Page 1: Sinamics v20 Drive

SINAMICS V20DRIVE

Page 2: Sinamics v20 Drive

V20-The versatile Inverter for Basic Demands

• Power Range

0.12KW to 15KW• Voltage Range

1 AC 200V … 240V(+/- 10%)

3 AC 380V … 480V(+10% /-15%)• Control Modes

V/f, v^2/f, FCC• Supply frequency

• 50Hz/60Hz

Page 3: Sinamics v20 Drive

Signal Inputs and Outputs

• Analog Inputs - AI1:bipolar current/voltage mode

-AI2 :unipolar current /voltage mode

(can be used as digital inputs)• Analog Outputs -AO:0 … 20mA• Digital Inputs - DI1-DI4,optically isolated PNP/NPN selectable

by terminal• Digital Outputs -DO1:transistor output

-DO2: relay output

-250V AC 0.5A with resistive load

- 30V DC 0.5A with resistive load

Page 4: Sinamics v20 Drive

CONNECTION DIAGRAM

Page 5: Sinamics v20 Drive

BUILT IN BOP

Page 6: Sinamics v20 Drive

RESTORING TO DEFAULTS

Page 7: Sinamics v20 Drive

QUICK COMMISIONING THROUGH PARAMETERS

PARAMETER FUNCTION SETTINGP0003 User access level =0(user defined parameter list)

=1(standard)=2(extended)=3(expert)=4(service)

P0010 Commissioning parameter

=1(quick commissioning)

P0100 50/60Hz selection =0(50Hz,KW in Europe)=1(60Hz,hp in north America)=2(60Hz, KW in north America)

P0304[0] Rated motor voltage[V]

Range 10…..2000

P0305[0] Rated motor current[A]

Range 0.01….10000

P0307[0] Rated motor power [KW/Hp]

Range 0.01…2000.0

Page 8: Sinamics v20 Drive

PARAMETER FUNCTION SETTING

P0308[0] Rated motor power factor Range 0.000…..1.000

P0310[0] Rated motor frequency(Hz) Range 12….599

P0311[0] Rated motor speed(RPM) Range 0…40000

P0700[0..2] Selection of command source

=0(Factory default setting)=1(Operator panel)=2(Terminal)=5(USS/MODBUS on RS485)

P1000[0] Selection of frequency set point

Range 0…77(factory default 1)=0(no main set point)=1(MOP set point)=2(analog set point)=3(fixed frequency)=5(USS on RS485)=7(analog set point 2)

P1080[0] Minimum frequency[Hz] Range 0…599(factory default=0)

QUICK COMMISIONING THROUGH PARAMETERS

Page 9: Sinamics v20 Drive

PARAMETER FUNCTION SETTING

P1082[0] Maximum frequency[Hz] Range 0…599

P1120[0] Ramp up time[s] Range 0.00…650.00(factory default=10)

P1121[0] Ramp down time[s] Range 0.00…650.00(factory default=10)

P3900 End of commissioningNote:After completion of calculation, P3900 and P0010 areautomatically reset to their original value 0.The inverter displays "8.8.8.8.8" which indicates that it is busywith internal data processing.

=0(no quick commissioning)-factory default=1(end of quick commissioning with factory reset)=2(end quick commissioning)=3(end of quick commissioning only for motor data)

QUICK COMMISIONING THROUGH PARAMETERS

Page 10: Sinamics v20 Drive

P0700[1]-OPERATOR PANEL

• Start• Stop• Multi-function button• Hand/jog/auto• Forward and reverse motor direction• Speed up and speed down motor

Page 11: Sinamics v20 Drive

PO700[2]-TERMINALSParameter Description Range Factory default Acc. level

P0701[0...2] Function of digital input 1

0 - 99 0 2

0 Digital input disabled

16 Fixed frequency selector bit1

1 ON / OFF1 17 Fixed frequency selector bit2

2 ON reverse/OFF1 18 Fixed frequency selector bit3

3 OFF2-coast to standstill

22 Quick stop source1

4 OFF3-quick ramp down

23 Quick stop source2

9 Fault acknowledge

24 Quick stop override

Page 12: Sinamics v20 Drive

PO700[2]- TERMINALSParameter Description Range Factory

defaultAcc. level

9 Fault acknowledge

24 Quick stop override

10 JOG right 25 DC brake enable

11 JOG left 27 Enable PID

12 Reverse 29 External trip

13 MOP down(increase frequency)

33 Disable additional freq set point

14 MOP down(decrease frequency)

99 Enable BICO parameterization

15 Fixed frequency selector bit0

Page 13: Sinamics v20 Drive

PO700[2]- TERMINALS

Parameter Description Range Fa0ctory defa0ult

Acc. level

P0702[0...2] Function of digital input 2

0 - 99 0 2

P0703[0...2] Function of digital input 3

0 - 99 9 2

P0704[0...2] Function of digital input 4

0 - 99 15 2

P0712 [0...2] Analog / digital input 1

0 - 99 0 2

P0713[0...2] Analog / digital input 2

0 - 99 0 2

Page 14: Sinamics v20 Drive

FIXED FREQUENCY SELECTION

• P1000=3(fixed frequency)• P1016[0..2](Fixed frequency mode)

=1(direct selection)

=2(binary selection)

If P1016=1• P0701=15(Fixed frequency selector bit 0)• P0702=16(Fixed frequency selector bit 1)• P0703=17(Fixed frequency selector bit 2)• P0704=18(Fixed frequency selector bit 3)

Frequency selected from-P1001 to P1004

If P1016=2• P1020[0]:DI1• P1021[0]:DI2• P1022[0]:DI3• P1023[0]:DI4

Assigning frequency to each input-

P1001:Fixed frequency 1(Hz)…..

P1015:Fixed frequency 15(Hz)

Page 15: Sinamics v20 Drive

ANALOG PARAMETERS

P1000=2(Analog set point)

Analog operation through BOP(P0700=1)

P1000=12(analog set point + MOP set point)

P1000=21(MOP set point + analog set point)

Analog operation through Terminals(P0700=2)

P1000=23(fixed frequency + analog set point)

Page 16: Sinamics v20 Drive

MACROS

DEFINITION:

• CONNECTION MACROS• APPLICATION MACROS

Page 17: Sinamics v20 Drive

CONNECTION MACRO

Page 18: Sinamics v20 Drive

APPLICATION MACROS

Page 19: Sinamics v20 Drive

Ease of Use

• Energy consumption monitoring• Automatic restart• Parameter cloning• USS/MODBUS communication• Connection and application macro• Customized default values

Page 20: Sinamics v20 Drive

APPLICATION• Hibernation mode• Slip compensation• Keep running mode• Kinetic buffering• Flying start• Motor staging• BICO function• Dual ramp• Wobble function• PID Controller• Super torque mode• Hammer start• Blockage clearing mode

Page 21: Sinamics v20 Drive