, correct discharge pipe temperature, and
others. 31 R8T Thermistor (Suction pipe: TsA) Detects suction pipe
temperature.32 R31T Thermistor (INV discharge pipe: Tdi) Detects
discharge pipe temperature. Used for compressor temperature
protection control.33 R32T Thermistor (STD1 discharge pipe: Tds1)35
R4T Thermistor (Heat exchanger deicer: Tb)
Detects liquid pipe temperature of the outdoor unit heat
exchanger. Used to make judgments on defrosting operation.
36 R2T Thermistor (Heat exchanger gas pipe Tg)Detects
temperature of gas pipe for air heat exchanger. Used to exercise
the constant control of superheated degree when an evaporator is
used for outdoor unit heat exchanging.
37 R7T Thermistor (Heat exchanger liquid pipe Tf)Detects
temperature of liquid pipe between the the outdoor unit heat
exchanger and main electronic expansion valve. Used to make
judgments on the recover or discharge refrigerants to the
refrigerant regulator.
38 R5T Thermistor (Subcooling heat exchanger gas pipe:
Tsh)Detects gas pipe temperature on the evaporation side of
subcooling heat exchanger. Used to exercise the constant control of
superheated degree at the outlet of subcooled heat exchanger.
39 R6T Thermistor (Subcooling heat exchanger liquid pipe
Tl)Detects temperature of liquid pipe between the main expansion
valve and subcooling heat exchanger.
40 R9T Thermistor (Liquid pipe Tsc) Detects temperature of
liquid pipe between the liquid stop valve and subcooling heat
exchanger.VRVIII R-410A Heat Pump 60Hz 17
-
Refrigerant Circuit SiUS34-801A_bRXYQ72P, 96P, 120P
2.2 RXYQ144PTJU
40
7
9
6
Stop ValveLiquid Pipe
Stop ValveHigh Side
Equalizer Pipe
Stop ValveGas Pipe
Stop ValveLow Side
Equalizer Pipe
Gauge Port
22
15
36 35
37
23
11
38
24
39
4
10
17
16
8
31
26
19 20
18
32 33
141 2
27 13
12
25
29
30
INV S1
S1NPH
S1PH S2PH
S2NPL
No. in refrigerant
system diagram
Symbol Name Major Function
1 M1C Inverter compressor (INV1) Inverter compressor is operated
on frequencies between 52Hz and 266Hz by using the inverter. The
number of operating steps is as follows.RXYQ144PTJU : 26 step2 M2C
Standard compressor 1 (INV2)
3 M1F Inverter fan Since the system is the outdoor unit heat
exchanging type, the fan is operated at 9-step rotation speed by
using the inverter.
4 M2F Inverter fan Since the system is the outdoor unit heat
exchanging type, the fan is operated at 9-step rotation speed by
using the inverter. 18 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Circuit5(6) Y1E(Y3E)Electronic
expansion valve (Main1 (Main2))
While in heating operation, PI control is applied to keep the
outlet superheated degree of the outdoor unit heat exchanger
constant.
7(8) Y2E(Y5E)Electronic expansion valve (Subcool1
(Subcool2))
PI control is applied to keep the outlet superheated degree of
subcooling heat exchanger constant.
9 Y4E Electronic expansion valve (Refrigerant charge EVJ)
Opens/closes refrigerant charge port.
10(11) Y5S(Y10S)Solenoid valve (Main bypass1 (Main bypass2))
Opens in cooling operation.
12 Y4S Solenoid valve (Hot gas: SVP) Prevents the low pressure
from transient falling.13 Y3S Solenoid valve (Refrigerant regulator
liquid pipe SVL) Collects refrigerant to the refrigerant
regulator.
14 Y1S Solenoid valve (Refrigerant regulator gas purging pipe
SVG) Collects refrigerant to the refrigerant regulator.
15 Y7S Solenoid valve (Refrigerant regulator discharge pipe SVO)
Discharges refrigerant from the refrigerant regulator.
16 Y6S Solenoid valve (Discharge pipe of refrigerant regulator)
Bypasses the high pressure gas to the refrigerant regulator.
17(18) Y2S(Y9S)4 way valve (Heat exchanger switch 20SA) Used to
switch outdoor heat exchanger to evaporator or condenser.
19 Y8S 4 way valve (Dual pressure gas pipe switch 20SB) Used to
switch dual pressure gas pipe to high pressure or low pressure.20
S1NPH High pressure sensor Detects high pressure.21 S2NPL Low
pressure sensor Detects low pressure.
22(23) S1PH(S2PH)HP pressure switch (For INV compressor)
Functions when pressure increases to stop operation and avoid
high pressure increase in the event of a fault.
24 Pressure regulating valve (Liquid pipe) Used when pressure
increases, to prevent any damage on components caused by pressure
increase in transport or storage.
25 Pressure regulating valve (Refrigerant regulator) Used when
pressure increases, to prevent any damage on components caused by
pressure increase in transport or storage.
26 Subcooling heat exchanger Applies subcooling to liquid
refrigerant. 27 Refrigerant regulator Surplus refrigerant is held
according to the operation conditions.
28 Capillary tube Used to return the refrigerating oil separated
through the oil separator to the INV compressor.29 Capillary tube
Discharges refrigerant from the refrigerant regulator.30 R1T
Thermistor (Outdoor air: Ta) Detects outdoor temperature, correct
discharge pipe temperature, and others.
31(41) R8T(R10T) Thermistor (Suction pipe: TsA) Detects suction
pipe temperature.
32 R31T Thermistor (INV1 discharge pipe: Tdi)Detects discharge
pipe temperature. Used for compressor temperature protection
control.
33 R32T Thermistor (INV2 discharge pipe: Tds1)35(45)
R4T(R12T)
Thermistor (Heat exchanger deicer: Tb)
Detects liquid pipe temperature of the outdoor unit heat
exchanger. Used to make judgments on defrosting operation.
36(46) R2T(R11T)Thermistor (Heat exchanger gas pipe Tg)
Detects temperature of gas pipe for the outdoor unit heat
exchanger. Used to exercise the constant control of superheated
degree when an evaporator is used for outdoor unit heat
exchanging.
37(47) R7T(R15T)Thermistor (Heat exchanger liquid pipe Tf)
Detects temperature of liquid pipe between the the outdoor unit
heat exchanger and main electronic expansion valve. Used to make
judgments on the recover or discharge refrigerants to the
refrigerant regulator.
38(48) R5T(R13T)Thermistor (Subcooling heat exchanger gas pipe:
Tsh)
Detects temperature of gas pipe on the evaporator side for the
subcooling heat exchanger. Used to exercise the constant control of
superheated degree at the outlet of subcooled heat exchanger.
39 R6T Thermistor (Subcooling heat exchanger liquid pipe
Tl)Detects temperature of liquid pipe between the main expansion
valve and subcooling heat exchanger.
40(50) R9T(R14T) Thermistor (Liquid pipe Tsc)Detects temperature
of liquid pipe between the liquid stop valve and subcooling heat
exchanger.VRVIII R-410A Heat Pump 60Hz 19
-
Refrigerant Circuit SiUS34-801A_bRXYQ144PTJU(12ton Single
Type)(INV Unit 2)
LiquidPipe
Dual PressureGas Pipe
Suction Pipe
Stop Valve
Stop Valve
Stop Valve
Gauge Port
5026
48 8
4546
18
19
23
33
28
2
41
40
2639
37
103536
20
12
22
31
3
738
175
13 25
27
30
16
32
1
21
29
14
1528
24
9
476
4
11
Liquid Pipe
INV1
INV2
Right
Left
S2PH
S1NPH
S2NPL
S1PH
Gauge Port
Subcool Heat Exchanger 2
Heat Exchanger 2
Subcool Heat Exchanger 1
Heat Exchanger 120 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Functional Parts Layout RXYQ72P, 96P, 120PGROUND
WIRE
16
15
36
37
39
35
12
13
4
6
17
30
14
2
1
3. Functional Parts Layout RXYQ72P, 96P, 120PPlan
Front View
Note: For reference number, refer to page 17.
3.1 RXYQ144PTJU
REFRIGERANT REGULATOR
11
7
9
25
20
19
33
31
31 10
8 18
40
38VRVIII R-410A Heat Pump 60Hz 21
-
Functional Parts Layout RXYQ72P, 96P, 120P SiUS34-801A_bPlan
Front View
Note: For reference numbers, refer to page 18.
19
18
11
23
10 17
33 32
22
12
16 15
13
14
36
46
47
48
41
45
4
9
6
8
2 35
1
31
39
37
30
21
20
38
5
3
740 COIL FOR EXPANSION VALVE
COIL FOR EXPANSION VALVECOIL FOR EXPANSION VALVE
COIL FOR EXPANSION VALVE
COIL FOR EXPANSION VALVE22 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Flow for Each Operation Mode4.
Refrigerant Flow for Each Operation ModeRXYQ72, 96, 120PYDN,
PTJUCooling Operation
Indoor Unit
CoolingUnit
Operation "OFF"
Operation "ON"Theromstat "OFF"
Operation "ON"Theromstat "ON"
CoolingUnit
CoolingUnit
S1NPH
EVM
EVT
20SB
TbTg
Tsc
TS_A
Tsh
INVFAN
TL
SVP
20SA
SVE
Tf
SVO
SVL
SVG
EVJ
INV
HPSTdi
S1
HPSTds1
SVT
S2NPL
Liquid PipeStop Valve
High Side Equalizer PipeStop Valve
Low Side Equalizer PipeStop Valve
Gas PipeStop Valve
Refrigerant Regulator
GaugePort
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
RXYQ72, 96, 120PYDN, PTJU
Fan "OFF"
Fan "ON"
Fan "ON"VRVIII R-410A Heat Pump 60Hz 23
-
Refrigerant Flow for Each Operation Mode SiUS34-801A_bRXYQ72,
96, 120PYDN, PTJUHeating Operation
S1NPH
EVM
EVT
20SB
TbTg
Tsc
TS_A
Tsh
INVFAN
TL
SVP
20SA
SVE
Tf
SVO
SVL
SVG
EVJ
Indoor Unit
HeatingUnit
Operation "OFF"
Operation "ON"Theromstat "OFF"
Operation "ON"Theromstat "ON"
HeatingUnit
HeatingUnit
INV
HPSTdi
S1
HPSTds1
SVT
S2NPL
Liquid PipeStop Valve
High Side Equalizer PipeStop Valve
Low Side Equalizer PipeStop Valve
Gas PipeStop Valve
Refrigerant Regulator
GaugePort
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
RXYQ72, 96, 120PYDN, PTJU
Fan "OFF"
Fan "ON"
Fan "LL"
192pls
192pls24 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Flow for Each Operation ModeRXYQ72,
96, 120PYDN, PTJUCooling Oil Return Operation
S1NPH
EVM
EVT
20SB
TbTg
Tsc
TS_A
Tsh
INVFAN
TL
SVP
20SA
SVE
Tf
SVO
SVL
SVG
EVJ
INV
HPSTdi
S1
HPSTds1
SVT
S2NPL
Indoor Unit
CoolingUnit
Operation "ON"Theromstat "OFF"
CoolingUnit
CoolingUnit
Operation "ON"Theromstat "ON"
Operation "OFF"
Liquid PipeStop Valve
High Side Equalizer PipeStop Valve
Low Side Equalizer PipeStop Valve
Gas PipeStop Valve
Refrigerant Regulator
GaugePort
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
RXYQ72, 96, 120PYDN, PTJU
Fan "OFF"
192pls
Fan "ON"
Fan "ON"VRVIII R-410A Heat Pump 60Hz 25
-
Refrigerant Flow for Each Operation Mode SiUS34-801A_bRXYQ72,
96, 120PYDN, PTJUHeating Oil Return Operation
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
S1NPH
EVM
EVT
20SB
TbTg
Tsc
TS_A
Tsh
INVFAN
TL
SVP
20SA
SVE
Tf
SVO
SVL
SVG
EVJ
INV
HPSTdi
S1
HPSTds1
SVT
S2NPL
Liquid PipeStop Valve
High Side Equalizer PipeStop Valve
Low Side Equalizer PipeStop Valve
Gas PipeStop Valve
Refrigerant Regulator
GaugePort
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
RXYQ72, 96, 120PYDN, PTJU
Indoor Unit
HeatingUnit
Operation "ON"Theromstat "OFF"
Operation OFF
HeatingUnit
HeatingUnit
Operation "ON"Theromstat "ON"
Fan "LL"
Fan"OFF"
224pls
Fan "ON"26 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Flow for Each Operation ModeRXYQ72,
96, 120PYDN, PTJU (When a single unit is connected)Defrost
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"Indoor Unit
HeatingUnit
Operation "OFF"
Operation "ON"Theromstat "OFF"
Operation "ON"Theromstat "ON"
HeatingUnit
HeatingUnit
S1NPH
EVM
EVT
20SB
TbTg
Tsc
TS_A
Tsh
INVFAN
TL
SVP
20SA
SVE
Tf
SVO
SVL
EVJ
INV
HPSTdi
S1
HPSTds1
SVT
S2NPL
Liquid PipeStop Valve
High Side Equalizer PipeStop Valve
Low Side Equalizer PipeStop Valve
Gas PipeStop Valve
RefrigeRegu
GaugePort
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
RXYQ72, 96, 120PYDN, PTJU
Fan "OFF"
Fan "OFF"
Fan "OFF"VRVIII R-410A Heat Pump 60Hz 27
-
Refrigerant Flow for Each Operation Mode
SiUS34-801A_bRXYQ144PTJUCooling Operation
S1NPH
S2NPL
HPS
EVM
EVT
20SB
Tdi
TbTg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
TfSVL
SVO
SVG
EVJ
INV2
HPS
EVM
EVT
Tdi
TbTg
Tsc
Tsh
20SA
SVE
TS_A
Tf
Ta
INV1
Suction Pipe
LiquidPipe
EqualizingPipe
Refrigerant Regulator
EqualizingPipe
Stop Valve
Stop Valve
Stop Valve
Left
Right
One Body Type
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
Indoor Unit
CoolingUnit
Thermostat "ON"
Thermostat "OFF"
CoolingUnit
CoolingUnit
LowPressureEqualizerPipe
Gas Pipe
LiquidPipe
Fan "OFF"
Indoor unitOperation
Fan "ON"
"ON"
Fan "ON"
"ON"
"OFF"28 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Flow for Each Operation
ModeRXYQ144PTJUHeating Operation
Indoor Unit
HeatingUnit
Thermostat "ON"
Thermostat "OFF"
HeatingUnit
HeatingUnit
Gas Pipe
LiquidPipe
LowPressureEqualizerPipe
Fan "OFF"
Indoor unitOperation
Fan "ON"
"ON"
Fan "LL"
"ON"
192pls
192pls
"OFF"
S1NPH
S2NPL
HPS
EVM
EVT
20SB
Tdi
TbTg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
TfSVL
SVO
SVG
EVJ
HPS
EVM
EVT
Tdi
TbTg
Tsc
Tsh
20SA
SVE
TS_A
Tf
Ta
INV2
INV1
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
Stop Valve
Stop Valve
Stop Valve
Left
Right
One Body Type
Suction Pipe
LiquidPipe
EqualizingPipe
Refrigerant Regulator
EqualizingPipeVRVIII R-410A Heat Pump 60Hz 29
-
Refrigerant Flow for Each Operation Mode
SiUS34-801A_bRXYQ144PTJUCooling Oil Return Operation
Indoor Unit
CoolingUnit
Thermostat "ON"
Thermostat "OFF"
CoolingUnit
CoolingUnit
Gas Pipe
LiquidPipe
LowPressureEqualizerPipe
S1NPH
S2NPL
HPS
EVM
EVT
20SB
Tdi
TbTg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
TfSVL
SVO
SVG
EVJ
HPS
EVM
EVT
Tdi
TbTg
Tsc
Tsh
20SA
SVE
TS_A
Tf
Ta
INV2
INV1
"High temperature, high pressure gas""High temperature, high
pressure liquid""Low temperature, low pressure"
Stop Valve
Stop Valve
Stop Valve
Left
Right
One Body Type
Suction Pipe
LiquidPipe
EqualizingPipe
Refrigerant Regulator
EqualizingPipe
Fan "OFF"
Indoor unitOperation
Fan "ON"
"ON"
Fan "ON"
"ON"
192pls"OFF"30 VRVIII R-410A Heat Pump 60Hz
-
SiUS34-801A_b Refrigerant Flow for Each Operation
ModeRXYQ144PTJUHeating Oil Return Operation
Indoor Unit
HeatingUnit
Thermostat "ON" Gas Pipe
LiquidPipe
Indoor Unit
HeatingUnit
Thermostat "OFF"
Indoor Unit
HeatingUnit
Low SideEqualizerPipe
Fan "LL"
"ON"
S1NPH
INV1
HPS
EVM
EVT
20SB
Tdi
TbTg
Tsc
Tsh
TL
SVP
20SA
SVE
TS_A
TfSVL
SVO
SVG
EVJ
HPS