INGAT BENTUK JARINGAN YANG SEDANG DIPELAJARI ? JARINGAN DISTRIBUSI YANG DIPASOK DARI GARDU INDUK : TRAFO DAYA BUS 20 KV BUS 150 KV PENYULANG 1 RELAI GANG. TANAH YANG DITINJAU PENYULANG 2 GANGGUAN TANAH DI PENYULANG 1 RELAI PENY. 1 BETUL BEKERJA RELAI PENY 2 KERJA OLEH I CE MENJADI SALAH SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
INGAT BENTUK JARINGAN YANG SEDANG DIPELAJARI ?
JARINGAN DISTRIBUSI YANG DIPASOK DARI GARDU INDUK :
TRAFODAYA
BUS20 KVBUS
150 KV
PENYULANG 1
RELAI GANG. TANAH YANG DITINJAU
PENYULANG 2
GANGGUAN TANAH DI PENYULANG 1
RELAI PENY. 1 BETUL BEKERJA
RELAI PENY 2 KERJA OLEH
ICE MENJADI SALAH
SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
BAGAIMANA PENJELASANNYA ?
PENYULANG 1
PENYULANG 2
GANGGUAN TANAH DI PENYULANG 1
GFR
GFR
ICE SEIMBANG
GFR TDK KERJAGFR PENY. 1KERJA, BETULICE TIDAK
MASUK GFR
ICE KE
MASUK GFR
GFR PENY. 2BISA KERJA
PENYELESAIAN SIMPATETIK TRIP DENGAN GFR INVERSE
TERDIRI DARI IF DAN ICE
IF DIHITUNG SEPERTI HITUNGAN BIASA SESUAI LOKASI
25%, 50%, 75% ATAU 100% PANJANG PENYULANG
ICE DIHITUNG DARI ARUS
CHARGING JARINGAN DISTRIBUSI
ICE = 3 x x CE x EPH AMPER
EPH = TEGANGAN FASA - NETRAL
KAPASITANSI JARINGAN PER FASA
= 2 x x f
BESAR ARUS GANGGUAN TANAH DI PENYULANG= 3 I0
SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
IF =3 x EPH
Z1 + Z2 + Z0
CE =
URAIAN VEKTOR TEGANGAN SEWAKTU GANGGUAN TANAH
SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
S T
N
-ICT1,2ICS1
IR
ICT1
ICS1+ ICT1
-ICS1,2
-ICS1,2 -ICT1,2
R
GANGGUAN TANAH DI FASA R
FASA R BERIMPITDENGAN TANAH
TEGANGAN FASA SNAIK THD TANAH
TEGANGAN FASA TNAIK THD TANAH
ARUS NETRAL =
IR
,G
TEGANGAN NETRALNAIK THD TANAH
URAIAN VEKTOR ARUS DI PENYULANG TERGANGGU
ARUS KAPASITIF
FASA S = ICS1 FASA T = ICT1
RESULTANTENYA = ICS1 + ICT1 ARUS KAPASITIF
YANG MELALUI FASA TERGANGGU ( R )
RESULTANTENYA = - ICS1,2 - ICT1,2
KESIMPULAN :
PENYULANG TERGANGGU
DIHARAPKAN RELAI LEBIH CEPAT
SEMENTARA RELAI PENYULANG SEHAT DIALIRI ARUS ICE NYA
DIALIRI ARUS
SELAIN ARUS IR ,JUGA ARUS ICE PENYULANG
SEHATJADI ARUS RELAI LEBIH BESAR
SIMPATETIK TRIP SEWAKTU GANGGUAN TANAH
S T
N
ICS2
ICT2
ICS2+ ICT2
R,G
ICE PENYULANG
2RESULTANTENYA = ICS2 + ICT2
URAIAN VEKTOR ARUS ICE NYA
ARUS KAPASITIF INI YANGDAPATMEMBUAT GFR PICK UP
TETAPI KARENA LEBIH KECIL DARI ARUS PENYULANG TERGANGGU,WAKTU KERJANYA LEBIH LAMBAT