SINAMICS V20 DRIVE
SINAMICS V20DRIVE
V20-The versatile Inverter for Basic Demands
• Power Range
0.12KW to 15KW• Voltage Range
1 AC 200V … 240V(+/- 10%)
3 AC 380V … 480V(+10% /-15%)• Control Modes
V/f, v^2/f, FCC• Supply frequency
• 50Hz/60Hz
Signal Inputs and Outputs
• Analog Inputs - AI1:bipolar current/voltage mode
-AI2 :unipolar current /voltage mode
(can be used as digital inputs)• Analog Outputs -AO:0 … 20mA• Digital Inputs - DI1-DI4,optically isolated PNP/NPN selectable
by terminal• Digital Outputs -DO1:transistor output
-DO2: relay output
-250V AC 0.5A with resistive load
- 30V DC 0.5A with resistive load
CONNECTION DIAGRAM
BUILT IN BOP
RESTORING TO DEFAULTS
QUICK COMMISIONING THROUGH PARAMETERS
PARAMETER FUNCTION SETTINGP0003 User access level =0(user defined parameter list)
=1(standard)=2(extended)=3(expert)=4(service)
P0010 Commissioning parameter
=1(quick commissioning)
P0100 50/60Hz selection =0(50Hz,KW in Europe)=1(60Hz,hp in north America)=2(60Hz, KW in north America)
P0304[0] Rated motor voltage[V]
Range 10…..2000
P0305[0] Rated motor current[A]
Range 0.01….10000
P0307[0] Rated motor power [KW/Hp]
Range 0.01…2000.0
PARAMETER FUNCTION SETTING
P0308[0] Rated motor power factor Range 0.000…..1.000
P0310[0] Rated motor frequency(Hz) Range 12….599
P0311[0] Rated motor speed(RPM) Range 0…40000
P0700[0..2] Selection of command source
=0(Factory default setting)=1(Operator panel)=2(Terminal)=5(USS/MODBUS on RS485)
P1000[0] Selection of frequency set point
Range 0…77(factory default 1)=0(no main set point)=1(MOP set point)=2(analog set point)=3(fixed frequency)=5(USS on RS485)=7(analog set point 2)
P1080[0] Minimum frequency[Hz] Range 0…599(factory default=0)
QUICK COMMISIONING THROUGH PARAMETERS
PARAMETER FUNCTION SETTING
P1082[0] Maximum frequency[Hz] Range 0…599
P1120[0] Ramp up time[s] Range 0.00…650.00(factory default=10)
P1121[0] Ramp down time[s] Range 0.00…650.00(factory default=10)
P3900 End of commissioningNote:After completion of calculation, P3900 and P0010 areautomatically reset to their original value 0.The inverter displays "8.8.8.8.8" which indicates that it is busywith internal data processing.
=0(no quick commissioning)-factory default=1(end of quick commissioning with factory reset)=2(end quick commissioning)=3(end of quick commissioning only for motor data)
QUICK COMMISIONING THROUGH PARAMETERS
P0700[1]-OPERATOR PANEL
• Start• Stop• Multi-function button• Hand/jog/auto• Forward and reverse motor direction• Speed up and speed down motor
PO700[2]-TERMINALSParameter Description Range Factory default Acc. level
P0701[0...2] Function of digital input 1
0 - 99 0 2
0 Digital input disabled
16 Fixed frequency selector bit1
1 ON / OFF1 17 Fixed frequency selector bit2
2 ON reverse/OFF1 18 Fixed frequency selector bit3
3 OFF2-coast to standstill
22 Quick stop source1
4 OFF3-quick ramp down
23 Quick stop source2
9 Fault acknowledge
24 Quick stop override
PO700[2]- TERMINALSParameter Description Range Factory
defaultAcc. level
9 Fault acknowledge
24 Quick stop override
10 JOG right 25 DC brake enable
11 JOG left 27 Enable PID
12 Reverse 29 External trip
13 MOP down(increase frequency)
33 Disable additional freq set point
14 MOP down(decrease frequency)
99 Enable BICO parameterization
15 Fixed frequency selector bit0
PO700[2]- TERMINALS
Parameter Description Range Fa0ctory defa0ult
Acc. level
P0702[0...2] Function of digital input 2
0 - 99 0 2
P0703[0...2] Function of digital input 3
0 - 99 9 2
P0704[0...2] Function of digital input 4
0 - 99 15 2
P0712 [0...2] Analog / digital input 1
0 - 99 0 2
P0713[0...2] Analog / digital input 2
0 - 99 0 2
FIXED FREQUENCY SELECTION
• P1000=3(fixed frequency)• P1016[0..2](Fixed frequency mode)
=1(direct selection)
=2(binary selection)
If P1016=1• P0701=15(Fixed frequency selector bit 0)• P0702=16(Fixed frequency selector bit 1)• P0703=17(Fixed frequency selector bit 2)• P0704=18(Fixed frequency selector bit 3)
Frequency selected from-P1001 to P1004
If P1016=2• P1020[0]:DI1• P1021[0]:DI2• P1022[0]:DI3• P1023[0]:DI4
Assigning frequency to each input-
P1001:Fixed frequency 1(Hz)…..
P1015:Fixed frequency 15(Hz)
ANALOG PARAMETERS
P1000=2(Analog set point)
Analog operation through BOP(P0700=1)
P1000=12(analog set point + MOP set point)
P1000=21(MOP set point + analog set point)
Analog operation through Terminals(P0700=2)
P1000=23(fixed frequency + analog set point)
MACROS
DEFINITION:
• CONNECTION MACROS• APPLICATION MACROS
CONNECTION MACRO
APPLICATION MACROS
Ease of Use
• Energy consumption monitoring• Automatic restart• Parameter cloning• USS/MODBUS communication• Connection and application macro• Customized default values
APPLICATION• Hibernation mode• Slip compensation• Keep running mode• Kinetic buffering• Flying start• Motor staging• BICO function• Dual ramp• Wobble function• PID Controller• Super torque mode• Hammer start• Blockage clearing mode
THANK YOU