Simple, Reliable and Accurate Reducing... · CLA-VAL 100-01 NGE Main Valve HYTROL ` CLA-VAL Europe [email protected] 1 - HYN001DE B 01/08 ` Simple, Reliable and Accurate ` CLA-VAL
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CLA-VAL 90-01
Pressure Reducing Valve
CLA-VAL Europe www.cla-val.ch [email protected] 1 - 090001DE B 12/09
The CLA-VAL SERIES 90 reduces a higher inlet pressure to a constant downstream pressure (Pressure Reducing Control) regardless of changing flow rate and/or varying inlet pressure.
CLA-VAL 90-01 Typical Application
The CLA-VAL 90-01 is designed to hold downstream pressure to a pre-determined limit.
Typical Pressure Reducing Valve station using two valves in parallel to handle high flows and low flows.
Make your Valve even Better!LFS Option? Control Low flows or night flows
KO Option? Extend valve life with Anti-Cavitation trim
KG1 Option? Use stem cleaning for harsh water
Maintenance? Check on periodic maintenance
Environment? Adapt to high temperatures or frost risk
Security? Add hydraulic safety back-up to your valve
Protection? Remove excessive system overpressures
Corrosion? Protect your valve with upgraded materials
Not just Products but Solutions: contact CLA-VAL!
Pressure Reducing Control CRD
CLA-VAL 90-01
"Anti-Shock" Air Release & Vacuum
Break Valves AQUA 70-506
Strainer AQUA 90-501
Recommended typical assembly for CLA-VAL automatic control valves
The H-Strainer AQUA 90-501 combined with the "anti-shock" air release & vacuum break valve AQUA 70-506 are added system products for the best CLA-VAL regulation.
CLA-VAL 90-01
Pressure Reducing Valve
CLA-VAL Europe www.cla-val.ch [email protected] 1 - 090001CE B 10/10
Operating data
1.1 PRESURE REDUCING FEATURE
Pressure reducing control CRD (5) is a "normally open" control that senses main valve (1) outlet pressure changes. An increase in outlet pressure tends to close control (5) and a decrease in outlet pressure tends to open control (5). This causes main valve cover pressure to vary and the main valve (1) to modulate (open and close) maintaining a relatively constant outlet pressure.
Pressure reducing control (5) adjustment: Turn the adjusting screw clockwise to increase the setting.
1.2 OPENING SPEED CONTROL
Flow control CV (4) regulates the opening speed of main valve (1).
Flow control (4) adjustment: Turn the adjusting screw clockwise to make the main valve (1) open more slowly.
1.3 (E*) EUROPEAN STANDARDS
ITEM (2) - Isolation ball valve:
The isolation ball valves RB-117 (2) are used to isolate the pilot system from main line pressure. These isolation ball valves must be open during normal operation.
ITEM (3) - Y-Strainer with incorporated orifice:
The strainer X44-A (3) is installed in the pilot supply line to protect the pilot system from foreign particles. The strainer screen must be cleaned periodically.
1.4 OPTIONAL FEATURES
Suffix (A) - Internal strainer self-cleaning:
In some applications the self-cleaning strainer CLA-VAL, type X46A screwed at the inlet of main valve (1) reduces maintenance generated by the cleaning of the standard strainer screen (3).
With this option (A) the strainer X46A replaces the strainer (3) and the orifice of the X44A strainer (3) is replaced by the orifice assembly X58-CSA.
The cleaning of the strainer X46A is requesting its removal from the main valve body (1).
Suffix (C) - Closing speed:
Flow control CV (C) regulates the closing speed of main valve (1).
Flow control (C) adjustment: Turn the adjusting screw clockwise to make the main valve (1) close more slowly.
Suffix (Y) - High capacity filter:
When too many foreign particles are contained into the control pressure, it is recommended to replace the standard filter X44 by the high capacity filter X43/80-EP, whose screen (Ø 80 mm x 110 mm) offers a much bigger filtration surface. However an additional union fitting, with incorporated calibrated orifice, model X52-VR must be mounted between the filter outlet and the T-piece connecting the main valve control chamber.
1.5 CHECK LIST FOR PROPER OPERATION
System valves open upstream and downstream.
Air removed from the main valve cover and pilot system at all high points.
Isolation ball valves (2) open.
Periodical cleaning of the filter screen (3) or of the self-cleaning strainer, [optional feature (A)].
Flow control (4) or [optional features (C)] open from 1 turn.
CLA-VAL 100-01 NGE Main Valve HYTROL
CLA-VAL Europe www.cla-val.ch [email protected] 1 - HYN001DE B 01/08
Simple, Reliable and Accurate CLA-VAL SERIES 100 Main Function
The CLA-VAL 100-01 HYTROL Valve is a hydraulically operated, diaphragm actuated, globe or angle pattern valve. It consists of three major components: body, diaphragm assembly and cover. The diaphragm assembly is the only moving part, guided top and bottom by a precision machined stem. The disc retainer and rubber disc form a drip-tight seal with the renewable seat when pressure is applied above the diaphragm (cover chamber). The CLA-VAL 100-01 is the basic valve used in nearly in all CLA-VAL Automatic Control Valves.
CLA-VAL 100-01 Principle of Operation
Full Open Operation: When pressure in the cover chamber is relieved to a lower pressure or to atmosphere, the pressure inlet opens the valve.
Tight Closing Operation: When pressure from the inlet pressure is applied to the cover chamber, the valve closes drip-tight.
Modulating Control: The valve is pressure operating balanced. The CLA-VAL "Modulating" Controls will allow the valve to automatically compensate for pressure changes.
Usual Main Valves More Information
HYTROL Main Valve / HYTROL NGE-316 100-01 Sheet # TYTAN Main Valve 100-01 Schematic Diagram HYN001TT HYTROL Auxiliary Valve 000130TT Quick Valve Selection 000121DE ROLL SEAL Main Valve 100-42 Dimensions 000122DE-1 DELUGE Main Valve 100G Pressure Ratings & Materials 000123DE
Other Functions : Please Contact CLA-VAL
There are 3 HYTROL body types: NGE: New Globe Execution GE: Globe Execution AE: Angle Execution
CLA-VAL Europe www.cla-val.ch [email protected] 1 - RB1171TT B 01/11
ROBINET DE BARRAGE A BILLE En acier inoxydable 316 Pour applications chimiques, industrielles et alimentaires Testés selon EN 12266 (1) (2), ASME B16.34 PED 97/23/EC Catégorie II, Module D1 Pression maximale de service: 68 bar (1000 psi) Température: Max. 200°C ISOLATION BALL VALVE In stainless steel 316 For chemical, industrial and food service applications Testing according pr EN 12266 (1) (2), ASME B16.34 PED 97/23/EC Category II, Module D1 Maximal working pressure: 68 bar (1000 psi) Working temperature: Max. 200°C KUGELHAHN Aus Edelstahl 316 Für Chemische-, Industrie- und Lebensmittel-Anwendungen Prüfung nach EN 12266 (1) (2), ASME B16.34 PED 97/23/EC Klasse II, Modul D1 Max. Betriebsdruck: 68 bar (1000 psi) Temperaturbereich: Max. 200°C
Rp 3/8'' Rp 1/2'' Rp 3/4'' Rp 1'' Rp 1-1/4" Rp 1-1/2" Rp 2" P/N RBT2001 RBT3001 RBT4001 RBT6001 RBT7001 RBT8001 RBT9001
Ø d (mm) 12,5 15 20 25 32 38 50 L (mm) 54 65 75 87 101 110 132
Information X44A Standard X44001LT X44A/SWS X44002LT X44A/WWS X44003LT X44A/IND X44004LT X44A/OFS X44005LT X44A/AF X44801LT
FILTRE A BUSE INCORPOREECe filtre empêche tout corps étranger d'entrer dans le circuit d'asservissement. Il est recommandé de nettoyer périodiquement la cartouche du filtre. La vitesse de réaction de la vanne est liée au diamètre de labuse. Plus la diamètre est petit, plus la vanne réagit rapidement. Au contraire, pour un grand diamètre de buse la vanne va réagir lentement. STRAINER AND ORIFICE ASSEMBLYThe strainer is installed in the pilot supply line to protect the pilot system from foreign particles. The strainerscreen must be cleaned periodically. Speed reaction of the valve and orifice plug are directly connected. The valve will react quickly with a small orifice and on the contrary slowly with a big orifice. FILTER MIT EINGEBAUTER DÜSEDer Filter verhindert das Eindringen von Fremdkörpern ins Steuersystem. Das Sieb des Filters muss von Zeit zu Zeit gereinigt werden. Die Geschwindigkeitsreaktion des Ventils hängt mit der Düse zusammen. Je kleiner die Düse ist, je schneller wird das Ventil reagieren.
CLA-VAL CVRobinet à pointeau - Flow Control Cock - Nadelventil
1 - CV0001TT D 09/11 CLA-VAL Europe
®
TM
PN 10 - 16 - 25
ROBINET A POINTEAULe robinet à pointeau à action unidirectionnelle permet derégler la vitesse d'ouverture de la vanne de base.Réglage: visser le pointeau (8) dans le sens horaire pourdiminuer le passage. FLOW CONTROL COCKFlow control cock regulates the opening speed of main valve.Adjustement: turn the adjusting stem (8) clockwise to increase restriction. EIN-WEG NADELVENTILDas Einweg Nadelventil ermöglicht die Oeffnungsgeschwindigkeit des Hauptventils zu regulieren.Einstellung: Nadelschraube (8) im Uhrzeigersinndrehen um Strömmung zu beschränken.
PILOTE DE REDUCTION DE PRESSIONLe pilote de réduction de pression est du type normalement ouvert, à actionindirecte.Une augmentation de la pression de sortie tend à fermer le pilote, au contraire une diminution de la pression de sortie tend à l'ouvrir.Réglage : visser la vis de réglage (2) pour augmenter la pression de sortie. PRESSURE REDUCING CONTROLThe pressure reducing control is a "normally open" control. An increase in outlet pressure tends to close the pressure reducing control, and a decrease in outlet pressure tends to open it.Adjustment : turn the adjusting screw (2) clockwise to increase the outlet pressure. DRUCKREDUZIERVENTIL Das Druckreduzier-Steuerventil ist eine sogenannte"Auf-Kontrolle" welche die Schwankunden dessekundären Druckes am Ausgang des Hauptventilsmisst. Eine Erhöhung des Druckes bewirkt dieSchliessung des Steuerventils;eine Druckminderung hingebenbewirkt seine Öffnung.Einstellung : Regulierschraube (2)im Uhrzeigersinn drehen um denAusgangsdruck zu erhöhen.
Domaine de réglageAdjustement ranges
Einstellung
0,1-0,5 bar0,1-2,1 bar1,0-5,3 bar1,4-7,2 bar2,1-21,0 bar
0,04 bar0,2 bar0,6 bar1,0 bar1,9 bar
Information CRD STANDARD CRD001LT CRD/WWS CRD003LT CRD/IND CRD004LT CRD/OFS CRD005LT CRD/SWS CRD002LT CRD/AF CRD801LT