Page ONE of two: Application for Certificate of Appropriateness-or-Design Approval-or-Exemption REVISED JAN 2018 DO NOT RETURN THIS FORM BY FAX OR EMAIL DO NOT STAMP THIS BOX I. PROPERTY ADDRESS_________________________________________________________________________ NAME of BUSINESS/PROPERTY____________________________________________________________ The names, telephone numbers, postal and e-mail addresses requested below will be used for all subsequent communications relating to this application. Environment Department personnel cannot be responsible for illegible, incomplete or inaccurate contact information provided by applicants. II. APPLICANT__________________________________________________________________________________ CONTACT NAME_______________________________ RELATIONSHIP TO PROPERTY___________________ MAILING ADDRESS___________________________________________________________________ZIP_________ PHONE ________________________________________ EMAIL_________________________________________ PROPERTY OWNER_______________________________ CONTACT NAME______________________________ MAILING ADDRESS___________________________________________________________________ZIP_________ PHONE ________________________________________ EMAIL_________________________________________ ARCHITECT______________________________________ CONTACT NAME_______________________________ MAILING ADDRESS___________________________________________________________________ZIP_________ PHONE ________________________________________ EMAIL_________________________________________ CONTRACTOR ___________________________________ CONTACT NAME_______________________________ MAILING ADDRESS___________________________________________________________________ZIP_________ PHONE ________________________________________ EMAIL_________________________________________ III. DESCRIPTION OF PROPOSED WORK A BRIEF OUTLINE OF THE PROPOSED WORK MUST BE PROVIDED IN THE SPACE BELOW, OR THE APPLICATION WILL NOT BE ACCEPTED. This description MUST include ALL proposed work, as the basis for the official notice and subsequent decision. Additional pages may be attached, if necessary, to provide more details. For Office Use Only APPLICATION #______________________ RECEIVED__________________________ FEE______________________________ HEARING DATE_____________________ APPLICATION CERTIFICATE of APPROPRIATENESS-or- DESIGN APPROVAL-or-EXEMPTION Deliver or mail to: Environment Department Boston City Hall, Room 709 Boston, MA 02201 300 Summer Street, Boston, MA 02210 The Artist Building at 300 Summer Street Board of Directors, The Artist Building at 300 Summer Street Karen Clepper Board Director 300 Summer Street, Boston, MA 02210 [email protected]Artist Building at 300 Summer St Karen Clepper 300 Summer Street, Boston, MA [email protected]Simpson Gumpertz & Heger Susan Knack-Brown 800 Boylston Street, Suite 2320, Boston, MA 02199 617-963-5403 [email protected]Berkley Building Company Emil Frei-Howe 248 Main Street, Suite 103, Reading, MA 01867 781-246-3353 [email protected]Scope of work includes replacing the existing roof top chiller on the existing dunnage. Replacement chiller to have similar profile and will be located in the same location as the existing chiller. 02210
16
Embed
Simpson Gumpertz & Heger Susan Knack-Brown APPLICATION …
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page ONE of two: Application for Certificate of Appropriateness-or-Design Approval-or-Exemption REVISED JAN 2018
DO NOT RETURN THIS FORM BY FAX OR EMAIL DO NOT STAMP THIS BOX
I. PROPERTY ADDRESS_________________________________________________________________________
NAME of BUSINESS/PROPERTY____________________________________________________________
The names, telephone numbers, postal and e-mail addresses requested below will be used for all subsequent communications relating to this application.
Environment Department personnel cannot be responsible for illegible, incomplete or inaccurate contact information provided by applicants.
II. APPLICANT__________________________________________________________________________________
CONTACT NAME_______________________________ RELATIONSHIP TO PROPERTY___________________
248 Main Street, Suite 103, Reading, MA 01867781-246-3353 [email protected]
Scope of work includes replacing the existing roof top chiller on the existing dunnage. Replacementchiller to have similar profile and will be located in the same location as the existing chiller.
02210
TBD
Chiller Replacement
300 Summer Street Fort Point Channel Landmark District Application for Design Approval
20 February 2020
Roof Existing Conditions
Looking east (chiller noted with red arrow) Looking west (chiller noted with red arrow)
Roof Existing Conditions
Looking west (chiller noted with red arrow) Looking west (chiller noted with red arrow)
Proposed Rooftop Equipment Changes
Proposed Rooftop Equipment Changes Photo 1
Photo 1
Photo 2 Photo 3Photo 3
Photo 2
Photo 4
Chiller not visible from Summer Street
Proposed Rooftop Equipment ChangesPhoto 5
Photo 6
Photo 7
Photo 5 Photo 6
Photo 7Chiller not visible
from A Street and
adjacent streets
–
SIMPSON GUMPERTZ & HEGEREngineering of Structuresand Building Enclosures
Certified Drawing for 130 ton chillerProject: ~Untitled5 01/08/2020 Prepared By: 01:44PM
Packaged Chiller Builder NACO 3.59f Page 2 of 20
Field Wiring Diagram for 130 ton chillerProject: ~Untitled5 01/08/2020 Prepared By: 01:44PM
Packaged Chiller Builder NACO 3.59f Page 3 of 20
Summary Performance Report For 130 ton chillerProject: ~Untitled5 01/08/2020 Prepared By: 01:44PM
PackagedChillerReport:DoNotEdit;
30RB with Greenspeed®Intelligence
Unit Information Tag Name: 130 ton chiller Model Number: 30RB130 Quantity: 1 Manufacturing Source: Charlotte, NC USA ASHRAE 90.1: 2013/2016, 2010, 2007 Refrigerant: R-410A Independent Refrigerant Circuits: 2 Shipping Weight: 7671 lb Operating Weight: 8046 lb Refrigerant Weight (Circuit A): 133 lb Refrigerant Weight (Circuit B): 106 lb Unit Length: 189 in Unit Width: 89 in Unit Height: 90 in Evaporator Information Fluid Type: Fresh Water Fouling Factor: 0.000100 (hr-sqft-F)/BTU Leaving Temperature: 44.00 °F Entering Temperature: 54.00 °F Fluid Flow: 303.7 gpm Pressure Drop: 12.4 ft H2O Condenser Information Altitude: 0.000 ft Number of Fans: 8 Total Condenser Fan Air Flow: 99,200 CFM Entering Air Temperature: 95.0 °F Integrated Pump Information No Pump Selected Performance Information Cooling Capacity: 127.0 Tons Total Compressor Power: 130.6 kW Total Fan Motor Power: 20.64 kW Total Unit Power (without pump): 151.3 kW Efficiency (without pump) (EER): 10.07 BTU/Wh IPLV:.IP: 16.66 BTU/Wh
Accessories and Installed Options Al Fin/Cu Tube, E-Coat Low Sound Option Single Point BACnet Translator Control No Coil Trim Panels Greenspeed Intelligence: High-Efficiency Variable Condenser Fans Electrical Information Unit Voltage: 208/230-3-60 V-Ph-Hz Connection Type: Single Point Minimum Voltage: 187 Volts Maximum Voltage: 253 Volts