Simon Chen, Low Voltage Products Division, ABB Taiwan, Oct. 29, 2014 低壓隔離開關於高科技廠房的應用 © LP Division Controlling October 30, 2014 | Slide 1
Simon Chen, Low Voltage Products Division, ABB Taiwan, Oct. 29, 2014
低壓隔離開關於高科技廠房的應用
© LP Division ControllingOctober 30, 2014 | Slide 1
© ABB GroupLow Voltage Products divisionOctober 30, 2014 | Slide 2
© ABB GroupLow Voltage Products divisionOctober 30, 2014 | Slide 2
Low Voltage ProductsBusiness Units
MNS
Conventional
Switchgear
MNS Intelligent
Switchgear
MNS Integrated
Switchgear
Circuit Breakers
Switches
Fusegear and
Cable
Distribution
Cabinets
Modular DIN-Rail
Products
Intelligent
Building Control
KNX
Enclosures and
Cable Systems
Control and
Protection
Electronic
Products and
Relays
Connection
Wiring
Accessories
Industrial Plugs
and Sockets
Door Entry
Systems
Breakers
and SwitchesLV Systems
Enclosures and
DIN-Rail Products
Control
Products
Wiring
Accessories
Wire and cable
management
Cable protection
systems
Critical process
protection
People protection
Thomas &
Betts
© ABB Group October 30, 2014 | Slide 3
Low Voltage ProductsBreakers and Switches
Circuit Breakers
Moulded Case Circuit Breakers (MCCB)
Air Circuit Breakers (ACB)
Switches
Switch-disconnectors, switch fuses, cam
switches, change-over and transfer switches
Enclosed / safety switches
Fusegear and Cable Distribution Cabinets
Switch fuses, fuse switch disconnectors, fuse
links, fuse monitors and enclosures with
busbar system and apparatus
Safely break and switch power.
All over the world
New Emax: Lively performances.
E1 current ratings
up to 1600 A
Icu=150 kA @ 440
V AC
Now there is remote control Extremely simple installation
New Emax: Brilliant intelligence
Current sensor Faults: no problemRating plug Test kit-PR010/T
New Emax: Ensured reliability.
Reliability and
sturdiness- Materials
- Assembly
- Testing stage
Standardized range of
accessoriesCertifications
© ABB Group October 30, 2014 | Slide 7
PR121
PR12
2
PR123
Protection release
Modularity:通訊,量測,藍芽,
信號接點模組
© ABB Group
October 30, 2014 | Slide 8
ABB Emax –the 1000 V DC 1150V AC E2-E6 range
Automatic circuit-
breakers E1B E1N E2B E2N E2S E2L E3N E3S E3H E3V E3L E4S E4H E4V E6H E6V
Automatic circuit-
breakers fully rated E4S/f E4H/f E6H/f
Switch-disconnector E1B/MS E1N/MS E2B/MS E2N/MS E2S/MS E3N/MS E3S/MS E3V/MS E4S/MS E4H/MS E4H/f MS E6H/MS E6H/f MS
Automatic circuit-
breakers
up to 1150 V AC E2B/E E2N/E E3H/E E4H/E E6H/E
Switch-disconnector
up to 1150 V AC E2B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MS
Switch-disconnector
up to 1000 V DC E1B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MS
Sezionalizing truck
Earthing switch with
making capacity
Earthing truck E6 MT
E4 E6
E6 CS
E6 MTP
E3MT
Standard version
E4 CS
E4MTP
E4 MT
E3
E3 CS
E3 MTP
E2 CS
E2 MTP
E2 MT
E2
Standard version
E1
E1 CS
E1MTP
E1 MT
Standard version
© ABB Group
October 30, 2014 | Slide 9
The ranges – Automatic circuit-breakers
MORE
Performance levels B N B N S L N S H V L S H V H V
Rated current Iu [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 3200
[A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 4000 5000 4000
[A] 1250 1250 1600 1250 1600 1250 1600 6300 5000
[A] 1600 1600 2000 1600 2000 1600 2000 6300
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200
Breaking capacity
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 75 100 150 100 150
Icu @ 690 V AC [kA] 36 36 42 55 65 85 65 75 100 100 85 75 85 100 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 75 100 150 100 125
Ics @ 690 V AC [kA] 36 36 42 55 65 65 65 75 85 85 65 75 85 100 100 100
Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 165 220 330 220 330
Icm @ 690 V AC [kA] 75,6 75,6 88,2 121 143 187 143 165 187 220 187 165 186 220 220 220
Rated withstand current
Icw @ 1 s [kA] 42 50 42 55 65 10 65 75 75 85 15 75 100 100 100 100
Icw @ 3 s [kA] 36 36 42 42 42 - 65 65 65 65 - 75 75 75 85 85
Utilisation category B B B B B A B B B B A B B B B B
E6E1 E2 E3 E4
© ABB Group
October 30, 2014 | Slide 10
The ranges – Switch-disconnectors
Version B/MS N/MS B/MS N/MS S/MS N/MS S/MS V/MS S/MS H/MS H/f MS H/MS H/f MS
Rated current Iu [A] 800 800 1600 1000 1000 2500 1000 800 4000 3200 3200 4000 4000
[A] 1000 1000 2000 1250 1250 3200 1250 1250 4000 4000 5000 5000
[A] 1250 1250 1600 1600 1600 1600 6300 6300
[A] 1600 1600 2000 2000 2000 2000
[A] 2500 2500
[A] 3200 3200
Rated service voltage Ue
AC [V]
DC [V]
Rated insulation voltage Ui [V]
Rated impulse withstand volt. [kV]
Rated withstand current
Icw @ 1 s [kA] 42 50 42 55 65 65 75 85 75 100 85 100 100
Icw @ 3 s [kA] 36 36 42 42 42 65 65 65 75 75 75 85 85
Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 143 165 286 165 220 220 220 220
Icm @ 690 V AC [kA] 75,6 75,6 88,2 121 143 143 165 220 165 187 220 220 220
E6E1 E2 E3 E4
1000
690
12 12 12 12 12
1000 1000 1000 1000
250 250 250 250 250
690 690 690 690
© ABB Group
October 30, 2014 | Slide 11
Automatic circuit-breakers UL1066 and ANSI standard
E4 E6
Levels of performance
B-A N-A B-A N-A S-A H-A N-A S-A H-A V-A H-A/f H-A/f
Continuous current rating
[A] 800 800 1600 800 800 800 2000 800 800 800 3200 4000
[A] 1200 1200 1200 1200 1200 2500 1200 1200 1200 3600 5000
[A] 1600 1600 1600 1600 1600 1600
[A] 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
Neutral
[%Iu] 100 100 100 100 100 100 100 100 100 100 100 100
Rated short circuit current
240 V [kA] 42 50 42 65 65 85 65 85 85 125 100 125
480 V [kA] 42 50 42 50 65 85 50 65 85 125 85 85
600 V [kA] 42 50 42 50 65 65 50 65 85 100 85 85
Rated short time current
[kA] 42 50 42 50 65 65 50 65 65 85 85 100
E1 E2 E3
© ABB Group
October 30, 2014 | Slide 12
Switch-disconnectors in IEC 60947-3 standard
在 IEC60947-3 Switch-Disconnector 具有遮斷能力
Protection release for ACB 保護電驛
Trip Unit PR122
Internal Current Sensor
Rating Plug
No external CT
Trip Coil
Mechanical signaling of
trip
Switch-Disconnector +Protection Relay
Switch-Disconnector
Protection Relay
External CT
No Trip Coil
No mechanical signaling of tripped
Shunt opening release
High stability
© ABB Group
October 30, 2014 | Slide 15
Electronic diagram of Switch-disconnectors
© ABB Group
October 30, 2014 | Slide 15
© ABB Group
October 30, 2014 | Slide 16
Electronic diagram of Switch-disconnectors
Charge Motor Closing Coil Opening coil Signalling Closing Spring Charge
Switch-Disconnector 之電氣接點
© ABB Group
October 30, 2014 | Slide 17
ACB Switch-Disconnector
Standard: IEC 60947-2 IEC 60947-3
Current Sensor: YES NO
Protection Release: YES NO
Trip Coil: YES NO
Trip : Internal External
Difference between ACB and Switch-disconnector
© ABB Group
October 30, 2014 | Slide 18
Difference between ACB and Switch-disconnector
ACB Switch-Disconnector
沒有控制保護模組
© ABB Group
October 30, 2014 | Slide 19
Difference between ACB and Switch-Disconnector
ACB Switch-Disconnector
© ABB Group
October 30, 2014 | Slide 20
Difference between ACB and Switch-Disconnector
ACB Switch-DisconnectorProtection Release
© ABB Group
October 30, 2014 | Slide 21
Difference between ACB and Switch-Disconnector
ACB Switch-DisconnectorTrip coil
Switch-Disconnector 使用Open coil 來做外部控制跳脫
© ABB Group
October 30, 2014 | Slide 22
Difference between ACB and Switch-Disconnector
ACB Switch-DisconnectorCurrent Sensor
Current Sensor
© ABB Group
October 30, 2014 | Slide 23
2008 TSMC 12P-4 Q’ty 250 pcs
2009 TSMC 14P4 Q’ty 300 pcs
2010 TSMC UPS Portion 15P1/P2 Q’ty 250 pcs
2011 TSMC UPS portion 12P6 Q’ty 150 pcs
2012 TSMC UPS portion 15P3/P4 Q’ty 250 pcs
2012 Qualcomm Q’ty 300 pcs
2012 Innolux 7 Q’ty 300pcs in Tainan
Performance Reference List